HC900 Process Controller Modules Specifications: 51-52-03-41, June 2015
HC900 Process Controller Modules Specifications: 51-52-03-41, June 2015
Specifications
51-52-03-41, June 2015
Remote Terminal Panels shunt resistors and transmitter power terminals with individual
Optional DIN rail mounted Remote Terminal Panels (RTPs) circuit fuses. The Relay Output RTP includes a fuse and
are available for use with pre-wired cables to reduce power disconnect switch for each output. All the three types of
installation time and labor expense. Three types of RTPs are RTP panels also switch power to allow module removal and
available: analog inputs relay outputs and other I/O modules. installation under controller power. See page 31.
Three cable lengths are also available to match hardware to
installation variations. Analog inputs RTPs include transmitter
Terminal Blocks
20-screw Barrier style and Euro style terminal blocks are available for use with all HC900 I/O Modules.
Red terminal blocks are used for high voltage connections for added safety while black terminal blocks are used for low
voltage connections. A 36-terminal Euro style block is available with the 16 AI, the 8 and 16 AO as well as the 32 DC DI and
32 DC DO module types.
See page 25.
Power Supply
P01 Power Supply (900P01-xxxx )
The P01 power supply provides 5VDC and 24VDC to satisfy the power requirements of a rack with a controller and local I/O,
a rack with a scanner, and remote I/O. The 60 watt capacity allows for almost any mix of I/O modules in one rack. See
Module Specifications starting on page 6. A tool-secured door covers the high voltage connections; test jacks behind the
door allow for quick verification of proper operation. An internal non-replaceable fuse limits supply current under certain fault
conditions.
The P02 power supply provides 5VDC and 24VDC to satisfy the power requirements of a rack with a controller and local I/O,
a rack with a scanner and remote I/O or a redundant controller rack. The 28 watt capacity provides a cost-effective solution
for smaller I/O configurations. A tool-secured door covers the high voltage connections. An
internal non-replaceable fuse limits supply current under certain fault conditions.
A B C D E
Max Max Calculate 5V
Enter Current @ Current @ current Calculate 24V current
Module type Quantity 5V 24 V (D=A*B) (E=A*C)
SIL CPU
Controller C30S CPU ( ) 820 mA 0 mA ( ) ( 0 )
Controller C50S CPUL ( ) 930 mA 0 mA ( ) ( 0 )
Controller C70S CPU ( ) 1150 mA 0 mA ( ) ( 0 )
Controller C75S ( ) 1500 mA 0 mA ( ) ( 0 )
I/O Scanner 1 Port (1 per I/O 670 mA 0 mA
rack) - SIL ( ) ( ) ( 0 )
I/O Scanner 2 Port (1 per I/O 770 mA 0 mA
rack) - SIL ( ) ( ) ( 0 )
Non-SIL CPU
Controller C30 CPU ( ) 820 mA 0 mA ( ) ( 0 )
Controller C50 CPU ( ) 930 mA 0 mA ( ) ( 0 )
Controller C70 CPU ( ) 1150 mA 0 mA ( ) ( 0 )
Controller C70R CPU ( ) 1500 mA 0 mA ( ) ( 0 )
I/O Scanner 1 Port (1 per I/O 670 mA 0 mA
rack) ( ) ( ) ( 0 )
I/O Scanner 2 Port (1 per I/O 770 mA 0 mA
rack) ( ) ( ) ( 0 )
Power Status Module (PSM) ( ) 22 mA 0 mA ( ) ( 0 )
Analog Input (8 pts) ( ) 40 mA 25 mA ( ) ( )
Analog Input (16 pts) ( ) 75 mA 50 mA ( ) ( )
Analog Output (4 pts)* ( ) 40 mA 200 mA ( ) ( )
Analog Output (8 pts)*** ( ) 225 mA 350 mA ( ) ( )
Analog Output (16 pts)*** ( ) 350 mA 700 mA ( ) ( )
AC Digital Input (16 pts) ( ) 130 mA 0 mA ( ) ( 0 )
DC Digital Input (16 pts) ( ) 130 mA 0 mA ( ) ( 0 )
AC/DC Digital Input (16 pts) ( ) 130 mA 0 mA ( ) ( 0 )
Contact Input (16 pts) ( ) 130 mA 40 mA ( ) ( )
DC Digital Input (32 pts) ( ) 215 mA 0 mA ( ) ( 0 )
AC Digital Output (8 pts) ( ) 220 mA 0 mA ( ) ( 0 )
DC Digital Output (16 pts) ( ) 340 mA 0 mA ( ) ( 0 )
DC Digital Output (32 pts) ( ) 235 mA 0 mA ( ) ( 0 )
Relay Output (8 pts) ( ) 110 mA 100 mA ( ) ( )
Pulse/Frequency/Quadrature** ( ) 110 mA 250 mA ( ) ( )
6 HC900 Process Controller Modules
** Type K thermocouple (mid-range) has a working range from 75 to 1800 °F, 25 to 982 °C. Input measurements below
75°F or 25°C may cause the input to default to the programmed failsafe value. Use type K low or full ranges if
measurements are required outside the mid- working range.
HC900 Process Controller Modules 9
A DIP switch on the module selects the use of 24V from External Power Source requirements:
Rack PS (internal) power or external loop power via a
Voltage Vin: 18 to 36 Vdc
separate 24V DC power source. The as-shipped (default)
Current 350 mA per module
switch setting is external power.
14 HC900 Process Controller Modules
A DIP switch on the module selects the use of 24V from rack PS (internal) power or external loop power via a separate 24V
DC power source. The as-shipped (default) switch setting is external power.
*excluding controllers scan time and excluding transmission time from module to backplane
HC900 Process Controller Modules 17
* Nominal times excluding controllers scan time and excluding transmission time from
module to backplane. DC application must include controller line filter setting of 50/60 Hz
Active input De-rating table for AC/DC DI
240 Vac
264 Vac / 150 Vdc
HC900 Process Controller Modules 19
In 6+ 6
blinking status LED on the module indicates when the
7
module is being scanned. An amber blinking status LED In 7+
In 8+ 8
indicates when channels are forced and a red status LED In 9+ 9
when module diagnostics exist. Logic in the controller In 10+ 10
allows the state to be inverted when necessary. In 11+ 11
In 12+ 12
In 13+ 13
Requires Euro style 36-terminal terminal block In 14+ 14
In 15+ 15
In 16+ 16
Inputs per module 32 (sinking) 1-16COM 17
18
Input Voltage Range 10 VDC to 32 VDC 1-16COM 19
In 17+
Peak Voltage 32 VDC In 18+ 20
AC Frequency N/A In 19+ 21
In 20+ 22
Galvanic Isolation 2 groups of 16 inputs 23
In 21+
(30VDC max.) 24
In 22+
In 23+ 25
ON Voltage Level 9.5 VDC minimum
In 24+ 26
OFF Voltage Level 3.5 VDC maximum In 25+ 27
Input Impedance 6.9 K ohms nominal In 26+ 28
In 27+ 29
Input Current 1.7 mA @ 12 VDC 3.5 mA In 28+ 30
@ 24 VDC nominal In 29+ 31
In 30+ 32
Minimum ON Current 1.0 mA 33
In 31+
Maximum OFF Current 0.7 mA In 32+ 34
17-32COM 35
OFF to ON response time* 5 ms max 17-32COM 36
ON to OFF response time* 5 ms max
Power Supply Loading 5V; 215mA max
24V; 0mA
*excluding controllers scan time and excluding
transmission time from module to backplane
20 HC900 Process Controller Modules
*excluding controllers scan time and excluding transmission time from module to backplane
22 HC900 Process Controller Modules
resistive load
0.25 A per point
24 HC900 Process Controller Modules
Channels Used Only channels 1 and 2 can be used for quadrature pulses A and
B respectively.
Index pulse is provided in addition.
Input Voltage Range Differential: -6 VDC to +6 VDC
Single-ended: 0 VDC to 24 VDC
ON Voltage Level Differential: 0.2 VDC minimum
Single-ended: 3.0 VDC minimum
OFF Voltage Level Differential: -0.2 VDC maximum
Single-ended: 1 VDC maximum
Common Mode Voltage +/- 12VDC
Input Sensitivity +/- 200mV
Hysteresis +/- 50mV
Module powered encoder 5V DC, 0.50A
Frequency 200 KHz maximum
Minimum Pulse Width 2.25 µsec
Quadrature Counter 32 bits signed
Quadrature Modes For variable resolution there are three count modes for the
Pulse/Quadrature input:
X1: rising edges of signal A are counted (increment); falling
edges of signal A (decrement)
X2: rising & falling edges of signal A are counted
X4: rising & falling edges of signals A & B are counted
Quadrature LEDs Two LEDs indicate UP and DOWN direction of counting.
26 HC900 Process Controller Modules
Channels Used Any one of the channels can be used for Pulse Output.
However, the use of a particular channel for outputting pulses
will render the particular input channel unusable for either of
pulse, frequency or quadrature input.
Digital Output Type Open Collector, 5 to 24V, 30 mA max
Frequency Range 25 Hz – 10 KHz
Duty cycle Always 50%
Pulse Output Duration Selectable CONTINUOUS or NUMBERED PULSES.
All terminal blocks support customer wiring entering the Shield terminal strips are also available to terminate the
block from the top or bottom when mounted in the shields of shielded cables at the controller.
controller. A locking swing out door provides easy access
for wiring and covers potential high voltage connections
during operation.
Number of 20 36*
terminals
Type Terminal blocks removable Terminal blocks removable
under instrument power. under instrument power.
(Field power disconnected) (Field power disconnected)
Terminal styles
Gauge Wires Barrier and Euro: #14 to 26 Euro: #12 to 26 AWG, solid (top) Barrier
AWG, solid or stranded or stranded (middle) Euro
(bottom) 36-terminal
Terminal color High voltage: Red Black Euro
Mounting
Standard 35mm wide DIN Rail Provides connection of field wiring to controller I/O within an enclosure only.
Dimensions 4.38” (111.1 mm) x 3.70” (94.0mm) x 2.60” (66.0mm) (L x W x H)
Cables
High voltage Lengths: 1.0, 2.5, 5.0 meters. Cable power is limited to 24 Amps per module
at 60C (140 degrees F) and 32 Amps at 54C (129 degrees F).
Low voltage Lengths: 1.0, 2.5, 5.0 meters.
HC900 Process Controller Modules 31
11
The analog input RTP cannot be used for 15 13
16 1 17
21
SW SW SW SW SW SW SW SW
8(1) 7(1) 6(1) 5(1) 4(1) 3(1) 2(1) 1(1)
SW 9
1
F1 24
F2 25
F3 30
F4 31
F5 34
F6 35
F7 38
F8 39
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
+
24 VDC
-
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
Note:
You must set
switches 1- 8 for
transmitters. - - - -
+ - - -
- + +
+ + +
+ +
Input 3 Input 5
Input 1 Input 7
Transmitter Input 4 Transmitter Input 6
Transmitter Input 2 Transmitter Input 8
Transmitter Transmitter
Transmitter Transmitter
32 HC900 Process Controller Modules
HC900
Terminal Block
J1 TB1
1 6 1
F1 SW1
2 7 2
3 8 3
4 9 4
F2 SW2
5 10 5
6 20 6
7 19 7
F3 SW3
8 18 8
9 17 9
F4 SW4
10 16 10
11 15 11
F5 SW5
12 14 12
13 13 13
F6 SW6
14 12 14
15 11 15
F7 SW7
16 1 16
17 2 17
18 3 18
F8 SW8
19 4 19
20 5 20
Relay Output RTP Used with Relay Output Relay common disconnect per circuit
Module Fuse per circuit – 6.3A, time lag type
24A maximum per RTP
HC900 Process Controller Modules 33