Spaj 160 C Capacitor Protection Relay: Features
Spaj 160 C Capacitor Protection Relay: Features
1MRS 750420-MBG
Page 1
Issued: April 1999
Status: New
Data subject to change without notice
Features • One-, two- and three-phase overload stage • Numerical display of setting values, mea-
with definite time characteristic sured current values, memorized values,
etc.
• One-, two- and three-phase overload stage
with inverse (ANSI) time characteristic • Continuous self-supervision of hardware
and software
• Phase unbalance protection stage with def-
inite time characteristic • Serial interface for connecting the relay to
the fibre-optic SPA bus and further to
• Phase unbalance protection stage with
higher-level data acquisition, reporting
inverse time characteristic
and/or control systems
• Undercurrent protection for detection of
• Powerful software support for parameter-
capacitor disconnection. Reconnection
ization of the relay, for reading measured
time with wide setting range
and recorded values, events, etc., and for
• Compensation for natural unbalance cur- storing readings
rent
• Member of the SPACOM product family,
• Fully user-selectable output relay configu- ABB’s Distribution Automation system and
ration ABB’s Panorama concept
• Easy selection of appropriate operational • CE marking according to the EC directive
scheme for various applications for EMC
Application The numerical capacitor relay SPAJ 160 C is reconnection of a charged capacitor to an
an integrated current measuring multi-func- energized network is also to be included. All
tion relay designed to be used for the protec- these functions are incorporated in the capac-
tion of capacitor banks. Capacitor banks are itor protection relay.
used in the power system for compensating
the reactive power and for filtering harmon- A complete protection system for capacitor
ics. banks should also include overcurrent, short
circuit and earth-fault protection. The capaci-
The capacitor banks are usually protected tor protection relay SPAJ 160 C is easily sup-
against overload caused by harmonic currents plemented with adequate overcurrent and
and overvoltage caused by internal faults in earth-fault relays from the SPACOM product
the bank. Protection against unintentional range.
ABB Network Partner Capacitor protection relay SPAJ 160 C
1MRS 750420-MBG
Page 2
Design The capacitor protection relay includes a nection attempt and/or for resetting a latched
three-phase, two-stage overload unit, a two- output relay in the manual reset mode of
stage unbalance unit, an undercurrent unit operation.
and a reconnection inhibit timer.
Technical data (cont’d) Table 5: Capacitor protection relay module SPCJ 4D40
Overload stage Ib> Start current Ib> 0.30…1.50 × In
Start time <80 s
Operation characteristic ANSI inverse
Time multiplier k 0.2…2.0
Reset time <100 ms
Drop-off/pick-up ratio, typically 0.95
Operate time accuracy ±3% of set value
Operation accuracy ±3% of set value
Overload stage Ia> Start current Ia> 80…120% of Ib>
Operate time 0.5…100 s
Reset time <250 ms
Drop-off/pick-up ratio, typically 0.95
Operate time accuracy ±2% of set value
Operation accuracy ±3% of set value
Undercurrent stage Start current I< 0.10…0.70 × In
I< Operate time 1.0…100 s
Reconnection inhibit time trec 0.5…100 min
Reset time <80 ms
Drop-off/pick-up ratio, typically 1.1
Operate time accuracy ±2% of set value
or ±75 ms
Operation accuracy within the range of 0.25…0.70 × In ±3% of set value
Phase unbalance Start current ∆I1> 1.0…100% of ∆In
∆I1> Operate time t∆1 1.0…300 s
Reset time <100 ms
Drop-off/pick-up ratio, typically 0.90
Operate time accuracy ±2% of set value
or ±75 ms
Operation accuracy within the range of 1.5…100% In ±3% of set value
Phase unbalance Start current ∆I2> 2.0…80.0% of ∆In
∆I2> Start time <70 s
Operation characteristic Inverse time
characteristic
Time multiplier k∆2 0.1…1.0
Reset time <100 ms
Drop-off/pick-up ratio, typically 0.90
Operate time accuracy of theoretical characteristic 7.5% or ±35 ms
Operation accuracy ±3% of set value
Shortest possible operate time ~100 ms
Unbalance Compensation current ∆Ics 0.0…20.0% of In
compensation Operation accuracy <3% of In
Block diagram L1
L2
L3
-
0
-
I
I 0
+
Rx Tx
SPA-ZC_
+ (~)
Uaux +
- (~)
RECONNECTION
CONTROL IRF ENABLE START SIGNAL 2 SIGNAL 1 TRIP
INPUT BS +
SERIAL
PORT
63 1 2 3 4 5 6 7 8 9 25 26 27 11 10 61 62 70 71 72 74 75 77 78 80 81 68 69 65 66
@
5A
1A
5A
1A
5A
1A
5A
1A
+ + + + + +
_
F E D C B A
+ -
U2 SPTU_R2
TS1 SS1 SS2 SS3 TS2
1
TRIP
R
U3 1 1 1 1 1
SGB/7
SGB/8
SGR1/1
SGR1/2
SGR1/3
SGR1/4
SGR2/2
SGR2/3
SGR2/4
SGR2/5
SGR2/6
SGR2/7
SGR1/5
SGR1/6
SGR1/7
SGR1/8
SGR2/8
SGR2/1
LATCHING
T8
SGF/1
IRF
3Ia>
T1
SGB/1 3Ib> T2
T3
DI1
T4
SGF/2
DI2 T5
SGB/2
T6
3I<
SGB/3
T7
SGB/4
RECONN.INHIBIT
SGB/5
EXTERNAL TRIP T9
SGB/6 RELAY RESET
I/O
SPAJ 160 C
U1 SPCJ 4D40
139 ±1
Panel cut-
136
162
out
dim100
Semi-flush mounting
a b
Raising frame a b
SFM100_1
SPA-ZX104 SPA-ZX110
SPA-ZX105 SPA-ZX115
SPA-ZX106
+0,4 158 263
482,6 –0 (19")
115
ø6
10
177 –0 (4U)
101,6
7
+0,4
312
292
21,5
6
115 98
104_6_10
Fig. 4 Mounting cabinets and frames as well as projecting mounting (dimensions in mm)
ABB Network Partner Capacitor protection relay SPAJ 160 C
1MRS 750420-MBG
Page 8
Order numbers
Capacitor protection relay SPAJ 160 C without test RS 611 051-AA, CA, DA, FA
adapter
Capacitor protection relay SPAJ 160 C including test RS 611 251-AA, CA, DA, FA
adapter RTXP 18
The last two letters of the order number indicate the AA equals fn = 50 Hz and Uaux = 80…265 V ac/dc
rated frequency fn and the auxiliary voltage Uaux of CA equals fn = 50 Hz and Uaux = 18…80 V dc
the relay as follows:
DA equals fn = 60 Hz and Uaux = 80…265 V ac/dc
FA equals fn = 60 Hz and Uaux = 18…80 V dc