Multicontrol Ai / Bi: Operating Manual
Multicontrol Ai / Bi: Operating Manual
Operating manual
MultiControl AI / BI
Analogue Interface / Bus Interface – 24 V / 48 V DC
Manufacturer details
Interroll Engineering GmbH
Höferhof 16
42929 Wermelskirchen
Germany
Tel.: +49 (0) 2193 23 0
Fax: +49 (0) 2193 2022
www.interroll.com
Content
We strive for the accuracy, timeliness and completeness of the information and have carefully prepared the contents
in this document. Regardless of this, errors and changes are expressly reserved.
The manufacturer assumes no liability for damage and malfunctions that occur as a result of non-
compliance with this operating manual.
Should you still have any unanswered questions after reading this operating manual, please contact Interroll
customer service. Contact details for your region can be found online at www.interroll.com/contact/
Please direct any comments and suggestions regarding our operating manuals to [email protected]
SIGNAL WORD
Type and source of hazard
Consequence(s) in the event of non-compliance
¾ Measure(s) for avoiding hazard
Signal words indicate the type and severity of the consequences if measures to avoid the hazard are not observed.
DANGER
Denotes an imminent hazard.
If measures to avoid the hazard are not observed, death or severe injury will occur.
¾ Preventive measures
WARNING
Denotes a potentially hazardous situation.
If measures to avoid the hazard are not observed, death or severe injury may occur.
¾ Preventive measures
CAUTION
Denotes the possibility of a hazardous situation.
If measures to avoid the hazard are not observed, minor or moderate injury may occur.
¾ Preventive measures
NOTE
Denotes a situation that can lead to material damage.
¾ Preventive measures
1.3 Symbols
ü This symbol indicates a requirement that must be fulfilled before carrying out assembly or repair work.
2 Safety-related information
2.1 State of the art
The Interroll MultiControl has been constructed with respect to applicable standards and the current state of the art
and has been delivered in a condition that is safe to operate. Nevertheless, hazards can occur as a result of use.
Non-compliance with the instructions in this operating manual can result in life-threatening injuries.
In addition, the applicable local accident prevention regulations for the area of application and general safety
regulations must be adhered to.
The MultiControl AI, 24 V DC can also be used to control the Interroll PalletControl.
Application field
The following applications are possible:
2.5 Dangers
Here, you will find information about the different types of dangers or damage that can occur in
connection with the operation of the MultiControl.
Injury to persons
Maintenance, installation and repair work on the unit must only be carried out by authorised technical personnel
in compliance with the applicable provisions.
Before switching on the MultiControl, ensure that no unauthorised personnel are situated in the vicinity of the
conveyor/conveying system.
Electricity
Installation and repair work must only be carried out when the system has been disconnected from the power
supply. Switch off the power to the MultiControl and ensure that it cannot be unintentionally switched on again.
Work environment
Remove any materials and objects that are not required from the working area.
Faults in operation
Regularly check the MultiControl for visible damage.
If smoke develops, immediately switch off the power to the MultiControl and ensure that it cannot be
unintentionally switched on again.
Immediately contact specialist personnel to determine the cause of the malfunction.
Maintenance
Since the product in question requires no maintenance, it is sufficient to simply examine the MultiControl for
visible damage on a regular basis.
Never open up the MultiControl.
Unintentional start-up
Ensure that the connected RollerDrives/motors cannot start up unintentionally, particularly during assembly and
maintenance work or in the event of a fault.
MTTF (h):
812691 Hours
MTTF (a):
93 Years
Provided that the behavior of the MultiControl is changed in the event of system-relevant errors in the “Error
Handling Settings” of the MultiControl user interface, this results in an achievable performance level of “C” (see
„Error Handling Settings“ on page 45).
Submit Reset
In order to fulfill a safety function, the safety-related disconnection of the load voltage (motor voltage) is also
required.
Also ensure that you adhere to the information given in the operating manuals of the connected devices.
Further notes on operating and programming the MultiControl can be found in the “MultiControl / RollerDrive - Start-
up and Programming” supplement.
The latest version of this supplement can be found online at: www.interroll.com
3 Product information
3.1 Product description
The MultiControl is a control system for conveyor systems, which can control up to four Interroll RollerDrives. It is also
a certified I/O device for PROFINET, EtherNet/IP and EtherCAT and can therefore be linked with other MultiControls
and a PLC.
Sensors and RollerDrives can be directly integrated into the fieldbus level via the MultiControl. This completely
eliminates the need for an additional sensor/actuator level.
Some applications are already pre-programmed in the MultiControl for applications with special conveying logic. It
can therefore be used as a standalone control system – with or without connected PLC.
The MultiControl is compatible with all 24 V/48 V conveyor modules from Interroll Automation GmbH. So-called ZPA
(zero pressure accumulation) programs are used for operating the conveyor modules with zero pressure accumulation.
The MultiControl BI communicates with the connected RollerDrive EC5000 BI via the CANopen protocol.
Further information on the integrated programs and functions can be found in accompanying document
"MultiControl / RollerDrive - Start-up and Programming".
Note the energy recovery capacity of the power supply units used.
We recommend the use of Interroll High Performance power supplies HP 5424 / HP5448 with a
regenerative strength up to 35 V / 60 V.
With the MultiControl 24 V it is possible to reduce the brake chopper operating voltage to 26 V
(see „Motor Settings“ on page 36).
Overload protection
If the brake chopper remains switched on for longer than two seconds, it is switched off again as it is assumed that the
power supply unit is delivering an incorrect voltage. The activated overload protection is indicated by the LED display.
Whenever the overload protection is active, the motors cannot be switched on.
The MultiControl does not provide a protective mechanism against excess temperature in the connected RollerDrive.
3.2 Setup
MultiControl AI and BI
Base plate
3.6 Dimensions
The distance between the MultiControl and neighbouring components must be at least 10 mm in order to
be able to operate the magnetic sensor.
CAUTION
Risk of injury from improper transport.
¾ Transport operations must only be carried out by authorised, qualified personnel.
4.2 Storage
CAUTION
Risk of injury due to improper storage.
¾ Ensure that the MultiControl is stored safely.
NOTE
An improper approach to installing the MultiControl can lead to material damage or reduce the service life of
the MultiControl.
¾ To preserve the interior of the MultiControl, do not allow the MultiControl to fall or for it to be used in an
improper fashion.
¾ Check each MultiControl before assembly for any visible damage.
¾ Ensure that the MultiControl is not tensioned during the assembly process (no bending or torsional load).
¾ Do not drill any additional mount holes into the housing or the base plate and do not enlarge any existing
holes.
To simplify electrical installation, all MultiControls should only be attached to one side of the conveyor
system if possible. In the case of curves, the MultiControls should be attached as close to the outer radius of
the curve as possible, as the RollerDrive connection is on this side.
¾ Find a level surface on the conveyor frame where the MultiControl can be attached. Leave approximately
25 mm to the left of this to enable the MultiControl to subsequently be moved if necessary (see „Subsequent
assembly“ on page 24).
¾ Use the base plate as a template and mark the middle of the installation holes. Ensure the correct orientation
of the base plate (the cable guide label must be legible).
¾ Drill two holes with a diameter of 6.5 mm through the markings in the conveyor frame.
¾ Attach the base plate to the conveyor frame with M6 screws.
¾ Make sure the base plate has not been distorted.
¾ Insert the ribbon cables for the power supplies (see „Connecting the power supply“ on page 26).
¾ Place the MultiControl on the left-hand holes and press it down until the lock engages.
¾ Screw the MultiControl onto the base plate (max. tightening torque 2,5 - 2,75 Nm). This drives the piercing
contacts through the ribbon cable and makes contact with the power supplies.
Use the screws provided to attach the MultiControl to the base plate.
Subsequent assembly
If a MultiControl that has already been connected needs to be detached from the base plate, the ribbon cables must
not make contact again at the same point, as otherwise proper contact cannot be guaranteed. So as not to have
to disconnect the ribbon cables from all MultiControls and then reconnect them, in this case the MultiControl can be
attached via the installation holes on the right.
CAUTION
Risk of injury when working on electrical equipment.
¾ Electrical installation work must only be carried out by a qualified electrician.
¾ Before installing, removing or connecting the MultiControl, switch off the power to the conveyor system and
ensure that it cannot be unintentionally switched on again.
¾ Set all the power supplies used to the same earth potential in order to avoid compensating currents via the
MultiControl or bus cable.
¾ Ensure all components are earthed correctly. Improper earthing can lead to a build-up of static charge,
which can result in a fault or premature failure of the MultiControl.
¾ Ensure that suitable switching devices and protective systems are in place that will allow the equipment to be
operated safely.
¾ Only switch on the operating voltages when all cables are connected.
NOTE
Improper electrical installation can result in damage to the MultiControl.
¾ Observe national regulations for electrical installation.
¾ Only operate the MultiControl with a protective extra-low voltage (PELV) of 24 V or 48 V.
¾ Never operate the MultiControl with an alternating voltage.
¾ Ensure that the polarity of the power supply is correct.
¾ Ensure that the existing electrical installation has no disruptive influence on the MultiControl.
¾ Only use cables that are adequately dimensioned for the specific operating conditions.
¾ Ensure that the calculations for the drop in voltage in the cables are taken into account.
¾ Observe regulations for laying cables.
¾ Do not expose the connectors to excessively high tensile or pressure loads. If the connector cable is bent, this
can damage the cable insulation and cause the MultiControl to fail.
A ribbon cable distributor can be used to enable the MultiControl to be used as a replacement part in
existing systems (see „Accessories“ on page 66).
Both earth potentials (L-) of the power supplies are connected to one another in the MultiControl.
¾ Insert the ribbon cables with the correct orientation, without mechanical tension or torsion, into the cable
guides on the base plate. The cable guides have a form-fit design (see figure). This means that the ribbon
cables can only be inserted with the correct orientation and the polarity of the cables cannot be reversed.
¾ If necessary, implement appropriate strain relief and vibration reduction measures.
1 Cable guide for power supply to logic and 2 Cable guide for power supply to RollerDrive (L2)
sensors (L1)
Upper pin: L+, brown cable wire Upper pin: L+, brown cable wire
Lower pin: L-, blue cable wire Lower pin: L-, blue cable wire
¾ Seal the ends of the ribbon cables with end caps to achieve protection rate IP54.
¾ Mount the MultiControl on the base frame to establish contact (see „Initial assembly“ on page 22).
¾ Connect the cables to the power source. Connect the brown wire to L+ and the blue wire to L-.
¾ Seal unused RollerDrive connections with an M8 blind cap to achieve protection rate IP54.
RollerDrive BI
¾ Seal unused RollerDrive connections with an M8 blind cap to achieve protection rate IP54.
NOTE
Incorrect connected loads can destroy the RollerDrive.
¾ Do not attempt to operate a RollerDrive EC5000 24 V DC at 48 V DC. This will destroy the motor
electronics.
NOTE
Connecting/disconnecting under voltage can destroy the MultiControl / RollerDrive EC5000 with bus interface
¾ The MultiControl and the RollerDrive EC5000 BI are not hot-plug-compatible. Disconnect the power supply
to connect/disconnect the RollerDrive EC5000 BI.
The MultiControl features an integrated two-port switch. This enables the MultiControl to be integrated into line
structures of the bus wiring, for example.
¾ Observe the installation guidelines for the corresponding bus systems:
• PROFINET: PROFIBUS & PROFINET International (PI), www.profibus.com
• EtherCAT: EtherCAT Technology Group, www.ethercat.org
• EtherNET/IP: ODVA, www.odva.org
¾ Seal any unused connections with an M12 blind cap to achieve protection rate IP54.
It is possible to connect the shielding of the bus cables on both sides of the MultiControl. This minimises EMC
problems.
4 2
3 1
1 +24 V 3 Earth
2 AUX I/O 4 Sensor input
¾ Seal any unused connections with an M8 blind cap to achieve protection rate IP54.
NOTE
Connections are not short circuit-proof
In the event of a short circuit, particularly between Pin 1 and Pin 3, the internal fuse (PTC) in the MultiControl trips.
Standard operation can be resumed once the internal fuse has cooled down.
¾ Ensure the correct polarity.
¾ Seal any unused sensor connections with an M8 blind cap to achieve protection rate IP54.
Overview of connections
CAUTION
Risk of malfunction!
¾ Change the motor configuration via SDO or web browser only when motors are stopped!
The MultiControl must be configured before it can be started up. There are various ways of doing this:
• All settings can be configured via a web-based user interface on a computer connected to the MultiControl.
• Directly on the MultiControl via the built-in magnetic sensor (see the “MultiControl / RollerDrive - Start-up and
Programming” supplement).
• All settings except the bus type can be configured via service data objects (SDOs) written by a higher-level control
system (see the “MultiControl / RollerDrive - Start-up and Programming” supplement).
• The station name, the IP configuration and the connection settings can be modified via a PLC development
environment.
• The data is automatically transferred by the Plug&Play function when the MultiControl is replaced.
NOTE
Possible loss of data during the start process
If the supply voltage is interrupted during the start process, this can result in a loss of data.
¾ Do not switch off the supply voltage during the start process (approx. 10 seconds).
Unless otherwise specified, the figures apply to the MultiControl AI and the MultiControl BI.
MultiControl AI
MultiControl Overview
Bus Info
Overview Bus Protocol : PROFINET
Network and Settings Host Name : multicontrol2
Motor IP Adress : 192.168.0.2
State : Disconnected
Settings
TestPanel
Error Info
Digital I/O
State : Operational
States
Active Error : BusComFail (21)
Settings Last Error : 00:00:42.536.21 BusComFail
Control Program
Settings
Error Control Program Info
State Program ID : I/O Device
Settings Version : 2017-04-10-09
Log
Find Device
Service
Teach-In Start Identify
Plug&Play
System
Change Password
Factory Reset
Restart
Version
Up-/Download
Log Out
MultiControl BI
MultiControl Overview
Bus Info
Overview Bus Protocol : PROFINET
Network and Settings Host Name : multicontrol2
Motor IP Adress : 192.168.0.2
Settings State : Disconnected
Information
Monitor Error Info
TestPanel State : Operational
Digital I/O Active Error : BusComFail (21)
States Last Error : 00:00:42.536.21 BusComFail
Settings
Control Program Control Program Info
Settings Program ID : I/O Device
Error Version : 2017-04-10-09
State
Settings Find Device
Log Start Identify
Service
Teach-In
Plug&Play
CAN Gateway
System
Change Password
Factory Reset
Restart
Version
Up-/Download
Log Out
Use the menu on the left-hand side of the screen to navigate through further information and settings.
MultiControl Overview
Bus Info
Bus Protocol : PROFINET
Host Name : multicontrol2
IP Adress : 192.168.0.2
State : Disconnected
Error Info
State : Operational
Active Error : BusComFail (21)
Last Error : 00:00:42.536.21 BusComFail
Find Device
Start Identify
The EDS file for the respective software version is stored on the MultiControl and can be downloaded via
the link at the bottom of the home page.
¾ To exit the user interface, click on “Log Out” (not necessary if the MultiControl is restarted).
Network Settings
Network Settings
Bus Protocol Neighbours
EtherCAT IP address upstream : 192.168.0.16
EtherCAT BI IP address downstream : 192.168.0.17
EtherCAT/CAN
EtherCAT/CAN Pro
PROFINET Option
EtherNet/IP Big Endian Format
Domains
Host Name : multicontrol
Domain Name :
DNS server 1 : 0.0.0.0
DNS server 2 : 0.0.0.0
Configuration Mode
Static
I/O Controller
Submit Reset
In order to integrate the MultiControl into an automation system, bus parameters may also need to be modified. This
includes the setting for the bus type used as well as addressing.
The MultiControl supports the following bus types:
• PROFINET I/O device – Conformance Class B, Netload Class 1
• EtherNet/IP slave
• EtherCAT slave
The following parameters can be modified in order to address the MultiControl:
• IP address and subnet mask
• Gateway
• Host name: When using the MultiControl with PROFINET, the unique PROFINET name of the MultiControl must be
entered here
• Domain name plus DNS server 1 and 2
• Configuration mode of the address:
Static: The IP address is assigned by the user
I/O controller: The IP address is assigned by the PLC (input field is greyed out)
To avoid communication problems in the bus system, we recommend changing the standard IP address
192.168.0.1.
Depending on the system configuration, in PROFINET projects we recommend manually increasing the
update time of the MultiControl (automatic 2 ms) to half the CPU cycle time or at least 8 ms.
Press the "Submit" button to transfer the modified parameters to the MultiControl.
NOTE
Irreparable damage to the MultiControl due to premature shutdown of the supply voltage
¾ Ensure that the power supply is not interrupted during the entire process of changing the bus type until the
restart is complete. This process takes approx. two minutes.
Motor Settings
Motor Settings
Motor 1 Motor 2 Motor 3 Motor 4
Motor Type EC5000 EC5000 Disabled Disabled
Roller Diameter [mm] 50.0 50.0 50.0 50.0
Gearing Ratio 49:1 49:1 none none
Direction CW CCW CW CCW CW CCW CW CCW
Normal Speed [m/s]: 1.00 1.00 1.00 1.00
Alternate Speed [m/s]: 0.50 0.50 0.50 0.50
Acceleration [m/s2]: 0.00 0.00 0.00 0.00
Decceleration [m/s2]: 0.00 0.00 0.00 0.00
28 V
Brake Chopper Level: 26 V Submit Reset
CAUTION
Risk of malfunction!
¾ Change the motor configuration via web browser only when motors are stopped!
If a motor is activated but not connected, the RD1 – RD4 LED flashes.
¾ Enter the “Roller diameter”, “Gearing ratio” and “Normal speed” according to the RollerDrive used.
In the case of conical rollers (curves), enter the average roller diameter as the diameter.
In the “I/O device” control program, the speed in % relates to the value set here under “Normal speed”.
Due to tolerances and / or voltage drop on cables, it is possible that the RollerDrive does not rotate when it is set to
its minimum values. In this case a higher setting and thus speed must be selected.
The “Direction” parameter is used to adapt the rotational direction of the RollerDrive to the installation location
(rotational direction as viewed from the cable end of the RollerDrive).
“Acceleration” and “Deceleration” adapt the start/stop behaviour of the RollerDrive. The “Alternate speed” parameter
is not currently in use.
Gear 9:1 13:1 18:1 21:1 30:1 42:1 49:1 78:1 108:1
Acceleration value m/s2 13,2 9.2 6.6 5.7 4.0 2.8 2.4 1.5 1.1
Press the "Submit" button to transfer the modified parameters to the MultiControl.
Motor Information
Motor Monitor
Motor 1 Motor 2 Motor 3 Motor 4
Lifetime
Temperature
Power
Error
Visual displays
Service life indicator lights
Health indicator lights for:
• Temperature
• Power
• Frequency of errors
Monitoring data
Start/stops – Number of start/stops per minute
Run time (s)
Up time (s)
Temp. max (°C) – Maximum temperature of the motor electronics
Temp. min (°C) – Minimum temperature of the motor electronics
Current temp. (°C) – Actual temperature of the motor electronics
Num. quick stops – Number of quick stops
Actual Torque (mNm) - Actual Torque
Power/time (Wh) – Average mechanical power output
Num. rotations – Number of motor revolutions
WARNING
Risk of crushing due to unintentional start-up of the RollerDrive!
¾ Changes in this menu have direct influence on the connected RollerDrive!
¾ Before starting motors make sure, ensure that no persons are present in the hazardous areas surrounding
the conveyor system!
I/O 1 I/O 3
State: Off State: Off
Sensor 2 Sensor 4
State: Off Throughput: 0 Parts/Hour State: Off Throughput: 0 Parts/Hour
I/O 2 I/O 4
State: Off State: Off
Throughput
Based on the sensor signals, the throughput of the individual zones is determined.
For this, the signals of the last five minutes are extrapolated to one hour.
This means that the system must have been running for at least five minutes.
The counters are active in all operating modes.
Not a real-time status. Status changes are only visible once the web browser has been refreshed ("F5" key).
I/O 1 I/O 3
Type : PNP NPN Type : PNP NPN
Polarity : positive negative Polarity : positive negative
Function : PLC Input Function : PLC Input
Sensor 2 Sensor 4
Type : PNP NPN Type : PNP NPN
Polarity : positive negative Polarity : positive negative
ON Delay [ms] : 0 ON Delay [ms] : 0
OFF Delay [ms] : 0 OFF Delay [ms] : 0
I/O 2 I/O 4
Type : PNP NPN Type : PNP NPN
Polarity : positive negative Polarity : positive negative
Function : PLC Input Function : PLC Input
Function Description
None -
PLC input Input signal from the PLC
PLC output Output signal to the PLC
Sensor 5 Start sensor zone 1 (polarity must be negative)
Sensor 6 Spare
Sensor 7 Spare
Sensor 8 Spare
Control input 1 Stops zone 1
Control input 2 Stops zone 2
Control input 3 Stops zone 3
Control input 4 Stops zone 4
Control input 5–8 No function
Control output 1 Zone 1 occupied
Control output 2 Zone 2 occupied
Function Description
Control output 3 Zone 3 occupied
Control output 4 Zone 4 occupied
Control output 5–8 No function
Handshake in up Handshake signals to neighbouring ZPA modules
Handshake in down
Handshake in left
Handshake in right
Handshake out up
Handshake out down
Handshake out left
Handshake out right
VDC motor #1 error in VDC motor error input
VDC motor #2 error in
VDC motor #1 direction out VDC motor directional rotation
VDC motor #2 direction out
VDC motor #1 step pulse out VDC motor pulse output
VDC motor #2 step pulse out
Not activated The aux outputs are reset when the RollerDrive voltage is switched off and cannot be
controlled.
Activated The Aux outputs keep their current status when the RollerDrive voltage is switched off and can
still be controlled.
The functions vary depending on the selected control program (see the description of control programs in
the "MultiControl / RollerDrive - Start-up and Programming" supplement).
Press the "Submit" button to transfer the modified parameters to the MultiControl.
Control Timer
Timer 1 [ms] : 0
Timer 2 [ms] : 0
Timer 3 [ms] : 0
Timer 4 [ms] : 0
Submit Reset
ZPA single release program ZPA train release program ZPA module program No ZPA program ID
ID ID ID
Single release 1 zone Train release 1 zone ZPA transfer in I/O device
Single release 2 zone Train release 2 zone ZPA transfer out
Single release 3 zone Train release 3 zone ZPA merge
Single release 4 zone Train release 4 zone ZPA HPD
HPD semi automatic
Transfer semi automatic
Control Timer
Timer 1: Single release: Transfer communication time
Train release: Time-delayed start of the RollerDrive
Timer 2: Internal monitoring of the material to be conveyed
Timer 3: RollerDrive overrun
Timer 4: Error reset
The functions and default settings for the timers vary depending on the selected control program (see
the description of control programs in the "MultiControl / RollerDrive - Start-up and Programming"
supplement).
Press the "Submit" button to transfer the modified parameters to the MultiControl.
Error State
Error State
Error Info
State : Operational
Active Error : BusComFail (21)
Last Error : 00:02:29:756 51 DriveError #2
Submit Reset
Network error
Monitoring of communication between MultiControl and PLC:
Ignore: Error is not displayed.
Warning: Error is indicated by fault LED flashing twice.
The conveying process is not interrupted.
Immediate stop: Error is indicated by fault LED flashing twice.
The conveying process is interrupted.
Motor error
Monitoring of the motors:
Ignore: Error is not displayed.
Warning: Error is indicated by fault LED flashing three times.
The LED goes out when the error is no longer present. Further motors connected to the
MultiControl rotate.
Immediate stop: Error is indicated by fault LED flashing three times.
Further motors connected to the MultiControl stop.
Error log for the most recent errors/messages with time stamp.
For an explanation of error codes, see „Error codes“ on page 62.
Teach-in
WARNING
Risk of crushing due to unintentional start-up of the RollerDrive!
¾ Changes in this menu have direct influence on the connected RollerDrive!
¾ Before starting motors make sure, ensure that no persons are present in the hazardous areas surrounding
the conveyor system!
Teach-in
Teach-in Feature
Please read the manual before trigger any of the options below!
Init
Start
Finish
Abort
Submit Reset
Plug&Play
Plug&Play
Plug and Play Feature
Enabled Submit
The "Teach-in" and "Plug&Play" functions are described in the "MultiControl / RollerDrive - Start-up and
Programming" supplement.
CAN Gateway
CAN Gateway
CAN Bus Terminal
Send
Submit Reset
¾ To change the password, enter the old password followed by the new password twice and transfer this to the
MultiControl by pressing the “Submit” button.
Yes
No
Submit Reset
NOTE
Irreparable damage to the MultiControl due to premature shutdown of the supply voltage
¾ Ensure that the power supply is not interrupted until the restart is complete. This process takes approx. two
minutes.
CAUTION: A restart of MultiControl will stop the control process and interrupt the network connection.
Do you want to restart MultiContol now?
Yes
No
Submit Reset
While the MultiControl is being restarted, the existing bus connection to the computer or PLC is interrupted
and this must subsequently be restored.
Display of the version, serial number and software version of the MultiControl.
Service – Up-/Download
Up- Download
Download Upload
For download under a different name, please use „Right Click --> Save To make settings effective, please restart module afterwards!
As...“-option Bus Config : upload
Bus Config : download Application Config : upload
Application Config : download
The MultiControl settings can be downloaded via the user interface and saved to a computer. By storing this data, the
settings can be restored when the MultiControl is replaced.
¾ Right-click on the desired file and select “Save as” to save to the connected PC.
NOTE
Irreparable damage to the MultiControl due to premature shutdown of the supply voltage
¾ Ensure that the power supply is not interrupted during the entire process of changing the bus type until the
restart is complete. This process takes approx. two minutes.
Further information can be found in the "MultiControl / RollerDrive - Start-up and Programming"
supplement.
Further information can be found in the "MultiControl / RollerDrive - Start-up and Programming"
supplement.
Ethernet/IP, Object Class Adapter = 0x64, Get Attribute Single, Set Attribute Single
Profinet, HW Identification acyclic access point, RDREC, WRREC
6.6 Operation
WARNING
Risk of crushing due to unintentional start-up of the RollerDrive!
¾ Before switching on the power supply, ensure that no persons are present in the hazardous areas
surrounding the conveyor system!
¾ In ZPA mode, all connected RollerDrives carry out an initialization run for a maximum of four seconds after
switching on the supply voltage!
When the MultiControl is functioning as an I/O device, it cannot start or stop motors or carry out other
actions independently. To do this, it requires commands from a higher-level control system, e.g. a PLC.
Take the ambient conditions into account during operation (see „Technical Specifications“ on page 19).
Start
¾ Ensure that the ambient conditions are maintained during operation (see „Technical Specifications“ on page 19).
¾ Switch on the power supply.
¾ MultiControl BI: After switching on the motor voltage, wait 30 seconds until all connected RollerDrive are
initialized.
¾ Send the corresponding signal to the MultiControl.
Stop
The conveyor system will stop under the following circumstances:
• When the power supply is switched off
• When no start signal is present
• When an error from a corresponding error class is present (see „Error Handling Settings“ on page 45)
CAUTION
Risk of injury from following incorrect procedure.
¾ Maintenance and repair work must only be carried out by authorised and trained (specialist) personnel.
¾ Maintenance and repair work must only be carried out when the system has been disconnected from the
power supply. Switch off the power to the MultiControl and ensure that it cannot be unintentionally switched
on again.
¾ Put up signs to indicate that maintenance or cleaning work is being carried out.
7.1 Maintenance
Checking the MultiControl
The MultiControl itself requires no maintenance. However, in order to prevent faults from occurring, the connections
and fixings must be examined on a regular basis.
¾ In the course of regular inspection and maintenance work on the conveyor, ensure that the screws of the
MultiControl are still tight, that the cables are still arranged correctly and that the corresponding connections
are correctly attached.
Replacing the MultiControl
If a MultiControl is damaged or defective, it must be replaced.
¾ Install a new MultiControl (see „Decommissioning“ on page 65 and „Assembling the MultiControl“ on page 22).
¾ Configure the new MultiControl (see „Start-up and operation“ on page 31).
7.2 Cleaning
Under humid conditions, dust and dirt can cause a short circuit. Therefore, ensure dirty environments are cleaned
regularly to prevent short circuits that could damage the MultiControl.
NOTE
The MultiControl can be damaged if it is not properly cleaned.
¾ Never immerse the MultiControl in fluids.
General LEDs
If several errors occur at the same time, only the error with the highest priority is displayed.
Connection LEDs
8.2 Troubleshooting
The MultiControl is a complex system. There are many correlations between all participants in the system. In such a
system, errors are of course likely to occur, either as a result of the conveying processes or the interaction between
the individual components. Not all errors can be displayed in detail and it is not always possible to make a correlation
between the error location and the place at which it is displayed. More detailed error diagnosis is possible via the
PLC.
If you are not able to successfully troubleshoot the problem or eliminate the error, contact Interroll Support and have
the following information to hand:
• Serial number of the affected MultiControl
• Information about the configuration
• Information about the LED displays
• Information about the error codes
The MultiControl is defective or Internal fuse has been triggered or is ¾ Replace the MultiControl
damaged defective
Error codes
CAUTION
Risk of injury from following incorrect procedure.
¾ Decommissioning must only be carried out by authorised, qualified personnel.
¾ Only decommission the MultiControl when the system has been disconnected from the power supply.
¾ Switch off the power to the MultiControl and ensure that it cannot be unintentionally switched on again.
9.1 Decommissioning
¾ Remove all cables from the MultiControl.
¾ Loosen the screws that have been used to attach the MultiControl to the base plate and remove the
MultiControl.
¾ If the MultiControl is to be completely dismantled, also loosen the screws that have been used to attach the
base plate to the conveyor frame and remove the base plate from the conveyor frame.
9.2 Disposal
The operating company is responsible for disposing of the MultiControl according to correct procedure. In
doing so, the industry-specific and local provisions for disposing of the MultiControl and its packaging must
be observed.
10 Appendix
10.1 Accessories
Article Article number
Ribbon cable distributor S-1115717
Ribbon cable for power supply (25 m) S-1004030
High Performance power supply unit HP 5424 S-1113899
High Performance power supply unit HP 5448 S-1113900
Magnetic key S-64100210
MultiControl Y-cable S-1104460
MultiControl communication cable (3 m) S-1104438
MultiControl dummy plugs S-1104466
Pack:
3 x RollerDrive M8, plug-in
3 x sensor M8, screw-in
1 x communication M12, screw-in
RollerDrive EC310 extension cable (2 m) S-1004033
RollerDrive EC5000 extension cable (2 m) S-1113897
Cable bridge for ribbon cable S-1004028
Cable bridge for shielding S-1113876
EU Declaration of Conformity
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU
The manufacturer
conform to the applicable provisions and the associated CE marking in accordance with
the aforementioned Directives.
Jörg Schiffler
Product Compliance Officer
Interroll Engineering GmbH
Wermelskirchen 08.01.2019
© 2021 INTERROLL