GT22 Operation Manual

1. The gas turbine cycle involves three main stages: air compression, combustion heat addition, and expansion through turbines. 2. In the LM2500, air is compressed from 1 to 2 stages then heated in combustion from 2 to 3 before expanding to drive the high pressure and low pressure turbines from 3 to 4. 3. Key components are the multi-stage axial compressor, annular combustor with 30 fuel nozzles, and two-stage high-temperature turbine that drives the compressor and powers the output shaft.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
377 views

GT22 Operation Manual

1. The gas turbine cycle involves three main stages: air compression, combustion heat addition, and expansion through turbines. 2. In the LM2500, air is compressed from 1 to 2 stages then heated in combustion from 2 to 3 before expanding to drive the high pressure and low pressure turbines from 3 to 4. 3. Key components are the multi-stage axial compressor, annular combustor with 30 fuel nozzles, and two-stage high-temperature turbine that drives the compressor and powers the output shaft.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 72

1.

1 Basic Gas Turbine Theory


The practical process used within the General Electric design of the LM2500 uses the basic
gas turbine cycle, such as the Joule or Brayton cycles. The process can be broken up into
three main stages:

A. Atmospheric air is drawn in and compressed from 1 to 2 in the multi-stage


compressor. The compression process is adiabatic and reversible in the ideal
process, but has an isentropic efficiency of 85~90% in the real process.

B. Heat is added at a constant pressure from 2 to 3 in the combustion chamber.

C. The heated and compressed air is expanded from 3 to 4. The expansion process is
also adiabatic and reversible in the ideal process, as with the compression process.
With the twin spool arrangement of the LM2500, the expanded work occurs in two
stages; the high pressure turbine (which drives the compressor) and the low
pressure turbine (which drives the output shaft).

At point 4 the working substances (air) (and the combustion gases) are returned to the
atmosphere again in a constant pressure process.

The gas turbine engine is often referred to as an external combustion engine because the
combustion processes occur in devices that are separate from their work developing
engines (turbines).

Figure 1
If each turbine has its own isentropic efficiency then the cycle can be shown on a
T~ s diagram as shown below

Figure 2

Line 1-2 represents irreversible adiabatic compression between P1 and P2


Line 2-3 represents constant pressure heat addition in the combustion chamber
Line 3-4 represents irreversible adiabatic expansion between P 2 and the turbine inter-
stage pressure Pi
Line 4-5 represents irreversible adiabatic expansion between the inter-stage pressure
Pi and P1

Line 1-2s represents ideal isentropic compression between P1 and P2


Line 3-4s represents ideal isentropic expansion between P2 and Pi
Line 4-5s represents ideal isentropic expansion between Pi and P1
Figure 3

This graph illustrates the relationship between the energy input at the combustor, and the
useful energy output at the LP turbine. The compression stage changes the pressure from
inlet pressure, P1, up to the operating pressure of the combustion unit, P 2. At this stage
energy is added and the entropy will increase. The energy required to drive the compressor
absorbs most of the energy available after the combustion chamber. The remaining energy
is used by the LP turbine to drive the output shaft. The two turbines drop the pressure from
P2 to P1.

1.1.1 Compressor Stage


To develop the high pressure ratios required, multi-stage axial compressors are employed.
The LM 2500 uses a 16 stage, axial-flow compressor developing a 17:1 pressure ratio. As
each stage operates at the same speed, it is possible that the first compressor stages could
be overloaded, and later stages would operate inefficiently at some compressor rotor
speeds. To avoid this problem, variable stator vanes are required.

The inlet guide vanes and the first six stages of stator vanes are controllable in pitch, and
are modelled in the programme as the Variable Stator Vanes (VSV). The pitch is
controllable in order to match aerodynamically the low-pressure stages of compression to
the high-pressure stages and to prevent stall. The variable vanes allow the compressor
stator blades to attain the correct angle of attack over the wide range of the turbine
operation. The angles of the blades are adjusted to compensate for changes in compressor
rotor speed.
This adjustment will prevent the air flow within the compressor stalling (also called
surging), and is required for the first stage of the compressor only. By utilising this method
of stall prevention in the early stages, the problem of choking in the latter compressor
stages can also be reduced.

1.1.2 Combustion Stage


The Combustion Chamber is where the energy input, in the form of heat, is added to the
gas turbine system. The LM2500 unit uses an annular combustor design with 30 fuel
nozzles arranged around its periphery. This combustion unit configuration is very compact,
and it widely used within industrial gas turbine units.

The combustor requires a constant flame, which is achieved by spraying or atomising the
gas oil fuel. Combustion occurs within three stages; the first is the primary zone, where 15
to 20% of the air is introduced around the fuel spray, (in the same direction of flow), to
generate the high temperatures required for rapid combustion.

The second stage then admits another 30% of the air through holes in the flame tube to
complete the combustion process. The air holes that admit the air must be carefully
positioned to avoid chilling the flame, and hence producing uneven or delayed combustion.
The final stage is the dilution stage, where the remaining air is mixed with the products of
combustion to cool them to the required temperature required at entry to the high pressure
turbine. This stage must provide sufficient turbulence between the combustion products
and the air to ensure that the temperature distribution of the gas stream leaving the
combustor is even, as high temperature areas would damage the turbine blades.

The type of burners used in gas turbines are very similar to those used in modern steam
boilers, namely spill and duplex burners. Both are used to achieve good atomisation of the
fuel across the full range of fuel flow. In the duplex burner, two orifices are used, each
with its own supply channel. The small central orifice is used for small flows, whilst the
outer larger orifice is used for the full load flows. Fuel pressure alone is used to achieve the
atomisation process rather than air or steam assistance, although air is admitted through the
burner tip on its periphery to maintain the burner tip free from carbon deposits.

Under normal operating conditions, the combustion within the gas turbine is self
maintaining. The ignition and starting systems are used to initiate this combustion process.
With the separate power turbine used for the LM2500, only the gas generator has to be
started by the external means. During the start (by either the air or hydraulic start unit) the
compressor must rotate at sufficient speed to generate the quantity of air required. An
igniter plug is situated within the primary combustion zone, and the high intensity surface
discharge of the igniter provides the energy required to initiate combustion. The flame
produced will then “light round” the annular combustion chamber. To ensure a long igniter
life-time the igniter is situated just within the outer edge of the fuel spray. As the igniter
can discharge up to 100 sparks per minute, the igniters require renewal after a period of
operation.

For the LM2500 unit, using liquid fuel, the hot section and combustor will need to be
refurbished after 16,000 hours of operation (about two years at base load). After 50,000
hours (six years at base load), the entire engine will need to be overhauled..

1.1.3 Turbine Stage


After the combustion chamber, the hot gases travel to the high pressure turbine. To ensure
that the casing temperature is not excessive, and hence a danger to ignite any oil sources
present, then the casing is cooled by air. A gap is provided in the wall or casing skin, so
that coolant air can travel along it.

The gases then reach the turbine stages, which on the LM 2500 Gas-Generator Turbine is a
two stage, high-temperature, high-pressure air cooled turbine. This turbine drives the
compressor and the auxiliary drive gear box. The turbine utilises the axial design, so that
engineers familiar with steam turbine designs would recognise the fixed nozzle blades, and
rotor blades. The main difference between the gas and steam turbine would be the
operating temperatures of the turbines. The gas temperature entering the high pressure
turbine would be in the region of 1300K or 1030oC. This means that the blade metal
temperatures would approach this level, and thus the blade material and blade cooling must
be designed for the purpose. The cooling of the turbine blades is by air (hence the term air
cooled turbine), which is passed through the blade, exiting by small or porous holes along
the blade surface. Cooling of the blades allows the turbine to operate at these high
temperatures, and hence provide improved overall thermal efficiency of the turbine unit.

Figure 4

The materials used for these high temperature duties are classed as “superalloys”, such
high-chromium, carbide strengthened, cobalt base superalloy, or cast, precipitation
hardened, nickel based superalloy. As well as utilising special alloys, the process of
manufacture is improving to include directional solidification (to align the material crystal
in the radial direction) and even single crystal castings.
In the low pressure turbine, the temperatures are lower, with an inlet temperature of 1100K
or 850oC, thus the blades are no longer required to be cooled, and the material specification
is reduced to high strength, nickel based alloys.
1.1.4 Basic System Calculations
For the LM2500 unit simulated within this model, the output power from the LP turbine is
20MW. The following data is taken from the simulation model when operating at this
power output.

On electrical load On water brake load


Output power 20 MW 20 MW

Ambient or inlet 30oC 30oC


temperature
Compressor outlet 16.8 bara 16.8 bara
pressure
Fuel input flow 4745 kg/hour 4710 kg/hour
Calorific value of fuel =
42MJ/kg
Power turbine inlet 820oC 819oC
temperature
Power turbine inlet 3.88 bara 3.86 bara
pressure
Specific fuel consumption 237.6 g/kWh 236 g/kWh

Power turbine speed 3600 rev/min 3600 rev/min

Gas generator speed 9400 rev/min 9380 rev/min

Table 5

To illustrate the various pressure, and temperatures within the system, a basic calculation
will be used. This calculation does not illustrate the mathematical modelling used, and is
only to gain an understanding of the system thermodynamics.

The intake conditions are set at 30oC or 303K and 0.98 bara. (note all pressures and
temperatures for calculations will be quoted in absolute units of bara and K).

If isentropic compression is assumed, then at the operating temperatures c p for air = 1.05
kJ/kg K and  = 1.39.

Thus as the compressor discharge pressure is given from the model as 16.8 bara, then from

616K
Considering isentropic efficiency, then from and using an isentropic

efficiency of 90%, then the compressor discharge temperature would rise to 650.8K

From text book reference graphs 3, the temperature rise within the combustion chamber can
be found.

An Air/Fuel ratio of 50 will be assumed, and this produces a temperature rise of 715K
within the combustion unit, at the inlet temperature of 650K. This figure can be checked
with the heat input from the fuel. The model gives an average fuelling rate of 4728 kg/hour
or 1.31 kg/sec. This equates to a heat input of 56.2 MW for the calorific value of the fuel
used. (See variable page 50000 for Calorific Value used within the model.)

This heat input gives a first estimate of turbine thermal efficiency of 20/56.2 = 35.6%

Equating the heat input with the increase in air temperature

From Q = mair x Cp x T, then 56.2 x 103 = (50 x 1.31) Cp T.

At these temperatures and with the A/F ratio of 50, then Cp = 1.18 kJ/kg K,
so T = 727K, similar to the empirical result from the graphs.

Hence the temperature at inlet to the high pressure turbine is 651 + 715 ≈1366K.

The work done within the high pressure turbine equates to the work absorbed by the
compressor it is driving, hence the temperature drop across the high pressure turbine can
be found.
From mair Cp T = mgases CpT, and equating the mass flow of air, with the mass flow of the
air and gas, then

65.5 x 1.05 x (651 – 303) = (1.02 x 65.5) x 1.18 x T

hence the temperature drop across the high pressure turbine is 303K.

This produces a temperature at inlet to the power turbine as 1366 – 303 = 1063K.
This compares with the simulation model figure of 1093K at full load, a difference of 30K.

The simulation model also predicts a power turbine inlet pressure of 3.87 bara.
With the expected power output of 20MW, then with Cp = 1.14 kJ/kg K at these
temperatures and air/fuel ratio’s, thus the temperature change expected in the power
turbine will be 20/65.5 x 1.02 x 1.14 = 263K,
hence the turbine outlet temperature will be 800K or 527oC.
Finally the calculation of the specific fuel consumption is the quantity of fuel consumed for
a given output. Thus SFC = 1.31 x 3600/20 x 103 = 235.8 g/kWh.

These figures suggest the temperature and pressure stages within the gas turbine cycle, and
when isentropic efficiencies are taken into account they should be modified.

STAGE Temperature (oC) Pressure (bar gauge)


Compressor inlet 30 -0.02 bar
Compressor outlet 378 15.8
Combustion inlet 378 15.8
Combustion outlet 1093 15.8
High pressure turbine in 1093 15.8
High pressure turbine out 790 2.9
Power turbine inlet 790 2.9
Power turbine outlet 527 0.0

Table 6 Ideal calculated values

By understanding the expected pressures and temperatures within the gas turbine, then the
engineer should become more aware that turbine operations are outside the normal
operating range, rather than rely on the functioning of the alarm channels.
1.2 GT-LM2500 Training Package

Fig. 7 “GT Load System”

1.2.1 Model Software


The Gas Turbine simulation software uses two General Electric LM2500 gas turbines
units. Each of these units can be connected to either an electric load or a water-brake via
reduction gears, as shown in Fig 1. Hence the load can be changed with:
 Operation at constant speed when using the electric load, or
 Operation using the water brake at either the propeller law (Power  Speed 3 ) or power
as a function of both speed and torque

The General Electric heavy-duty gas turbine is a two-shaft gas turbine. The gas turbine
model GE-LM2500 comprises a single spool gas generator followed by a power turbine.
1.2.2 Main Particulars

Type GE LM 2500-30 (General Electric)


Power 19700 kW
Speed 3600 rpm (Power Turbine)
SFC 237 g/kWh (at 100% load)

Figure 8 Gas turbine module within housing


1.2.3 GE LM2500 System
This graph illustrates the change in output power when the ambient temperature changes.
The broken line shows the temperature of the gas generator output for the differing power
and ambient temperature changes, and it is this parameter that limits turbine output.

Figure 9 1
Figure 10 Gas turbine and generator assembly

The LM 2500 system comprises the four major assemblies:


1. Base Enclosure Assembly, comprising
- base structure and shock mounts
- enclosure
- inlet components
- exhaust components
2. Gas Turbine Assembly, comprising
- inlet components
- gas generator
- compressor
- compressor discharge chamber
- combustor
- high pressure turbine
- accessory drive system
- low-pressure turbine (or power turbine)
- high speed coupling shaft
- exhaust components
3. Lube Storage and Conditioning Assembly
- This is remotely located from the gas turbine and incorporates an oil
storage tank, a heat exchanger, a duplex filter and a scavenge oil check
valve. It supplies cooled and filtered lubrication oil to the gas turbine.
4. Advanced Engine Control Module (AECM)
- This is the control interface between the gas turbine module and the
local operating panel (LOP). It provides the fuel command to the gas
turbine, and includes the automatic start/stop sequence programs,
overspeed and overtorque protection, as well as the other control and
protective functions.
- The AECM is not shown as the usual console in the engine room, but its
main functions will be included in the simulator model.
Basic operating principle of the gas turbine unit

Figure 11

During gas turbine operation, air from the inlet section enters the compressor where its
pressure is increased. The compressor is a multistage axial flow compressor and consists of
a rotor and a stator within a casing.

Figure 12 Compressor stator arrangement showing VSV Actuator


The high-pressure air is then directed into the combustion section where it is mixed with
fuel and ignited, raising its temperature.
Fuel preparation, mixing, and burning takes place in the combustion section, which
consists of the combustor, the fuel manifold, fuel nozzles, and igniters.
The combustor is annular and consists of four major components riveted together cowl
(diffuser) assembly, dome, inner skirt, and outer skirt. The whole assembly, in conjunction
with the compressor rear frame, serves as a diffuser and distributor for the compressor
discharge air. It furnishes uniform air flow to the combustor throughout the operating
range, thereby providing uniform combustion and even temperature distribution at the
turbine.

Thirty vortex inducing axial swirl cups in the dome (one at each fuel nozzle tip) provide
flame stabilization and mixing of the fuel and air. The interior surface of the dome is
protected from the high temperature of combustion by a cooling air film. Accumulation of
carbon on the fuel nozzle tips is prevented by venturi-shaped spools attached to the swirler.

Figure 13 Annular Combustor

Primary combustion and cooling air enters through closely spaced holes in each ring of the
annular construction.. These holes help to stabilise the flame in the centre of the system,
and admit the balance of the combustion air.
Dilution holes are employed on the outer and inner liners for additional mixing to lower
the gas temperature at the turbine inlet. Combustor/turbine nozzle air seals at the aft end of
the liners prevent excessive air leakage while providing for thermal growth.
The hot gases from the combustor are directed into the high-pressure turbine, where power
is extracted from the gas stream to drive the compressor rotor. The high-pressure turbine is
mounted on the same shaft as the compressor. The compressor consumes approximately
75% of all the energy available from the combustion process. The remaining energy is
available for useful work from the power turbine.

From the high-pressure turbine the gases, now at reduced pressure and temperature, are
ducted into the low-pressure turbine (or power turbine) and through the exhaust section
into the exhaust collector. The power turbine is the component of the gas turbine engine
that produces useful work. The power turbine rotor is directly mounted on the output
power shaft, which drives aft through the exhaust collector.

Figure 14 Power turbine element

The exhaust section consists of the inner and outer duct forming the diffusing passage from
the power turbine rear frame into the exhaust collector.

Each gas turbine is separately surrounded by a noise-reducing and airtight enclosure. The
enclosure is resiliently mounted on the foundation with shock mounts.

Figure 15
Resilient mounting
Figure 16 Comparison of the family of GE LM2500 gas turbine units

The gas turbine model used within this simulator package is the LM2500 series.
To provide additional power many modern marine plants are specifying the higher output
of 25MW from the LM2500+ gas turbine, which is physically a larger unit as shown in
Fig 16.

Both the LM2500 and LM2500+ units are classed as free power turbine units, in that the
power turbine is not mechanically connected to the gas generator or compressor as shown
in Fig 17. This arrangement provides greater flexibility for the power turbine to operate at
a speed different to the gas generator section.

Figure 17 Overview of the configuration of the gas turbine


The basic sub-systems of the gas turbine are:

a) starting air system


The purpose of the starting air system is to drive the gas generator mechanically to
a speed at which the gas generator can start. The starting air system is also used to
water wash and motoring the gas generator in certain maintenance tasks.

b) ignition system
The ignition system is used to initiate combustion during the start sequence. It
produces high-energy sparks that ignite the mixture of air and fuel in the
combustion chamber when starting the gas generator.

c) fuel system
The fuel system supplies filtered fuel to the gas turbines pumping from the day
tanks to the engines via booster pumps and oil/water separators.

d) engine fuel system


The engine fuel system delivers a metered flow of fuel, recirculates fuel, or routes
fuel depending on the selected mode of operation. It also positions the compressor
VSV's to regulate primary air flow through the engine during all modes of
operation.

e) lubrication system
The engine lubrication system circulates, cools, cleans and contains the flow of
lubrication fluid through the gas turbine gearboxes and sumps.

f) bleed air system


The bleed air system permits to extract high pressure air from the compressor
discharge chamber to warm-up the ship inlet duct of each engine, and avoid icing.

g) fire detection and extinguish systems


Fire detection in the gas turbine is provided by the gas turbine fire system which
stops the engine and extinguish the fire by using CO2.

h) sensing systems
Extensive monitoring capability of all significant systems functions is provided by
numerous probes and sensors located at strategic points throughout the gas turbine
and its associated equipment.
1.3 Fuel Supply System MD200

Figure 18

The main components of the fuel supply system are:


- fuel pump suction filter
- booster pump with relief valve
- coalescer filter, with water drain
- expansion tanks
- pneumatically actuated quick closing valves

Fuel from the day tanks is supplied to the booster pumps, which supply the 3 bar delivery
pressure to the module fuel inlet located on the floor of the base enclosure. This supply
pressure is maintained constant by a bleed line that relieves to the expansion tank fitted
above the fuel supply system. The expansion tank then overflows excess fuel back to the
day tank.

If the overflow shut off valve (between the expansion tank and the day tank) is closed, the
expansion tank will be filled by the booster pump and flooded. The simulator model will
cause any overflow of the expansion tank to trigger an engine space fire.
1.3.1 Operation

1. Open outlet valves from the day tank


2. Open the booster pump suction and delivery valves
3. Open the supply valves to the gas turbine.
4. Open overflow shut-off valve from expansion to day tank.
5. Start booster pump.
6. Refill day tank, when required.

NOTE! The water drain of filter is not modelled in detail, but included for
procedural purpose.
1.4 Lubrication Oil System MD201

Figure 19

The lubrication oil system consists of:


- oil storage tank
- lube supply and scavenge pump
- supply oil filter (duplex)
- supply check valve
- scavenge oil filter (duplex)
- oil cooler
- air / oil separator (within oil storage tank vent)

Three separate flows are maintained through the system:


1. Lubricating oil supply,
2. Lubricating oil scavenge or drain system
3. Sump vent.

The lubricating supply and scavenge pump is driven from the power turbine output gear
box.
The oil is fed by gravity from the storage tank to the supply lubricating oil pump. The
pump discharges through a duplex supply oil filter and is delivered into a distribution
manifold through the supply check valve. This supply oil supplies the nozzles that spray
directly on the gears, bearings and splines.
The oil from the gears and bearings drains out of the gearboxes and oil sumps, where the
scavenge oil pump evacuates these drains through the duplex scavenge filters and system
oil cooler before returning the oil back to the oil tank. Thus filtered and cooled scavenged
oil is stored in the lube oil storage tank. Entrained air and other gases are vented to the
atmosphere through the tank demister/flame arrester.

A scavenge check valve is provided between the filters and cooler to prevent the back-flow
of the oil into the gas turbine sumps and gearboxes after engine shutdown.

The sump vent flow prevents excessive oil consumption by reclaiming vaporised oil out of
the vent air exhausted from the gas turbine sumps. This reclaiming is carried out by the
air / oil separator (not shown), and drains into the lubricating oil storage tank.

1.4.1 Operation

1. Open one supply filter


2. Open one scavenge oil filter
3. Check that the oil storage tank is over 50% full
1.5 GT Starting / Ignition System MD202

Figure 20

The main components of this system are:

- high pressure air bottles


- air reduction station
- starter air regulating valve
- pneumatic starter
- ignition exciter boxes
- spark igniters

From the high pressure air bottles (250 bar) available for each gas turbine, the air flows
through the air reduction valves where the pressure is reduced in two stages (250 to 20 and
then 20 to 3 bar) to get the ideal pressure to start the gas turbines. Shut-off valves are
provided before and after the reduction air valves, and to isolate the air circuits from each
turbine starter.
In case of air system failure the air circuits are interconnected. The storage capacity of the
high pressure air is sufficient to start the gas turbines four consecutive times, under worst
conditions within a 60 seconds start sequence.

The starter air regulating valve is a solenoid controlled air actuated butterfly valve, capable
of providing two regulated air outputs; one for starting and another for motoring.

When performing maintenance tasks in the gas turbines, which may need to motor the
turbine at low speed, such as for water washing the turbine, the push-buttons on the screen
MD202 should be operated.

The pneumatic starter consists of a high-speed turbine driving an output shaft through a set
of reduction gears and an over-running clutch assembly. During start sequence, when the
speed of the gas generator (NGG) exceeds 4500 rev/min, the flow of air to the starter is
stopped by de-energizing the starter air regulating valve, and the starter overrunning clutch
is thus disengaged.

Start sequence
During the start sequence the gas turbine is driven up to idle speed. This sequence is
divided into three phases:
1. cranking,
2. light-off, and
3. acceleration to idle.

1. Upon opening the starting air regulating valve, the pneumatic starter begins to rotate
and produces the necessary torque to drive the gas generator and increases its speed. As
the turbine is cranked and the gas generator speed increases (cranking operation),
lubricating oil pressure will increase.

2. Fuel is not yet admitted to the turbine. When the gas generator reaches 1200 rpm the
Advanced Engine Control Module (AECM) activates the ignition exciters, and after a
delay of 1 to 2 seconds energises the fuel shutdown valves. At this point the air and
fuel flow are sufficient to initiate and sustain combustion, and light off commences
within the combustion chamber. The gas generator (compressor and high-pressure
turbine) rotor is now driven by the combined efforts of both the starter and the ignition
combustion gases.

3. When gas generator speed (NGG) reaches 4500 rpm the AECM disables the starter and
de-activates the turbine igniter system. At this point the gas generator rotor will
continue to accelerate to idle speed with no further assistance from the starting and
ignition components.

If fuel is injected before the ignition exciters are activated, there will be an abnormal start.
Depending on how much fuel that is injected, there will be a degree of 'hot start' (with
possible damage of the gas turbine) or the ignition exciters could fail as no spark can be
generated when they are wetted by the fuel.
1.6 Water Wash System
Onboard - periodic water washing of the gas turbine compressor and high pressure turbine
are required to maintain engine performance at rated levels.

Water wash is performed by:


 motoring the gas turbine,
 injecting a cleaning solution into the gas turbine main gas flow path
 providing a 15 minutes soaking period, and then
 motoring the engine again several times with water.

A complete water wash should be performed every 72 hours of running time (depending
upon the quality of fuel used). Off line cleaning should not be initiated until the engine
skin temperatures have dropped to 93°C or lower. Also water washing should not be
carried out when the ambient temperature is below 10°C.

The modelling of this system is simplified, with just a 'water wash' start command that
represents the above-mentioned procedure on the simulator.

Within the compressor model a certain rate of contamination of the compressor during gas
turbine operation is incorporated. The water wash operation will reduce this contamination,
and hence compressor efficiency improvements after water washing are modelled.

1.6.1 Operation

1. The gas turbine must be stopped


2. Check the gas turbine temperature has fallen below 90oC
3. Press the water wash button, the “in progress” light will illuminate
4. Once the water wash operation is complete, the “finished” light will illuminate
1.7 Engine Fuel System MD203

Figure 21

The Engine Fuel System is comprised by the following components:


- Fuel Pump
- Fuel Filter
- Main Fuel Control (MFC)
- Fuel Pressurising Valve
- Fuel Shutdown Valves (2 off)
- Fuel Manifold
- Fuel Nozzles (30 off)
- Compressor Inlet Temperature (CIT) Sensor
- Fuel Purge Valve
- Fuel Purge Check Valve
- Variable Stator Vane (VSV's) and Variable Stator Feedback Cable

The gas turbine fuel system regulates and distributes fuel to the combustion section of the
gas generator, and thus controls the speed of the gas generator.
The power turbine speed is established by the gas stream energy level produced by the gas
generator. It is not directly controlled by the fuel system, as the power turbine has a
different shaft from the gas generator.

Fuel from the supply system flows through the base inlet connector to the shaft driven
pump where it is pressurised up to 90 bar, for admission to the combustion chambers
through the “Can Annular” type combustion chamber.

Three valves control fuel flow to the engine fuel manifold;


 2 fuel shutoff valves, and a
 fuel-metering valve.

A hydraulically actuated fuel flow control valve meters fuel flow to the turbine according
to turbine command signals, which are generated in response to changes in load demands
on the turbine engine. According to the valve position, a portion of the pressurized fuel is
used for turbine operation and the remainder is returned to the pump suction by the Main
Fuel Control (MFC) unit. To assure an adequate supply of fuel to the gas turbine operation,
the fuel pump has a higher fuel flow capacity than the gas turbine uses.

The MFC is the engine governor and contains a hydro-mechanical computer. The Power
Level Angle (PLA) actuator, the compressor inlet temperature (CIT) sensor and the
variable stator vane (VSV) feedback cable are associated units with the MFC. The PLA
actuator is an engine mounted unit that converts electrical throttle inputs coming from the
Advanced Engine Control Module (AECM). The CIT sensor is mounted on the compressor
front frame in the gas turbine inlet airflow path, and provides a hydraulic (by fuel) pressure
signal proportional to the inlet air temperature. The variable stator feedback cable is
connected to a bell-crank operated by the VSV master lever, and provides a mechanical
input to the MFC proportional to the degree of the VSV opening or closing.

The variable stator vane (VSV)


control is an electro-hydraulic
system consisting of an engine
mounted hydraulic pump, servo
valve, and VSV actuators with
integral linear variable differential
transformer (LVDT) to provide
feedback position signals to the
main engine control.

Figure 22
The primary control functions performed by these fuel system components are combustion
chamber fuel metering and VSV positioning. The fuel metering function regulates the
amount of fuel delivered to the combustor in order to control gas generator speed (NGG)

The VSV positioning function opens and closes the compressor variable stator vanes to
regulate the amount of primary airflow through the compressor, and prevent stalls within
the compressor stator vanes. VSV position is scheduled primarily as a function of N GG, and
secondly as a function of both the CIT sensor, and VSV position feedback.

At shutdown, the bypass solenoid valve opens in the MFC, opening the bypass valve in the
metering valve, so that fuel flow to the turbine is shut off and all liquid fuel flows to the
liquid fuel return line. The quick-closure shutoff valves are engine mounted, and are fail-
close valves that are either fully open, to allow fuel flow; or fully closed, to prevent fuel
flow.

During start-ups, the fuel control system first opens these shutoff valves, and then
modulates the metering valve in pre-set increments, as controlled by the MFC.
During normal shutdowns, the MFC first closes the metering valve in pre-set increments to
allow for turbine engine cooling. When the metering valve is fully closed, the MFC closes
the shutoff valves. In emergency shutdowns, the MFC initiates the immediate closure of
the metering valve and both the shutoff valves.

From the metering valve fuel is routed through the shutoff valves, to the liquid fuel
manifold and distributed to the 30 fuel nozzles. At shutdown and during coast-down
following fuel valve closure, the fuel shutoff valves drain any fuel from the manifold to the
fuel manifold drain.
1.8 GT - Fire Detection and Extinguish MD204

Figure 23

The fire detection and extinguishing systems consist of:


- two temperature switches
- three flame detectors
- a manual push button switch
- CO2 cylinders
- CO2 discharge nozzles

The temperature switches are mounted to the enclosure ceiling above the gas generator and
electrically connected in parallel. The electrical sensing circuit is normally open, and
closes when subjected to a temperature of 250°C or more.

The flame detectors are mounted to the ceiling at the forward end of the gas turbine
environment within the enclosure.
When a fire is sensed by any of the flame detectors or the temperature switches or if the
manual fire alarm is operated, the following simultaneous actions occur:
1. shut-down of the turbine mounted fuel shut-off valves
2. closing of external quick-acting fuel shut-off valve
3. closing of cooling air inlet vent damper
4. stopping of the post shut-down fan (if operating)
5. the fire alarm is activated
6. the fire alarm signal is indicated at screen MD204

From the initial alarm activation there is a delay of 20 seconds before the CO 2 is released
to allow the operator a positive verification of the fire. During this time, the release of the
CO2 can be inhibited by the inhibit switch on the MD204 screen display (“INH button”).

After the 20 seconds delay, an electrical-pneumatic-actuator is automatically activated and


the valves from the cylinders are opened allowing the flow of the CO 2 to the nozzles in the
enclosure of the gas turbine. An indication signalling that the CO 2 has been released is
indicated on MD204 (AUTO released).

The CO2 can also be released manually from the screen display, using the button “REL”
but the shut down procedures must be manually activated, as detailed in the items 1 to 6
shown above.
1.9 GT - Sensing systems MD300

Figure 24

Numerous probes and sensors are used to control and monitor the turbine unit whilst
running. They are located at strategic points throughout the gas turbine and its associated
equipment, and give important information to be used by the control system in performing
specific engine control functions and to indicate the main operating parameters to the duty
engineer.

Engine monitored parameters include:


1. compressor inlet total pressure (PT 2)
2. compressor discharge static pressure (PS 3) {Variable page 30001 for P30002 GT1,
and variable page 30011 for P40002 GT2}
3. power turbine inlet total pressure (PT 5.4)
4. power turbine inlet temperature (T 5.4)
5. gas generator speed (NGG)
6. power turbine speed (NPT)
7. gas generator and power turbine vibrations
The first six parameters are used by the Advanced Engine Control Module (AECM) to
compute the gas turbine power and torque. The AECM protects the power turbine against
overload and over-torque, hence changes in speed of the N GG can be observed every time
the power turbine limit conditions are reached.
A vibration monitoring system is installed in the software model to match actual LM2500
turbine monitoring. This will notify the engineer of excessive vibration in the power
turbine and/or generator, and is displayed on screens MD300 and MD821. Each
monitoring device has alarm and shutdown settings, which are set by the AECM unit.
1.10 Gas Turbine Operator Panels #1 MD820

Figure 25

The Gas Turbine operator panel #1 provides the following functions:

GG motoring: Push button, which is used during water washing of the


turbine. The turbine is then driven on air by the starting
system.
Fuel Purge Valve: Push button, this will purge the fuel system, and is activated
when the turbine shut-down is activated.
Vent Damper: Push button, this is opened for air entry into the turbine
housing. During normal operation this would be open, and
closed then the turbines is shut-down, or fire is detected
within the turbine enclosure.
Bleed air: Push button, this will circulate the heated air from the gas
generator to the compressor air inlet. This function is used
when the ambient temperature is low and the humidity is
high, but will reduce turbine plant efficiency.
Brake in/out: Push button, selects that the turbine brake is on or off
Emerg. Stop: Push button, closes the fuel shuts off valves on MD 203
Post shutd Fan on/off Push button, purges the turbine after stopping
Heater on/off Push button, pre-heats the turbine before starting
AECM mode: Push button, Advanced Engine Control Module in
Automatic, manual or aux. mode as required.

1.10.1 Operation

1. Check GT enclosure temperature is above 0oC. If not, then heater should be turned
ON. The heater coil will connect and disconnect automatically.
2. Open vent damper
3. Ensure gas turbine brake is off

1.10.2 Bleed Air System


This system is used when the gas turbine is used at low temperatures.

The bleed air system comprises the following main components:


- icing detector
- bleed air valves (electrically operated)
- hot air pipe work
- anti-ice noses

When the icing detector sensor reports an icing situation due to the outside air conditions
of temperature and humidity, the bleed air system should be operated by opening the bleed
air valves on MD820 in order to distribute the hot air along the anti-ice noses. In this
condition, the hot air feeds into the noses and is exhausted upwards through slots in the top
of each anti-ice nose and into the incoming inlet air stream, thus heating up the mixture.

The performance of the gas turbine is considerably reduced when the bleed air is opened,
as the air compressed by the gas generator is used for another purpose.
1.11 GT Local Operation Panel #2 MD821

Figure 26

This screen is used together with the Local Operation Panel #1 to operate and monitor the
operation of the gas turbine unit.

The following buttons are provided

Start Permi This indicates that starter permission is granted by the automation
control and monitoring system. Once this button is lit the turbine
start command can be activated.
Start Activation of this button will start the turbine on an automatic
programme.
Normal Stop This button will activate the automated turbine stop sequence.

PT O/S Reset This button will manually reset the over-speed of power turbine.

SEQ Reset This button will reset the automatic start sequence. It should be reset
before the automated start sequence is selected.
Start On/Off This button is selected when manual operation of the turbine is
required, and will over-ride the automated functions selected on
MD821.
Ignit On This button will automatically start the ignitor within the
combustion chamber.
Fuel On This button will open the shut-down isolation valves fitted on screen
MD203.

Emerg Over-ride This button will over-ride the shut-down functions of the gas
turbine. It could be used to prevent turbine shut-down.
Shutdown bypass This button will block the signal to the fuel bypass valve that dumps
the fuel entering the gas turbine on screen MD203. It could be used
when testing the turbine shut-down systems without causing the
turbine to shut-down.
Lost speed sign This button will over-ride the control shut-down that would occur if
the speed signal from the power turbine were lost.

Indication lights

Ready for start Indicates that the turbine is ready to start. This lamp will
light once the “Start Permission” button is pressed on this
screen, and all systems are operating.

Fail to reach 1200 rpm Indicates that the cranking operation using the starting air
starter has failed to reach 1200 rev/min.

Fail to reach 4500 rpm Indicates that the ignition start sequence has failed when the
turbine air starter is supplemented by the initial combustion
start-up.

Fail to light off Indicates that the ignition start sequence has failed.

GG inlet air icing Indicates that the air inlet temperature is below 0oC, and that
the bleed air system should be activated.

PT inlet temp high S/D Indicates that the temperature at inlet to the power turbine
has exceeded the safe limit, and that the turbine shut-down
has been activated. A fire could be present within the turbine
enclosure.

PT O/S switch shut down Indicates that the power turbine has exceeded the over-speed
limit of 4000 rev/min, and that the turbine shut down has
been activated.
Lube low press shut down Indicates that the oil pressure on MD201 at turbine inlet has
fallen below the shut-down limit of 1.3 bar.
PT inlet temp high Indicates that the power turbine temperature is above the
alarm limit of 900oC.

Lube supply low press Indicates that the lube oil pressure is below its alarm limit.

Normal stop initiated Indicates that the turbine stop has been initiated, and that the
turbine will now stop.

Stop failure Indicates that the turbine has not stopped within the expected
time scale. Manual intervention may be required (closing the
fuel inlet valves, or applying the turbine brake if NGG is low).

Normal stop complete Indicates that the turbine has now stopped.

Lube oil scav temp A Indicates that the oil temperature in sump A is above the
alarm limit of 120oC.

Lube oil scav temp B Indicates that the oil temperature in sump B is above the
alarm limit of 120oC.

Lube oil scav temp C Indicates that the oil temperature in sump C is above the
alarm limit of 120oC.

Lube oil scav temp D Indicates that the oil temperature in sump D is above the
alarm limit of 120oC.

Lube oil scav temp gear Indicates that the oil temperature in gear box sump is above
the alarm limit of 120oC.

Starter failure Indicates that the starter unit on MD202 has not operated
when activated.

Vibration GG Indicates that the vibration of the gas generator is excessive.

Vibration PT Indicates that the vibration of the power turbine is excessive.

PLA Act failure Indicates that the Power Level Angle (PLA) actuator is not
responding.

Fuel valve no current Indicates that the fuel shut-down valves on MD203 have no
current, and hence can not be opened.
Over torque Indicates excessive torque is being developed by the power
turbine.

PT speed limit Indicates that the power turbine has exceeded the speed limit,
but has not yet over-speeded.

GT cool air out high temp Indicates that the air temperature at outlet from the gas
turbine enclosure has exceeded the alarm limit of 175oC.

Vent damper closed Indicates that the vent damper on MD204 is closed.

Enclosure heater overtemp Indicates that the electric heater within the turbine enclosure
on MD204 has exceeded its temperature alarm set-point.

Exting. release inhibit Indicates that the CO2 release is manually inhibited on
MD204.

GT release unit power on Indicates that the gas turbine is running, and the fire
extinguishing system is ready to be activated if a fire is
detected.

Flame detector failure Indicates that the fire detection system for the turbine
enclosure on MD204 has failed.

Enclosure fire Indicates that the air temperature within the turbine enclosure
has exceeded the safe limit. If the automatic CO 2 release is
not inhibited within 20 seconds, then the automatic CO 2
release will automatically occur.

LOC outl temp high Indicates that the oil temperature at the outlet of the
lubricating oil cooler on MD201 has exceeded the alarm
limit of 100oC.

Lube tank high Indicates the oil storage tank on MD201 is at high level.

Lube tank low Indicates the oil storage tank on MD201 is at low level and
requires to be filled.
1.11.1 Start up and Shut down of Gas Turbines

Gas turbine start up procedure for gas turbine No 1 on Electrical generation


(using Automatic start)

1. Screen MD201 (Lube oil system)


 Check level in lube oil storage tank is above 50%
 Open one supply filter (V20103 or V20104)
 Open one scavenge filter (V20105 or V20106)

2. Screen MD200 (Fuel supply system)


 Check both day tank levels are above 50%
 Open day tank suction (V20001)
 Open booster pump suction valve (V20002)
 Open booster pump delivery (V20003)
 Open fuel filter discharge valve (V20005)
 Open fuel main supply valve (V20006)
 Start booster pump (R20001)

3. Screen MD207
 Check that the speed controller output is zero
 Place the speed controller in AUTO

4. Screen MD820 (GT1 Local operating panel No 1)


 Place AECM in AUTO
 Switch Heater on
 Take brake off

5. Screen MD821 (GT1 Local operating panel No 2)


 Press the “Vibr Test" button to test the vibration alarms prior to starting
 Press “Seq. Reset” button (Automatic sequence reset)
 Press “PT O/S Reset button (Power Turbine Over-speed reset)
 Press “Start Perm.” button. The blue “Ready to Start” light should illuminate
 Press “Start” button. (MD 202 will show the start sequence)

6. Once the Gas Turbine has started, the gas generator speed will exceed 4500
rev/min, and the starter valve will be closed, then using screen MD820
 Stop the heater
 Open the vent damper
7. Check the operating conditions of the gas turbine on MD300

Parameter Usual value Your value


Lube oil supply pressure 1.6 bar
Lube oil supply temp 32oC
Gas turbine speed 5000 rpm
Power turbine speed 1500 rpm
Fuel manifold pressure 21.4 bar
Power turbine gas temp 400oC
Power turbine air pressure 2.1 bar
Enclosure temp 105oC

Once you are satisfied that the gas turbine is operating normally, the gas turbine can be
placed on load.

8. On screen MD207
 Increase the power setting up to 37 in stages using the power control set point
(X82033). Note this value can be changed at various screen, such as MD205
and MD820.
 Observe the operating parameters on MD300 as you increase the turbine power.

9. On screen MD205
 Ensure the generator magnetism is switched on and set to 50.
 Clutch in the Generator clutch, the generator speed should increase to 60Hz,
and check that the generator terminal voltage is about 6600V.
 Check there is not breaker trip present, if so reset the breaker.
 Press CONN on the breaker control.

10. On screen MD207


1. Gradually increase the power control up to 75 achieve an active power output
(E30001) from the generator of 15 - 15.5 MW. The maximum power control
setting is 85.

11. Recheck the operating conditions of the gas turbine on MD300


Parameter Usual value Your value
Lube oil supply pressure 4.8 bar
Lube oil supply temp 36oC
Gas turbine speed 9000 rpm
Power turbine speed 3600 rpm
Fuel manifold pressure 49.2 bar
Power turbine gas temp 760oC
Gas turbine air pressure 3.5 bar
Enclosure temp 72oC
Gas turbine start up procedure for gas turbine No 2 on the Water Brake
(using Automatic start)

1. Screen MD251 (Lube oil system)


 Check level in lube oil storage tank is above 50%
 Open one supply filter (V20123 or V20124)
 Open one scavenge filter (V20125 or V20126)

2. Screen MD200 (Fuel supply system)


 Check both day tank levels are above 50%
 Open day tank suction (V20021)
 Open booster pump suction valve (V20022)
 Open booster pump delivery (V20023)
 Open fuel filter discharge valve (V20025)
 Open fuel main supply valve (V20026)
 Start booster pump (R20021)

3. Screen MD257
 Check that the speed controller output is zero
 Place the speed controller in MANUAL

4. Screen MD920 (GT2 Local operating panel No 1)


 Place AECM in AUTO
 Switch Heater on
 Take brake off

5. Screen MD921 (GT2 Local operating panel No 2)


 Press the “Vibr Test" button to test the vibration alarms prior to starting
 Press “Seq. Reset” button (Automatic sequence reset)
 Press “PT O/S Reset button (Power Turbine Over-speed reset)
 Press “Start Perm.” button. The blue “Ready to Start” light should illuminate
 Press “Start” button. (MD 252 will show the start sequence)

6. Once the Gas Turbine has started, the gas generator speed will exceed 4500
rev/min, and the starter valve will be closed, then using screen MD920
 Stop the heater
 Open the vent damper
7. Check the operating conditions of the gas turbine on MD300

Parameter Usual value Your value


Lube oil supply pressure 1.6 bar
Lube oil supply temp 32oC
Gas turbine speed 5000 rpm
Power turbine speed 1500 rpm
Fuel manifold pressure 21.4 bar
Power turbine gas temp 400oC
Power turbine air pressure 2.1 bar
Enclosure temp 105oC

8. To illustrate the differing load conditions, the procedure for the GT2 will using the
water brake for a load, so that the gas turbine load is dependant on the torque and
speed rather than constant speed operation. As the speed of the power turbine is no
longer fixed by the electrical supply (which is held constant at 60 Hz), then a speed
controller is necessary for stable gas turbine operation.

9. On MD257 (GT2 Speed controller).


 Input the following values into the speed controller

Tag and name Value


C25736 Speed controller gain 8.0
C25737 Speed controller I time 10.0
C25738 Speed controller D time 4.0
C25741 Speed controller FF1 gain 0.1
C25742 Speed controller FF1 TC 1 6.0
C25743 Speed controller FF1 TC 2 6.0
C25751 Speed controller FF2 gain 0.1
C25752 Speed controller FF2 TC 1 6.0
C25753 Speed controller FF2 TC 2 6.0

 Input the following tag names into the feedback and feed forward unit.

Tag number Tagname Function Graph lower Graph higher


limit limit
N25202 Power turbine speed Feedback 0 4000
E30001 Gas turbine power Feed forward 0 30
Q40001 Gas turbine torque Feed forward 0 50

10. On MD255, clutch in the water brake


11. On MD257
 Set speed setting at 1000
 Switch the feedback and feed forward units on,
 Place the controller in AUTO and ON.
 Gradually increase the speed set point from 0 up to 2000

12. On MD257
 Increase the speed set point slowly from 2000 up to 3600 rev/min in stages over
at least one minute

13. On MD257
 Input 10 to the Torque set point for the water brake (Q25511)
 Increase the torque set point up to 40 in stages noting the suggested loading
programme rate shown below (Increasing up to full load should take about five
minutes)
Figure 27

14. Recheck the operating conditions of the gas turbine on MD300

Parameter Usual value Your value


Lube oil supply pressure 4.8 bar
Lube oil supply temp 36oC
Gas turbine speed 9000 rpm
Power turbine speed 3600 rpm
Fuel manifold pressure 49.2 bar
Power turbine gas temp 760oC
Gas turbine air pressure 3.5 bar
Enclosure temp 72oC
Figure 28

The status of the gas turbines following the procedures carried out for:
 Gas turbine #1 operating under water brake load
 Gas turbine #2 operating under electrical load
Gas turbine start up procedure for gas turbine No 1 (using Manual start)

Screen MD 820
 Take brake off
 Open bleed air (if the environmental conditions below 10oC, see variable
page 40000)
 Ensure post shut-down fan is off
 Switch on heater
 Place AECM in MAN.

Screen MD 821
 Press the manual “Start ON/OFF” button
 The Starter valve open light will illuminate.
 When Gas Generator speed reaches 1200 rev/min,
- press the “IGNIT. ON” button, and then
- press the “FUEL ON” button
 When Gas Generator speed reaches 4500 rev/min,
- de-select the “IGNIT. ON” button
- De-select the “Start ON/OFF” button, if AECM has not already done so, and
the Starter valve open light will go dark.

Screen MD820
When Gas Generator speed reaches the idling speed of 5000 rev/min;
 Press the “Damper Open” and
 Place the AECM in AUTO
 Close the bleed air valve if opened
 Stop space heater

To read the value of the gas generator speed (GT1 GG speed), the screen analogue display
or the exact value on variable page 82100 could be used.
Gas turbine shut-down procedure for gas turbine No 1 (using Manual stop)

Assuming that the turbine is already unloaded from its electric or water brake load, then on
Screen MD 820
 Place AECM mode into manual.

Screen MD 821
 Press the manual “Normal Stop” button

Screen MD820
 Start “Post shutdown fan”

Screen MD821
 Monitor shut-down sequence. The gas turbine will cool down for about three
minutes before the fuel shut-off valves on MD203 will close to extinguish the
combustion unit.

Screen MD820
 Once the gas turbine has stopped, engage the brake.
Shut-down of the gas turbine #2 from an electrical load

1. On Screen MD255
 Reduce power control from current operating value to 30, over 5 minutes to
allow the gas turbine to cool.
 As the power control is reduced to 30, the breaker will be tested on Reverse
Power trip.
 Reset breaker after it has tripped
 Switch off the magnetism
 Disengage the clutch
 Reduce the power control from 30 to zero over 1 minute

2. On screen MD921
 Press “Normal Stop”

3. On screen MD920
 Start “Post shutdown fan”

4. On Screen MD921
 Monitor shut-down sequence. The gas turbine will cool down for about three
minutes before the fuel shut-off valves on MD253 will close to extinguish the
combustion unit.

5. On Screen MD920
 Once the gas turbine has stopped, engage the brake.
Shut-down of the gas turbine #1 from the water brake load

1. On Screen MD205
 Reduce the torque set point to 3.0 over 5 minutes. By leaving a small
amount of torque on the power turbine, then the unit is less likely to over-
speed.

2. On screen MD207
 Reduce the speed setting(Z20732) from 3600 to 1500 over 2 minutes

3. On Screen MD205
 Open the clutch
 Reduce the torque set point to zero

4. On Screen MD207
 Switch the speed controller to OFF
 Set the Power Control setting to zero

5. On Screen MD821
 Press “Normal Stop”

6. On screen MD820
 Start “Post shutdown fan”

7. On Screen MD821
 Monitor shut-down sequence. The gas turbine will cool down for about three
minutes before the fuel shut-off valves on MD203 will close to extinguish the
combustion unit.

8. On Screen MD820
 Once the gas turbine has stopped, engage the brake.
2 GT LOAD SYSTEM MD205

Figure 29

The two main reduction gears are operating independently from each other, and can
transmit power to either load as required.

Main components of the main reduction gear:


- GT SSS (gas turbine synchro-self-shifting) clutch
- attached lube-oil pump
- attached control-oil pump
- attached seawater cooling pump
- electrically driven lube-oil pump
- electrically driven control-oil pump
- electrically driven seawater cooling pump
- turning and holding gear device
- power turbine brake
- reduction gearing
- thrust bearings
The SSS-overrunning clutch is an automatic synchronizing self-shifting clutch coupling
with torque transmission via a gear-type coupling in the engaged condition. The clutch will
engage automatically when the primary input rotates faster than the secondary output.
Similarly it will disengage automatically when the primary input rotates slower than the
secondary output.

The GT SSS clutch can be forced not to connect by means of the pawl-free position that is
a mechanically actuated, and is used for gas turbine test purposes.

An electrical motor drives the turning gear. The engagement of the turning gear can only
be done when the driving engines and the propulsion shaft are stationary. When the turning
gear is engaged, start of the gas turbine is inhibited.

A special brake for the gearbox is provided to hold the gears and the shaft plant into a
blocked position to be used in case of severe damage in the shaft plant or for maintenance
reasons.

Technical data of the main reduction gear:

Nominal Nominal Max.


Power Speed Acceleration
Input : GT 19700 kW 3600 rpm 500 rpm/s

Output -GT driven 19700 kW 220 rpm

Various systems are fitted to the main reduction gear, although not shown with this model:
- control oil system
- lube oil system
- seawater cooling system

The gearbox brake is connected on screen MD820.


Figure 30

The reduction gearbox showing:


 Turning gear
 Lubricating oil pump drive
 Thrust bearing
 Clutch unit
2.1 Water Brake Load
Water brakes (or dynamometers) are commonly used by engine manufacturers to perform
precision testing of engines with varying load. The water brake provides a well-controlled
torque to the rotating shaft. The power absorbed by the brake is proportional to the
rotational speed and brake torque i.e. .

The water brake is attached to the power turbine via a lamella clutch and the reduction
gearbox.

The water brake is simply modelled. To apply a stable and controllable shaft torque, the
applied torque is applied using two adjustable mathematical transfer functions. This will
allow the engineer to simulate real and different dynamic processes.

By connecting the two transfer functions in series, each transfer function can represent a
real dynamical process, thus introducing two first order lags. The output value from the
first transfer function (and hence input to the second transfer function) is presented as a
model variable that can be used for monitoring and control purposes.

The input to the first transfer function is the “torque set point”, and the output from the
second transfer function is the brake torque applied to the shaft. The dynamical behaviour
or delay of the water brake is not modelled specifically, but can be regarded as a part of H2.

These transfer functions generate H(s) which is a second order Laplace transform:

(3-1)

where the output brake torque is a delayed transfer of the input torque set-point. Both the
two time-constants T1 and T2 are adjustable, and allow the system dynamics to be adjusted
to suit the actual turbine operation.
The variables are adjusted on variable pages 20502 and 25502. Note if one of the time
constants are set to zero, then that function will become unity and hence have no delay.

Initially the time constants could be set to

Function 1 Function 1 Function 2 Function 2


Option 1 10 0 10 0
Option 2 5 2 5 2

Figure 31

The pen recorder demonstrates the loading up of the gas turbine using the torque input on
MD204/255. Channel 1 illustrates the set changes input into the Torque Setpoint”. The two
transfer functions H1(s) and H2(s) clearly provide a delay between the change of channel 1
and the changes within Channels 2 and 3.

The pen recorder screen also demonstrates the changes to these time functions, when the
time constants are adjusted. The first two step changes were carried out with a time
constant of 10 seconds and zero seconds for both transfer functions, whilst the subsequent
five step changes were carried out with a time constant of 5 seconds and 2 seconds for both
transfer functions. The 10 second delay provides a longer delay, than the 5 and 2 second
delay, which provides a smaller delay then the previously set 10 second delay setting.
The model hence allows the operator to model the practical delays that would occur within
an actual water brake.
3 GT SPEED CONTROLLER AND AECM MD207

Figure 32

The main functions of the Advanced Engine Control Module (AECM) used on real gas
turbine control systems are implemented in this simulator model.

The primary purpose of the AECM is control of the power turbine speed. The functional
subsystems consist of:
 power level angle (PLA) actuator electronics for gas generator speed control
 the over speed switch electronics for preventing power turbine overspeed
 the microprocessor for controlling the engine start/stop sequencer and computing
gas turbine output torque.

The command signal from the lever control (set at either screen MD207/257 or 820/920) to
the engine is modified in the AECM unit to ensure safe operation of the gas turbine. This
signal is then directed to the PLA actuator, which moves the Main Fuel Control (MFC)
position on either MD203/253, to the desired output.

The command signal is modified to limit the PLA actuator acceleration, and hence power
turbine acceleration, power turbine speed and power turbine output torque.
The start and stop sequence can be controlled either manually or by a programmed time
sequence. The automatic start program monitors several parameters in the gas turbine, and
may be interrupted if any anomaly is detected.
3.1 Speed and Power Controller MD207
To control the turbine speed and power, a general PID controller is added. This control
function is improved by the addition of three possible feed forward signals to the output of
the PID.

The feed back signal and the 3 feed forward signals can be taken from any variables in the
simulator. This gives the user a great flexibility in configurating the control system. Each
of the Feed Forward transfer functions is of the form:

(3-1)

A feed forward signal can, for example, be taken from the difference between two
variables (x1 and x2) by using the same transfer functions on the two variables, with
opposite sign on the K:

To allow various and different parameters to be compared within the control system, the
PID feedback signal and set point are converted to a percentage signal in the range defined
in the “feedback and feed forward configuration” pop-up window. The PID controller and
Feed Forward gain is therefore related to this scaling range.
The variable for the feed back and feed forward functions can be chosen from any of the
variables present within the model. The most common and useful sensors will be gas
turbine power, gas turbine torque and power turbine speed as reference. By clicking on the
box for the feed back signal, the feed back and feed forward configuration menu will
popup. The unique tag name for these values is placed in the required feed back and
forward configuration box as shown below.

Figure 33

In this example the feedback signal is the power turbine speed for gas turbine No 1
(N20202), and two feed forward signals have been used, namely the power turbine power
output (E30001) and the power turbine torque (Q30001).

Note also within this example the settings of the PID controller have been chosen as 6.0,
4 seconds, and 4 seconds. This provides a responsive and stable controller without
excessive offset.
The screen example also illustrates the gain and time constants for the two feed forward
signals.
Figure 34

A change in power turbine speed when the torque is removed using a water brake load.

Speed controllers are important in gas turbine control, as any major load change in the
power turbine will cause a major speed change, especially shedding of load. This could
cause a possible over speed situation for separate power turbine configurations, such as in
the LM2500 industrial gas turbine units. A procedure to ensure that the speed controller is
set to its optimum settings is given below.
3.1.1 Optimising Procedures for Speed Controller
To optimise the speed controller at high loads using Ziegler Nicholls closed loop
procedure

1. Operate the gas turbine with the water brake load at about 15 MW (torque setting of
40). This will provide a moderate load, without speed fluctuations causing an over
torque or over speed.
2. Using screen MD207 for Gas turbine #1
3. Ensure that the feed forward signals are isolated by opening the pop-up menu, and de-
selecting the feed forward channels.
4. Set the PID controller with values of P = 6, I = 4000, D = 0. Do not set I to zero or D
to a large value as these may produce instability.
5. Increase the setting of P until the speed oscillations are uniform. Note after every
adjustment of the P setting, the speed set point should be changed from 3600 to 3500
and back again.
6. During experiments a gain of 32 was found to just cause speed oscillations. The time
period (To) of these oscillations was measured at 13 seconds.
7. Using the Ziegler Nicholls relationships (see page 65 for the theory involved), the
suggested values of P, I and D can be found

18.8

I = 0.5 x To = 0.5 x 13 = 6.5 seconds

D = 0.12 x To = 0.12 x 13 = 1.6 seconds

8. Input these values into the PID settings.


9. Test the stability of the controller by changing the speed by 200 rev/min. Return the
speed to 3600 rev/min after the test. The speed controller should be stable without
undue lag and offset.
10. Select or engage feed forward 1 channel with a variable of E30001 (power turbine
kW).
11. Slowly increase the gain setting up to 0.2, whilst observing the stability of the speed.
Set both time constants to zero seconds.
12. To test the feed forward loop we shall now change the load of the turbine at the water
brake using screen MD205.
13. Increase the value of the torque set point to 42. Observe the speed controller output
for stability.
14. Note the value of the variable Z20744 of the feed forward output. To ensure that the
speed control loop of the PID controller is maintained as the dominant controlling
mechanism, the total feed forward contribution to the overall signal should not be
above 20% of the signal into the PLA actuator. You should find that at these high
power levels a gain of 0.2 for the variable E30001 (turbine power) is acceptable.
15. Once the feed forward signal level is acceptable, then input values of 4 seconds into
each time constant TC1 and TC2 to improve the feed forward stability.
16. Test the stability of the speed controller by reducing the torque set point on MD205
from 42 to 36.
17. Select or engage feed forward 2 channel with a variable of Q30001 (power turbine
torque).
18. Set the gain at 0.1, whilst observing the stability of the speed.
19. To test the feed forward loop we shall now change the load of the turbine at the water
brake using screen MD205.
20. Increase the value of the torque set point on MD205 to 40. Observe the speed
controller response for stability.
21. The level of gain for the feed forward 2 channel should provide an output signal
comparable to that of the feed forward 1 channel. Once the feed forward signal level
is acceptable, and then input values of 4 seconds into each time constant TC 1 and TC2
to improve the feed forward stability on channel 2.
22. Provide some speed and load changes to prove the controller is both stable and
responsive.

To optimise the speed controller at low loads


1. Operate the gas turbine under water brake load at about 5 MW (using a torque setting
of 16). This will provide a low load where the turbine speed fluctuations are not
dampened by the water brake load.
2. Using screen MD207 for Gas turbine #1
3. Ensure that the feed forward signals are isolated by opening the pop-up menu to
ensure the feed forward channels are de-selected.
4. Set the PID controller with values of P = 6, I = 4000, D = 0. Do not set I to zero or D
to a large value as these may produce instability.
5. Increase the setting of P until the speed oscillations are uniform. Note after every
adjustment of the P setting, the speed set point should be changed from 3600 to 3500
and back again.
6. The gain was found to be 24 and the period of oscillation at 17 seconds, so from
Ziegler Nicholls then P = 14.4, I = 8.5 seconds and D = 2 seconds.
7. Input these values into the PID settings of the speed controller.
8. Select or engage feed forward 1 channel with a variable of E30001 (power turbine
kW). Check that the time constants are zero.
9. Slowly over 4 steps increase the gain setting up to 0.5, whilst observing the stability
of the speed.
10. To test the feed forward loop we shall now change the load of the turbine at the water
brake using screen MD205.
11. Increase the value of the torque set point to 18. Observe the speed controller output
for stability.
12. Note the value of the variable Z20744 of the feed forward output. To ensure that the
speed control loop of the PID controller is maintained as the dominant controlling
mechanism, then the feed forward contribution should not be above 20% of the speed
control signal into the PLA actuator. You may find that at these power levels the gain
of 0.5 for the variable E30001 (turbine power) is too high and may need reducing to
0.4.
13. Once the feed forward signal level is acceptable, then input values of 4 seconds into
each time constant TC1 and TC2 to improve the feed forward stability.
14. Test the stability of the speed controller by reducing the torque set point on MD205
from 18 to 16.
15. Select or engage feed forward 2 channel with a variable of Q30001 (power turbine
torque).
16. Slowly increase the gain setting up to 0.2, whilst observing the stability of the speed.
17. To test the feed forward loop we shall now change the load of the turbine at the water
brake using screen MD205.
18. Increase the value of the torque set point on MD205 to 18. Observe the speed
controller response for stability.
19. The level of gain for the feed forward 2 channel should provide an output signal
comparable to that of the feed forward 1 channel. Once the feed forward signal level
is acceptable, and then input values of 4 seconds into each time constant TC 1 and TC2
to improve the feed forward stability on channel 2.
20. This adaptive control using the feed forward options can be further modified using the
third feed forward channel, with a variable such as torque set point (Q20511).
21. As with the other feed forward channels the level of gain should be set to ensure that
the speed controller PID controller remains dominant. Thus a gain of 0.2, and time
constants TC1 and TC2 at 4 seconds are suggested.
22. To test the speed controller stability with the main feed back and three feed forward
channels selected, reduce the torque set point to 7. This should produce a speed
change that is not excessive. During testing a maximum speed change of less than 200
rev/min was observed.
23. The stability will now be tested with a torque increase. On MD206 increase the torque
set point to 30. Observe the speed change on MD207. During testing speed stability
was achieved within 80 seconds.
24. The table shows the effect of the feed forward on the speed controller.

Speed Time to Speed Time to


fluctuation stabilise fluctuation stabilise
Feed forward Feed forward Feed forward Feed forward
ON ON OFF OFF
Torque decrease +180 rev/min 40 seconds + 200 rev/min 45 seconds
15 to 7
Torque increase - 410 rev/min 80 seconds - 620 rev/min 80 seconds
7 to 30
Speed decrease 3600 - 90 rev/min 45 seconds - 80 rev/min 30 seconds
to 3300
Speed increase + 90 rev/min 40 seconds + 75 rev/min 40 seconds
3300 to 3600
25. The test results illustrate the difference in controller response time and controlled
variable deviation under the influence of feed forward. When feed forward using
turbine torque and power is selected, the controller becomes more responsive to load
changes, and the feed forward outputs will modify the speed controller output to
change the PLA actuator position. However, the influence of the feed forward will
reduce effectiveness of the speed controller under speed changes only. As stability
under load is more desirable, then the influence of the feed forward is beneficial to
the speed controller operation.

26. We shall also compare the settings of the feed forward and PID units when optimised
at low and high loads

P I D FF1 gain FF2 gain FF3 gain


Low load (7 MW) 14.4 8.5 2 0.4 0.2 0.2
High load (15MW) 18.8 6.5 1.6 0.2 0.1 not tested

This shows the dilemma for tuning controllers. As the load increase/decreases we should
use different values for the controller settings. This would create an adaptive control,
where the controller is optimised for each load setting. As it is important that the controller
is stable over the full load range, then the lower gain settings should be chosen for the
turbine speed controller. i.e. use the low load values for the PID controller, but the high
load values for the feed forward functions.
The reaction of the speed controller when the torque setting is increased from 36 to 45 with
the suggested controller settings, at a nominal power turbine speed of 3600 rev/min.

Figure 35

The reaction of the speed controller when the torque setting is reduced from 45 to 20.
The higher speed fluctuation for the torque reduction is due to the reduced effect from the
feed forward channel, due to the lower loads. Note the feed forward combined signal in the
diagram is 15.8%, which should ensure the speed control loop remains the dominant
control mechanism.
Good Control Requires:

a) Rapid Reduction of Deviation from the Desired Value

b) A quick return to steady state after a disturbance (A short Recovery Time)

c) Minimum Offset

Each of these factors is affected by the controller proportional gain. The best control is
obtained with the highest value of proportional gain possible before the system becomes
unstable. The Maximum value of proportional gain possible depends upon the plant
characteristics, and means that in some instances proportional only control is ineffective and
must be supplemented by integral and/or derivative action.

Integral action is used to eliminate offset, but since it is a form of positive feedback, may
lead to instability and the proportional gain must therefore be reduced when integral action is
added.

Derivative action is used to reduce the recovery time and since it is a form of negative
feedback, is inherently stabilising. Proportional gain can thus be increased when derivative
action is added.

Every process suffers from lags to some extent. These are difficult to calculate and affect the
controller settings, so that in practice controller settings are often determined by empirical
means. There are a number of methods available including the Ziegler-Nicholls open and
closed loop tests. The closed loop test is undertaken when a controller disturbance will not
critically affect the system stability. Whereas the open loop test is carried out when the
controller test could affect plant stability.

3.1.2 Ziegler-Nicholls Test

Method :- Feed in a step input to the REGULATING UNIT and determine the process
response curve.

a) Change to manual control and select a new position of the regulating unit. Allow the
regulating unit to reach a new equilibrium position.

Record input and output as shown.


Draw tangent to the output curve from the steepest point. Measure time intervals L and T. The
steady state gain "Kp" is given by .
Ziegler-Nicholls Open-Loop Test.

The controller gains can now be estimated as a starting point for further manual adjustment.
CONTROL GAIN INTEGRAL DERIVATIVE
TERMS ACTION TIME ACTION TIME
P

P+I 3.3L seconds


0.9
P+I+D 2 L seconds 0.5L seconds
1.2
Ziegler- Nicholls Closed-Loop Test.

Method :- Alter the controller gain until process oscillates with constant amplitude.

a) Remove effect of integral and derivative action by setting their actions times to zero, or
if this is not possible, use high values of time (low action).

b) Create a disturbance to the process by introducing a step change in the desired value
setting of the controller and then returning it to its original value.

c) Observe system response.


 If the response is unstable, reduce gain and repeat b) and c)
 If the response is damped, increase gain and repeat b) and c)
 If the response is constant as shown below, then note the gain Ko and period of
oscillation, Tf.

CONTROL GAIN INT ACTION TIME DERIV. ACTION TIME


TERMS

P 0.5Ko
P+I 0.45Ko 0.8Tf
P+I+D 0.6Ko 0.5Tf 0.125Tf
Results of Open Loop Test

T = 12 sec’s N = 50/100 = 0.5 L = 2.5 sec’s

M = 22.9 - 19 = 0.205 Kp = M/N = 0.41


19

So, for a P + I+ D controller,


P = 1.2T/L.Kp = 14 I = 2.L = 5 seconds D = 0.5.L = 1.25 sec’s

This compares with the original settings of 6, 30 and 2 respectively.

Observations:-
Low time lag “L” and response time “T” make it difficult to measure accurately.
We have obtained higher values of gain and integral action, which is surprising because the
Z-N test normally gives “conservative” results. However, we do have more derivative
action which would balance the higher proportional gain and integral action.

It could be that when there is less load on the system the controller is less stable, and if this
is so, a second test under these conditions might yield lower values of gain and integral
action.

Results of Close Loop Test

Critical gain Ko = 12 Tf = 20 x 60 = 41 seconds


29
So, for a three term controller,
P = 0.6Ko = 7.2 I = 0.5 x 41 = 21 seconds D = 0.12 x 41 = 5 seconds

This compares with initial settings of 2, 100, and 5 respectively.

So we have obtained higher values of gain and integral action, which is surprising because
the Z-N test normally gives “conservative” results. However, there is nothing to say the
initial settings are correct! It could be that when there is less load on the system the
controller is less stable, and if this is so, a second test under these conditions might yield
lower values of gain and integral action.
Summary

Control system instability can arise from a number of causes, but most commonly arises
from having too much proportional gain in a system. This might seem strange at first
glance, since proportional control is said to be “inherently stable”, because the output is
proportional to the deviation. The problem arises due to the inherent “lags” in the plant
which mean that the controller action may become out of step with what is actually
happening on the plant.

Proportional gain should be as high as possible, but not so high as to produce instability.
Note that as the load on a plant changes, its characteristics may also change, and that the
controller settings used successfully at one load may produce instability at a different load.

3.1.3 Proportional Action


In proportional control the output is proportional to the deviation. Proportional control is
inherently stable and is used as a function of all multi-term controllers.

The amount the measured value of the controlled condition must change in order that the
control valve moves from fully closed to fully open position is known as the proportional
band and is expressed as a percentage of the instrument scale. For example, if the
instrument scale is 0-100°C, and a temperature change of 70-90°C (= 20°C) causes the
valve to move from fully open to fully closed then Proportional band = 20 x 100% =
20%

Note! The GAIN of the controller = That is they are INVERSELY related

The proportional band setting required for any given application will depend on plant
characteristics and the various lags in the control loop. There is an optimum value which
will give stable control. If the gain is too high (proportional band is too low), the process
will go unstable, while if gain too low (high proportional band) the process will be
sluggish.

3.1.4 Offset or Droop


All proportional controllers suffer from the disadvantage that if a load change takes place
on the plant the control point will not come back to the desired value. This is because there
is only one valve position that coincides with the desired value. If the load changes, a
different valve position is required for the same desired value. This cannot come about
unless there is a change in measured value, i.e. deviation from the desired value. The plant
will therefore settle down with a steady state deviation (offset) from the desired value. This
offset will only be removed if the load on the plant returns to its original level.
Offset will be at a minimum when the gain is at its optimum setting, i.e. at a point just
before the plant starts to hunt. The higher the proportional gain, the lower the offset after a
change in load, but since high controller gain may lead to instability, this may not be an
option.

3.1.5 Integral Action or Reset


Where, due to transfer lags, etc. it is necessary to use low gain to achieve stable control,
offset will occur after a load change. On some plants no offset can be tolerated. On a high
pressure boiler, for instance, it is essential that the steam pressure and temperature are at
fixed values.

To eliminate offset at all loads, integral action must be used. Integral action means that
the output is proportional to the deviation and the time of the deviation.

The time taken for the integral action to become equal in magnitude to the proportional
only action is known as the integral action time. Note that the shorter the time, the more
integral action there is. Integral action is a form of positive feedback and can therefore lead
to instability if too much is used.

3.1.6 Derivative Action or Proportional Rate


On a large and sudden load change the proportional action tends to cause a large overshoot
and undershoot to take place on the plant with an increase in recovery time before the
process stabilises. To cut down on the amount of plant swing, and decrease the recovery
time, derivative action is used.

Derivative action means that the output is proportional to the rate of change of deviation.
Recovery time is reduced, as is the amplitude of the oscillations. Note that when the
deviation is constant, no matter how large it is, derivative action will not alter the valve
position. It is used where plant lags are large, i.e. temperature and pressure control but is
not usually necessary for flow control.

Although derivative action has no direct effect on offset, it is a form of negative feedback
and allows higher proportional gain to be used, which can reduce (but not eliminate) offset.

The input to the PLA controller of the Gas Turbine is taken from the manually set “Power
Control” when the speed controller or regulator is switched off.