Technical Application Note 048
Technical Application Note 048
Affected Products
Triconex™ Tricon™, Tricon CX, Trident™, and Triconex General Purpose (Tri-GP) controllers
Introduction
This Technical Application Note (TAN) provides a summary of third-party products tested by, or with oversight
from, Schneider Electric® to show interoperability with Triconex products. The list of third-party products is
exemplary and is not intended to be all inclusive of hardware that is interoperable with Triconex products. The
scope of third-party products reviewed for interoperability includes those within the TÜV-approved safety
boundary as well as those outside the TÜV-approved safety boundary.
Triconex safety systems maximize the TÜV-approved safety boundary when used with TÜV-approved
Triconex External Termination Panels (ETPs) and Interface Cables. The use of non-Triconex-approved
cables and/or ETPs limits the TÜV safety certification boundary and potentially limits the ability of the logic
solver to respond to safety demands. Networking equipment is a black channel and outside the TÜV-
approved safety boundary.
Background
IEC 61508 and IEC 61511 define a programmable electronic Safety Instrumented System (SIS) as consisting
of sensors, logic solvers, and final control elements, as shown in this figure.
Logic Final
Sensors
Solver Elements
Together, these elements implement Safety Instrumented Functions (SIF) of the target Safety Integrity Level
(SIL). To implement a safety-certified SIF, the system designer must choose safety-certified loop elements,
including sensors, final elements, logic solvers, and other interconnecting components.
Public
2 of 11
In addition to the components shown in Figure 1, a typical SIS consists of other components such as cables
and external termination panels. Figure 2 shows the SIS including these components, which are used to
connect the sensors and final elements to the logic solvers.
Certifications
• TÜV approves the use of Triconex ETPs and interconnecting cables with the Tricon, Tricon CX,
Trident, and Tri-GP Safety Logic Solvers within the boundary of the TÜV-Certified Safety System.
• TÜV certifies the use of the Tricon, Tricon CX, and Trident Safety Logic Solvers in up to SIL 3
applications with the TÜV-approved ETPs and interconnecting cables in accordance with IEC 61508.
• TÜV certifies the use of the Tri-GP Safety Logic Solver in up to SIL 2 applications with the TÜV-
approved ETPs and interconnecting cables in accordance with IEC 61508.
• Triconex ETPs are certified for electrical safety in full compliance with international standards by the
Canadian Standards Association (CSA). They are qualified for general use in North America and
other jurisdictions requiring compliance with these standards, as well as the European CE mark as
per the Low Voltage Directive.
• Triconex ETPs and interconnecting cables comply with the applicable IEC EMC standard (IEC 61326-
3-1, 2) which includes the European CE mark per the EMC directive.
• Tricon, Tricon CX, Trident, and Tri-GP ETPs that are approved for hazardous locations comply with
North American Class I, Division 2 and European ATEX Zone 2 requirements. Additionally, Tricon CX
ETPs that are approved for hazardous locations also comply with IECEx Zone 2 requirements.
The boundary of the TÜV-Certified Safety System extends up to the ETPs, including the Interface Cables, as
shown in Figure 2 below. The use of non-Triconex ETPs or cables, even those with some form of TÜV
approval which are not part of this certified system, may reduce the TÜV-Certified Safety System boundary.
Approved external
Approved external
termination panel
termination panel
and cable
and cable
End-user
installed End-user
field wiring installed
field wiring
Approved ETPs and Interface Cables are listed in the Field Termination Guide for Tricon Systems, the
Planning and Installation Guide for Trident Systems, the Planning and Installation Guide for Tri-GP Systems,
and the Tricon CX Addendum to Tricon User Guides which are available on the Global Customer Support
(GCS) website.
Schneider Electric in Lake Forest, California controls the design, configuration management, supply chain
management, and quality assurance for Triconex ETPs and cable assemblies, as well as sourcing of
approved ETPs and Interface Cables.
Technical Application Note 48 March 22, 2022 Part No. 9791005-048, Rev 10
Public
3 of 11
Conclusion
The boundary of the safety system includes the ETPs and Interface Cables. To maximize the TÜV-approved
boundary, approved ETPs and cables must be used with the Tricon, Tricon CX, Trident, or Tri-GP Safety
Logic Solver. Non-Triconex ETPs and cables may be appropriate in some installations. Networking equipment
is outside the TÜV-approved safety boundary.
If you have any questions regarding this Technical Application Note, contact your regional support office or
the Global Customer Support (GCS) Center.
GM International (GMI) External Termination Panels (ETPs) Used with GMI Pluggable Conditioning
Modules (PCMs) and Tricon CX I/O Modules
I/O Module GMI ETP Model ETP Details Supported PCMs
3506X DI TBE-D5016-TRI-012 SIL3, HazLoc, 16 PCMs D6001S, D5031S, D5032S, D5037S,
D5038SA, D5039SA, D5093S,
D5038XA, D5039XA
3626X DO TBE-D5016-TRI-007 SIL3, HazLoc, 16 PCMs D6001S, D5040S, D5048S, D5049S,
D5090S, D5091S, D5096S, D5097S,
D5098S
3722X AI, TBE-D5016-TRI-011 SIL3, HazLoc, 16 PCMs D5011S, D5014S, D5015SS,
3723X AI D5072S, D6001S, D6017SS
3809X/AX AO TB-D5016-TRI-010 SIL3, HazLoc, 16 PCMs D5020S, D6001S
3902X/AX UIO TB-D5016-TRI-010 SIL3, HazLoc, 16 PCMs D6001S, D6004S, D5031S, D5032S,
D5037S, D5093S, D5038SB,
D5039SB, D5049S, D5090S-102,
D5091S-103, D5096S-106, D5097S-
107, D5014S, D5015SK, D6017SK,
D5072S-099, D5020S
GMI PCMs Used with Tricon CX I/O Modules
GMI PCM I/O Compatible I/O
Model Type PCM Type Details Modules
Technical Application Note 48 March 22, 2022 Part No. 9791005-048, Rev 10
Public
4 of 11
GM International (GMI) External Termination Panels (ETPs) Used with GMI Pluggable Conditioning
Modules (PCMs) and Tricon CX I/O Modules
I/O Module GMI ETP Model ETP Details Supported PCMs
Pass-Through
D6001S ANY NIS1 SIL 3, Pass-Through, 2-Wire, 1 Channel 3506X, 3626X,
3722X, 3723X,
3809X/AX,
3902X/AX
D6004S ANY NIS SIL 3, Pass-Through, 2- or 3-Wire, 1 Channel, 3902X/AX
Power Terminals
Digital Input (DI)
D5093S DI NIS SIL 3, 24 to 220 VAC/VDC Switch, Transistor 3506X, 3902X/AX
Out, 1 Channel
D5031S DI IS2 SIL 3, Switch/Proximity, Transistor Out, LFD3, 3506X, 3902X/AX
1 Channel
D5032S DI IS SIL 3, Switch/Proximity, Relay Out, LFD, 3506X, 3902X/AX
1 Channel
D5037S DI IS SIL 2, Switch/Proximity, Transistor Out, LFD, 3506X, 3902X/AX
1 Channel
D5038SA SDI IS SIL 3, Switch/Proximity, Line Monitor Out, LFD, 3506X
D5038XA FM4, 1 Channel
Technical Application Note 48 March 22, 2022 Part No. 9791005-048, Rev 10
Public
5 of 11
GM International (GMI) External Termination Panels (ETPs) Used with GMI Pluggable Conditioning
Modules (PCMs) and Tricon CX I/O Modules
I/O Module GMI ETP Model ETP Details Supported PCMs
D5096S- SDO NIS SIL 3, Relay Output, NO Contact, NE or
8
3902X/AX
1067 F&G9/ND Load, LFD, FM, 1 Channel
D5097S7 SDO NIS SIL 3, Relay Output, NC10 Contact, NE or 3626X
F&G/ND Load, LFD, FM, 1 Channel
D5097S- SDO NIS SIL 3, Relay Output, NC10 Contact, NE or 3902X/AX
1077 F&G/ND Load, LFD, FM, 1 Channel
D5098S DO NIS SIL 3, Relay Output, NE Load, 1 Channel 3626X
Analog Input (AI)
D5011S AIH IS SIL 3, 2-Wire Passive, 4-20 mA, HART, 3722X, 3723X
1 Channel
D5014S AIH IS SIL 3, 2/4-Wire Active/Passive 4-20 mA, HART, 3722X, 3723X,
1 Channel 3902X/AX
D5015SK AIH IS SIL 2, 2/4-Wire Active/Passive, 4-20 mA, HART, 3902X/AX
1 Channel
D5015SS AIH IS SIL 2, 2/4-Wire Active/Passive, 4-20 mA, HART, 3722X, 3723X
1 Channel
D5072S AI IS SIL 2, TC/RTD, Temperature Converter 4- 3722X, 3723X,
D5072S- 20 mA, 1 Channel 3902X/AX
099
D6017SK AIH NIS SIL 3, 3/4-Wire Active 4-20 mA, 200 mA 3902X/AX
Transmitter Power, HART, 1 Channel
D6017SS AIH NIS SIL 3, 3/4-Wire Active 4-20 mA, 200 mA 3722X, 3723X
Transmitter Power, HART, 1 Channel
Analog Output (AO)
D5020S AOH IS SIL 2, 4-20 mA, HART, LFD, 1 Channel 3809X/AX,
3902X/AX
1
NIS = not intrinsically safe 6
ND = normally de-energized
2
IS = intrinsically safe 7
Operational field voltage of 22.3 to 32 VDC
3
LFD = line and load fault detection 8
NO = normally open
4
FM = fault mirroring 9
F&G = fire and gas
5
NE = normally energized 10
NC = normally closed
Technical Application Note 48 March 22, 2022 Part No. 9791005-048, Rev 10
Public
6 of 11
MTL Instruments
Part or Model Number
MTL4850-TR HART Multiplexer
HCU3700/3703E HART Interface
HCU3704E FTA + HART Interface
HCU3805E HART Interface
BPM32+Adapter (DI, DO, AI, AO) Motherboard
BPM16U+Adapter (DI, DO, AI)
Isolators
MTL4015 MTL4016 MTL4024 MTL4041B
MTL4073 MTL4045C MTL4061
P
Pepperl+Fuchs (P+F) External Termination Panels (ETPs) Used with P+F Pluggable Conditioning
Modules (PCMs) and Tricon CX I/O Modules
I/O Module P+F ETP Model1 ETP Details Supported PCMs
3506X DI HiCTB16-TRX-RAC- SIL3, HazLoc, 16 PCMs HiC2821, HiC2841
PL-DI16
3626X DO HiCTB16-TRX-RAC- SIL3, HazLoc, 16 PCMs HiC2873, HiC2883, HiC5861,
PL-DO16 HiC5863
3722X AI, HiCTB16-TRX-RAC- SIL3, HazLoc, 16 PCMs HiC2025, HiC2025A, HiC2025ES,
3723X AI PL-AI16 HiC2025Y1, HiC2081
3809X/AX AO HiCTB16-TRX-RAC- SIL3, HazLoc, 16 PCMs HiC2031, HiC2031ES
PL-IO16
3902X/AX UIO HiCTB16-TRX-RAC- SIL3, HazLoc, 16 PCMs DI: HiC2821, HiC2841, HiC2853R4
PL-IO16 DO: HiC2873, HiC2883, HiC5861,
HiC5863
AI: HiC2025, HiC2025A,
HiC2025ES, HiC2025Y1, HiC2081
AO: HiC2031, HiC2031ES
UIO: HiC2441
1
See the “Tricon CX Field Termination Specifications” section of the Tricon CX Addendum to Tricon User Guides for information on
Triconex I/O Interface Cables.
Technical Application Note 48 March 22, 2022 Part No. 9791005-048, Rev 10
Public
7 of 11
Technical Application Note 48 March 22, 2022 Part No. 9791005-048, Rev 10
Public
8 of 11
Phoenix Contact
Part or Model Number
Termination Boards
VIP-TRICONEX-CX-ETP-16CH - 2908788
Modules
IOA FEED-THRU/EX - 2906598 IOA-PSR-PS22 - 2702971
Technical Application Note 48 March 22, 2022 Part No. 9791005-048, Rev 10
Public
9 of 11
STAHL
Part or Model Number
Modules
9161/DI-TR 9161/DO-TR 9161/GA-TR
Isolators
9103 9118 9123 9124
9150 9151
Weidmuller
Part or Model Number
Safety Relays
SCS 24VDC P1SIL3DS I, mat. no. 2500980000
Technical Application Note 48 March 22, 2022 Part No. 9791005-048, Rev 10
Public
10 of 11
Small Form-Factor Pluggable (SFP) Transceivers Used with Tricon CX Communication Modules1
SFP Model Tested Speed Fiber Type
Cisco MFEFX1 100BASE-FX multi-mode fiber (MMF)
Cisco MFELX1 100BASE-LX single-mode fiber (SMF)
Cisco GLC-LX-SM-RGD 1000BASE- single-mode fiber (SMF) or multi-mode
LX/LH fiber (MMF)
Extreme Networks 1000BASE-BX-D SFP 1000BASE-BX-D single-mode fiber (SMF)
Extreme Networks 1000BASE-BX-U SFP 1000BASE-BX-U single-mode fiber (SMF)
Proline GLC-SX-MM-RGD-CDW 1000BASE-SX multi-mode fiber (MMF)
Proline GLC-ZX-SM-RGD-PRO 1000BASE-ZX single-mode fiber (SMF)
1
SFPs listed in this table have been reviewed and found to be compatible with the following Tricon CX products: 4355X and 4610X.
Small Form-Factor Pluggable (SFP) Transceivers Used with Tricon CX I/O Bus1
SFP Model Tested Max. Distance Fiber Type
Cisco GLC-LX-SM-RGD 1800 ft (550 m) multi-mode fiber (MMF), or
6.2 mi (10 km) single-mode fiber (SMF)
Cisco GLC-SX-MM-RGD 1800 ft (550 m) multi-mode fiber (MMF)
Cisco GLC-ZX-SM-RGD 43.5 mi (70 km) single-mode fiber (SMF)
Perle PSFP-1000D-S1LC10D-XT 6.2 mi (10 km) single-mode fiber (SMF)
Perle PSFP-1000D-S1LC10U-XT 6.2 mi (10 km) single-mode fiber (SMF)
Proline GLC-ZX-SM-RGD-PRO 43.5 mi (70 km) single-mode fiber (SMF)
Transition Networks TN-SFP-GE-S-C2 1800 ft (550 m) multi-mode fiber (MMF)
Technical Application Note 48 March 22, 2022 Part No. 9791005-048, Rev 10
Public
11 of 11
Small Form-Factor Pluggable (SFP) Transceivers Used with Tricon CX I/O Bus1
SFP Model Tested Max. Distance Fiber Type
Transition Networks TN-SFP-GE-L-C 2
6.2 mi (10 km) single-mode fiber (SMF)
Transition Networks TN-SFP-GE-Z-C2 43.5 mi (70 km) single-mode fiber (SMF)
1
SFPs listed in this table have been reviewed and found to be compatible with the following Tricon CX products: 3009X and 4703X.
2
Conformal coated. We recommend the use of conformal coated SFPs in Safety Intelligent Enclosures (SIEs) and other outdoor
installations.
The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and furnished for informational use only. No part of this guide may be reproduced or transmitted in
any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide or its content, except for a non-exclusive and personal license to consult it on an "as is"
basis. Schneider Electric products and equipment should be installed, operated, serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information contained in this guide may be subject to change without notice. To the extent permitted by
applicable law, no responsibility or liability is assumed by Schneider Electric and its subsidiaries for any errors or omissions in the informational content of this material or
consequences arising out of or resulting from the use of the information contained herein.
Section Description
Conclusion • Describes third-party products that are within and outside of the TÜV approved safety
boundary
Appendix B • New section added to identify “Reviewed Devices outside of Safety Boundary”
• Added reference and network switch guidelines to the “Network Switches and Small
Form-Factor Pluggables (SFPs)” sub-section
Contact +1-866-746-6477
Information +86-21-37180086 +31-3554-84125
International:
+1-508-549-2424
Technical Application Note 48 March 22, 2022 Part No. 9791005-048, Rev 10