Operation Manual: Line Differential Protection and Control RED615
Operation Manual: Line Differential Protection and Control RED615
The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license.
Trademarks
ABB is a registered trademark of ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their
respective holders.
Guarantee
Please inquire about the terms of guarantee from your nearest ABB representative.
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 Vaasa, Finland
Telephone: +358 10 2211
Facsimile: +358 10 22 41094
http://www.abb.com/substationautomation
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in no
event shall ABB be responsible or liable for any loss or damage resulting from the
use of this manual or the application of the equipment.
When the plug-in unit has been detached from the case, do not touch
the inside of the case. The relay case internals may contain high
voltage potential and touching these may cause personal injury.
Table of contents
Section 1 Introduction.......................................................................7
This manual........................................................................................7
Intended audience..............................................................................7
Product documentation.......................................................................8
Product documentation set............................................................8
Document revision history.............................................................9
Related documentation................................................................10
Document symbols and conventions................................................10
Safety indication symbols............................................................10
Document conventions................................................................11
Functions, codes and symbols....................................................11
RED615 1
Operation Manual
Using LHMI.......................................................................................29
Logging in....................................................................................29
Logging out..................................................................................30
Turning display backlight on........................................................30
Selecting local or remote use......................................................31
Identifying the device...................................................................31
Adjusting display contrast............................................................32
Changing LHMI language............................................................32
Changing display symbols...........................................................33
Navigating in the menu................................................................33
Menu structure.......................................................................33
Scrolling the LCD view...........................................................34
Changing the default view......................................................34
Browsing setting values...............................................................35
Editing values..............................................................................35
Editing numerical values........................................................35
Editing string values...............................................................36
Editing enumerated values.....................................................37
Committing settings.....................................................................37
Clearing and acknowledging.......................................................38
Using LHMI help..........................................................................38
Using WHMI.....................................................................................39
Logging in....................................................................................39
Logging out..................................................................................39
Identifying the device...................................................................41
Navigating in the menu................................................................42
Menu structure.......................................................................43
Showing all parameters...............................................................43
Editing values..............................................................................45
Committing settings.....................................................................48
Clearing and acknowledging.......................................................50
Selecting alarm view....................................................................52
Selecting event view....................................................................53
Selecting phasor diagrams..........................................................54
Using WHMI help.........................................................................57
2 RED615
Operation Manual
RED615 3
Operation Manual
Section 8 Commissioning...............................................................83
Commissioning checklist..................................................................83
Checking installation.........................................................................83
Checking the power supply.........................................................83
Checking CT circuits....................................................................84
Checking binary input and output circuits....................................85
Binary input circuits................................................................85
Binary output circuits..............................................................85
Authorizations...................................................................................85
User authorization.......................................................................85
Using PCM600.................................................................................86
Setting communication between IEDs and PCM600...................86
Communication options..........................................................86
Setting communication parameters........................................87
Setting IED and communication.......................................................92
Setting communication................................................................92
Setting LHMI................................................................................92
Changing LHMI language.......................................................92
Adjusting display contrast.......................................................93
Changing display symbols......................................................93
Changing the default view......................................................93
Setting system time and time synchronization.......................94
Setting IED parameters...............................................................95
Defining setting groups...........................................................95
IED parametrization................................................................98
Configuring analog inputs.......................................................98
Testing IED operation.......................................................................98
Selecting test mode.....................................................................98
Testing digital I/O interface..........................................................99
Testing functions.........................................................................99
Selecting internal fault test........................................................100
4 RED615
Operation Manual
Section 9 Glossary.......................................................................103
RED615 5
Operation Manual
Section 1 Introduction
Operation Manual contains instructions on how to operate the IED during normal
service once it has been commissioned. The manual can be used to find out how to
handle disturbances or how to view calculated and measured network data in order
to determine the cause of a fault.
This manual addresses the operator, who operates the IED on a daily basis.
The operator must be trained in and have a basic knowledge of how to operate
protection equipment. The manual contains terms and expressions commonly used
to describe this kind of equipment.
RED615 7
Operation Manual
Decommissioning
Commissioning
Maintenance
Engineering
Operation
Installing
Engineering manual
Installation manual
Commissioning manual
Operation manual
Service manual
Application manual
Technical manual
Communication protocol
manual
en07000220.vsd
IEC07000220 V3 EN
Engineering Manual contains instructions on how to engineer the IEDs. The manual
provides instructions on how to use the different tools for IED engineering. It also
includes instructions on how to handle the tool component available to read
disturbance files from the IEDs on the basis of the IEC 61850 definitions. It further
introduces the diagnostic tool components available for IEDs and the PCM600 tool.
Installation Manual contains instructions on how to install the IED. The manual
provides procedures for mechanical and electrical installation. The chapters are
organized in the chronological order in which the protection IED should be installed.
8 RED615
Operation Manual
Operation Manual contains instructions on how to operate the IED during normal
service once it has been commissioned. The manual can be used to find out how to
handle disturbances or how to view calculated and measured network data in order
to determine the cause of a fault.
Service Manual contains instructions on how to service and maintain the IED. The
manual also provides procedures for de-energizing, de-commissioning and disposal
of the IED.
The Point List Manual describes the outlook and properties of the data points specific
to the IED. This manual should be used in conjunction with the corresponding
Communication Protocol Manual.
The latest revision of the document can be downloaded from the ABB
web site http://www.abb.com/substationautomation
RED615 9
Operation Manual
The information icon alerts the reader to relevant facts and conditions.
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
Although warning hazards are related to personal injury, it should be understood that
operation of damaged equipment could, under certain operational conditions, result
in degraded process performance leading to personal injury or death. Therefore,
comply fully with all warning and caution notices.
10 RED615
Operation Manual
RED615 11
Operation Manual
12 RED615
Operation Manual
Sustainability has been taken into account from the beginning of the product design
including the pro-environmental manufacturing process, long life time, operation
reliability and disposing of the IED.
The choice of the materials and the suppliers has been made according to the EU
RoHS directive (2002/95/EC). This directive limits the use of hazardous substances
which are the following:
Operational reliability and long life time have been assured with extensive testing
during the design and manufacturing processes. Moreover, long life time is supported
by maintenance and repair services as well as by the availability of spare parts.
Design and manufacturing have been done under a certified environmental system.
The effectiveness of the environmental system is constantly evaluated by an external
auditing body. We follow environmental rules and regulations systematically to
evaluate their effect on our products and processes.
All parts used in this product are recyclable. When disposing cast-off IEDs or its parts,
contact the local enterprisers who are authorized and specialized in handling
RED615 13
Operation Manual
electrical/electronics waste. These partners can sort the material by using dedicated
sorting processes and dispose the product according to the local requirements.
1) Polycarbonate
2) Liquid crystal polymer
3) Polybutylene terephthalate
4) Polyamide
14 RED615
Operation Manual
3.1 Overview
RED615 is a two terminal phase segregated line differential protection IED designed
for the protection, measurement and supervision of feeders in utility substations and
industrial power systems. Re-engineered from the ground up, the IED has been guided
by the IEC 61850 standard for communication and interoperability of substation
automation devices.
The IED provides unit type main protection for overhead lines and cable feeders in
distribution networks. The IED also features current-based protection functions for
remote back-up to the down stream protection relays and local back-up for the line
differential main protection.
The IED is adapted for the protection of overhead line and cable feeders in isolated
neutral, resistance earthed, compensated (impedance earthed) and solidly earthed
networks. Once the standard configuration IED has been given the application-
specific settings, it can directly be put into service.
The 615 series IEDs support a range of communication protocols including IEC
61850 with GOOSE messaging and Modbus®.
RED615 15
Operation Manual
Protection
Line differential protection and related measurements, stabilized low-set stage ●
Line differential protection and related measurements, instantaneous high-set stage ●
Three-phase non-directional overcurrent, low-set stage ●
Three-phase non-directional overcurrent, high-set stage, instance 1 ●
Three-phase non-directional overcurrent, high-set stage, instance 2 ●
Three-phase non-directional overcurrent, instantaneous stage ●
Negative-sequence overcurrent, instance 1 ●
Negative-sequence overcurrent, instance 2 ●
Circuit breaker failure protection ●
Three-phase inrush current detection ●
Binary signal transfer ●
Control
Circuit breaker control with interlocking ●
Supervision and Monitoring
Trip-circuit supervision of two trip circuits ●
Local and remote phase currents (protection co-ordinated) ●
Current circuit supervision ●
Protection communication supervision ●
Measurement
Transient disturbance recorder ●
Three-phase current measurement ●
Current sequence components ●
Differential current measurement ●
Bias current measurement ●
The IED consists of two main parts: plug-in unit and case. The plug-in unit content
depends on the ordered functionality.
16 RED615
Operation Manual
The rated input levels are selected in the IED software for phase current and residual
current. The binary input thresholds 18...176 V DC are selected by adjusting the IED's
parameter settings.
See the Installation Manual for more information about the case and
the plug-in unit.
RED615 17
Operation Manual
3.5 LHMI
GUID-F69BFFA3-FEBF-4651-954F-9669770928A1 V2 EN
Figure 1: LHMI
3.5.1 LCD
The LHMI includes a graphical LCD that supports two character sizes. The character
size depends on the selected language.
The amount of characters and rows fitting the view depends on the character size:
18 RED615
Operation Manual
A070705 V3 EN
1 Header
2 Icon
3 Content
4 Scroll bar (appears when needed)
• The header area at the top of the display view shows the current location in the
menu structure.
• The icon area at the upper right corner of the display shows the current action or
user level.
Current action is indicated by the following characters:
• U: Font/Firmware is being updated
• S: Parameters are being stored
• !: Warning and/or indication
Current user level is indicated by the following characters:
• V: Viewer
• O: Operator
• E: Engineer
• A: Administrator
• The content area with four rows shows the menu content. With larger character
size, the content area has only three rows.
• If the menu contains more rows than the display can show at a time, a scroll bar
appears on the right.
The display is updated either cyclically or based on changes in the source data such
as parameters or events.
RED615 19
Operation Manual
3.5.2 LEDs
The LHMI includes three protection indicators above the display: Ready, Start and
Trip.
There are also 11 matrix programmable alarm LEDs on front of the LHMI. The LEDs
can be configured with PCM600 and the operation mode can be selected with the
LHMI.
3.5.3 Keypad
The LHMI keypad consists of push buttons which are used to navigate in different
views or menus. With push buttons you can give open or close commands to one
primary object, for example, a circuit breaker, disconnector or switch. The push
buttons are also used to acknowledge alarms, reset indications, provide help and
switch between local and remote control mode.
A070680 V4 EN
Figure 3: LHMI keypad with object control, navigation and command push
buttons and RJ-45 communication port
1 Close
2 Open
3 Escape
4 Left
5 Right
6 Up
7 Down
8 Enter
9 Key
10 Clear
11 Menu
12 Remote/Local
13 Help
14 Communication port
15 Uplink LED
20 RED615
Operation Manual
16 Communication LED
Object control
If the control position of the IED is set to local with the R/L button, the IED can be
controlled using the object control buttons.
Navigation
The arrow buttons are used for navigation. To scroll information, press the arrow
button several times or simply keep it pressed down.
• Activating the authorization procedure, when the user is not logged in.
Key • Logging out, when the user is currently logged in.
RED615 21
Operation Manual
Commands
Table 7: Command push buttons
Name Description
• Moving directly to the Main Menu, if currently in default view or in any menu.
Menu • Moving to the default view, if currently in Main Menu.
Protection indicators
Protection indicator LEDs are called Ready, Start and Trip.
• If several protection functions start within a short time, the last start is
indicated on the display.
22 RED615
Operation Manual
Alarm indicators
The 11 matrix programmable LEDs are used for alarm indication.
The LHMI is used to access the IED parameters. Three types of parameters can be
read and written.
• Numerical values
• String values
• Enumerated values
Numerical values are presented either in integer or in decimal format with minimum
and maximum values. Character strings can be edited character by character.
Enumerated values have a predefined set of selectable values.
The RJ-45 port in the LHMI enables front communication. Two LEDs are located
above the communication port.
RED615 23
Operation Manual
• The green uplink LED on the left is lit when the cable is successfully connected
to the port.
• The yellow communication LED on the right blinks when the IED communicates
with the connected device.
A070816 V3 EN
When a computer is connected to the IED, the IED's DHCP server for the front
interface assigns an IP address to the computer. The fixed IP address for the front
port is 192.168.0.254.
3.6 WHMI
The WHMI enables the user to access the IED via a web browser.
The menu tree structure on the WHMI is identical to the one on the LHMI.
24 RED615
Operation Manual
GUID-E6D25BB7-850E-4AD0-9C83-4A8D3CD0B1F4 V3 EN
• Locally by connecting your laptop to the IED via the front communication port.
• Remotely through the Internet or over LAN/WAN.
RED615 25
Operation Manual
Name Description
Rejecting changes.
Clearing events.
3.7 Authorization
The user categories have been predefined for the LHMI and the WHMI, each with
different rights and default passwords.
26 RED615
Operation Manual
3.8 Communication
The IED supports two different communication protocols: IEC 61850 and
Modbus®. Operational information and controls are available through these
protocols. IEC 61850 communication can be used parallel with Modbus®.
Modbus® protocol uses either Ethernet or the RS-485 bus.
The IEC 61850 communication implementation supports all monitoring and control
functions. Additionally, parameter setting and disturbance file records can be
accessed using the IEC 61850-8-1 protocol. Further, the IED can send and receive
binary signals from other IEDs (so called horizontal communication) using the IEC
61850-8-1 GOOSE profile, where the highest performance class with a total
transmission time of 3 ms is supported. The IED can simultaneously report to five
different IEC 61850-8-1 clients.
The IED can support five simultaneous clients. If PCM600 reserves one client
connection, only four client connections are left, for example, for IEC 61850 and
Modbus.
All communication connectors, except for the front port connector, are placed on
integrated optional communication modules. The IED can be connected to Ethernet-
based communication systems via the RJ-45 connector (100BASE-TX). If connection
to a RS-485 network is required, the 9-pin screw-terminal connector can be used. An
ST-type connector for serial communication over fibre optics is available as well. A
direct, dedicated fibre-optic connection is used between the IEDs as a protection
communication link. 1300 nm multi-mode or single-mode fibres with LC connectors
are used for line differential communication. The LC port in the IED is always the
topmost.
Protection and Control IED Manager PCM600 offers all the necessary functionality
to work throughout all stages of the IED life cycle:
• Planning
• Engineering
• Commissioning
• Operation and disturbance handling
• Functional analysis
With the individual tool components, you can perform different tasks and functions
and control the whole substation. PCM600 can operate with many different topologies
depending on customer needs.
RED615 27
Operation Manual
Connectivity Package Manager is a tool that helps the user to define the right
connectivity package versions for different system products and tools. Connectivity
Package Manager is included in products supporting the connectivity concept.
• Description of IED's internal parameters and their properties such as data format,
unit, setting range, visibility and access rights. The description texts can be
translated into other languages as well.
• Software components that adapt the IED-specific interfaces to the standard
interfaces of system products and tools such as IED-specific dispatchers for tools.
This means that there is a protocol-specific adaptation for the parameter setting
and disturbance handling tool components, for example disturbance uploading
according to COMTRADE.
• Protection and Control IED Manager PCM600 Ver. 2.0 SP1 or later
• RED615 Connectivity Package Ver. 1.0
• Parameter Setting Tool
• Disturbance Handling Tool
• Signal Monitoring Tool
• Signal Matrix Tool
• Communication Management Tool
• Differential Characteristics Tool
28 RED615
Operation Manual
You must be logged in and authorized to use the LHMI. Password authorization is
disabled by default and can be enabled either via the LHMI or WHMI.
4.1.1 Logging in
A070888 V3 EN
RED615 29
Operation Manual
A070890 V3 EN
A070889 V3 EN
The user level you are logged into shows on the LCD's upper right
corner in the icon area.
1. Press .
2. To confirm logout, select Yes and press .
• To cancel logout, press .
30 RED615
Operation Manual
The backlight turns on and the panel is ready for further operations.
If the panel has not been used for a predefined timeout period, the backlight is
switched off. The user is logged out from the current user level 30 seconds after the
display backlight has turned off.
The display returns to the default view and all unconfirmed operations such as
parameter editing and breaker selection are cancelled.
The IED information is shown on the display for a few seconds when the device starts
up. The same information is also found in the IED menu.
RED615 31
Operation Manual
A071158 V3 EN
A071160 V3 EN
The selected contrast value is stored in the non-volatile memory if you are logged in
and authorized to control the IED. After an auxiliary power failure, the contrast is
restored.
32 RED615
Operation Manual
A071010 V3 EN
The Main Menu contains main groups which are divided further into more detailed
submenus.
RED615 33
Operation Manual
• Language
• Monitoring
• Settings
• Configuration
• Tests
• Information
• Clear
• Disturbance records
• Events
• Measurements
If a menu contains more rows than the display can show at a time, a scroll bar is
displayed on the right.
A070895 V2 EN
The default view of the display is the Measurements unless set otherwise.
34 RED615
Operation Manual
A070858 V3 EN
GUID-BE6E1EEE-CA9E-4273-9EAC-94E989712645 V3 EN
RED615 35
Operation Manual
A070755 V3 EN
A070756 V3 EN
Figure 16: Arrow symbol is active, the value is set to the maximum
After pressing , the previous value can be restored by pressing once, and
vice versa. Another press of or sets the value to the lower or higher limit.
The symbol in front of the value is ↕, when the previous value is shown.
A070757 V3 EN
36 RED615
Operation Manual
When editing string values, the cursor moves to the first character.
2. Press or to change the value of an active character.
One press changes the value by one step. The available UTF-8 character codes
are 32...126 and 192...383.
3. Press or to move the cursor to another character.
• To insert characters or space, press simultaneously and .
• To delete characters, press simultaneously and .
Some parameters have an edit-copy. If editing is cancelled, the values with an edit-
copy are immediately restored to the original value. The values without an edit-copy,
such as string values, are restored to the original value only after a reboot even though
the edited value is not stored in the flash memory.
A070891 V3 EN
RED615 37
Operation Manual
A070860 V3 EN
1. Press .
38 RED615
Operation Manual
WHMI is disabled by default. You must be logged in and authorized to use the WHMI.
Do not use favorites in the web browser. If you are unauthorized and
select a favorite pointing to a WHMI page, you are redirected to the
log in page. With authorization you are redirected to the startup page.
4.2.1 Logging in
A070923 V3 EN
RED615 39
Operation Manual
GUID-D0ACBF32-78F1-458C-853A-DAAA6E80E006 V2 EN
40 RED615
Operation Manual
GUID-87496248-4921-4189-A590-E8A60AF0FEB0 V2 EN
RED615 41
Operation Manual
GUID-E5829BC5-AA45-48E7-8581-51BBE695A1BC V3 EN
42 RED615
Operation Manual
GUID-C1B77CCF-935F-4B38-975D-65DC450B911D V3 EN
The Main Menu contains main groups which are divided further into more detailed
submenus.
• Language
• Monitoring
• Settings
• Configuration
• Tests
• Information
• Clear
• Disturbance records
• Events
• Measurements
RED615 43
Operation Manual
GUID-F2DA9249-778C-416F-BCFF-767F1E979D27 V3 EN
44 RED615
Operation Manual
GUID-87AE5708-8053-49A1-A996-C19F669257E3 V3 EN
Some parameters, for example the IED test mode, cannot be set
via the WHMI.
RED615 45
Operation Manual
GUID-C6230163-7FE4-4438-B863-B433682496D6 V3 EN
The selected setting group is shown in the Setting Group drop-down box. The
active setting group is indicated with an asterisk *.
5. Edit the value.
46 RED615
Operation Manual
• The minimum and maximum values for a parameter are shown in the Min.
and Max. columns.
• Setting group values are indicated with .
GUID-BAC48980-0C88-4531-B967-B563A5A77B7D V3 EN
• If the entered value is within the accepted value range, the selection is
highlighted in green. If the value is out of range, the row is highlighted in
red and a warning dialog box appears.
A070934 V3 EN
RED615 47
Operation Manual
GUID-E10EE091-CFB9-4278-9FA4-7340C26F5814 V3 EN
Figure 30: Warning indicating that the values were not written to the
IED
Some parameters have an edit-copy. If editing is cancelled, the values with an edit-
copy are immediately restored to the original value. The values without an edit-copy,
such as string values, are restored to the original value only after a reboot even though
the edited value is not stored in the flash memory.
1. Click Write to IED after editing parameter values to put the values into IED's
database for use.
48 RED615
Operation Manual
GUID-23EB9E90-97A9-480F-9DD3-998F594CCFFC V3 EN
RED615 49
Operation Manual
GUID-834A71AE-B6C1-4EAD-840F-929B3AF18A85 V3 EN
If you only write values to the IED and then reboot, the old values
will resume in the IED as active values and the new values are lost.
50 RED615
Operation Manual
GUID-7662335C-3F76-4C14-B87E-5659FC579ECA V3 EN
RED615 51
Operation Manual
GUID-9AFBA8CE-117E-427B-BFD0-0616D26149AA V3 EN
52 RED615
Operation Manual
GUID-6E6248B9-3F3B-49A4-A281-10FC62E4DC22 V3 EN
RED615 53
Operation Manual
GUID-14CA3F7C-3C58-4E94-89EA-BA98C6994CCD V3 EN
54 RED615
Operation Manual
GUID-D698C171-5947-4A2D-9D12-186626156210 V3 EN
Figure 37: Normal case with only high degrees of load currents
GUID-01FF8E6C-8FC4-47AE-8926-83C1B4B38D8D V3 EN
RED615 55
Operation Manual
GUID-BF7CF464-ACFC-4130-B823-A0996367B6AE V3 EN
56 RED615
Operation Manual
GUID-F6C4F84A-2CAA-4F21-8894-5602098637F0 V3 EN
Figure 40: The arrow extends outside the circle if the current value is too
high
1. Click .
The help dialog box is displayed.
RED615 57
Operation Manual
GUID-FD2BEFF5-AF4C-4AFF-ADFA-C005A8B355ED V3 EN
58 RED615
Operation Manual
All basic operations can be performed via the LHMI, WHMI or with PCM600.
The IED is designed to identify and indicate several types of disturbances. The main
purpose of a protective IED is to identify power system disturbances and operate
according to the disturbance to avoid damage for power system equipment and people.
In other words, to disconnect the disturbance from the healthy network.
Many disturbance origins are permanent and cannot be automatically cleared. The
IED then collects disturbance data for later analysis.
RED615 59
Operation Manual
Some disturbances can be IED related, for example, external damage to hardware.
The IED supervises internal faults and indicates them to ensure that the user can take
the right corrective actions. Disturbance data can be read, managed and analyzed with
PCM600.
Document the tripping case before clearing the information from the
IED.
60 RED615
Operation Manual
Errors can be caused by external or internal events damaging the IED. Internal
supervision functionality monitors different types of internal errors. These can be
divided to hardware errors, runtime errors in application or operating system and
communication errors. Further actions always depend on the cause of the errors.
Only authorized and skilled personnel should analyze the errors and
decide on further actions.
• Hardware errors
• Runtime errors
• Communication errors
Document all the recorded data from the IED before you reset the
tripping and IED lockout functions.
RED615 61
Operation Manual
Sometimes the cause of an application fault can be determined via the LHMI. Usually,
this is not enough and a more detailed analysis of the application configuration is
needed. This can be done with PCM600.
IED parameters are usually set with a parameter setting tool but it can also be done
via the LHMI or WHMI.
After completing the editing of setting group values, the new values are activated.
The user can either commit the edited values or discard them. Setting values can also
be copied from one setting group to another.
62 RED615
Operation Manual
RED615 63
Operation Manual
6.1 Monitoring
6.1.1 Indications
The operation of the IED can be monitored via three different indications on the
LHMI.
• Three indicator LEDs with fixed functionality: Ready, Start and Trip
• 11 programmable alarm LEDs
• A text message on the display.
A071264 V3 EN
The blinking green LED indicates an internal IED fault. Internal IED fault messages
are shown in a dialog box.
RED615 65
Operation Manual
A071144 V3 EN
All internal IED fault messages are collected in C:\userlog.txt. The log file
can be uploaded and viewed by the user. The timestamp of the fault is included in the
log file.
With PCM600 the user can map output signals from condition monitoring related
function blocks to the appropriate destinations.
All values show the momentary measurement value and some include also demand
values calculated from set period.
66 RED615
Operation Manual
• Disturbance records
• Fault records
• Events
Normally disturbance recordings are triggered by the IED applications but the
recording can also be triggered manually.
A070861 V3 EN
Upload individual disturbance recordings from the IED with appropriate software
such as PCM600 to monitor disturbance recorder data. All disturbance recordings are
found in the C:\COMTRADE directory.
RED615 67
Operation Manual
A070863 V3 EN
A071146 V3 EN
68 RED615
Operation Manual
Event view contains a list of events produced by the application configuration. Each
event takes one view area. The header area shows the currently viewed event index
and the total amount of the events. The most recent event is always first.
A071148 V3 EN
RED615 69
Operation Manual
6.2 Controlling
A071174 V3 EN
A071170 V3 EN
70 RED615
Operation Manual
A071172 V3 EN
The time between selecting the object and giving a control command
is restricted by an adjustable timeout. When an object is selected, the
control command has to be given within this time.
RED615 71
Operation Manual
A070860 V4 EN
A071154 V3 EN
72 RED615
Operation Manual
If you do not cancel the test mode, it remains on and the Ready LED
remains blinking. Test mode does not retain if the IED is reset.
Each analog channel has an equal set of parameters and correspondingly, each binary
channel has an equal set of parameters.
IED settings are planned in advance for different operation conditions by calculating
setting values to different setting groups. The active setting group can be changed by
the IED application or manually from the menu.
A071150 V3 EN
RED615 73
Operation Manual
A071152 V3 EN
A070858 V3 EN
74 RED615
Operation Manual
A071166 V3 EN
3. To browse the settings, scroll the list with and and to select a setting
press .
4. To browse different function blocks, scroll the list with and and to select
a function block press . To move back to the list, press .
The function block list is shown in the content area of the display. On the left
in the header, you see the current setting group, and on the right the menu path.
5. To browse the parameters, scroll the list with and and to select a
parameter, press .
The setting group values are indicated with #.
A070899 V3 EN
6. To select a setting group value, press and to edit the value press .
A071168 V3 EN
RED615 75
Operation Manual
A070922 V3 EN
76 RED615
Operation Manual
Section 7 Troubleshooting
1. Check the error origin from the IED's supervision events Main Menu/
Monitoring/IED status/Self-supervision.
2. Reboot the IED and recheck the supervision events to see if the fault has cleared.
3. In case of persistent faults, contact ABB for corrective actions.
RED615 77
Operation Manual
Internal fault indications have the highest priority on the LHMI. None
of the other LHMI indications can override the internal fault
indication.
78 RED615
Operation Manual
An indication about the fault is shown as a message on the LHMI. The text
Internal Fault with an additional text message, a code, date and time, is shown
to indicate the fault type.
Different actions are taken depending on the severity of the fault. The IED tries to
eliminate the fault by restarting. After the fault is found to be permanent, the IED
stays in internal fault mode. All other output contacts are released and locked for the
internal fault. The IED continues to perform internal tests during the fault situation.
The internal fault code indicates the type of internal IED fault. When a fault appears,
document the code and state it when ordering the service.
A071144 V4 EN
RED615 79
Operation Manual
7.2.2 Warnings
A fault indication message, which includes text Warning with additional text, a
code, date and time, is shown on the LHMI to indicate the fault type. If more than
one type of fault occur at the same time, indication of the latest fault appears on the
LCD. The fault indication message can be manually cleared.
When a fault appears, the fault indication message is to be recorded and stated when
ordering service.
80 RED615
Operation Manual
A071222 V3 EN
RED615 81
Operation Manual
82 RED615
Operation Manual
Section 8 Commissioning
Familiarize yourself with the IED and its functionality before you start the
commissioning work.
• Ensure that you have all the needed station drawings such as single line and
wiring diagrams.
• Ensure that your version of the technical reference manual applies to the IED
version you test.
• Ensure that your setting software and connectivity packages work with the IED
version you test.
• Find out if you need any additional software.
• Ensure that you have the IED settings either on paper or in electronic format.
The settings and logic should be well documented.
• Inspect the settings to ensure that they are correct.
• Ensure that you have the correct cable to connect your PC to the IED's
communication port. The RJ-45 port supports any CAT 5 Ethernet cable but the
recommendation is STP.
• Test your PC's communication port before you go to the site.
• Find out who to contact if you have trouble and make sure you have a means to
contact them.
• Find out who is responsible for the settings.
• Ensure that you have with you the proper test equipment and all needed
connection cables.
• Ensure that the owner of the switchgear familiarizes you with the work site and
any special aspects of it.
• Ensure that you know how to operate in emergency situations. Find out where
the first aid and safety materials and exit routes are.
RED615 83
Operation Manual
• Primary injection test to verify the current ratio of the CT, the correct wiring up
to the protection IED and correct phase sequence connection (that is L1, L2,
L3.)
• Polarity check to prove that the predicted direction of secondary current flow is
correct for a given direction of primary current flow. This is an essential test for
the proper operation of the directional function, protection or measurement in
the IED.
• CT secondary loop resistance measurement to confirm that the current
transformer secondary loop dc resistance is within specification and that there
are no high resistance joints in the CT winding or wiring.
• CT excitation test to ensure that the correct core in the CT is connected to the
IED. Normally only a few points along the excitation curve are checked to ensure
that there are no wiring errors in the system, for example due to a mistake in
connecting the CT's measurement core to the IED.
• CT excitation test to ensure that the CT is of the correct accuracy rating and that
there are no short circuited turns in the CT windings. Manufacturer's design
curves should be available for the CT to compare the actual results.
• Check the earthing of the individual CT secondary circuits to verify that each
three-phase set of main CTs is properly connected to the station earth and only
at one electrical point.
• Insulation resistance check.
• Phase identification of CT shall be made.
Both primary and secondary sides must be disconnected from the line
and IED when plotting the excitation characteristics.
84 RED615
Operation Manual
Preferably, disconnect the binary input connector from the binary input cards. Check
all connected signals so that both input level and polarity are in accordance with the
IEDs specifications.
Preferably, disconnect the binary output connector from the binary output cards.
Check all connected signals so that both load and voltage are in accordance with the
IED specifications.
8.3 Authorizations
Passwords are settable. LHMI password must be at least four and WHMI password
at least nine characters. Maximum number of characters is 20 for the WHMI password
and 8 for the LHMI password. Only the following characters are accepted:
• Numbers 0-1
• Letters a-z, A-Z
• Space
• Special characters !"#%&'()*+´-./:;<=>?@[\]^_`{|}~
RED615 85
Operation Manual
Each IED has an Ethernet front connector for PCM600 access. Depending on the
station concept and the used station protocol, additional Ethernet interfaces may be
available on the rear side of the IED. All Ethernet interfaces can be used to connect
PCM600.
When an Ethernet based station protocol is used, the PCM600 communication can
use the same Ethernet port and IP address. The IED is able to separate the information
belonging to the PCM600 dialog.
Two options are available for the connection of PCM600 to the IED.
The IED has a DHCP server for the front interface. The DHCP server assigns an IP
address to the computer connected to the front interface. The computer's LAN
interface has to be configured to obtain the IP address automatically.
86 RED615
Operation Manual
The IP address and the corresponding mask can be set via the LHMI for the rear port.
The front port uses a fixed IP address 192.168.0.254. The front port also uses
DHCP.
Each Ethernet interface has a factory default IP address when the complete IED is
delivered.
RED615 87
Operation Manual
A071162 V1 EN
88 RED615
Operation Manual
A071224 V1 EN
RED615 89
Operation Manual
A071162 V1 EN
4. Choose Use the following IP address. Enter an IP address and a subnet mask.
Make sure that the IP address is unique, that is not used by any other IED on
the network.
90 RED615
Operation Manual
A071164 V1 EN
The used method depends on the time at which the IP address is available. Defining
IP address in the Object Properties windows allows changing the IP address at any
time.
RED615 91
Operation Manual
• To define the settings for the Ethernet port, select Main Menu/Configuration/
Communication/Ethernet/Rear port.
• To define the settings for RS-485/RS-232 serial port, select Main Menu/
Configuration/Communication/COM1 or Main Menu/Configuration/
Communication/COM2.
• To define Modbus communication parameters, select Main Menu/
Configuration/Communication/Modbus.
92 RED615
Operation Manual
A071010 V3 EN
Adjust the display contrast anywhere in the menu structure to obtain optimal
readability.
The selected contrast value is stored in the non-volatile memory if you are logged in
and authorized to control the IED. After an auxiliary power failure, the contrast is
restored.
To switch between the display symbols IEC 61850, IEC 61617 and IEC-ANSI:
The default view of the display is the Measurements unless set otherwise.
RED615 93
Operation Manual
1. Set the DST on day and DST off day parameters to define on which week day
the time shift occurs.
2. Set the DST on date and DST off date parameters to define on which month and
week the time shift occurs.
The DST on/off date must precede the selected DST on/off day and be within
the same week as the DST shift.
For example, if the DST is observed from the last Sunday in March to the last
Sunday in October and the time shift occurs at 01:00 UTC, the setting parameters
are:
94 RED615
Operation Manual
Set the DST on day and DST off day to "not in use" to determine the
exact date and time for the DST shift. Repeat the setting yearly, as the
time for the DST shift is not on the same date every year.
To disable the DST, set the DST offset parameter to "0 min".
A070858 V3 EN
RED615 95
Operation Manual
A071166 V3 EN
3. To browse the settings, scroll the list with and and to select a setting
press .
4. To browse different function blocks, scroll the list with and and to select
a function block press . To move back to the list, press .
The function block list is shown in the content area of the display. On the left
in the header, you see the current setting group, and on the right the menu path.
5. To browse the parameters, scroll the list with and and to select a
parameter, press .
The setting group values are indicated with #.
A070899 V3 EN
6. To select a setting group value, press and to edit the value press .
A071168 V3 EN
96 RED615
Operation Manual
A070922 V3 EN
A071150 V3 EN
A071152 V3 EN
RED615 97
Operation Manual
IED parameters are usually set with a parameter setting tool but it can also be done
via the LHMI or WHMI.
The IED has to be in the test mode before the digital outputs and certain output signals
of protection and other functions can be activated.
98 RED615
Operation Manual
A071154 V3 EN
If you do not cancel the test mode, it remains on and the Ready LED
remains blinking. Test mode does not retain if the IED is reset.
RED615 99
Operation Manual
Differing from real internal fault situation, the other output contacts
are not released and locked during the test. In other words, protection
functions can operate and trip the outputs when the internal fault is
tested.
A071156 V3 EN
The ABB Product Data Registration feature traces composition changes related to
the IED's SW or HW.
After a composition change, an LCT indication is seen on the LHMI at the IED start-
up. At this point, PCM600 should be connected to the IED as it reads the changed
data from the IED. The LCT indication is cleared in the same way as other indications.
If PCM600 is not connected to the IED, the indication is seen again after the IED's
reboot.
100 RED615
Operation Manual
A071266 V3 EN
The number of composition changes can be seen from the Composition changes
parameter in Main Menu/Monitoring/IED status.
RED615 101
Operation Manual
Section 9 Glossary
RED615 103
Operation Manual
104 RED615
Operation Manual
RED615 105
Operation Manual
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone +358 10 22 11
Fax +358 10 22 41094
www.abb.com/substationautomation