100% found this document useful (1 vote)
970 views116 pages

Operation Manual: Line Differential Protection and Control RED615

Uploaded by

Mirza Atayev
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
970 views116 pages

Operation Manual: Line Differential Protection and Control RED615

Uploaded by

Mirza Atayev
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 116

Operation Manual

Line Differential Protection and Control


RED615

Downloaded from www.dlmanuals.com


Downloaded from www.dlmanuals.com
Document ID: 1MRS756499
Issued: 03.10.2008
Revision: A
Product version: 1.1

© Copyright 2008 ABB. All rights reserved

Downloaded from www.dlmanuals.com


Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third party,
nor used for any unauthorized purpose.

The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license.

Trademarks
ABB is a registered trademark of ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their
respective holders.

Guarantee
Please inquire about the terms of guarantee from your nearest ABB representative.

ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 Vaasa, Finland
Telephone: +358 10 2211
Facsimile: +358 10 22 41094
http://www.abb.com/substationautomation

Downloaded from www.dlmanuals.com


Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements are
complied with. In particular, any risks in applications where a system failure and/or
product failure would create a risk for harm to property or persons (including but not
limited to personal injuries or death) shall be the sole responsibility of the person or
entity applying the equipment, and those so responsible are hereby requested to ensure
that all measures are taken to exclude or mitigate such risks.

This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in no
event shall ABB be responsible or liable for any loss or damage resulting from the
use of this manual or the application of the equipment.

Downloaded from www.dlmanuals.com


Conformity
This product complies with the directive of the Council of the European Communities
on the approximation of the laws of the Member States relating to electromagnetic
compatibility (EMC Council Directive 2004/108/EC) and concerning electrical
equipment for use within specified voltage limits (Low-voltage directive 2006/95/
EC). This conformity is the result of a test conducted by ABB in accordance with
Article 10 of the directive in agreement with the product standards EN 50263 and EN
60255-26 for the EMC directive, and with the product standards EN 60255-6 and EN
60255-27 for the low voltage directive. The IED is designed in accordance with the
international standards of the IEC 60255 series.

Downloaded from www.dlmanuals.com


Safety information
Dangerous voltages can occur on the connectors, even though the
auxiliary voltage has been disconnected.

Non-observance can result in death, personal injury or substantial


property damage.

Only a competent electrician is allowed to carry out the electrical


installation.

National and local electrical safety regulations must always be


followed.

The frame of the device has to be carefully earthed.

When the plug-in unit has been detached from the case, do not touch
the inside of the case. The relay case internals may contain high
voltage potential and touching these may cause personal injury.

The device contains components which are sensitive to electrostatic


discharge. Unnecessary touching of electronic components must
therefore be avoided.

Downloaded from www.dlmanuals.com


Downloaded from www.dlmanuals.com
Table of contents

Table of contents

Section 1 Introduction.......................................................................7
This manual........................................................................................7
Intended audience..............................................................................7
Product documentation.......................................................................8
Product documentation set............................................................8
Document revision history.............................................................9
Related documentation................................................................10
Document symbols and conventions................................................10
Safety indication symbols............................................................10
Document conventions................................................................11
Functions, codes and symbols....................................................11

Section 2 Environmental aspects...................................................13


Sustainable development.................................................................13
Disposing of the IED.........................................................................13

Section 3 RED615 overview...........................................................15


Overview...........................................................................................15
Product version history.....................................................................15
Operation functionality......................................................................15
Standard configurations...............................................................15
Optional functions........................................................................16
Physical hardware............................................................................16
LHMI.................................................................................................18
LCD.............................................................................................18
LEDs............................................................................................20
Keypad........................................................................................20
LHMI functionality........................................................................22
Protection and alarm indication..............................................22
Parameter management ........................................................23
Front communication..............................................................23
WHMI................................................................................................24
Command buttons.......................................................................25
Authorization.....................................................................................26
Communication.................................................................................27
PCM600 configuration tool...............................................................27
Connectivity packages.................................................................28
PCM600 and IED connectivity package version..........................28

Section 4 Using HMI locally or via web interface...........................29

RED615 1
Operation Manual

Downloaded from www.dlmanuals.com


Table of contents

Using LHMI.......................................................................................29
Logging in....................................................................................29
Logging out..................................................................................30
Turning display backlight on........................................................30
Selecting local or remote use......................................................31
Identifying the device...................................................................31
Adjusting display contrast............................................................32
Changing LHMI language............................................................32
Changing display symbols...........................................................33
Navigating in the menu................................................................33
Menu structure.......................................................................33
Scrolling the LCD view...........................................................34
Changing the default view......................................................34
Browsing setting values...............................................................35
Editing values..............................................................................35
Editing numerical values........................................................35
Editing string values...............................................................36
Editing enumerated values.....................................................37
Committing settings.....................................................................37
Clearing and acknowledging.......................................................38
Using LHMI help..........................................................................38
Using WHMI.....................................................................................39
Logging in....................................................................................39
Logging out..................................................................................39
Identifying the device...................................................................41
Navigating in the menu................................................................42
Menu structure.......................................................................43
Showing all parameters...............................................................43
Editing values..............................................................................45
Committing settings.....................................................................48
Clearing and acknowledging.......................................................50
Selecting alarm view....................................................................52
Selecting event view....................................................................53
Selecting phasor diagrams..........................................................54
Using WHMI help.........................................................................57

Section 5 IED operation ................................................................59


Operation in normal case.................................................................59
Function settings.........................................................................59
Test data .....................................................................................59
Disturbance case operation..............................................................59
Disturbance case identification....................................................60
Operation in tripping case ...........................................................60
Internal IED errors.......................................................................60

2 RED615
Operation Manual

Downloaded from www.dlmanuals.com


Table of contents

Disturbance recording triggering.................................................61


Disturbance record analysis........................................................61
Disturbance reports.....................................................................61
Fault determination...........................................................................62
Application problem verification...................................................62
IED parametrization..........................................................................62
IED settings for IED functionality.................................................62
IED settings for different operating conditions.............................63

Section 6 Operating procedures.....................................................65


Monitoring.........................................................................................65
Indications...................................................................................65
Monitoring indication messages.............................................65
Monitoring internal IED fault ..................................................65
Monitoring condition monitoring data.....................................66
Measured and calculated values.................................................66
Measured values....................................................................66
Using LHMI for monitoring......................................................66
Recorded data.............................................................................67
Creating disturbance recordings............................................67
Monitoring disturbance recorder data.....................................67
Controlling and uploading disturbance recorder data.............68
Monitoring fault records..........................................................68
Monitoring events...................................................................69
Remote monitoring......................................................................69
Operating IED remotely..........................................................69
Controlling........................................................................................70
Controlling circuit breakers and disconnectors............................70
Resetting IED...................................................................................71
Clearing and acknowledging via LHMI........................................71
Changing IED functionality...............................................................72
Creating blockings.......................................................................72
Selecting test mode.....................................................................72
Connecting to trip and disturbance recorder functions................73
Defining disturbance recorder channel settings..........................73
Defining setting group..................................................................73
Activating a setting group.......................................................73
Copying a setting group.........................................................74
Selecting a setting group for editing.......................................74
Browsing and editing setting group values.............................75
Activating LEDs...........................................................................76

Section 7 Troubleshooting .............................................................77


Fault tracing......................................................................................77

RED615 3
Operation Manual

Downloaded from www.dlmanuals.com


Table of contents

Identifying hardware errors..........................................................77


Identifying runtime errors.............................................................77
Identifying communication errors.................................................78
Checking communication LEDs...................................................78
Running the display test..............................................................78
Indication messages.........................................................................78
Internal faults...............................................................................78
Warnings.....................................................................................80
LED and display messages.........................................................82
Corrections procedures....................................................................82
Rebooting software......................................................................82
Setting password.........................................................................82

Section 8 Commissioning...............................................................83
Commissioning checklist..................................................................83
Checking installation.........................................................................83
Checking the power supply.........................................................83
Checking CT circuits....................................................................84
Checking binary input and output circuits....................................85
Binary input circuits................................................................85
Binary output circuits..............................................................85
Authorizations...................................................................................85
User authorization.......................................................................85
Using PCM600.................................................................................86
Setting communication between IEDs and PCM600...................86
Communication options..........................................................86
Setting communication parameters........................................87
Setting IED and communication.......................................................92
Setting communication................................................................92
Setting LHMI................................................................................92
Changing LHMI language.......................................................92
Adjusting display contrast.......................................................93
Changing display symbols......................................................93
Changing the default view......................................................93
Setting system time and time synchronization.......................94
Setting IED parameters...............................................................95
Defining setting groups...........................................................95
IED parametrization................................................................98
Configuring analog inputs.......................................................98
Testing IED operation.......................................................................98
Selecting test mode.....................................................................98
Testing digital I/O interface..........................................................99
Testing functions.........................................................................99
Selecting internal fault test........................................................100

4 RED615
Operation Manual

Downloaded from www.dlmanuals.com


Table of contents

ABB Product Data Registration......................................................100

Section 9 Glossary.......................................................................103

RED615 5
Operation Manual

Downloaded from www.dlmanuals.com


6

Downloaded from www.dlmanuals.com


1MRS756499 A Section 1
Introduction

Section 1 Introduction

1.1 This manual

Operation Manual contains instructions on how to operate the IED during normal
service once it has been commissioned. The manual can be used to find out how to
handle disturbances or how to view calculated and measured network data in order
to determine the cause of a fault.

1.2 Intended audience

This manual addresses the operator, who operates the IED on a daily basis.

The operator must be trained in and have a basic knowledge of how to operate
protection equipment. The manual contains terms and expressions commonly used
to describe this kind of equipment.

RED615 7
Operation Manual

Downloaded from www.dlmanuals.com


Section 1 1MRS756499 A
Introduction

1.3 Product documentation

1.3.1 Product documentation set

deinstalling & disposal


Planning & purchase

Decommissioning
Commissioning

Maintenance
Engineering

Operation
Installing
Engineering manual
Installation manual

Commissioning manual
Operation manual
Service manual

Application manual

Technical manual

Communication protocol
manual

en07000220.vsd

IEC07000220 V3 EN

Engineering Manual contains instructions on how to engineer the IEDs. The manual
provides instructions on how to use the different tools for IED engineering. It also
includes instructions on how to handle the tool component available to read
disturbance files from the IEDs on the basis of the IEC 61850 definitions. It further
introduces the diagnostic tool components available for IEDs and the PCM600 tool.

Installation Manual contains instructions on how to install the IED. The manual
provides procedures for mechanical and electrical installation. The chapters are
organized in the chronological order in which the protection IED should be installed.

Commissioning Manual contains instructions on how to commission the IED. The


manual can also be used as a reference during periodic testing. The manual provides
procedures for energizing and checking of external circuitry, setting and
configuration as well as verifying settings and performing directional tests. The
chapters are organized in the chronological order in which the IED should be
commissioned.

8 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 1
Introduction

Operation Manual contains instructions on how to operate the IED during normal
service once it has been commissioned. The manual can be used to find out how to
handle disturbances or how to view calculated and measured network data in order
to determine the cause of a fault.

Service Manual contains instructions on how to service and maintain the IED. The
manual also provides procedures for de-energizing, de-commissioning and disposal
of the IED.

Application Manual contains application descriptions and setting guidelines sorted


per function. The manual can be used to find out when and for what purpose a typical
protection function can be used. The manual can also be used when calculating
settings.

Technical Manual contains application and functionality descriptions and lists


function blocks, logic diagrams, input and output signals, setting parameters and
technical data sorted per function. The manual can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during
normal service.

The Communication Protocol manuals describe the different communication


protocols supported by the IED. The manuals concentrate on vendor-specific
implementations.

The Point List Manual describes the outlook and properties of the data points specific
to the IED. This manual should be used in conjunction with the corresponding
Communication Protocol Manual.

All manuals are not available yet.

1.3.2 Document revision history


Document revision/date Product version History
A/03.10.2008 1.1 First release

The latest revision of the document can be downloaded from the ABB
web site http://www.abb.com/substationautomation

RED615 9
Operation Manual

Downloaded from www.dlmanuals.com


Section 1 1MRS756499 A
Introduction

1.3.3 Related documentation


Name of the document Document ID
Application Manual 1MRS756498
Modbus Communication Protocol Manual 1MRS756468
Installation Manual 1MRS756375
Technical Manual 1MRS756497

1.4 Document symbols and conventions

1.4.1 Safety indication symbols


This publication includes the following icons that point out safety-related conditions
or other important information:

The electrical warning icon indicates the presence of a hazard which


could result in electrical shock.

The warning icon indicates the presence of a hazard which could


result in personal injury.

The caution icon indicates important information or warning related


to the concept discussed in the text. It might indicate the presence of
a hazard which could result in corruption of software or damage to
equipment or property.

The information icon alerts the reader to relevant facts and conditions.

The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.

Although warning hazards are related to personal injury, it should be understood that
operation of damaged equipment could, under certain operational conditions, result
in degraded process performance leading to personal injury or death. Therefore,
comply fully with all warning and caution notices.

10 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 1
Introduction

1.4.2 Document conventions

The following conventions are used for the presentation of material:

• Abbreviations in this manual are spelled out in the section "Glossary". In


addition, the section contains descriptions on several terms.
• Push button navigation in the HMI menu structure is presented by using the push
button icons, for example:
To navigate between the options, use and .
• HMI menu paths are presented as follows:
Select Main menu/Configuration/HMI.
• Menu names are shown in bold in WHMI, for example:
Click Information in the WHMI menu structure.
• HMI messages are shown in Courier font, for example:
To save the changes in non-volatile memory, select Yes and press
• Parameter names are shown in italics, for example:
The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks, for example:
The corresponding parameter values are "On" and "Off".
• IED input/output messages and monitored data names are shown in Courier font,
for example:
When the function starts, the START output is set to TRUE.

1.4.3 Functions, codes and symbols


Table 1: Functions included in the RED615 standard configuration
Function IEC 61850 IEC 60617 ANSI
Line differential protection, stabilized low stage LNPLDF 3ΔI >, 3ΔI>> 87L
and instantaneous high stage
Three-phase non-directional overcurrent PHLPTOC1 3I> 51P-1
protection, low stage
Three-phase non-directional overcurrent PHHPTOC1 3I>> 51P-2
protection, high stage
Three-phase non-directional overcurrent PHIPTOC1 3I>>> 50P/51P
protection, instantaneous stage
Negative-sequence overcurrent protection NSPTOC1 I2> 46

Circuit breaker failure protection CCBRBRF1 3I>/I0>BF 51BF/51NBF

Three-phase inrush detector INRPHAR1 3I2f> 68


Binary signal transfer BSTGGIO BST BST
Circuit breaker control with interlocking CBXCBR I ↔ O CB -
Three-phase current measurement CMMXU1 3I 3I
Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0

Transient disturbance recorder RDRE1 - -


Table continues on next page

RED615 11
Operation Manual

Downloaded from www.dlmanuals.com


Section 1 1MRS756499 A
Introduction

Function IEC 61850 IEC 60617 ANSI


Trip circuit supervision TCSSCBR1 TCS TCM
Current circuit supervision CCRDIF1 MCS 3I MCS 3I
Protection communication supervision PCSRTPC1 PCS PCS

12 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 2
Environmental aspects

Section 2 Environmental aspects

2.1 Sustainable development

Sustainability has been taken into account from the beginning of the product design
including the pro-environmental manufacturing process, long life time, operation
reliability and disposing of the IED.

The choice of the materials and the suppliers has been made according to the EU
RoHS directive (2002/95/EC). This directive limits the use of hazardous substances
which are the following:

Table 2: Maximum concentration values by weight per homogeneous material


Substance Proposed maximum concentration
Lead - Pb 0,1%
Mercury - Hg 0,1%
Cadmium - Cd 0,01%
Hexavalent Chromium Cr (VI) 0,1%
Polybrominated biphenyls - PBB 0,1%
Polybrominated diphenyl ethers - PBDE 0,1%

Operational reliability and long life time have been assured with extensive testing
during the design and manufacturing processes. Moreover, long life time is supported
by maintenance and repair services as well as by the availability of spare parts.

Design and manufacturing have been done under a certified environmental system.
The effectiveness of the environmental system is constantly evaluated by an external
auditing body. We follow environmental rules and regulations systematically to
evaluate their effect on our products and processes.

2.2 Disposing of the IED

Definitions and regulations of hazardous materials are country-specific and change


when the knowledge of materials increases. The materials used in this product are
typical for electric and electronic devices.

All parts used in this product are recyclable. When disposing cast-off IEDs or its parts,
contact the local enterprisers who are authorized and specialized in handling

RED615 13
Operation Manual

Downloaded from www.dlmanuals.com


Section 2 1MRS756499 A
Environmental aspects

electrical/electronics waste. These partners can sort the material by using dedicated
sorting processes and dispose the product according to the local requirements.

Table 3: Materials of the IED parts


IED Parts Material
Case Metallic plates, parts and screws Steel
Plastic parts PC1), LCP2)
Electronics plug in module Various
Plug-in unit Electronics plug in modules Various
Electronics LHMI module Various
Plastic parts PC, PBT3), LCP, PA4)
Metallic plate Steel
Package Box Cardboard
Attached material Manuals Paper

1) Polycarbonate
2) Liquid crystal polymer
3) Polybutylene terephthalate
4) Polyamide

14 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 3
RED615 overview

Section 3 RED615 overview

3.1 Overview

RED615 is a two terminal phase segregated line differential protection IED designed
for the protection, measurement and supervision of feeders in utility substations and
industrial power systems. Re-engineered from the ground up, the IED has been guided
by the IEC 61850 standard for communication and interoperability of substation
automation devices.

The IED provides unit type main protection for overhead lines and cable feeders in
distribution networks. The IED also features current-based protection functions for
remote back-up to the down stream protection relays and local back-up for the line
differential main protection.

The IED is adapted for the protection of overhead line and cable feeders in isolated
neutral, resistance earthed, compensated (impedance earthed) and solidly earthed
networks. Once the standard configuration IED has been given the application-
specific settings, it can directly be put into service.

The 615 series IEDs support a range of communication protocols including IEC
61850 with GOOSE messaging and Modbus®.

3.2 Product version history

IED version Release date Product history


1.1 03.10.2008 Product released

3.3 Operation functionality

3.3.1 Standard configurations


The line differential protection IED RED615 supports the following functions:

Standard configuration functionality Std.


conf.
A
(DE01)
Table continues on next page

RED615 15
Operation Manual

Downloaded from www.dlmanuals.com


Section 3 1MRS756499 A
RED615 overview

Protection
Line differential protection and related measurements, stabilized low-set stage ●
Line differential protection and related measurements, instantaneous high-set stage ●
Three-phase non-directional overcurrent, low-set stage ●
Three-phase non-directional overcurrent, high-set stage, instance 1 ●
Three-phase non-directional overcurrent, high-set stage, instance 2 ●
Three-phase non-directional overcurrent, instantaneous stage ●
Negative-sequence overcurrent, instance 1 ●
Negative-sequence overcurrent, instance 2 ●
Circuit breaker failure protection ●
Three-phase inrush current detection ●
Binary signal transfer ●
Control
Circuit breaker control with interlocking ●
Supervision and Monitoring
Trip-circuit supervision of two trip circuits ●
Local and remote phase currents (protection co-ordinated) ●
Current circuit supervision ●
Protection communication supervision ●
Measurement
Transient disturbance recorder ●
Three-phase current measurement ●
Current sequence components ●
Differential current measurement ●
Bias current measurement ●

3.3.2 Optional functions


The optional functions available in the IED are:
• Modbus TCP/IP or RTU/ASCII

3.4 Physical hardware

The IED consists of two main parts: plug-in unit and case. The plug-in unit content
depends on the ordered functionality.

16 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 3
RED615 overview

Table 4: Plug-in unit and case


Main Content options
unit
Plug- HMI
in unit
CPU module
Auxiliary power/ 48-250V DC / 100-240 V AC
binary output module 2 normally-open PO contacts
(slot X100) 1 change-over SO contacts
1 normally open SO contact
2 double-pole PO contacts with TCS
1 dedicated internal fault output contact
AI module (slot 3 phase current inputs (1/5A)
X120) 1 residual current input (1/5A)
4 BIs
BI/O module (slot 7 BIs
X110) 3 SO contacts
Case Optional BI/O 6 BIs
module (slot X130) 3 SO contacts
AI module interface connectors
Auxiliary power/binary output module interface connectors
BI/O module interface connectors
Communication module

The rated input levels are selected in the IED software for phase current and residual
current. The binary input thresholds 18...176 V DC are selected by adjusting the IED's
parameter settings.

The connection diagrams of different hardware modules are presented in the


Application manual.

See the Installation Manual for more information about the case and
the plug-in unit.

RED615 17
Operation Manual

Downloaded from www.dlmanuals.com


Section 3 1MRS756499 A
RED615 overview

3.5 LHMI

GUID-F69BFFA3-FEBF-4651-954F-9669770928A1 V2 EN

Figure 1: LHMI

The LHMI of the IED contains the following elements:


• Display
• Buttons
• LED indicators
• Communication port

The LHMI is used for setting, monitoring and controlling.

3.5.1 LCD
The LHMI includes a graphical LCD that supports two character sizes. The character
size depends on the selected language.

The amount of characters and rows fitting the view depends on the character size:

18 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 3
RED615 overview

Character size Rows in view Characters on row


Small, mono-spaced (6x12 5 rows 20
pixels) 10 rows with large screen
Large, variable width (13x14 4 rows min 8
pixels) 8 rows with large screen

The display view is divided into four basic areas:

A070705 V3 EN

Figure 2: Display layout

1 Header
2 Icon
3 Content
4 Scroll bar (appears when needed)

• The header area at the top of the display view shows the current location in the
menu structure.
• The icon area at the upper right corner of the display shows the current action or
user level.
Current action is indicated by the following characters:
• U: Font/Firmware is being updated
• S: Parameters are being stored
• !: Warning and/or indication
Current user level is indicated by the following characters:
• V: Viewer
• O: Operator
• E: Engineer
• A: Administrator
• The content area with four rows shows the menu content. With larger character
size, the content area has only three rows.
• If the menu contains more rows than the display can show at a time, a scroll bar
appears on the right.

The display is updated either cyclically or based on changes in the source data such
as parameters or events.

RED615 19
Operation Manual

Downloaded from www.dlmanuals.com


Section 3 1MRS756499 A
RED615 overview

3.5.2 LEDs
The LHMI includes three protection indicators above the display: Ready, Start and
Trip.

There are also 11 matrix programmable alarm LEDs on front of the LHMI. The LEDs
can be configured with PCM600 and the operation mode can be selected with the
LHMI.

3.5.3 Keypad
The LHMI keypad consists of push buttons which are used to navigate in different
views or menus. With push buttons you can give open or close commands to one
primary object, for example, a circuit breaker, disconnector or switch. The push
buttons are also used to acknowledge alarms, reset indications, provide help and
switch between local and remote control mode.

A070680 V4 EN

Figure 3: LHMI keypad with object control, navigation and command push
buttons and RJ-45 communication port

1 Close
2 Open
3 Escape
4 Left
5 Right
6 Up
7 Down
8 Enter
9 Key
10 Clear
11 Menu
12 Remote/Local
13 Help
14 Communication port
15 Uplink LED

20 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 3
RED615 overview

16 Communication LED

Object control
If the control position of the IED is set to local with the R/L button, the IED can be
controlled using the object control buttons.

As a default, breaker 1 is always the first to be controlled. If other controllable objects


are available, the user can select them in the control menu.

Table 5: Object control push buttons


Name Description
Closing the selected object.
Close

Opening the selected object.


Open

Navigation
The arrow buttons are used for navigation. To scroll information, press the arrow
button several times or simply keep it pressed down.

Table 6: Navigation push buttons


Name Description
• Leaving setting mode without saving the values.
ESC • Cancelling certain actions.
• Adjusting the display contrast in combination with or .
• Changing the language in combination with .
• Running the display test in combination with .
• Deleting a character in combination with when editing a string
• Inserting a space in combination with when editing a sting.

• Entering parameter setting mode.


Enter • Confirming a new value of a setting parameter.

• Moving up and down in menus.


Up • Scrolling active digits of a parameter when entering a new setting value.
Down

• Moving left and right in menus.


Left • Changing the active digit of a parameter when entering a new setting value.
Right

• Activating the authorization procedure, when the user is not logged in.
Key • Logging out, when the user is currently logged in.

RED615 21
Operation Manual

Downloaded from www.dlmanuals.com


Section 3 1MRS756499 A
RED615 overview

Commands
Table 7: Command push buttons
Name Description
• Moving directly to the Main Menu, if currently in default view or in any menu.
Menu • Moving to the default view, if currently in Main Menu.

Changing the control position (remote or local) of the device.


R/L
• When the R LED is lit, remote control is enabled and local control disabled.
• When the L LED is lit, local control is enabled and remote control disabled.
• When none of the LEDs are lit, both control positions are disabled.

Activating the Clear/Reset view.


Clear

Showing context sensitive help messages.


Help

3.5.4 LHMI functionality

3.5.4.1 Protection and alarm indication

Protection indicators
Protection indicator LEDs are called Ready, Start and Trip.

Table 8: Ready LED


LED state Description
Off Auxiliary supply voltage is disconnected.
On Normal operation.
Blinking Internal fault has occurred or the IED is in test mode. Internal faults are
accompanied by an indication message.

Table 9: Start LED


LED state Description
Off Normal operation.
On A protection function has started and an indication message is displayed.

• If several protection functions start within a short time, the last start is
indicated on the display.

Blinking A protection function is blocked.

• The blocking indication disappears when the blocking is removed or


when the protection function is reset.

22 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 3
RED615 overview

Table 10: Trip LED


LED state Description
Off Normal operation.
On A protection function has tripped and an indication message is displayed.

• The trip indication is latching and must be reset via communication or


by pressing .
• If several protection functions trip within a short time, the last trip is
indicated on the display.

Alarm indicators
The 11 matrix programmable LEDs are used for alarm indication.

Table 11: Alarm indications


LED state Description
Off Normal operation. All alarms are OFF.
On • Non-latched mode: alarm is still on.
• Latched mode: alarm is still on or it is off but has not been
acknowledged.
• Latched blinking mode: alarm is still on but has been acknowledged.

Blinking • Non-latched blinking mode: alarm is still on.


• Latched blinking mode: alarm is still on or it is off but has not been
acknowledged.

3.5.4.2 Parameter management

The LHMI is used to access the IED parameters. Three types of parameters can be
read and written.
• Numerical values
• String values
• Enumerated values

Numerical values are presented either in integer or in decimal format with minimum
and maximum values. Character strings can be edited character by character.
Enumerated values have a predefined set of selectable values.

3.5.4.3 Front communication

The RJ-45 port in the LHMI enables front communication. Two LEDs are located
above the communication port.

RED615 23
Operation Manual

Downloaded from www.dlmanuals.com


Section 3 1MRS756499 A
RED615 overview

• The green uplink LED on the left is lit when the cable is successfully connected
to the port.
• The yellow communication LED on the right blinks when the IED communicates
with the connected device.

A070816 V3 EN

Figure 4: RJ-45 communication port and indication LEDs

When a computer is connected to the IED, the IED's DHCP server for the front
interface assigns an IP address to the computer. The fixed IP address for the front
port is 192.168.0.254.

3.6 WHMI

The WHMI enables the user to access the IED via a web browser.

WHMI is disabled by default. To enable the WHMI, select Main


Menu/Configuration/HMI/Web HMI mode via the LHMI. Reboot
the IED for the change to take effect.

WHMI offers the following functions:

• Alarm indications and event lists


• System supervision
• Parameter settings
• Measurement display
• Phasor diagram

The menu tree structure on the WHMI is identical to the one on the LHMI.

24 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 3
RED615 overview

GUID-E6D25BB7-850E-4AD0-9C83-4A8D3CD0B1F4 V3 EN

Figure 5: Example view of the WHMI

The WHMI can be accessed:

• Locally by connecting your laptop to the IED via the front communication port.
• Remotely through the Internet or over LAN/WAN.

3.6.1 Command buttons


Command buttons can be used to edit parameters and control information via the
WHMI.

Table 12: Command buttons


Name Description
Preventing automatic logout.

Enabling parameter editing.

Disabling parameter editing.

Writing parameters to the IED.

Refreshing parameter values.

Committing changes to IED's non-volatile flash memory.

Table continues on next page

RED615 25
Operation Manual

Downloaded from www.dlmanuals.com


Section 3 1MRS756499 A
RED615 overview

Name Description
Rejecting changes.

Showing context sensitive help messages.

Clearing events.

Saving values to CSV file format.

Freezing the values so that updates are not displayed.

3.7 Authorization

The user categories have been predefined for the LHMI and the WHMI, each with
different rights and default passwords.

The default passwords can be changed with Administrator user rights.

User authorization is disabled by default for LHMI and can be enabled


either via the LHMI or the WHMI Main Menu/Configuration/
Authorization. WHMI always requires authentication.

Table 13: Predefined user categories


Username User rights
VIEWER Read only access
OPERATOR • Selecting remote or local state with (only locally)
• Changing setting groups
• Controlling
• Clearing alarm and indication LEDs and textual indications

ENGINEER • Changing settings


• Clearing event list
• Clearing disturbance records
• Changing system settings such as IP address, serial baud rate or
disturbance recorder settings
• Setting the IED to test mode
• Selecting language

ADMINISTRATOR • All listed above


• Changing password

For user authorization for PCM600, see PCM600 documentation.

26 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 3
RED615 overview

3.8 Communication

The IED supports two different communication protocols: IEC 61850 and
Modbus®. Operational information and controls are available through these
protocols. IEC 61850 communication can be used parallel with Modbus®.
Modbus® protocol uses either Ethernet or the RS-485 bus.

The IEC 61850 communication implementation supports all monitoring and control
functions. Additionally, parameter setting and disturbance file records can be
accessed using the IEC 61850-8-1 protocol. Further, the IED can send and receive
binary signals from other IEDs (so called horizontal communication) using the IEC
61850-8-1 GOOSE profile, where the highest performance class with a total
transmission time of 3 ms is supported. The IED can simultaneously report to five
different IEC 61850-8-1 clients.

The IED can support five simultaneous clients. If PCM600 reserves one client
connection, only four client connections are left, for example, for IEC 61850 and
Modbus.

All communication connectors, except for the front port connector, are placed on
integrated optional communication modules. The IED can be connected to Ethernet-
based communication systems via the RJ-45 connector (100BASE-TX). If connection
to a RS-485 network is required, the 9-pin screw-terminal connector can be used. An
ST-type connector for serial communication over fibre optics is available as well. A
direct, dedicated fibre-optic connection is used between the IEDs as a protection
communication link. 1300 nm multi-mode or single-mode fibres with LC connectors
are used for line differential communication. The LC port in the IED is always the
topmost.

3.9 PCM600 configuration tool

Protection and Control IED Manager PCM600 offers all the necessary functionality
to work throughout all stages of the IED life cycle:

• Planning
• Engineering
• Commissioning
• Operation and disturbance handling
• Functional analysis

With the individual tool components, you can perform different tasks and functions
and control the whole substation. PCM600 can operate with many different topologies
depending on customer needs.

RED615 27
Operation Manual

Downloaded from www.dlmanuals.com


Section 3 1MRS756499 A
RED615 overview

For more information, see PCM600 documentation.

3.9.1 Connectivity packages


Connectivity package is a collection of software and information related to a specific
protection and control terminal providing system products and tools to connect and
interact with the IED.

Connectivity Package Manager is a tool that helps the user to define the right
connectivity package versions for different system products and tools. Connectivity
Package Manager is included in products supporting the connectivity concept.

Use the connectivity packages to create configuration structure in PCM600. In


addition to other products supporting connectivity concept, the connectivity packages
for PCM600 contain:

• Description of IED's internal parameters and their properties such as data format,
unit, setting range, visibility and access rights. The description texts can be
translated into other languages as well.
• Software components that adapt the IED-specific interfaces to the standard
interfaces of system products and tools such as IED-specific dispatchers for tools.
This means that there is a protocol-specific adaptation for the parameter setting
and disturbance handling tool components, for example disturbance uploading
according to COMTRADE.

3.9.2 PCM600 and IED connectivity package version


Supported tools:

• Protection and Control IED Manager PCM600 Ver. 2.0 SP1 or later
• RED615 Connectivity Package Ver. 1.0
• Parameter Setting Tool
• Disturbance Handling Tool
• Signal Monitoring Tool
• Signal Matrix Tool
• Communication Management Tool
• Differential Characteristics Tool

Download connectivity packages from the ABB web site http://


www.abb.com/substationautomation

28 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 4
Using HMI locally or via web interface

Section 4 Using HMI locally or via web interface

4.1 Using LHMI

You must be logged in and authorized to use the LHMI. Password authorization is
disabled by default and can be enabled either via the LHMI or WHMI.

To enable password authorization, select Main Menu/


Configuration/Authorization/Local override. Set the parameter to
False.

4.1.1 Logging in

1. Press any key except for to activate the login procedure.


2. Press or to select the user level.

A070888 V3 EN

Figure 6: Selecting access level

3. Confirm the selection with .


4. Enter the prompted password digit by digit.

RED615 29
Operation Manual

Downloaded from www.dlmanuals.com


Section 4 1MRS756499 A
Using HMI locally or via web interface

• Activate the digit to be entered with and .


• Enter the character with and .

A070890 V3 EN

Figure 7: Entering password

5. Press to confirm the login.


• To cancel the procedure, press .

A070889 V3 EN

Figure 8: Error message indicating wrong password

The user level you are logged into shows on the LCD's upper right
corner in the icon area.

4.1.2 Logging out

1. Press .
2. To confirm logout, select Yes and press .
• To cancel logout, press .

4.1.3 Turning display backlight on


The display backlight is normally off. It turns on during the display test at power up.

• To turn on the backlight manually, press any LHMI push button.

30 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 4
Using HMI locally or via web interface

The backlight turns on and the panel is ready for further operations.

If the panel has not been used for a predefined timeout period, the backlight is
switched off. The user is logged out from the current user level 30 seconds after the
display backlight has turned off.

The display returns to the default view and all unconfirmed operations such as
parameter editing and breaker selection are cancelled.

Change the backlight timeout period in Main Menu/


Configuration/HMI/Backlight timeout.

4.1.4 Selecting local or remote use


The control position of the IED can be changed with the R/L button. In local position
primary equipment, such as circuit breakers and disconnectors, can be controlled via
the LHMI. In remote position, control operations are possible only from a higher
level, that is from a control center.

• Press for two seconds.


• When the L LED is lit, local control is enabled and remote control disabled.
• When the R LED is lit, remote control is enabled and local control disabled.
• When none of the LEDs are lit, both control positions are disabled.

The control position cannot be simultaneously local and remote,


but it can be disabled when neither of the positions is active.

You must be logged in and authorized to control the IED.

4.1.5 Identifying the device


The IED information includes detailed information about the device, such as revision
and serial number.

The IED information is shown on the display for a few seconds when the device starts
up. The same information is also found in the IED menu.

1. Select Main Menu/Information.


2. Select a submenu with and .

RED615 31
Operation Manual

Downloaded from www.dlmanuals.com


Section 4 1MRS756499 A
Using HMI locally or via web interface

A071158 V3 EN

Figure 9: Selecting submenu

3. Enter the submenu with .


4. Browse the information with and .

A071160 V3 EN

Figure 10: IED information

4.1.6 Adjusting display contrast


Adjust the display contrast anywhere in the menu structure to obtain optimal
readability.

• To increase the contrast, press simultaneously and .


• To decrease the contrast, press simultaneously and .

The selected contrast value is stored in the non-volatile memory if you are logged in
and authorized to control the IED. After an auxiliary power failure, the contrast is
restored.

4.1.7 Changing LHMI language

1. Select Main Menu/Language and press .


2. Change the language with or .
3. Press to confirm the selection.
4. Commit the changes.

32 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 4
Using HMI locally or via web interface

A071010 V3 EN

Figure 11: Changing the LHMI language

You can change the language also by pressing simultaneously and


.

4.1.8 Changing display symbols


To switch between the display symbols IEC 61850, IEC 61617 and IEC-ANSI:

1. Select Main Menu/Configuration/HMI/FB naming convention and press


.
2. Change the display symbols with or .
3. Press to confirm the selection.

The IED has to be rebooted if the WHMI display symbols are


changed. With the LHMI, the change takes effect immediately.

4.1.9 Navigating in the menu


Navigate the menus and change the display views on the screen with the keypad.

• To move to the Main Menu or default view, press .


• To move up or down in a menu, press or .
• To move downwards in the menu tree, press .
• To move upwards in the menu tree, press .
• To enter setting mode, press .
• To leave setting mode without saving, press .

4.1.9.1 Menu structure

The Main Menu contains main groups which are divided further into more detailed
submenus.

RED615 33
Operation Manual

Downloaded from www.dlmanuals.com


Section 4 1MRS756499 A
Using HMI locally or via web interface

• Language
• Monitoring
• Settings
• Configuration
• Tests
• Information
• Clear
• Disturbance records
• Events
• Measurements

4.1.9.2 Scrolling the LCD view

If a menu contains more rows than the display can show at a time, a scroll bar is
displayed on the right.

A070895 V2 EN

Figure 12: Scroll bar on the right

• To scroll the view upwards, press .


• To scroll the view downwards, press .
• To jump from the last row to the first row, press again.
• Press to jump from the first row to the last row.
• To scroll parameter names and values that do not fit the screen, press . Press
once to return to the beginning.

4.1.9.3 Changing the default view

The default view of the display is the Measurements unless set otherwise.

1. Select Main Menu/Configuration/HMI/Default view and press .


2. Change the default view with or .
3. Press to confirm the selection.

34 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 4
Using HMI locally or via web interface

4.1.10 Browsing setting values

1. Select Main Menu/Settings/Settings and press .


2. Select the setting group to be viewed with or .

A070858 V3 EN

Figure 13: Selecting a setting group

3. Press to confirm selection.


4. To browse the settings, scroll the list with and and to select a setting
press . To move back to the list, press .

GUID-BE6E1EEE-CA9E-4273-9EAC-94E989712645 V3 EN

Figure 14: Setting alternatives in the selected setting group

4.1.11 Editing values


You must be logged in and authorized to edit values.

4.1.11.1 Editing numerical values

1. Select Main Menu/Settings and then a setting.


When you start editing numerical values, the last digit is active.
• When the symbol in front of the value is ↑, you can only increase the active
value.
• When the symbol is ↓ you can only decrease the active value.
• When the symbol in front of the value is ↕, you can either increase or
decrease the active value.

RED615 35
Operation Manual

Downloaded from www.dlmanuals.com


Section 4 1MRS756499 A
Using HMI locally or via web interface

A070755 V3 EN

Figure 15: Last digit is active and it can only be increased

2. Press to increase or to decrease the value of an active digit.


One press increases or decreases the value by a certain step. For integer values,
the change is 1, 10, 100 or 1000 (...) depending on the active digit. Additionally,
for decimal values, the change can be fractions 0.1, 0.01, 0.001 (...) depending
on the active digit.
3. Press or to move the cursor to another digit.
4. To select the minimum or maximum value, select the arrow symbol in front of
the value.
• To set the value to the maximum, press .
• To set the value to the minimum, press .

A070756 V3 EN

Figure 16: Arrow symbol is active, the value is set to the maximum

After pressing , the previous value can be restored by pressing once, and
vice versa. Another press of or sets the value to the lower or higher limit.
The symbol in front of the value is ↕, when the previous value is shown.

A070757 V3 EN

Figure 17: Restoring the previous value

4.1.11.2 Editing string values

1. Activate the setting mode and select a setting.

36 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 4
Using HMI locally or via web interface

When editing string values, the cursor moves to the first character.
2. Press or to change the value of an active character.
One press changes the value by one step. The available UTF-8 character codes
are 32...126 and 192...383.
3. Press or to move the cursor to another character.
• To insert characters or space, press simultaneously and .
• To delete characters, press simultaneously and .

4.1.11.3 Editing enumerated values

1. Activate the setting mode and select a setting.


When editing an enumerated value, the selected value is shown inverted.
2. Press or to change the value of an active enumerated value.
One press changes the enumerated value by one step in the parameter specific
order.

4.1.12 Committing settings


Editable values are stored either in RAM or in non-volatile flash memory. Values
stored in flash memory are in effect also after reboot.

Some parameters have an edit-copy. If editing is cancelled, the values with an edit-
copy are immediately restored to the original value. The values without an edit-copy,
such as string values, are restored to the original value only after a reboot even though
the edited value is not stored in the flash memory.

1. Press to confirm any changes.


2. Press to move upwards in the menu tree or to enter the Main Menu.
3. To save the changes in non-volatile memory, select Yes and press .

A070891 V3 EN

Figure 18: Confirming settings

• To exit without saving changes, select No and press .

RED615 37
Operation Manual

Downloaded from www.dlmanuals.com


Section 4 1MRS756499 A
Using HMI locally or via web interface

• If the parameter has an edit-copy, the original parameter value is


restored.
• If the parameter does not have an edit-copy, the edited parameter
value remains visible until you reboot the IED. However, the edited
value is not stored in non-volatile memory and the reboot restores
the original value.
• To cancel saving settings, select Cancel and press . The value returns
to editing mode.

After certain parameters are changed, the IED has to be restarted.

4.1.13 Clearing and acknowledging


The Clear button is used to reset, acknowledge or clear all messages and indications,
including LEDs and latched outputs as well as registers and recordings. Press the
Clear button to activate a selection menu, where you can choose which clearance or
reset function you want to make. Events and alarms assigned to alarm LEDs are
cleared with the Clear button as well.

1. Press to activate the Clear view.

A070860 V3 EN

Figure 19: Clear view

2. Select the item to be cleared with or .


3. Press , change the value from False to True with or and press
again.
The item is now cleared and the value changes back to False.
4. Repeat steps 2 and 3 to clear other items.

4.1.14 Using LHMI help


The context sensitive LHMI help is used to get information from, for example, the
selected view, menu or a single parameter.

1. Press .

38 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 4
Using HMI locally or via web interface

The help view is displayed.


2. If the help text exceeds the display area, scroll the text with or .
3. To close the help, press .

4.2 Using WHMI

WHMI is disabled by default. You must be logged in and authorized to use the WHMI.

1. To enable the WHMI, select Main Menu/Configuration/HMI/Web HMI


mode via the LHMI.
2. Reboot the IED for the change to take effect.

Do not use favorites in the web browser. If you are unauthorized and
select a favorite pointing to a WHMI page, you are redirected to the
log in page. With authorization you are redirected to the startup page.

4.2.1 Logging in

1. Enter the username with capital letters.


2. Enter the password.
3. Click Log in.

A070923 V3 EN

Figure 20: Entering username and password to use the WHMI

4.2.2 Logging out


The user is logged out after session timeout. The timeout can be set in Main Menu/
Configuration/HMI/Web HMI timeout. The red session timeout bar appears one
minute before the timeout expires. You can prevent automatic logout by clicking
Close this dialog.

RED615 39
Operation Manual

Downloaded from www.dlmanuals.com


Section 4 1MRS756499 A
Using HMI locally or via web interface

GUID-D0ACBF32-78F1-458C-853A-DAAA6E80E006 V2 EN

Figure 21: Session timeout

40 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 4
Using HMI locally or via web interface

• To log out manually, click Logout on the menu bar.

GUID-87496248-4921-4189-A590-E8A60AF0FEB0 V2 EN

Figure 22: WHMI logout

4.2.3 Identifying the device


The IED information includes detailed information about the device, such as revision
and serial number.

RED615 41
Operation Manual

Downloaded from www.dlmanuals.com


Section 4 1MRS756499 A
Using HMI locally or via web interface

1. Click Information in the WHMI menu structure.


2. Click a submenu to see the data.

GUID-E5829BC5-AA45-48E7-8581-51BBE695A1BC V3 EN

Figure 23: Device information

4.2.4 Navigating in the menu


The menu tree structure on the WHMI is identical to the one on the LHMI. Use the
menu bar to access different views.
• The General view shows the IED version and status.
• The Events view contains a list of events produced by the application
configuration.
• The Alarms view shows the status of alarm LEDs.
• The Phasor diagrams view shows phasor diagrams.
• The Parameter list view shows all parameters.
• The WHMI settings view contains user settings for the client, that is the web
browser. WHMI settings include, for example, the client-specific setting for the
WHMI language. Different users can use different languages when connecting
to the same IED. The WHMI language selection is independent of the language
selection for the LHMI.
• Logout ends the session.

42 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 4
Using HMI locally or via web interface

GUID-C1B77CCF-935F-4B38-975D-65DC450B911D V3 EN

Figure 24: Navigating in the WHMI menus

4.2.4.1 Menu structure

The Main Menu contains main groups which are divided further into more detailed
submenus.

• Language
• Monitoring
• Settings
• Configuration
• Tests
• Information
• Clear
• Disturbance records
• Events
• Measurements

4.2.5 Showing all parameters

1. Click Parameter list in the menu bar.

RED615 43
Operation Manual

Downloaded from www.dlmanuals.com


Section 4 1MRS756499 A
Using HMI locally or via web interface

GUID-F2DA9249-778C-416F-BCFF-767F1E979D27 V3 EN

Figure 25: Show all parameters

2. Click Print to print out all parameters on paper.

44 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 4
Using HMI locally or via web interface

GUID-87AE5708-8053-49A1-A996-C19F669257E3 V3 EN

Figure 26: All parameters listed

3. Click Save to save all parameters in CSV file format.

4.2.6 Editing values

1. Click the menu in the WHMI tree.


2. Click the submenu to see function blocks.
3. Click a function block to see the setting values.
4. Click Enable Write.

Some parameters, for example the IED test mode, cannot be set
via the WHMI.

RED615 45
Operation Manual

Downloaded from www.dlmanuals.com


Section 4 1MRS756499 A
Using HMI locally or via web interface

GUID-C6230163-7FE4-4438-B863-B433682496D6 V3 EN

Figure 27: Enable writing to edit a value

The selected setting group is shown in the Setting Group drop-down box. The
active setting group is indicated with an asterisk *.
5. Edit the value.

46 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 4
Using HMI locally or via web interface

• The minimum and maximum values for a parameter are shown in the Min.
and Max. columns.
• Setting group values are indicated with .

GUID-BAC48980-0C88-4531-B967-B563A5A77B7D V3 EN

Figure 28: Editing value

• If the entered value is within the accepted value range, the selection is
highlighted in green. If the value is out of range, the row is highlighted in
red and a warning dialog box appears.

A070934 V3 EN

Figure 29: Warning indicating that the entered value is incorrect

• If writing values fails, a warning dialog box appears.

RED615 47
Operation Manual

Downloaded from www.dlmanuals.com


Section 4 1MRS756499 A
Using HMI locally or via web interface

GUID-E10EE091-CFB9-4278-9FA4-7340C26F5814 V3 EN

Figure 30: Warning indicating that the values were not written to the
IED

If you accidentally click Enable Write, click Disable Write.


However, Disable Write is not selectable if some value has already
been written to the IED. If Write to IED has been clicked, you can
only Commit or Reject.

4.2.7 Committing settings


Editable values are stored either in RAM or in non-volatile flash memory. Values
stored in flash memory are in effect also after reboot.

Some parameters have an edit-copy. If editing is cancelled, the values with an edit-
copy are immediately restored to the original value. The values without an edit-copy,
such as string values, are restored to the original value only after a reboot even though
the edited value is not stored in the flash memory.

1. Click Write to IED after editing parameter values to put the values into IED's
database for use.

48 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 4
Using HMI locally or via web interface

GUID-23EB9E90-97A9-480F-9DD3-998F594CCFFC V3 EN

Figure 31: Writing values to IED

The values are not stored to the flash memory.


2. Click Commit to write the values to the flash memory.
• Click Reject to cancel saving settings.
• If the parameter has an edit-copy, the original parameter value is
restored.
• If the parameter does not have an edit-copy, the edited parameter
value remains visible until you reboot the IED. However, the edited

RED615 49
Operation Manual

Downloaded from www.dlmanuals.com


Section 4 1MRS756499 A
Using HMI locally or via web interface

value is not stored in non-volatile memory and thus the reboot


restores the original value.

GUID-834A71AE-B6C1-4EAD-840F-929B3AF18A85 V3 EN

Figure 32: Committing changes

Committing values will take a few seconds.

If you only write values to the IED and then reboot, the old values
will resume in the IED as active values and the new values are lost.

4.2.8 Clearing and acknowledging


Reset, acknowledge or clear all messages and indications, including LEDs and latched
outputs as well as registers and recordings, in the Clear menu.

1. Click the Clear menu.

50 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 4
Using HMI locally or via web interface

GUID-7662335C-3F76-4C14-B87E-5659FC579ECA V3 EN

Figure 33: Selecting clear menu

2. Click Enable write.


3. In the New Value box, click True to select the item to be cleared.
4. Click Write to IED.
5. Click Reject.

RED615 51
Operation Manual

Downloaded from www.dlmanuals.com


Section 4 1MRS756499 A
Using HMI locally or via web interface

GUID-9AFBA8CE-117E-427B-BFD0-0616D26149AA V3 EN

Figure 34: Clearing indications and LEDs

4.2.9 Selecting alarm view


Alarm view shows the status of alarm LEDs. These are the same LEDs that are located
on the upper right side of the LHMI panel.

• Click Alarms in the menu bar.

52 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 4
Using HMI locally or via web interface

GUID-6E6248B9-3F3B-49A4-A281-10FC62E4DC22 V3 EN

Figure 35: Monitoring alarms

4.2.10 Selecting event view


The event view contains a list of events produced by the application configuration.

1. Click Events in the menu bar.

RED615 53
Operation Manual

Downloaded from www.dlmanuals.com


Section 4 1MRS756499 A
Using HMI locally or via web interface

GUID-14CA3F7C-3C58-4E94-89EA-BA98C6994CCD V3 EN

Figure 36: Monitoring events

2. Click Save to save the events in CSV file format.


The CSV file can be opened with a spreadsheet program such as OpenOffice.org
Calc or Microsoft Excel.
3. Click Clear events to clear all events from the IED.

4.2.11 Selecting phasor diagrams

1. Click Phasor diagrams in the menu bar.

54 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 4
Using HMI locally or via web interface

GUID-D698C171-5947-4A2D-9D12-186626156210 V3 EN

Figure 37: Normal case with only high degrees of load currents

2. Toggle the diagram visibility by selecting it from the drop-down menu.

GUID-01FF8E6C-8FC4-47AE-8926-83C1B4B38D8D V3 EN

Figure 38: Toggling the diagram visibility

RED615 55
Operation Manual

Downloaded from www.dlmanuals.com


Section 4 1MRS756499 A
Using HMI locally or via web interface

Visible diagrams are indicated with an asterisk *.


3. Change the size of the diagram by changing the zoom value.

GUID-BF7CF464-ACFC-4130-B823-A0996367B6AE V3 EN

Figure 39: Zooming the diagram

4. Click Freeze to stop updating the phasor diagram.


No updates will appear in the diagram.

56 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 4
Using HMI locally or via web interface

GUID-F6C4F84A-2CAA-4F21-8894-5602098637F0 V3 EN

Figure 40: The arrow extends outside the circle if the current value is too
high

Install an SVG plugin to view the phasor diagrams.

4.2.12 Using WHMI help


The context sensitive WHMI help provides information, for example, of a single
parameter.

1. Click .
The help dialog box is displayed.

RED615 57
Operation Manual

Downloaded from www.dlmanuals.com


Section 4 1MRS756499 A
Using HMI locally or via web interface

GUID-FD2BEFF5-AF4C-4AFF-ADFA-C005A8B355ED V3 EN

Figure 41: Clicking the help button

2. To close the help dialog box, click OK.

58 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 5
IED operation

Section 5 IED operation

5.1 Operation in normal case

The basic operation procedures in normal IED use situation are:


• Monitoring of measured values
• Checking the function setting parameters
• Checking the test data

All basic operations can be performed via the LHMI, WHMI or with PCM600.

For more information, see PCM600 documentation.

5.1.1 Function settings


To check the correct operation of the IED, check the function settings via the
LHMI, WHMI or PCM600.

5.1.2 Test data


The IED's functions can be tested to ensure correct operation. After a specific test,
you can analyze the results.

5.2 Disturbance case operation

The IED is designed to identify and indicate several types of disturbances. The main
purpose of a protective IED is to identify power system disturbances and operate
according to the disturbance to avoid damage for power system equipment and people.
In other words, to disconnect the disturbance from the healthy network.

Many disturbance origins are permanent and cannot be automatically cleared. The
IED then collects disturbance data for later analysis.

Only authorized and skilled personnel should analyze possible errors


and decide on further action. Otherwise, stored important disturbance
data can be permanently lost

RED615 59
Operation Manual

Downloaded from www.dlmanuals.com


Section 5 1MRS756499 A
IED operation

Some disturbances can be IED related, for example, external damage to hardware.
The IED supervises internal faults and indicates them to ensure that the user can take
the right corrective actions. Disturbance data can be read, managed and analyzed with
PCM600.

For more information, see PCM600 documentation.

5.2.1 Disturbance case identification


Disturbances and their causes can be identified on the basis of indicator LEDs: Ready,
Start and Trip. In normal operation case the Ready LED is steady green.

Table 14: Disturbance indications


LED State Description
Start LED Yellow, steady Protection started
Start LED Yellow, blinking Protection function blocked
Trip LED Red, steady Protections operated
Ready LED Green, blinking Internal faults

Further actions to be taken to identify the disturbance:

• Analyzing disturbance recordings


• Monitoring recorded data
• Reading internal events
• Finding available functions

5.2.2 Operation in tripping case


If a protection function trip is not cleared automatically, the cause of fault should be
checked to identify needs for further actions.

Document the tripping case before clearing the information from the
IED.

5.2.3 Internal IED errors


The IED monitors internal software and hardware errors. Internal error information
is collected to the IED for later analysis. The main indication of an internal fault is a
blinking green Ready LED.

60 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 5
IED operation

Errors can be caused by external or internal events damaging the IED. Internal
supervision functionality monitors different types of internal errors. These can be
divided to hardware errors, runtime errors in application or operating system and
communication errors. Further actions always depend on the cause of the errors.

Only authorized and skilled personnel should analyze the errors and
decide on further actions.

Internal IED errors may be caused by:

• Hardware errors
• Runtime errors
• Communication errors

The IED records:

• IED self-supervision report


• Event list
• System registrations

Document all the recorded data from the IED before you reset the
tripping and IED lockout functions.

5.2.4 Disturbance recording triggering


Disturbance recordings are normally triggered by IED applications when they detect
fault events. Disturbance recordings can also be triggered manually or periodically.

5.2.5 Disturbance record analysis


The IED collects disturbance records of fault events which are set to trigger the
disturbance recorder. Disturbance data is collected and stored for later viewing and
analysis. The disturbance recorder data can be uploaded and analyzed, for example,
with PCM600.

For more information, see PCM600 documentation.

5.2.6 Disturbance reports


PCM600 can be used for creating reports of disturbance recorder data.

RED615 61
Operation Manual

Downloaded from www.dlmanuals.com


Section 5 1MRS756499 A
IED operation

For more information, see PCM600 documentation.

5.3 Fault determination

Sometimes the cause of an application fault can be determined via the LHMI. Usually,
this is not enough and a more detailed analysis of the application configuration is
needed. This can be done with PCM600.

5.3.1 Application problem verification


The faulty operation of application functions is usually related to wrong configuration
or incorrect wiring of the external voltage and currents or binary inputs.

5.4 IED parametrization

IED parameters are usually set with a parameter setting tool but it can also be done
via the LHMI or WHMI.

Setting parameters need to be calculated according to the electrical network


conditions and the electrical characteristics of the protected equipment. The IED's
settings need to be verified before the IED is connected to a system.

For more information, see PCM600 documentation.

Document all changes to parameter settings.

5.4.1 IED settings for IED functionality


Function settings can be edited one by one by navigating to the individual setting
values, for example via the LHMI. The values in other setting groups should be known
before editing a certain setting value.

After completing the editing of setting group values, the new values are activated.
The user can either commit the edited values or discard them. Setting values can also
be copied from one setting group to another.

62 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 5
IED operation

5.4.2 IED settings for different operating conditions


IED settings can be designed for various operation conditions by defining different
setting values to different setting groups. The active setting group can be changed by
the IED application or manually via the LHMI.

RED615 63
Operation Manual

Downloaded from www.dlmanuals.com


64

Downloaded from www.dlmanuals.com


1MRS756499 A Section 6
Operating procedures

Section 6 Operating procedures

6.1 Monitoring

6.1.1 Indications
The operation of the IED can be monitored via three different indications on the
LHMI.

• Three indicator LEDs with fixed functionality: Ready, Start and Trip
• 11 programmable alarm LEDs
• A text message on the display.

6.1.1.1 Monitoring indication messages

Indication messages and tripping data are shown in a dialog box.

1. Read the indication message in the dialog box.


The message can indicate the starting or tripping of protection functions or an
internal fault in the device.
2. Press to close the indication message without clearing it or press to
activate the Clear view and to clear messages.

A071264 V3 EN

Figure 42: Indication message

6.1.1.2 Monitoring internal IED fault

The blinking green LED indicates an internal IED fault. Internal IED fault messages
are shown in a dialog box.

RED615 65
Operation Manual

Downloaded from www.dlmanuals.com


Section 6 1MRS756499 A
Operating procedures

A071144 V3 EN

Figure 43: Fault indication

1. Select Main Menu/Monitoring/IED status/Self-supervision to monitor the


latest fault indication.
2. Press or to scroll the view.

All internal IED fault messages are collected in C:\userlog.txt. The log file
can be uploaded and viewed by the user. The timestamp of the fault is included in the
log file.

6.1.1.3 Monitoring condition monitoring data

1. Select Main Menu/Monitoring/I/O status/Condition monitoring.


2. Press or to scroll the view.

With PCM600 the user can map output signals from condition monitoring related
function blocks to the appropriate destinations.

6.1.2 Measured and calculated values


Measurement view in Main Menu/Measurements shows the momentary actual
values for various power system measurements.

All values show the momentary measurement value and some include also demand
values calculated from set period.

6.1.2.1 Measured values

Measured values can be accessed through the LHMI or WHMI.

6.1.2.2 Using LHMI for monitoring

1. Select Main Menu/Measurements to monitor measured and calculated values.

66 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 6
Operating procedures

The list of IED's basic measurements is shown.


2. Scroll the view with and .

6.1.3 Recorded data


The IED is provided with intelligent and flexible functionality which collects different
kinds of data, for example, in case of fault event. The data gives substantial
information for the post fault analysis.

• Disturbance records
• Fault records
• Events

6.1.3.1 Creating disturbance recordings

Normally disturbance recordings are triggered by the IED applications but the
recording can also be triggered manually.

1. Select Main Menu/Disturbance records.


2. Select Trig recording with or .
3. Press , change the value from False to True with or and press
again.

A070861 V3 EN

Figure 44: Changing the value

The disturbance recorder is now triggered.

6.1.3.2 Monitoring disturbance recorder data

Upload individual disturbance recordings from the IED with appropriate software
such as PCM600 to monitor disturbance recorder data. All disturbance recordings are
found in the C:\COMTRADE directory.

1. Select Main Menu/Disturbance records.


All the disturbance recorder information is listed.
2. Scroll the view with or .
The following items are listed in the view:

RED615 67
Operation Manual

Downloaded from www.dlmanuals.com


Section 6 1MRS756499 A
Operating procedures

• Number of recordings currently in the IED memory.


• Remaining amount of recordings that fit into the available recording
memory.
• Recording memory used in percentage.
• If the periodic triggering function is used, the time to trigger which
indicates the remaining time to the next periodic triggering of the
disturbance recorder.

A070863 V3 EN

Figure 45: Monitoring disturbance recorder via the LHMI

6.1.3.3 Controlling and uploading disturbance recorder data

Disturbance recorder data can be controlled and read with PCM600.

For more information, see PCM600 documentation.

6.1.3.4 Monitoring fault records

1. Select Main Menu/Monitoring/Recorded data.


2. To navigate between the fault records, press and .
3. To enter or exit a submenu, press or .

A071146 V3 EN

Figure 46: Monitoring fault records

68 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 6
Operating procedures

6.1.3.5 Monitoring events

Event view contains a list of events produced by the application configuration. Each
event takes one view area. The header area shows the currently viewed event index
and the total amount of the events. The most recent event is always first.

1. Select Main Menu/Events.


2. Press to view the first event.
Date, time, device description, object description and event text elements of the
event are shown.
3. Press or to scroll the view.

A071148 V3 EN

Figure 47: Monitoring events

6.1.4 Remote monitoring


The IED supports comprehensive remote monitoring.

6.1.4.1 Operating IED remotely

With the PCM600 tool you can:

• Read maintenance record and version log


• Analyze disturbance record data
• Create disturbance record
• Read IED values.

For more information, refer to PCM600 documentation.

RED615 69
Operation Manual

Downloaded from www.dlmanuals.com


Section 6 1MRS756499 A
Operating procedures

6.2 Controlling

6.2.1 Controlling circuit breakers and disconnectors


The primary equipment can be controlled via the LHMI with the Open and Close
buttons when the IED is set to local control mode and you are authorized to access
control operations.

As a default, breaker 1 is always the first to be controlled. If other controllable objects


are available, select them in the control menu.

1. Select Main menu/Control.


The list of controllable objects is shown.
2. Enter the password when prompted.
3. Select an object with or and press .
The object is selected and is ready to be controlled.
4. Press to open or to close the object.

A071174 V3 EN

Figure 48: Selecting object

5. To confirm the operation, select Yes and press .

A071170 V3 EN

Figure 49: Opening circuit breaker

• To cancel the operation, select No and press .

70 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 6
Operating procedures

A071172 V3 EN

Figure 50: Cancelling operation

The time between selecting the object and giving a control command
is restricted by an adjustable timeout. When an object is selected, the
control command has to be given within this time.

6.3 Resetting IED

6.3.1 Clearing and acknowledging via LHMI


You can reset, acknowledge or clear all messages and indications, including LEDs
and latched outputs as well as registers and recordings, with the Clear button. Pressing
the Clear button activates a selection menu, where you can choose which clearance
or reset function you want to make. You can also clear events and alarms assigned to
alarm LEDs with the Clear button.

1. Press to activate the Clear view.


All the items that can be cleared are shown:
• Indications and LEDs
• Alarm LEDs
• Recorded data
• Events
• Disturbance records
• Temperature functions
• Trip lockout functions

RED615 71
Operation Manual

Downloaded from www.dlmanuals.com


Section 6 1MRS756499 A
Operating procedures

A070860 V4 EN

Figure 51: Clear view

2. Select the item to be cleared with or .


3. Press , change the value from False to True with or and press
again. The item is now cleared and the value changes back to False.
4. Repeat steps 2 and 3 to clear other items.

6.4 Changing IED functionality

6.4.1 Creating blockings


PCM600 can be used for creating blockings.

For more information, see PCM600 documentation.

6.4.2 Selecting test mode


The test mode can be activated using the LHMI. The green Ready LED will be
blinking to indicate that the test mode is activated.

1. Select Main Menu/Tests/IED test/Test mode and press .

A071154 V3 EN

Figure 52: Entering test mode

2. Select Test off or Test on with or .


3. Press to confirm the selection.

72 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 6
Operating procedures

If you do not cancel the test mode, it remains on and the Ready LED
remains blinking. Test mode does not retain if the IED is reset.

6.4.3 Connecting to trip and disturbance recorder functions


PCM600 can be used for connecting trip and disturbance recorder functions.

For more information, see PCM600 documentation.

6.4.4 Defining disturbance recorder channel settings

1. Select Main Menu/Configuration/Disturbance recorder/Channel settings.


2. Press or to scroll the view.
3. To change channel settings, press .

Each analog channel has an equal set of parameters and correspondingly, each binary
channel has an equal set of parameters.

6.4.5 Defining setting group

6.4.5.1 Activating a setting group

IED settings are planned in advance for different operation conditions by calculating
setting values to different setting groups. The active setting group can be changed by
the IED application or manually from the menu.

1. Select Main Menu/Settings/Setting group/Active group and press .

A071150 V3 EN

Figure 53: Active setting group

2. Select the setting group with or .


3. Press to confirm the selection or to cancel.

RED615 73
Operation Manual

Downloaded from www.dlmanuals.com


Section 6 1MRS756499 A
Operating procedures

A071152 V3 EN

Figure 54: Selecting active setting group

4. Commit the settings.

Remember to document the changes you make.

6.4.5.2 Copying a setting group

1. Select Main menu/Copy setting group and press .


2. Select the source and the destination with and .
3. Set the group numbers with and .
4. Press to confirm or to cancel.
If the destination group is the active one, these settings become valid.

6.4.5.3 Selecting a setting group for editing

1. Select Main Menu/Settings/Edit setting group.


2. Select the setting group to be edited with or .
3. Press to confirm the selection.
4. Edit the settings.

A070858 V3 EN

Figure 55: Selecting a setting group

74 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 6
Operating procedures

6.4.5.4 Browsing and editing setting group values

1. Select Main Menu/Settings/Settings and press .


2. Select the setting group to be viewed with or and press to confirm
the selection.

A071166 V3 EN

Figure 56: Selecting setting group

3. To browse the settings, scroll the list with and and to select a setting
press .
4. To browse different function blocks, scroll the list with and and to select
a function block press . To move back to the list, press .
The function block list is shown in the content area of the display. On the left
in the header, you see the current setting group, and on the right the menu path.
5. To browse the parameters, scroll the list with and and to select a
parameter, press .
The setting group values are indicated with #.

A070899 V3 EN

Figure 57: Setting group parameter

6. To select a setting group value, press and to edit the value press .

A071168 V3 EN

Figure 58: Selecting setting group value

RED615 75
Operation Manual

Downloaded from www.dlmanuals.com


Section 6 1MRS756499 A
Operating procedures

Only values within the selected setting group can be changed.


7. Press or to change the value and to confirm the selection.

A070922 V3 EN

Figure 59: Editing setting group value

The active setting group is indicated with an asterisk * .

6.4.6 Activating LEDs

1. Select Main Menu/Configuration/Alarm LEDs and press .


2. Select an Alarm LED with or .
3. Press to confirm the selection and to change the Alarm LED mode.
4. Press or to change the value and to confirm the selection.

For more information, see PCM600 documentation.

76 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 7
Troubleshooting

Section 7 Troubleshooting

7.1 Fault tracing

7.1.1 Identifying hardware errors


Most hardware errors are caused by external events which physically damage the
IED's hardware. Probable causes are, for example, overvoltage, spikes and short
circuits which damage one or several of the IED's physical inputs or outputs. Human
errors can also cause damage during installation or operation. As a consequence, one
or several physical cards, inputs or outputs may stop operating due to the damage.

1. Check the module with an error.


Check the IED supervision events in Main Menu/Monitoring/IED status/Self-
supervision for a faulty hardware module.
2. Inspect the IED visually
• Inspect the IED visually to find the physical error causes.
• If you can find some obvious physical damage, contact ABB for repair or
replacement actions.
3. Check whether the error is external or internal.
• Check that the error is not caused by external origins.
• Remove the wiring from the IED and test the input and output operation
with an external test device.
• If the problem remains, contact ABB for repair or replacement actions.

7.1.2 Identifying runtime errors


Runtime errors may be caused by component failures or software problems. Some
errors are cleared automatically but sometimes, for example in case of a component
failure, proper corrective actions are needed.

1. Check the error origin from the IED's supervision events Main Menu/
Monitoring/IED status/Self-supervision.
2. Reboot the IED and recheck the supervision events to see if the fault has cleared.
3. In case of persistent faults, contact ABB for corrective actions.

RED615 77
Operation Manual

Downloaded from www.dlmanuals.com


Section 7 1MRS756499 A
Troubleshooting

7.1.3 Identifying communication errors


Communication errors are normally communication interruptions or synchronization
message errors due to communication link breakdown.

1. Check the operation of the communication link.


2. Check the time synchronization. On the LHMI, this can be done by navigating
from Main Menu/Monitoring/IED status/Time synchronization.
3. In case of persistent faults originating from IED's internal faults such as
component breakdown, contact ABB for repair or replacement actions.

7.1.4 Checking communication LEDs


There are two LEDs on the LHMI above the RJ-45 communication port.

• To verify communication, check that both LEDs are lit.

Table 15: Communication LEDs


LED Communication ok
Uplink Steady green light
Communication Blinking yellow light

7.1.5 Running the display test


A short display test is always run, when auxiliary voltage is connected to the IED.
You can also run the display test manually.

• Press simultaneously and .


The LEDs are tested by turning them on simultaneously. The LCD shows a set
of patterns so that all the pixels are activated. After the test, the display returns
to normal state.

7.2 Indication messages

7.2.1 Internal faults

Internal fault indications have the highest priority on the LHMI. None
of the other LHMI indications can override the internal fault
indication.

78 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 7
Troubleshooting

An indication about the fault is shown as a message on the LHMI. The text
Internal Fault with an additional text message, a code, date and time, is shown
to indicate the fault type.

Different actions are taken depending on the severity of the fault. The IED tries to
eliminate the fault by restarting. After the fault is found to be permanent, the IED
stays in internal fault mode. All other output contacts are released and locked for the
internal fault. The IED continues to perform internal tests during the fault situation.

The internal fault code indicates the type of internal IED fault. When a fault appears,
document the code and state it when ordering the service.

A071144 V4 EN

Figure 60: Fault indication

Table 16: Internal fault indications and codes


Fault indication Fault code Additional information
Internal Fault 2 An internal system error has occurred.
System error
Internal Fault 7 A file system error has occurred.
File system error
Internal Fault 8 Internal fault test activated manually by the
Test user.
Internal Fault 10 Watchdog reset has occurred too many
SW watchdog error times within an hour.
Internal Fault 43 Faulty Signal Output relay(s) in card
SO-relay(s),X100 located in slot X100.
Internal Fault 44 Faulty Signal Output relay(s) in card
SO-relay(s),X110 located in slot X110.
Internal Fault 46 Faulty Signal Output relay(s) in card
SO-relay(s),X130 located in slot X130.
Internal Fault 53 Faulty Power Output relay(s) in card
PO-relay(s),X100 located in slot X100.
Internal Fault 54 Faulty Power Output relay(s) in card
PO-relay(s),X110 located in slot X110.
Internal Fault 56 Faulty Power Output relay(s) in card
PO-relay(s),X130 located in slot X130.
Internal Fault 57 Faulty ARC light sensor input(s).
Light sensor error
Internal Fault 62 Card in slot X000 is wrong type.
Conf. error,X000
Internal Fault 63 Card in slot X100 is wrong type or does not
Conf. error,X100 belong to the original composition.
Table continues on next page

RED615 79
Operation Manual

Downloaded from www.dlmanuals.com


Section 7 1MRS756499 A
Troubleshooting

Fault indication Fault code Additional information


Internal Fault 64 Card in slot X110 is wrong type, is missing
Conf. error,X110 or does not belong to the original
composition.
Internal Fault 65 Card in slot X120 is wrong type, is missing
Conf. error,X120 or does not belong to the original
composition.
Internal Fault 66 Card in slot X130 is wrong type, is missing
Conf. error,X130 or does not belong to the original
composition.
Internal Fault 72 Card in slot X000 is faulty.
Card error,X000
Internal Fault 73 Card in slot X100 is faulty.
Card error,X100
Internal Fault 74 Card in slot X110 is faulty.
Card error,X110
Internal Fault 75 Card in slot X120 is faulty.
Card error,X120
Internal Fault 76 Card in slot X130 is faulty.
Card error,X130
Internal Fault 79 LHMI module is faulty. The fault indication
LHMI module may not be seen on the LHMI during the
fault.
Internal Fault 80 Error in the RAM memory on the CPU
RAM error card.
Internal Fault 81 Error in the ROM memory on the CPU
ROM error card.
Internal Fault 82 Error in the EEPROM memory on the CPU
EEPROM error card.
Internal Fault 83 Error in the FPGA on the CPU card.
FPGA error
Internal Fault 84 Error in the RTC on the CPU card.
RTC error

7.2.2 Warnings
A fault indication message, which includes text Warning with additional text, a
code, date and time, is shown on the LHMI to indicate the fault type. If more than
one type of fault occur at the same time, indication of the latest fault appears on the
LCD. The fault indication message can be manually cleared.

When a fault appears, the fault indication message is to be recorded and stated when
ordering service.

80 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 7
Troubleshooting

A071222 V3 EN

Figure 61: Warning

Table 17: Warning indications and codes


Warning indication Warning code Additional information
Warning 10 A watchdog reset has occurred.
Watchdog reset
Warning 11 The auxiliary supply voltage has dropped
Power down det. too low.
Warning 20 Error when building the IEC 61850 data
IEC61850 error model.
Warning 21 Error in the Modbus communication.
Modbus error
Warning 22 Error in the DNP3 communication.
DNP3 error
Warning 24 Error in the Data set(s).
Dataset error
Warning 25 Error in the Report control block(s).
Report cont. error
Warning 26 Error in the GOOSE control block(s).
GOOSE contr. error
Warning 27 Error in the SCL configuration file or the file
SCL config error is missing.
Warning 28 Too many connections in the
Logic error configuration.
Warning 29 Error in the SMT connections.
SMT logic error
Warning 30 Error in the GOOSE connections.
GOOSE input error
Warning 32 Error in the GOOSE message receiving.
GOOSE rec. error
Warning 33 Analog channel configuration error.
AFL error
Warning 40 A new composition has not been
Unack card comp. acknowledged/accepted.
Warning 50 Error in protection communication.
Protection comm.
Warning 85 A continuous light has been detected on
ARC1 cont. light the ARC light input 1.
Warning 86 A continuous light has been detected on
ARC2 cont. light the ARC light input 2.
Warning 87 A continuous light has been detected on
ARC3 cont. light the ARC light input 3.

RED615 81
Operation Manual

Downloaded from www.dlmanuals.com


Section 7 1MRS756499 A
Troubleshooting

7.2.3 LED and display messages


Usually when a LED is lit, an indication is shown on the LHMI and event 10 is
generated.

7.3 Corrections procedures

7.3.1 Rebooting software

1. Select Main Menu/Configuration/General and press .


2. Change the value from False to True with or button and press .

7.3.2 Setting password


If user authorization is off or the user is logged in as an administrator, user passwords
can be set via the LHMI or WHMI or with PCM600.

The password can be set to write mode with engineer or operator


rights but the changes to the password are not saved.

1. Select Main Menu/Configuration/Authorization.


2. Select the password to be reset with or .
3. Press , change the password with or and press again.
4. Repeat steps 2 and 3 to set the rest of the passwords.

82 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 8
Commissioning

Section 8 Commissioning

8.1 Commissioning checklist

Familiarize yourself with the IED and its functionality before you start the
commissioning work.
• Ensure that you have all the needed station drawings such as single line and
wiring diagrams.
• Ensure that your version of the technical reference manual applies to the IED
version you test.
• Ensure that your setting software and connectivity packages work with the IED
version you test.
• Find out if you need any additional software.
• Ensure that you have the IED settings either on paper or in electronic format.
The settings and logic should be well documented.
• Inspect the settings to ensure that they are correct.
• Ensure that you have the correct cable to connect your PC to the IED's
communication port. The RJ-45 port supports any CAT 5 Ethernet cable but the
recommendation is STP.
• Test your PC's communication port before you go to the site.
• Find out who to contact if you have trouble and make sure you have a means to
contact them.
• Find out who is responsible for the settings.
• Ensure that you have with you the proper test equipment and all needed
connection cables.
• Ensure that the owner of the switchgear familiarizes you with the work site and
any special aspects of it.
• Ensure that you know how to operate in emergency situations. Find out where
the first aid and safety materials and exit routes are.

8.2 Checking installation

8.2.1 Checking the power supply


Check that the auxiliary supply voltage remains within the permissible input voltage
range under all operating conditions. Check that the polarity is correct.

RED615 83
Operation Manual

Downloaded from www.dlmanuals.com


Section 8 1MRS756499 A
Commissioning

8.2.2 Checking CT circuits


The CTs must be connected in accordance with the terminal diagram provided with
the IED, both with regards to phases and polarity. The following tests are
recommended for every primary CT or CT core connected to the IED:

• Primary injection test to verify the current ratio of the CT, the correct wiring up
to the protection IED and correct phase sequence connection (that is L1, L2,
L3.)
• Polarity check to prove that the predicted direction of secondary current flow is
correct for a given direction of primary current flow. This is an essential test for
the proper operation of the directional function, protection or measurement in
the IED.
• CT secondary loop resistance measurement to confirm that the current
transformer secondary loop dc resistance is within specification and that there
are no high resistance joints in the CT winding or wiring.
• CT excitation test to ensure that the correct core in the CT is connected to the
IED. Normally only a few points along the excitation curve are checked to ensure
that there are no wiring errors in the system, for example due to a mistake in
connecting the CT's measurement core to the IED.
• CT excitation test to ensure that the CT is of the correct accuracy rating and that
there are no short circuited turns in the CT windings. Manufacturer's design
curves should be available for the CT to compare the actual results.
• Check the earthing of the individual CT secondary circuits to verify that each
three-phase set of main CTs is properly connected to the station earth and only
at one electrical point.
• Insulation resistance check.
• Phase identification of CT shall be made.

Both primary and secondary sides must be disconnected from the line
and IED when plotting the excitation characteristics.

If the CT secondary circuit is opened or its earth connection is missing


or removed without the CT primary being de-energized first,
dangerous voltages may be produced. This can be lethal and damage,
for example, insulation. The re-energizing of the CT primary should
be inhibited as long as the CT secondary is open or unearthed.

84 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 8
Commissioning

8.2.3 Checking binary input and output circuits

8.2.3.1 Binary input circuits

Preferably, disconnect the binary input connector from the binary input cards. Check
all connected signals so that both input level and polarity are in accordance with the
IEDs specifications.

8.2.3.2 Binary output circuits

Preferably, disconnect the binary output connector from the binary output cards.
Check all connected signals so that both load and voltage are in accordance with the
IED specifications.

8.3 Authorizations

8.3.1 User authorization


The user categories have been predefined for LHMI and WHMI, each with different
rights and default passwords.

Passwords are settable. LHMI password must be at least four and WHMI password
at least nine characters. Maximum number of characters is 20 for the WHMI password
and 8 for the LHMI password. Only the following characters are accepted:
• Numbers 0-1
• Letters a-z, A-Z
• Space
• Special characters !"#%&'()*+´-./:;<=>?@[\]^_`{|}~

User authorization is disabled by default and can be enabled either


via the LHMI or WHMI Main Menu/Configuration/
Authorization.

Table 18: Predefined user categories


Username LHMI WHMI password User rights
password
VIEWER 0001 remote0001 Only allowed to view
OPERATOR 0002 remote0002 Authorized to make operations
ENGINEER 0003 remote0003 Allowed to change IED parameters, but no
operation rights
ADMINISTRATOR 0004 remote0004 Full access

RED615 85
Operation Manual

Downloaded from www.dlmanuals.com


Section 8 1MRS756499 A
Commissioning

For user authorization for PCM600, see PCM600 documentation.

8.4 Using PCM600

8.4.1 Setting communication between IEDs and PCM600


The communication between the IED and PCM600 is independent of the used
communication protocol within the substation or to the NCC. It can be seen as a
second channel for communication.

The communication media is always Ethernet and the protocol is TCP/IP.

Each IED has an Ethernet front connector for PCM600 access. Depending on the
station concept and the used station protocol, additional Ethernet interfaces may be
available on the rear side of the IED. All Ethernet interfaces can be used to connect
PCM600.

When an Ethernet based station protocol is used, the PCM600 communication can
use the same Ethernet port and IP address. The IED is able to separate the information
belonging to the PCM600 dialog.

To configure the physical connection and the IP addresses:

1. Set up or get the IP addresses of the IEDs.


2. Set up the PC for a direct link or connect the PC or workstation to the network.
3. Configure the IED IP addresses in the PCM600 project for each IED. The
addresses are used for communication by the OPC interface of PCM600.

8.4.1.1 Communication options

Two options are available for the connection of PCM600 to the IED.

• Direct point to point link between PCM600 and the IED


• Indirect link via a station LAN or from remote via a network

Point to point link


The IED is provided with an RJ-45 connector on the LHMI. The connector is mainly
for configuration and setting purposes. Any Ethernet cable can be used but the
recommendation is STP.

The IED has a DHCP server for the front interface. The DHCP server assigns an IP
address to the computer connected to the front interface. The computer's LAN
interface has to be configured to obtain the IP address automatically.

86 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 8
Commissioning

LAN or WAN network


In TCP/IP networking, a LAN is often but not always implemented as a single IP
subnet. A router connects LANs to a WAN. In IP networking, the router maintains
both a LAN address and a WAN address. Design considerations for computer
networks cover a wide range of topics including layout, capacity planning, and
security. To some extent, the network configuration also depends on user preferences.

8.4.1.2 Setting communication parameters

The IP address and the corresponding mask can be set via the LHMI for the rear port.
The front port uses a fixed IP address 192.168.0.254. The front port also uses
DHCP.

Each Ethernet interface has a factory default IP address when the complete IED is
delivered.

Setting front communication


To set up a standard PC with Microsoft Windows operating system for front
communication:

1. To open Network Connections, click Start, point to Settings, click Control


Panel, and then double-click Network Connections.
2. Double-click the connection that you want to configure, and then click
Properties.
3. Select the TCP/IP protocol from the list of configured components using this
connection and click Properties.

RED615 87
Operation Manual

Downloaded from www.dlmanuals.com


Section 8 1MRS756499 A
Commissioning

A071162 V1 EN

Figure 62: Selecting TCP/IP protocol

4. Select Obtain an IP address automatically and Obtain DNS server address


automatically.

88 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 8
Commissioning

A071224 V1 EN

Figure 63: Obtaining IP address automatically

5. Close all open windows by clicking OK and start PCM600.

Administrator rights are requested to change the configuration


as described above.

Setting rear communication


To set up a standard PC with MicroSoft Windows operating system for rear
communication:

1. To open Network Connections, click Start, point to Settings, click Control


Panel, and then double-click Network Connections.
2. Double-click the connection that you want to configure, and then click
Properties.
3. Select the TCP/IP protocol from the list of configured components using this
connection and click Properties.

RED615 89
Operation Manual

Downloaded from www.dlmanuals.com


Section 8 1MRS756499 A
Commissioning

A071162 V1 EN

Figure 64: Selecting TCP/IP protocol

4. Choose Use the following IP address. Enter an IP address and a subnet mask.
Make sure that the IP address is unique, that is not used by any other IED on
the network.

90 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 8
Commissioning

A071164 V1 EN

Figure 65: Setting IP address and subnet mask

5. Close all open windows by clicking OK and start PCM600.

Administrator rights are requested to change the configuration


as described above.

Setting IED's IP address in PCM600


In PCM600 the IED's IP address can be defined either via the first window of the
wizard by including a new IED in the project or by entering the IED's IP address in
the Object Properties window.

1. Select the IED to which you want to define the IP address.


2. Open the Object Properties window.
3. Place the cursor in the IP Address row and enter the IP address.

The used method depends on the time at which the IP address is available. Defining
IP address in the Object Properties windows allows changing the IP address at any
time.

RED615 91
Operation Manual

Downloaded from www.dlmanuals.com


Section 8 1MRS756499 A
Commissioning

8.5 Setting IED and communication

8.5.1 Setting communication


The IED is provided with an RJ-45 connector on the LHMI. The connector is mainly
used for configuration and setting purposes. The fixed IP address for the front port is
192.168.0.254.

Different communication ports are available via optional communication modules.


There are three options for rear port communication intended mainly for station level
communication, that is station bus. The options are galvanic Ethernet (RJ-45), optical
Ethernet (LC) and RS-485/RS-232 twisted pair. Communication protocols used via
Ethernet ports are IEC 61850-8-1 and Modbus TCP/IP. Protocol available for
RS-485/RS-232 serial port is Modbus RTU/Modbus ASCII.

• To define the settings for the Ethernet port, select Main Menu/Configuration/
Communication/Ethernet/Rear port.
• To define the settings for RS-485/RS-232 serial port, select Main Menu/
Configuration/Communication/COM1 or Main Menu/Configuration/
Communication/COM2.
• To define Modbus communication parameters, select Main Menu/
Configuration/Communication/Modbus.

For more information, see Modbus Communication Protocol Manual


and Technical Manual.

8.5.2 Setting LHMI

8.5.2.1 Changing LHMI language

1. Select Main Menu/Language and press .


2. Change the language with or .
3. Press to confirm the selection.
4. Commit the changes.

92 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 8
Commissioning

A071010 V3 EN

Figure 66: Changing the LHMI language

You can change the language also by pressing simultaneously and


.

8.5.2.2 Adjusting display contrast

Adjust the display contrast anywhere in the menu structure to obtain optimal
readability.

• To increase the contrast, press simultaneously and .


• To decrease the contrast, press simultaneously and .

The selected contrast value is stored in the non-volatile memory if you are logged in
and authorized to control the IED. After an auxiliary power failure, the contrast is
restored.

8.5.2.3 Changing display symbols

To switch between the display symbols IEC 61850, IEC 61617 and IEC-ANSI:

1. Select Main Menu/Configuration/HMI/FB naming convention and press


.
2. Change the display symbols with or .
3. Press to confirm the selection.

The IED has to be rebooted if the WHMI display symbols are


changed. With the LHMI, the change takes effect immediately.

8.5.2.4 Changing the default view

The default view of the display is the Measurements unless set otherwise.

RED615 93
Operation Manual

Downloaded from www.dlmanuals.com


Section 8 1MRS756499 A
Commissioning

1. Select Main Menu/Configuration/HMI/Default view and press .


2. Change the default view with or .
3. Press to confirm the selection.

8.5.2.5 Setting system time and time synchronization

1. Select Main Menu/Configuration/Time/System time and press .


2. Select the parameter with or .
3. Press , change the value with or and press again.
4. Repeat steps 2 and 3 to set the rest of the system time parameters.
5. Select Main Menu/Configuration/Time/Synchronization/Synch source and
press .
6. Set the time synchronization source to SNTP, Modbus, Line
differential or IRIG-B with or .
7. Press to confirm the selection.
If SNTP is used, the SNTP server's IP address is set in Main Menu/
Configuration/Time/Synchronization/IP SNTP Primary and Main Menu/
Configuration/Time/Synchronization/IP SNTP Secondary.

Setting daylight saving time


The IED can be set to determine the correct date for the DST shift every year. The
UTC time is used to set the DST.

1. Set the DST on day and DST off day parameters to define on which week day
the time shift occurs.
2. Set the DST on date and DST off date parameters to define on which month and
week the time shift occurs.
The DST on/off date must precede the selected DST on/off day and be within
the same week as the DST shift.

Table 19: DST change on Sunday


Day of the DST shift DST on/off date
First Sunday of the month 1
Second Sunday of the month 8
Third Sunday of the month 15
Fourth Sunday of the month 22
Last Sunday, if the month has 30 days 24
Last Sunday, if the month has 31 days 25

For example, if the DST is observed from the last Sunday in March to the last
Sunday in October and the time shift occurs at 01:00 UTC, the setting parameters
are:

94 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 8
Commissioning

DST on time: 01:00


DST on date: 25.03
DST on day: Sun
DST off time: 01:00
DST off date: 25.10
DST off day: Sun

Set the DST on day and DST off day to "not in use" to determine the
exact date and time for the DST shift. Repeat the setting yearly, as the
time for the DST shift is not on the same date every year.

To disable the DST, set the DST offset parameter to "0 min".

8.5.3 Setting IED parameters

8.5.3.1 Defining setting groups

Selecting a setting group for editing

1. Select Main Menu/Settings/Edit setting group.


2. Select the setting group to be edited with or .
3. Press to confirm the selection.
4. Edit the settings.

A070858 V3 EN

Figure 67: Selecting a setting group

Browsing and editing setting group values

1. Select Main Menu/Settings/Settings and press .


2. Select the setting group to be viewed with or and press to confirm
the selection.

RED615 95
Operation Manual

Downloaded from www.dlmanuals.com


Section 8 1MRS756499 A
Commissioning

A071166 V3 EN

Figure 68: Selecting setting group

3. To browse the settings, scroll the list with and and to select a setting
press .
4. To browse different function blocks, scroll the list with and and to select
a function block press . To move back to the list, press .
The function block list is shown in the content area of the display. On the left
in the header, you see the current setting group, and on the right the menu path.
5. To browse the parameters, scroll the list with and and to select a
parameter, press .
The setting group values are indicated with #.

A070899 V3 EN

Figure 69: Setting group parameter

6. To select a setting group value, press and to edit the value press .

A071168 V3 EN

Figure 70: Selecting setting group value

Only values within the selected setting group can be changed.


7. Press or to change the value and to confirm the selection.

96 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 8
Commissioning

A070922 V3 EN

Figure 71: Editing setting group value

The active setting group is indicated with an asterisk * .

Activating a setting group


IED settings are planned in advance for different operation conditions by calculating
setting values to different setting groups. The active setting group can be changed by
the IED application or manually from the menu.

1. Select Main Menu/Settings/Setting group/Active group and press .

A071150 V3 EN

Figure 72: Active setting group

2. Select the setting group with or .


3. Press to confirm the selection or to cancel.

A071152 V3 EN

Figure 73: Selecting active setting group

4. Commit the settings.

Remember to document the changes you make.

RED615 97
Operation Manual

Downloaded from www.dlmanuals.com


Section 8 1MRS756499 A
Commissioning

8.5.3.2 IED parametrization

IED parameters are usually set with a parameter setting tool but it can also be done
via the LHMI or WHMI.

Setting parameters need to be calculated according to the electrical network


conditions and the electrical characteristics of the protected equipment. The IED's
settings need to be verified before the IED is connected to a system.

For more information, see PCM600 documentation.

Document all changes to parameter settings.

8.5.3.3 Configuring analog inputs

1. Select Main Menu/Configuration/Analog inputs and press .


2. Select the analog input to be configured with or .
3. Press , change the value with or and press again.
• For CTs, the secondary current and primary current need to be set to the
correct values.
• For VTs, the secondary voltage and primary voltage need to be set to the
correct values.

8.6 Testing IED operation

The IED has to be in the test mode before the digital outputs and certain output signals
of protection and other functions can be activated.

8.6.1 Selecting test mode


The test mode can be activated using the LHMI. The green Ready LED will be
blinking to indicate that the test mode is activated.

1. Select Main Menu/Tests/IED test/Test mode and press .

98 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 8
Commissioning

A071154 V3 EN

Figure 74: Entering test mode

2. Select Test off or Test on with or .


3. Press to confirm the selection.

If you do not cancel the test mode, it remains on and the Ready LED
remains blinking. Test mode does not retain if the IED is reset.

8.6.2 Testing digital I/O interface


To activate or deactivate, for example, a digital output:

1. Select Main Menu/Tests/Binary Outputs/X100 (PSM)/X100-Output 1 and


press .
2. Select False or True with or .
3. Press to confirm the selection.

If the optional BIO-module (X110) is included in the IED, the menu


path could also be Main Menu/Tests/Binary Outputs/X110
(BIO1)/<binary output>.

8.6.3 Testing functions


To activate or deactivate an output signal for protection or other function:

1. Select Main Menu/Tests/Function tests/Current protection/PHLPTOC and


press .
2. Select the output signal to be activated or deactivated with or and press
.
3. To deactivate all output signals for the function, select Reset with or
and press .

RED615 99
Operation Manual

Downloaded from www.dlmanuals.com


Section 8 1MRS756499 A
Commissioning

8.6.4 Selecting internal fault test


The internal fault may be tested by using the LHMI. When enabling the test, the
internal relay fault output contact is activated, the green Ready LED will be blinking
and internal fault test indication is shown on the LHMI. See Technical Manual for
internal relay fault output contact location.

Differing from real internal fault situation, the other output contacts
are not released and locked during the test. In other words, protection
functions can operate and trip the outputs when the internal fault is
tested.

1. Select Main Menu/Tests/IED test/Internal fault test and press .

A071156 V3 EN

Figure 75: Internal fault test

2. Select False or True with or .


3. Press to confirm the selection.

8.7 ABB Product Data Registration

The ABB Product Data Registration feature traces composition changes related to
the IED's SW or HW.

After a composition change, an LCT indication is seen on the LHMI at the IED start-
up. At this point, PCM600 should be connected to the IED as it reads the changed
data from the IED. The LCT indication is cleared in the same way as other indications.
If PCM600 is not connected to the IED, the indication is seen again after the IED's
reboot.

100 RED615
Operation Manual

Downloaded from www.dlmanuals.com


1MRS756499 A Section 8
Commissioning

A071266 V3 EN

Figure 76: LCT indication

The number of composition changes can be seen from the Composition changes
parameter in Main Menu/Monitoring/IED status.

RED615 101
Operation Manual

Downloaded from www.dlmanuals.com


102

Downloaded from www.dlmanuals.com


Section 9
Glossary

Section 9 Glossary

100BASE-TX A physical media defined in the IEEE 802.3 Ethernet


standard for local area networks (LANs). 100BASE-TX
uses twisted-pair cabling category 5 or higher with RJ-45
connectors.
AI Analog input
ANSI American National Standards Institute
ASCII American Standard Code for Information Interchange
BI/O Binary input/output
CAT 5 A twisted pair cable type designed for high signal
integrity
COMTRADE COMmon format for Transient Data Exchange for power
systems. Defined by the IEEE Standard.
Connectivity Software that helps the user to define right connectivity
Package Manager package versions for different applications and tools.
CPU Central processing unit
CSV Comma separated values
CT Current transformer
DHCP Dynamic Host Configuration Protocol allows devices
joining the network to dynamically receive an IP address
from the DHCP server that contains a pool of IP
addresses.
DMS Distribution Management System
DST Daylight saving time
EEPROM Electrically Erasable Programmable Read-Only
Memory
EMC Electromagnetic compatibility
Ethernet A large, diverse family of frame-based computer
networking technologies that operate at many speeds
for LANs interconnecting computing devices. Ethernet is
a trademark of Xerox Corporation, Inc. and defined in
the IEEE 802.3 standard in which computers access the
network through a CSMA/CD protocol.
FB Function block.
Firmware System software or hardware that has been written and
stored in a device's memory that controls the device.

RED615 103
Operation Manual

Downloaded from www.dlmanuals.com


Section 9
Glossary

FPGA Field Programmable Gate Array


GOOSE Generic Object Oriented Substation Event
HMI Human-machine interface
HW Hardware
IEC International Electrotechnical Commission
IEC 61850 International standard for substation communication
and modelling.
IEC 61850-8-1 A communication protocol based on the IEC 61850
standard series and a standard for substation modelling.
IED Intelligent Electronic Device
IP address Internet protocol address is a set of four numbers
between 0 and 255, separated by periods. Each server
connected to the Internet is assigned a unique IP
address that specifies a location for the TCP/IP protocol.
LAN Local area network
LC Connector type for glass fibre cable.
LCD Liquid crystal display
LCP Liquid crystal polymer
LCT Life cycle traceability
LED Light-emitting diode
LHMI Local Human-Machine Interface
LON Local operating network
Modbus A serial communication protocol developed by the
Modicon company in 1979. Originally used for
communication in PLCs and RTU devices.
Modbus ASCII Modbus link mode. Character length 10 bits.
Modbus RTU Modbus link mode. Character length 11 bits.
Modbus TCP/IP Modbus RTU protocol which uses TCP/IP and Ethernet
to carry data between devices.
NCC Network control center
OPC OLE (object linking and embedding) for process control
PA Polyamide
PBT Polybutylene terephthalate
PC Personal Computer; Polycarbonate
PCM600 Protection and Control IED Manager
PO Power output
R/L Remote/Local

104 RED615
Operation Manual

Downloaded from www.dlmanuals.com


Section 9
Glossary

RAM Random access memory


RJ-45 Galvanic connector type.
RoHS Restriction of the use of certain Hazardous Substances
in electrical and electronic equipment.
ROM Read-only memory
RS-232 Serial interface standard.
RS-485 Serial link according to EIA standard RS485.
RTC Real Time Clock
RTU Remote Terminal Unit
SCADA Supervision, control and data acquisition
SCL Substation Configuration Language
SMT Signal Matrix Tool
SNTP Simple Network Time Protocol
SO Signal output
STP Shielded Twisted-Pair
SVG Scalable Vector Graphics
SW Software
TCP/IP Transmission Control Protocol / Internet Protocol
TCS Trip-circuit supervision
UTC Coordinated Universal Time
VT Voltage transformer
WAN Wide area network
WHMI Web Human-Machine Interface

RED615 105
Operation Manual

Downloaded from www.dlmanuals.com


106

Downloaded from www.dlmanuals.com


107

Downloaded from www.dlmanuals.com


© Copyright 2008 ABB. All rights reserved.
1MRS756499 A

ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone +358 10 22 11
Fax +358 10 22 41094
www.abb.com/substationautomation

Downloaded from www.dlmanuals.com

You might also like