Touch-Screen Network Control Function Specification
Touch-Screen Network Control Function Specification
Function Specification
I UI Process
Starting Unit
UIs
System Setting User Setting Log Instructions Status Inquiry Error Inquiry
II Introduction to UIs
1. Startup Interface
中 En
Description:
The logo of McQuay is displayed.
The number in the upper left corner is counted down. When the number is counted down to 0, the
main interface is displayed.
When the number is counted down to 0, press the upper left corner of M to display the Factory
Page 3 of 13
Setting interface.
When the number is being counted down, press the lower right corner of the interface to skip the
logo and display the main interface.
When the number is being counted down, press Chinese/English[Frank1] to choose a language
for the UIs.
2. Factory Setting
Factory setting
ESC
Description:
Enter the default password to display the Factory Setting interface.
The Others button is available.
2.1 Setting
setting
℃
Comp Start 17sec
℃
Defrost Temp Setting -3
℃
Defrost Check on/off Temp 0/25
Return Water Temp Makeup 0/ 3
Water On-off Check Time 145sec
Screensaver Time 10min
ESC Up Down
Description:
Defrost Check on/off Temp indicates the temperature when the defrost check starts and the
temperature when the defrost ends.
Return Water Temp Makeup indicates the return water temperature makeups for cooling and
heating purposes.
When Screensaver Time is set to 0, it indicates that the screensaver is cancelled.
Page 4 of 13
1:Current time
2:Set #1 Usage Time
3:Set #2 Usage Time
4:Set #3 Usage Time
1:Current Time
limit time: 1 2 3
12/23/20 09
4 5 6
Status:
Disable
Password : 7 8 9
Esc 0
Description:
The operators are not allowed to set this function.
Page 5 of 13
2.2.3 Reset
Reset
Initialize NVRAM
ESC
Description:
After Initialize NVRAM is executed, all the records are cleared, and the system parameter
settings and factory settings are restored to the default values.
2.2.4 Password Setting
********
1 2 3
4 5 6
7 8 9
Description:
When you set the password, the system will ask you to enter the old password. After you correctly
entering the new password twice, the old password is changed. A password of a higher level can
replace the password of a lower level.
3. Main Interface
Status: Standby...
Status
Mode: Cool
Inlet : C Errors
Outlet : C
Start Stop
Outdoor: C
Description:
Inlet, Outlet and Outdoor respectively indicate the average of the inlet temperature, outlet
temperature and outdoor temperature of all the units in the system.
The maintenance staff must enter the password before accessing the System Settings and Log
interfaces.
4. System Setting
Config
1:Model Setting
2:Module Address Setting
3:Sys. Para Setting
4:Change Password
5:Sys. Malfunction Reset
ESC Up Down
Description:
Max Defrost Unit Num must be not larger than the number of the units.
Unit Model can be changed only when the system is off.
Caution: The parameters set here must be the same with that set through the main control board;
otherwise, the unit will run abnormally.
Page 7 of 13
Reset
Unit 1: Sure
Unassigned
ESC Comm
Description:
Use the Up and Down buttons to select a unit, and then press Enter. The address of the unit is
sent to the main control board. If the setting succeeds, the system displays that the setting is
completed. Press Enter to save the address. If the setting fails, the system displays a
communication error. In this case, press the Comm button to query the communication status of
the modules. Press Exit for three seconds to exit the Module Address Setting interface.
Caution: When setting an address for a unit, power on the unit only and power off other units;
otherwise, the address will be shared by multiple units.
4.3 Communications
Comm
Unit 1:Unassign
ESC
Description:
You can which units have been configured with addresses and which units are not. If the small
arrow in the box is moving, it indicates that the unit is communicating.
Page 8 of 13
℃
℃
Cooling backwater temp 25
℃
Heating backwater temp 50
℃
Winter antifreeze temp 2
Cooling antifreeze temp 2
Auto Restart forbid
Num of Unit 1
Defrost Between Time 45 min
Defrost Running Time 10 min
Description:
Defrost Between Time and Defrost Running Time must be set for every unit in the network.
If a parameter needs to be modified in a wide range, press and hold down the + and – buttons so
that the value can vary successively.
Press Reset to restore the default settings.
5. User Setting
Setup
ESC Up Down
Description:
If Week timed is set to forbid, the week setting is invalid.
Page 9 of 13
Description:
You can change the current date and the current time.
5.3 Timer Setting
3.Sys. Para Setting
On Off On Off On Off
1 00:00 00:00 00:00 00:00 00:00 00:00
2 00:00 00:00 00:00 00:00 00:00 00:00
3 00:00 00:00 00:00 00:00 00:00 00:00
4 00:00 00:00 00:00 00:00 00:00 00:00
5 00:00 00:00 00:00 00:00 00:00 00:00
6 00:00 00:00 00:00 00:00 00:00 00:00
7 00:00 00:00 00:00 00:00 00:00 00:00
Description:
The system shutdown time must be later than the system startup time.
Click Zero to clear all the week settings.
The week setting is valid only when Week timed is set to allow on the User Parameter Setting
interface.
5.4 Contrast Setting
Item 4:Contrast setting
Description:
Page 10 of 13
Select the optimal contrast according to the ambient brightness and the installation position.
5.5 Chart Setting
Setup
Description:
This function allows you to change the interface display from "blue lettering on white background"
to "white lettering on blue background" or vice versa.
If a color screen is used, more optional backgrounds are available.
6. Log
Log
ESC
7. Instructions
Instructions
8. Status
Status: Warm!
ESC Help
Description:
When the small bulb is on, it indicates that the compressor of the unit is running.
8.2 Chart of Water System
Page 13 of 13
Modular Chart
25
ESC Help
Description:
The inlet temperature indicates the average of the inlet temperatures of all the units.
The outlet temperature indicates the average of the outlet temperatures of all the units.
8.3 Chart of Refrigerating System
Sys Chart
Unit:
0
Sys:
0
25
Description:
The displayed temperature indicates the tested temperature of the unit.
The Defrost button is used for manual defrosting.
9. Error Inquiry
Current error
2000/08/25 09:45:25
LY503B comm failure
2000/08/25 09:45:25
01Set Communication fault