BITZER Output Data: Created On: 13/11/2013 9:49:26

The document is a report from BITZER software summarizing the selection and specifications of a condensing unit. It includes a project survey showing one LH135/4PES-15Y unit was selected. The second section provides details of the compressor selection for this unit such as its cooling capacity of 25.8 kW at specified operating conditions. The third section lists technical specifications for the selected LH135/4PES-15Y unit including its dimensions, connections, weight, coil volume, and sound levels.

Uploaded by

Yogi Dwi Andi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
72 views6 pages

BITZER Output Data: Created On: 13/11/2013 9:49:26

The document is a report from BITZER software summarizing the selection and specifications of a condensing unit. It includes a project survey showing one LH135/4PES-15Y unit was selected. The second section provides details of the compressor selection for this unit such as its cooling capacity of 25.8 kW at specified operating conditions. The third section lists technical specifications for the selected LH135/4PES-15Y unit including its dimensions, connections, weight, coil volume, and sound levels.

Uploaded by

Yogi Dwi Andi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

BITZER Output data

Created on : 13/11/2013 9:49:26


chiller

BITZER Software v6.4.0 rev1076 13/11/2013 / All data subject to change. 2/6

Table of content

Project survey............................................................................................................................................................ 3
Compressor Selection: Condensing Units................................................................................................................. 4
Technical Data: LH135/4PES-15Y............................................................................................................................. 5
Condensing Units...................................................................................................................................................... 6
chiller

BITZER Software v6.4.0 rev1076 13/11/2013 / All data subject to change. 3/6

Project survey
Selected compressors
Condensing Units 1x LH135/4PES-15Y
chiller

BITZER Software v6.4.0 rev1076 13/11/2013 / All data subject to change. 4/6

Compressor Selection: Condensing Units

Input Values
Unit type LH135/4PES-15Y
Series Standard
Refrigerant R404A
Reference temperature Dew point temp.
Evaporating SST -10,00 °C
Ambient temp. 32,0 °C
Suction gas temperature 20,00 °C
Useful superheat 100%
Operating mode Auto
Power supply 400V-3-50Hz
Capacity Control 100%

Result
Unit type LH135/4PES- 15Y-40P
Capacity steps 100%
Cooling capacity 25,8 kW
Evaporator capacity 25,8 kW
Power input * 10,00 kW
Current (400V) 18,33 A
Voltage range 380-420V
Mass flow 722 kg/h
Condensing SDT 42,9 °C
Liquid subcooling 3,00 K
Operating mode Standard

Tentative Data.
*Power input compressor, power input fan see ''T. Data''

Application Limits

Legend
additional cooling or suction gas
superheat ≤20K
additional cooling or max. toh
<0°C
M1: motor 1

M2: motor 2
chiller

BITZER Software v6.4.0 rev1076 13/11/2013 / All data subject to change. 5/6

Technical Data: LH135/4PES- 15Y


Dimensions and Connections

Technical Data
Technical Data
Weight 331 kg
Total width 1591 mm
Total depth 1000 mm
Total height 998 mm
Connection suction line 42 mm - 1 5/8''
Connection liquid line 22 mm - 7/8''
Fans: Number 2
Voltage (more on request) 230VD / 400VY-3-50Hz (Standard)
Current / Power consumption of each fan 2,80 A 1,62 A / 750 W
Air flow condenser 50Hz 12650 m³/h
Voltage (more on request) 230VD / 400VY-3-60Hz (Option)
Current / Power consumption of each fan 3,40 A 1,95 A / 1050 W
Air flow condenser 60Hz 13900 m³/h
Coil Volume 22,0 dm3
Receiver type (Standard) F302H
Max. refrigerant charge 90% at 20°C
R22 32,7 kg
R134a 33,1 kg
R407C 31,3 kg
R404A/R507A 28,8 kg
Extent of delivery (Standard)
Discharge line Standard
Protective charge Standard
Available Options
Oil separator Option
Check valve Option
High & low pressure switch Option
Dressed unit Option
Weather protective housing Option
Sound measurement
Sound power level (-10°C / 45°C) 89,0 dB(A) @ 50Hz
Sound pressure level @ 1m (-10°C / 45°C) 81,0 dB(A) @ 50Hz
Data of compressors: see compressor program
chiller

BITZER Software v6.4.0 rev1076 13/11/2013 / All data subject to change. 6/6

Condensing Units
Motor 1 = e.g. LH../4TES-12 (4T-12.2) with 12"HP", primary for air-conditioning (e.g. R22,R407C) and medium
temperature application (e.g. R134a, R407F, R407A, R404A, R507A, R22) and air-conditioning with R134a at high
ambient temperatures
Motor 2 = e.g. LH../4TES-8 (4T-8.2) with 8"HP", for medium and low temperature application (e.g. R134a, R407F,
R407A, R404A, R507A, R22) and air-conditioning with R134a.
For more information concerning the application range use the "limits" button.

Operation modes for LH../4VES-7 (4Z-5.2) to LH../6HE-25 (6H-25.2) with R22:


CIC = liquid injection with low temperature application, suction gas cooled motor

Specifications for sound emission Ecostar:


The data are based on 50Hz operation with R404A
Soundpressure: Data are valid for free field conditions according to EN13487 with a block-shaped reference area in a
distance of 10m.
For further informations see technical information for sound data.

Legend of connection positions according to "Dimensions":

1 Suction valve
2 Discharge gas line
3 Cndensate line
4 Refrigerant outlet
5 Pressure relief valve connection