2 - APM 303 - Settings Menu - EN

This document provides instructions for accessing and navigating the settings menu on an APM 303 generator control panel. It describes how to switch the panel from automatic to manual mode in order to access the settings. The settings menu includes options to modify basic settings, motor safety features, generating set safety features, MODBUS settings, input/output settings, and view information. Navigation of the menu is done using arrow keys and buttons to select and save changes or exit menus.

Uploaded by

Chhoan Nhun
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
2K views47 pages

2 - APM 303 - Settings Menu - EN

This document provides instructions for accessing and navigating the settings menu on an APM 303 generator control panel. It describes how to switch the panel from automatic to manual mode in order to access the settings. The settings menu includes options to modify basic settings, motor safety features, generating set safety features, MODBUS settings, input/output settings, and view information. Navigation of the menu is done using arrow keys and buttons to select and save changes or exit menus.

Uploaded by

Chhoan Nhun
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 47

APM 303

Settings menu

Non-contractual document - In accordance with our product quality improvement policy,


SDMO reserves the right to modify the contents of this document, without prior notice.
CONTENTS

1. Modification from the


MMI
2. The software

Non-contractual document - In accordance with our product quality improvement policy,


SDMO reserves 2the right to modify the contents of this document, without prior notice.
1. Modification from the MMI

Non-contractual document - In accordance with our product quality improvement policy,


SDMO reserves 2the right to modify the contents of this document, without prior notice.
Access to settings mode
The APM 303 must be in Manual mode and displaying the screen below to access
the settings.

The AUTO button must be used to switch from AUTO to MANUAL.

The mode LED must be off when in MANUAL mode.

AUTO button Mode LED

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Access to settings mode
If you do not have any introductory text configured:
► whilst pressing STOP, briefly press the arrow at the top, then the auto button.

1 2
+

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Access to settings mode
If you do have introductory text configured:
► whilst pressing STOP, briefly press the arrow at the top then the arrow at the
bottom, then the auto button.
+

1 2
+

4 3
+

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
The menu icons

Basic setting

Motor safety features and parameters

Generating set safety feature

Setting the MODBUS

Setting the Outputs

Setting the Inputs

Info

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Navigation

Select (a menu or parameter)

Exit the settings (save the changes)


or a menu.

Select a menu or parameter.

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Basic settings

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Basic settings

Code Name Setting Default


B01 Nominal phase-to-neutral voltage * 80 – 480 V 230
B02 Nominal phase-to-phase voltage * 80 – 600 V 400
B03 Nominal frequency 1: 50Hz; 2: 60Hz 1
B04 Type of connection 1: 1Ph+N; 2: 2Ph+N; 3: 3Ph; 4: 3Ph +N 4
B05 Format for the units 1: Bar, °C; 2: PSI, °F 1
B07 Zero consumption mode 0-360 min 0
B09 Nominal current 1- 5000 A 50
B10 CT primary 1- 5000 A 50
B11 Nominal speed 100-4000 1500
B12 Nominal power 1-3000 kW 100
B13 Automatic screen scrolling 1: Inactive; 2: Active 1
B14 Auto detection of the frequency and voltage 1: Inactive; 2: Active 1
B15 Fuel solenoid valve 1: Diesel; 2: Gas 1
B16 Priority mode 1: Manual ; 2: Automatic 1

* B01 or B02, depending on configuration

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Motor safety features and parameters

Code Name Setting Default


E01 Preheating delay 0 – 600s 10
E02 Starter attempt delay 0 – 60s 5
E03 Cooling delay 0 – 3600s 180
E04 Oil pressure fault threshold 0 – 10 Bar 1 (3s)
E05 Coolant temperature fault threshold 0 – 150C° 90 (5s)
E06 Battery voltage minimum threshold 8 – 40V 11.5 (3min)
E07 Maintenance alarm threshold 0 - 10000h 9999
E08 Starter cutout due to oil pressure 1: Inactive; 2: Active 1
E10 Stabilisation delay 1 – 300s 5
E11 Low fuel level fault threshold 0 – 80% 20 (10s)
E12 Delay for maintaining preheating when GS started (cold country) 0 – 3600s 30
E13 Auto startup on min battery voltage 1: Inactive; 2: Active 1
E14 Recharge delay on min battery voltage 1 – 240min 60
E15 Low fuel level fault 1: Alarm; 2: Fault 1

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Generating set safety features

Code Name Setting Default


G01 Max voltage fault G02 – 200% of nominal U 110 (3s)
G02 Min voltage fault 0 – G01% of nominal U 70 (3s)
G03 Max frequency fault G04 – 130% of nominal F 110 (3s)
G04 Min frequency fault 0 – G03% of nominal F 85 (3s)
G05 Short circuit fault 100 – 500% of nominal I 150 (G06)
G06 Short circuit delay 0 – 10s of nominal I 0
G07 Overload alarm 70 – 130% of nominal P 110 (G08)
G08 Overload delay 0 – 300s of nominal P 10

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Modbus

Code Name Setting Default


M01 Speed 1: 9600bps; 2: 19200bps; 3: 38400bps; 4: 57600bps 1
M02 Stop bits: 1: 1 stop bit; 2: 2 stop bit 1
M03 Parity 1: none; 2: even; 3: odd 1
M04 Address 1 - 247 5

* Example taken from the Modbus APM303 documentation

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
General information on the
inputs/outputs
Inputs
Connection Type Direction Functions which can be allocated
T10 binary input I00, I02, I04, I07, I10, I11, I12, I13, I14, I15, I20, I22, I24
T11 binary input I00, I04, I07, I10, I11, I12, I13, I14, I15, I20, I22, I24
T12 binary input I00, I04, I07, I10, I11, I12, I13, I14, I15, I20, I22, I24
T13 binary/analog input I00, I04, I07, I10, I11, I12, I13, I14, I15, I20, I21, I22, I23, I24, I25
T14 binary/analog input I00, I04, I07, I10, I11, I12, I13, I14, I15, I20, I21, I22, I23, I24, I25
T15 binary/analog input I00, I04, I07, I10, I11, I12, I13, I14, I15, I20, I21, I22, I23, I24, I25

Outputs
Connectio
Type Direction Functions which can be allocated
n
T07 binary output O00, O03, O04, O05, O07, O08, O10, O11, O12, O13, O14, O15
T08 binary output O00, O03, O04, O05, O07, O08, O10, O11, O12, O13, O14, O15
T09 binary output O00, O03, O04, O05, O07, O08, O10, O11, O12, O13, O14, O15

The emergency stop binary input (T04) and the fuel solenoid valve (T06) and starter (T05) outputs are fixed.

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
General information on the
inputs/outputs

Contact normally open - output

Contact normally open - input

Contact normally closed - output

Contact normally closed - input

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Outputs
Default outputs:
► T07: Preheating Fixed outputs:
► T08: GS started and stabilised ► T05: starter motor
► T09: General fault ► T06: Fuel solenoid valve

Number Name Type Possible connector


O00 Not used binary T07, T08, T09
O03 Solenoid valve stop control binary T07, T08, T09
O04 Fault summary (fault or alarm) binary T07, T08, T09
O05 GS breaker open/close control binary T07, T08, T09
O07 GS started and stabilised binary T07, T08, T09
O08 Air preheating control binary T07, T08, T09
O10 Starter motor control binary T07, T08, T09
O11 Spark plug preheating control binary T07, T08, T09
O12 Low fuel level fault (Alarm or Fault) binary T07, T08, T09
O13 Shut-off valve control binary T07, T08, T09
O14 General alarm binary T07, T08, T09
O15 General fault binary T07, T08, T09

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Inputs
Default inputs:
► T10: Remote start order
► T11: Exterior fault 1
► T12: High coolant temperature Fixed inputs:
► T13: Fuel level (VDO 1 analog) ► T04: emergency stop
► T14: Coolant temperature (VDO 1
analog)
► T15: Oil pressure (VDO 2 analog)
Number Name Type Possible connector
I00 Not used binary T10, T11, T12, T13, T14, T15
I02 Remote start order binary T10
I04 Locking the APM 303 binary T10, T11, T12, T13, T14, T15
I07 Info feedback from the GS breaker binary T10, T11, T12, T13, T14, T15
I10 External alarm 1 binary T10, T11, T12, T13, T14, T15
I11 External alarm 2 binary T10, T11, T12, T13, T14, T15
I12 External alarm 3 binary T10, T11, T12, T13, T14, T15
I13 External fault 1 binary T10, T11, T12, T13,T14, T15
I14 External fault 2 binary T10, T11, T12, T13, T14, T15
I15 External fault 3 binary T10, T11, T12, T13, T14, T15
I20 Low fuel level binary T10, T11, T12, T13, T14, T15
I21 Fuel level analog T13, T14, T15
I22 Low oil pressure binary T10, T11, T12, T13, T14, T15
I23 Oil pressure analog T13, T14, T15
I24 High coolant temperature binary T10, T11, T12, T13, T14, T15
I25 Coolant temperature analog T13, T14, T15

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Curves

► Fuel level: VDO Datcon

►Coolant temperature: VDO 40-120°C VDO 50-150°C Datcon High

Datcon Low

►Oil pressure: VDO 5 Bar VDO 10 Bar Datcon 5 Bar

Datcon 7 Bar Datcon 10 Bar

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
2. Software

Non-contractual document - In accordance with our product quality improvement policy,


SDMO reserves 2the right to modify the contents of this document, without prior notice.
Main screen: not connected

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Main screen: connected

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Navigation

Non-contractual document - In accordance with our product quality improvement policy,


SDMO reserves 2the right to modify the contents of this document, without prior notice.
Icons

Open a Copy the configuration Update the firmware Exit the current
configuration from the APM 303 version configuration
(Open file) (Download from controller) (Firmware update) (Close)

Save a Upload the configuration Help and About


configuration on the PC to the APM 303
(Save file) (Upload to controller)

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Open a configuration

This function is used to open a configuration found on the PC.

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Save a configuration

This function is used to save a configuration on the PC.

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Copy a configuration

This function is used to copy the configuration from the APM 303 to the software.

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Upload a configuration

This function is used to upload the configuration from the software to the APM 303.

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Change the firmware

This function is used to change the firmware from the APM 303.

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Software version

This function is used to find out the APM Configurator software version.

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Exit the current configuration

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
The configuration

Non-contractual document - In accordance with our product quality improvement policy,


SDMO reserves 2the right to modify the contents of this document, without prior notice.
The setpoints

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Basic settings
B02
B03
B04

B05
B07

B09
B10

B11
B12

B13
B14

B15
B16

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Motor safety features and parameters
E01
E02
E03
E04
E05
E06
E07
E08
E10
E11

E12
E13
E14
E15

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Alternator safety features

G01

G02

G03

G04

G05

G06

G07

G08

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Modbus parameters

M01

M02

M03

M04

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Outputs
This menu is used to configure the outputs.

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Inputs
This menu is used to configure the inputs.

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Miscellaneous

Non-contractual document - In accordance with our product quality improvement policy,


SDMO reserves 2the right to modify the contents of this document, without prior notice.
Curves

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Curves: configuration
Open a curve saved on the PC

Add a point to the curve Choice of curve:


(32 points possible) - Fuel level
- Coolant temperature (°C)
- Oil pressure

Deleting a point Saving a curve creation or modification


on the curve on the PC

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Curves: allocation

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Introductory text

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Log (connected APM only)

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Archiving information

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Firmware update

Non-contractual document - In accordance


2 with our product quality improvement
policy, SDMO reserves the right to modify the contents of this document, without prior
Thank you for your attention!!