LP1502 Intelligent Controller: 1. General
LP1502 Intelligent Controller: 1. General
com
2355 MIRA MAR AVE. LONG BEACH, CA 90815-1755, (562)986-9105 FAX (562) 986-9205
1. General:
The LP1502 intelligent controller provides decision making, event reporting, and database storage for the
Mercury hardware platform. Two reader interfaces provide control for two physical barriers.
The LP1502 communicates with the host via on-board 10-BaseT/100Base-TX Ethernet port or the Micro
USB port (2.0) with an optional Micro USB to Ethernet adapter.
Each reader port can accommodate a reader that utilizes TTL (D1/D0, Clock/Data), F/2F (standard or
supervised) or 2-wire RS-485 device signaling (OSDP reader for example) and also provides tri-state LED
control, and buzzer control (one wire LED mode only). Four Form-C relay outputs may be used for door
strike control or alarm signaling. Eight inputs are provided that may be used for monitoring the door
contacts, exit push buttons and alarm contacts. Input circuits may be configured as unsupervised or
supervised. The LP1502 requires 12 to 24 Vdc for power.
2. LP1502 Hardware:
BATTERY: BR/CR2330 S2: RESET
REPLACE ANNUALLY SWITCH Ø.156 [3.96]
8 PLACES
3V BR/CR2330
GND
STATUS 2
LEDs 3
TMP
S2
4
GND
BT1
5
FLT
R1
J2: ETHERNET
GND
R2 JACK
TB1
J2
S1 : DIP SWITCHES 2.00 [50.80]
EARTH
GROUND
D16
1
2
JACK
3
4
GND_C
J8: microSD
ON V
|
|
TB8 J6 CARD
8.00 [203.20] GND
VIN
READER 1
DAT
D0
CLK
J8
D1
J5
LED
3.00 [76.20]
VO TB3
TR+
TB9
GND TR-
VIN GND
READER 2
DAT TB4
D0
CLK IN1
D1
LED
IN2 J5: RS-485
VO
PASS 12V
TERMINATOR
NO
J7
IN3
OUT 1 C
NC
IN4 INPUT
NO
TB5
STATUS
2.00 [50.80]
OUT 2 C TB6
LEDs
TB10
IN5
NC
TB11
NO IN6
OUT 3 C
K
1 TB7
NC
K IN7
NO 2
J7: READER OUT 4 C
K
3
IN8
POWER .50 [12.70] NC
K
4
SELECT
LP1502 Layout
Mercury Security © 2018 LP1502 DOC 10107-0062 REV 1.01 Page 1
3. LP1502 Wiring and Setup:
CONNECTION CONNECTION
TB1-1 Power Fault GND TB8-1 Reader 1 GND: Ground
TB1-2 TB8-2 DAT/D0: Data/Data 0/TR- (A)
Input FLT
See note 1
TB1-3 TB8-3 CLK/D1: Clock/Data 1/TR+ (B)
Cabinet GND
See note 1
TB1-4 Tamper Input TMP TB8-4 BZR: Reader Buzzer
TB1-5 Power Input GND TB8-5 LED: Reader LED
TB1-6 VIN: 12 to 24 Vdc TB8-6 VO: Reader Power
TB2 N/A Not Used TB9-1 Reader 2 GND: Ground
TB9-2 DAT/D0: Data/Data 0/TR- (A)
TB3-1 GND
See note 1
SIO Port
TB9-3 CLK/D1: Clock/Data 1/TR+ (B)
TB3-2 (2-wire RS-485) TR- (B) See note 1
See note 1
TB3-3 TR+ (A) See note 1 TB9-4 BZR: Reader Buzzer
TB4-1 Input 2 IN2 TB9-5 LED: Reader LED
TB4-2 IN2 TB9-6 VO: Reader Power
TB4-3 Input 1 IN1 TB10-1 Out 1 NO: Normally Open Contact
TB4-4 IN1 TB10-2 C: Common
TB5-1 Input 4 IN4 TB10-3 NC: Normally Closed Contact
TB5-2 IN4 TB10-4 Out 2 NO: Normally Open Contact
TB5-3 Input 3 IN3 TB10-5 C: Common
TB5-4 IN3 TB10-6 NC: Normally Closed Contact
TB6-1 Input 6 IN6 TB11-1 Out 3 NO: Normally Open Contact
TB6-2 IN6 TB11-2 C: Common
TB6-3 Input 5 IN5 TB11-3 NC: Normally Closed Contact
TB6-4 IN5 TB11-4 Out 4 NO: Normally Open Contact
TB7-1 Input 8 IN8 TB11-5 C: Common
TB7-2 IN8 TB11-6 NC: Normally Closed Contact
TB7-3 Input 7 IN7
TB7-4 IN7
Note 1: Terms A & B are from the RS-485 standard
Jumpers and Jacks:
The LP1502 processor hardware interface is configured using jumpers to setup the reader port power and
end of line termination.
JUMPERS SET AT DESCRIPTION
J1 N/A Factory Use Only
J2 N/A 10-Base-T/100Base-Tx Ethernet Connection (Port 0)
J3 N/A Factory Use Only
J4 N/A N/A
J5 OFF RS-485 EOL Terminator is Off
ON RS-485 EOL Terminator is On
J6 N/A Micro USB Port (2.0)
J7 Reader Power Select. See Note 2
12V 12 Vdc at Reader Ports
PASS VIN "Pass Through" to Reader Ports
J8 N/A microSD Card
Note 2:
Install jumper J7 in the 12V position ONLY if the input voltage (VIN) is greater than 20 Vdc!
Failure to do so may damage the reader or LP1502!
TB3
TR+
TR-
GND
1
IMPORTANT NOTE! Install the termination jumper ONLY on the panel at each end of the RS-485
bus. Failure to do so will compromise the proper operation of the communication channel!
7. Reader Wiring:
Each reader port supports a reader with TTL (D1/D0, Clock/Data), F/2F (standard or supervised) or 2-wire
RS-485 signaling (OSDP reader for example). Power to the readers is selectable: 12 Vdc (VIN must be
greater than 20 Vdc), or power is passed-through (PASS) from the input voltage of the LP1502 (TB1-VIN),
300 mA maximum per reader port. Readers that require different voltage or have high current requirements
must be powered separately. Refer to the reader manufacture specifications for cabling requirements. In
the 2-wire LED mode the buzzer output is used to drive the second LED. Reader port configuration is set
via the host software.
To fully utilize each reader port:
TTL signaling requires a 6-conductor cable (18 AWG)
F/2F signaling requires a 4-conductor cable
RS-485 signaling requires two 2-conductor cables. Use one cable for power (18 AWG) and one
cable for communication (24 AWG, with drain wire and shield)
1K,1%
Terminal Blocks
TB4 through TB7
IN4
1K,1%
Unsupervised Circuit,
Normally Closed Contact
Unsupervised Circuit,
Normally Open Contact
Diode Selection:
13. Specifications:
The interface is for use in low voltage, Class 2 Circuits only.
The installation of this device must comply with all local fire and electrical codes.
Primary Power: 12 to 24 Vdc ± 10 %, 500 mA maximum (reader and USB ports not included)
Reader Ports: 600 mA maximum (add 600 mA to primary power current)
Micro USB Port: 5 Vdc, 500 mA maximum (add 270 mA to primary power current)
Memory and Clock
Backup Battery: 3 Volt Lithium, type BR2330 or CR2330
microSD Card: Format: microSD or microSDHC; 2GB to 8GB
Host Communication: Ethernet: 10-BaseT/100Base-TX and Micro USB port (2.0) with optional
adapter: pluggable model USB2-OTGE100
Serial I/O Device: One each: 2-wire RS-485, 2,400 to 115,200 bps, asynchronous, half-duplex,
1 start bit, 8 data bits, and 1 stop bit
Mercury Security © 2018 LP1502 DOC 10107-0062 REV 1.01 Page 7
Inputs: Eight unsupervised/supervised, standard EOL: 1k/1k ohm, 1%, ¼ watt
Two unsupervised dedicated for cabinet tamper and UPS fault monitoring
Outputs: Four relays, Form-C with dry contacts
Normally open contact (NO) contact: 5 A @ 30 Vdc resistive
Normally closed contact (NC) contact: 3 A @ 30 Vdc resistive
Reader Interface:
Power: 12 Vdc ± 10 % regulated, 300 mA maximum each reader
(jumper selectable) (input voltage (VIN) must be greater than 20 Vdc)
or
12 to 24 Vdc ± 10 % (input voltage (VIN) passed through), 300 mA maximum
each reader
Data Inputs: TTL compatible, F/2F or 2-wire RS-485
RS-485 Mode: 9,600 to 115,200 bps, asynchronous, half-duplex, 1 start bit, 8 data bits, and
1 stop bit. Maximum cable length: 2000 ft. (609.6 m)
LED Output: TTL levels, high>3 V, low<0.5 V, 5 mA source/sink maximum
Buzzer Output: Open collector, 12 Vdc open circuit maximum, 40 mA sink maximum
Cable requirements:
Power and Relays: 1 twisted pair, 18 to 16 AWG
Ethernet: CAT-5, minimum
RS-485:
(I/O Device Port): 1 twisted pair, shielded, 120 ohm impedance, 24 AWG, 4,000 ft. (1,219 m)
max.
(Reader Port): 1 twisted pair, shielded, 120 ohm impedance, 24 AWG, 2,000 ft. (610 m)
max.
Alarm Input: 1 twisted pair, 30 ohms maximum
Environmental:
Temperature: -55 to +85 °C, storage
0 to +70 °C, operating
Humidity: 5 to 95 % RHNC
Mechanical:
Dimension: 8 in. (203.2 mm) W x 6 in. (152.4 mm) L x 1 in. (25 mm) H
Weight: 9 oz. (255 g) nominal, board only
UL294, 6th edition Performance Levels:
Feature Level
Standby Power I
Endurance IV
Line Security I
Destructive Attack I
Mercury Security warrants the product is free from defects in material and workmanship under normal use
and service with proper maintenance for one year from the date of factory shipment. Mercury Security
assumes no responsibility for products damaged by improper handling or installation. This warranty is
limited to the repair or replacement of the defective unit.
There are no expressed warranties other than set forth herein. Mercury Security does not make, nor
intends, nor does it authorize any agent or representative to make any other warranties, or implied
warranties, and expressly excludes and disclaims all implied warranties of merchantability or fitness for a
particular purpose.
Returns must be accompanied by a Return Material Authorization (RMA) number obtained from customer
service, and prepaid postage and insurance.
Liability
The Interface should only be used to control exits from areas where an alternative method for exit is
available. This product is not intended for, nor is rated for operation in life-critical control applications.
Mercury Security is not liable under any circumstances for loss or damage caused by or partially caused
by the misapplication or malfunction of the product. Mercury Security’s liability does not extend beyond the
purchase price of the product.