CT Calculation MFAC14
CT Calculation MFAC14
APPR'D
CHK'D National Grid Saudi Arabia
MFAC14
CT1 CORE-3
CT DATA FOR MFAC14- 87REF
DESCRIPTION
3000-2500-2000-1500-1250-1000-750/1A
CLASS:TPS, Rct<=6.7Ω, VK>=5500V, Im<=50mA
BY
DATE
NO.
REVISIONS
DRAWN
BY:-
DATE:-
CHECKED
BY:-
DATE:-
OPRG. DEPT
BY
DATE:-
ENG'G. DEPT.
BY:-
DATE:-
CERTIFIED.
BY:-
DATE:-
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION CT & PT CALCULATIONS
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED 132/13.8kV S/S P 01 OF 00
AND DATED
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED P 01 OF 00
AND DATED
1 SYSTEM PARAMETERS
CHK'D
where:
ρ20 Resistivity of the copper at 20 deg c = 0.01786 Ωmm2/m
REVISIONS
DRAWN
BY:-
DATE:-
CHECKED
BY:-
DATE:-
OPRG. DEPT
BY
DATE:-
ENG'G. DEPT.
BY:-
DATE:-
CERTIFIED.
BY:-
DATE:-
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION CT & PT CALCULATIONS
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED 132/13.8kV S/S P 01 OF 00
AND DATED
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED P 01 OF 00
AND DATED
System Data
System Voltage 110 kV
System Frequency 60 Hz
System fault level 40 kA
Time constant 80 ms
CT Data
DESCRIPTION
CT Ratio 3000-2500-2000-1500-1250-1000-750/1 A
CT used tap 3000 A
Class TPS
CT resistance (Rct) 6.7 Ω
CT secondary 1 A
CT knee voltage 5550 V
CT mag current 50 mA
Cable data
Cable Length (lwire1) 240 m
Cross Section (awire1) 4 mm2
Resistivity at 75 deg C (ρ75) 0.021720439 Ωmm2/m
Eff. Wire length p.u. (k) 2
BY
RLEAD1 = (k*lwire1*pcu)/awire1
DATE
= 2.607 Ω
Relay Data
NO.
BY:-
BY:-
DATE:-
DATE:-
CERTIFIED.
BY:-
DATE:-
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION CT & PT CALCULATIONS
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED 132/13.8kV S/S P 01 OF 00
AND DATED
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED P 01 OF 00
AND DATED
Requirement No.-1
CHK'D
To prevent maloperation of the relay during saturation of the CT on external fault, the relay setting Vs
must be greater than the voltage produced by the maximum secondary flowing through the cable resistance.
Requirement No.-3
The Knee point voltage must be greater than twice the voltage setting of the relay.
DESCRIPTION
Vkp ≥ 2 * VS
Where,
Iop = Minimum relay primary operating current
Vkp = Knee point voltage of the CT
IFL = Nominal primary full load current
Vs = Relay voltage setting
Ithrough = Maximum through fault current
T = Turns ratio of CT
RLEAD = Connecting cable resistance
Ri = Internal resistance of the CT
IMAG. = CT mag. Current at Vs.
CT Adequacy Check
BY
Requirement No.-1
DATE
Thus,
REVISIONS Vs = 124 V
DRAWN Requirement No.-2
BY:- Iop ≥ 0.1 * IFL
DATE:- ≥ 263.482 A
CHECKED
BY:-
DATE:-
CERTIFIED.
BY:-
DATE:-
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION CT & PT CALCULATIONS
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED 132/13.8kV S/S P 01 OF 00
AND DATED
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED P 01 OF 00
AND DATED
As the relay will operate at a current much less than the actual fault current , therefore ,
it may be increased by the addition of a resistor RST to give a current IST to achieve the necessary primary current.
IST1 = (IOP/Tp)-(IR+n*IMAG1)
IST1 = 0.05665616216 A
RST1 = Vs/IST1
RST1 = 2188.641
BY
METROSIL CALCULATIONS:
DATE
VP1 = 2√(2*Vkp(Vf1-Vkp)
If:
NO.
VP1 > 2 kV
REVISIONS Then metrosil are required
DRAWN VP1 = Peak voltage across relay under maximum internal fault condition
BY:- Vkp = Knee point voltage of C.T
DATE:- Vf1 = (ISCC/Tp)*(RLEAD+Ri+RRELAY)
CHECKED
DATE:- Therefore
CERTIFIED. VP1 = 58561.8454627 Vp-p
BY:- METROSIL IS REQUIRED
DATE:-
DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION CT & PT CALCULATIONS
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED 132/13.8kV S/S P 01 OF 00
AND DATED
THIS DRAWING IS NOT TO BE
USED FOR CONSTRUCTION
OF FOR ORDERING
MATERIALS UNTIL CERTIFIED P 01 OF 00
AND DATED