Automatic Microprocessor Control Panel For Stand-By Generator
Automatic Microprocessor Control Panel For Stand-By Generator
GCM01
AUTOMATIC MICROPROCESSOR CONTROL PANEL FOR
STAND-BY GENERATOR
MANUAL:
• INSTALLATION
• USE
• MAINTENANCE
1.1 PURPOSE
The manual has been prepared specifically for the user of the generator unit.
Information required for the following is provided:
1. To learn the operational principle of the unit;
2. To interpret the indications given on the electronic control panel;
3. To control it for the various operational requirements;
4. To perform the basic checks required ensuring the efficiency of the generator itself.
Technical or adjustment matters are not dealt with as these involve the installation engineer when setting up the system.
Fig.1 shows the system components that consist of a public mains R, a generator unit G-M, and a command and control
panel QGE with a built-in mains contact maker CR, a generator unit contact maker CG and the GCM01 module
QGE
GC-M01
R
G M
CR C
Fig. 1
USERS
Supposing that the mains R is within the normal limits, the CR mains contact maker is closed therefore the utility is powered
from the mains. The GCM01 module controls the R mains and if there should be a drop in voltage, a phase should be
missing or the phases should be dissymmetrical, the control panel:
1. Opens the CR mains contact maker;
2. Starts the G-M generator unit, which when the established operating conditions are reached, the M01 module
closes the CG contact maker that then powers the utility from the generator unit G;
3. When running, the engine M and the generator G are safeguarded against possible anomalies, which if
encountered cause to stop the generator immediately;
4. When the R mains is restored within the normal limits, the GCM01 module after an adjustable delay, opens the
contact maker of the CG generator and one second later closes the CR contact maker, thus powering the utility
from the mains again;
5. The generator continues to run for at least another minute to cool down after which it stops automatically;
6. Only reserve and overload.
To ensure the perfect efficiency of the generator a battery charger automatically holds the battery perfectly efficient. An
automatic fuel filling system constantly keeps the correct level in the daily tank. A pre-heating system maintains the motor
at the ideal temperature so that it is ready to start whenever necessary.
FILE VER DATE LANGUAGE PAGE
GCM01-MU-GB-12_en.doc LVI/03 16/09/2005 ING 3 of 33
1.3 VIEW OF THE GC-M01 UNIT
6 4 5 8 15 1
10 11 12 14 3 2
13
Description of the components
1 : Programming switch
2 : Start button only with (1) manual start mode.
3 : Stop button
4 : Display reading selection push buttons display (6).
5 : Reset/Enter push button used to reset the functions and to eliminate an alarm status and also to
confirm parameters entered in the programming phase.
6 : Alphanumerical display that shows all the parameters together with the literal description of the type of alarm
7 : Leds which show the visualized measure, and indicate parameter’s anomaly if flashing.
8 : Led for engine alarm, (a) battery charter dynamo failure, (b) oil pressure low, (c) engine temperature high, (d) water/oil
level low, (e) fuel reserve, (f) remote and local safety stop button ON, (g) reserve alarm 1 (to define), (h) start failure
alarm.
9 : Led indicates mains presence within normal limits.
10 : Led indicates mains contact maker closed and use supplied by mains.
11 : Led indicates generator unit contact maker closed and use supplied by generator unit.
12 : Intervention led of generator overload protection, has to be reset manually.
13 : Generator unit ON
14 : Supplied module.
15 : Led PROG/WAIT; fixed: programming mode, flashing: timing phases or automatic running delay.
1.4 CONTROLS
The operational modes that can be selected with the programming switch are six, namely:
1. Automatic test: This starts to test the generator without disconnecting the mains power supply from the utility.
When the switch is turned back to automatic mode the generator stops following a delay of roughly one minute
(it is used for periodic tests or to check the running efficiency following maintenance).
2. Automatic mode: if there should be a failure in the mains the circuit board responds by opening the mains contact
maker. Once the mains is re-connected, after a certain time, the utility is switched back to the mains and the
generator is stopped (this is the normal operational situation).
WARNING
When the programming switch is in this position all the utility circuits of the generator are powered such as the
solenoid valves, electronic rpm regulators etc. If the switch were in this position with the generator stopped the
starting battery would run flat very quickly.
STOP
This is enabled whatever the situation (enabling even only in manual mode)
It is to be held down until the motor stops completely
EMERGENCY STOP
If pressed, the red mushroom push button in the middle of the door stops the generator immediately, instantaneously
opening the contact maker of the generator (CG) thus locking it.
To release the emergency status set the programming switch in Lock position and then turn the emergency push button and
pull up.
A newly conceived and remarkably useful LED has been fitted on the GCM01 module to assist the operator, namely the
WAIT/PROG LED. This LED flashes each time the timer is triggered informing the operator what is happening even over a
lengthy timer period.
All leds are provided with a general description that makes the control panel easily comprehensible.
LED TEST
To verify the functioning of all the leds, bring the programming hand grip to lock.Hold the + /- push buttons down together for
2 seconds.
ALARM SILENCING
Hold the RESET key down for 2 seconds to silence the buzzer alarm.
FUNCTIONS RESET
Hold the RESET key down for 2 seconds to reset the alarm status and to restore the functions.
SUMMERY
In normal running the generator unit is programmed in AUTOMATIC mode.
During maintenance on the generator unit put it on LOCKED ENGINE.
With no intervention need even in case of mains failure, set the programming switch in MANUAL MAINS. Thus the
supply by mains would be assured.
CLC SIGNAL
With the setting of the automatic TEST or AUTOMATIC LOCK, in case of disconnection of the battery the timer has to be
reprogrammed.
To indicate the loss of the programming, on the display appears CLC for 0,5” every 1,5”.
It does not have any influence on emergency functioning; it is only a call-up for the re-programming of the timer.
1.5 MAINTENANCE
SECURITY PROCEDURES FOR THE USER
WARNING
It is strictly prohibited for anyone to touch powered parts.
1.5.1 ELECTRICAL MAINTENANCE
Skilled personnel must perform all jobs.
The control unit is equipped externally with all the possible command, control and reset functions.
Proceed as follows to access the equipment within the control panel:
1. Set the programming switch on LOCKED mode.
2. Check if the unit has stopped completely.
3. Disconnect the mains line that powers the control panel and switch the main switch ON/OFF of the mains off.
4. Check if the mains has been effectively disconnected, which can be seen by the mains OK LED switched off and
by the display switched to the mains that must indicate zero.
1. Open the control panel and check for any anomalies in the:
• Fuses;
• Automatic switches;
• Thermal relays.
Once maintenance has been completed repeat the procedure in reverse order to reset the unit.
1. Check the electrolytic level of the battery every 15 days following installation and request the assistance of an
engineer if an excessive consumption is noticed. Following the initial period check every 90 days;
2. In generators complete with motor pre-heating system check if the motor is warm each time a check is made
otherwise request technical assistance. (WARNING: a cold motor at low temperatures could have difficulty in
starting or outputting once started);
3. If the generator is rarely triggered due to the lack of mains power supply execute an automatic test for at least 2
minutes.
4. If new electrical machines are installed in the system powered by the generator, request technical assistance to
check the suitability of the CG/CG mains/generator switching to the new load.
SUMMERY
On a periodic basis check the electrolytic level of the clear batteries. Touch the motor to feel if it is warm (if
equipped with pre-heating system) and execute an automatic test.
EXTERNAL COMPOSITION
The control panel consists of the following:
1. GCM01 electronic circuit board that houses the control logic, control and reading of the operational parameters of the
generator;
2. Emergency stop mushroom push button (optional);
3. Nameplate with operational standards;
4. Nameplate with safety instructions.
INTERNAL COMPOSITION
1. Numbered cables placed within PVC sheathing;
2. 10 x 38 fuses with not fixed fuse boxes;
3. Battery charger transformer of adequate capacity;
4. Automatic generator protection switch (if provided);
5. Switch with tetrapolar contact makers of adequate capacity for the power of the unit, interlocked mechanically and
electrically and scaled in AC1 in compliance with standard ISO DIS 8528-4;
6. Three amperometric transformers for measuring the generator and mains current;
7. Terminal for the mains and generator inputs, the utility output and any auxiliary connections;
8. Safety fuse gauges and connection terminals nameplate.
Switching is controlled directly by CG and CR relays built in the MP-M01 module, which directly command switching via not
powered contacts.
IMPORTANT
The CG and CR command contacts are normally closed to allow the command circuits, in the case of certain
anomalies, to force the mains contact maker to close. For example by disconnecting the battery and also the
power supply to the battery charger transformer the mains contact maker is forced to close.
FUNCTIONING
MEASURES
All parameters are visualized on three displays of seven sections.
All the reading pages are controlled using the < and > push buttons, which run in both directions.
The reading pages available are the following:
• Mains voltage
• Generator voltage
• Generator frequency
• Generator current
• Hour counter
• Battery tension
• Battery charter current
If an alarm is triggered it will be shown on the display. For example a low oil pressure, fuel reserve, high battery voltage
alarm, etc.
CONTROLS
The GCM01 control panel equipped with a programming switch to select the following functions controls all operational
modes:
TEST
It performs all the automatic functions with the exception of the switching function.
It tests the efficiency of the whole system without disconnecting the mains power supply to the utility.
All safety devices are enabled while the test is running.
If the mains should be disconnected while the test is running the generator starts immediately. The test ends automatically
when the mains power supply is restored or following a programmed external command.
LOCKED STATUS
It is the safety condition for simple maintenance operation on the generator.
Guarantees utility supply through mains, blocks any start possibilities of the generator. If the engine is running it stops
automatically.
MANUAL START
Enables the push button START that starts the generator. Enables the supply of the auxiliary circuits
through 15/54.
START
Engine start push button, for the start up cycle
STOP
The stop push button is enabled at all times. Press it until the motor stops completely.
STOP
RESET / SILENT
Press ones the push button RESET to deactivate the acoustic alarm, press twice to deactivate the alarm
status and bring back to use the normal functions of the electronic module.
LED TEST
To verify the functioning of all signal leds, select with the programming switch LOCKED ENGINE.
And press +/- for 2”
AUTOMATIC FUNCTIONING
A. The DIP SWITCH 1 selects a three-phase or two-phase sensor to monitoring the mains.
In case RIF MONO use, don’t use the three-phase reading even if available.
The mains sensor guarantees the following controls:
• Drop from -5% up to – 30% of nominal voltage (t16adjustable) even of a single phase.
• Rising from +5 up to 20% of nominal voltage (t15 adjustable) even of a single phase
• Phase lack;
• Wrong angle between phases (dissymmetry)
B. Encountering one of the above-named anomalies, the mains contactor opens immediately as to assure the running
of the generator even in case of high voltage drops.
C. In case of mains failure the start delay timer is activated (t5); it makes the system insensitive to short mains
interruptions.
D. The 5 start cycles begin after the START DELAY (t0) and last 5” (t1), with pauses 5’’
E. In case of start failure, after the start cycles (5’’) the signal FAILED START appears.
F. Delivered voltage and frequency of the generator are measured when the speed is reached; when they restore
within the normal parameters of functioning the generator delay will be activated (t3), after this time the generator
contactor will be closed (CG).
G. During the functioning the following functions and signalisations are active, which are displayed at their intervention:
ENGINE
1 Failed start R F A
2 Oil pressure low R F A YES
3 Level low R F A
4 Water temperature high R F A SR
5 Generator battery charger R F A SR
6 Alarm available R F A SR
7 Fuel reserve R SR
8 Hour counter (maintenance requirement) A
BATTERY
9 Battery present V F
10 Battery overvoltage (fixed thresholds) V L A
11 Battery undervoltage (fixed thresholds) V L A
12 Battery overload (fix threshold) V L A
GENERATOR
13 Overvoltage (59) V L A YES
14 Undervoltage (27) V L A SR
15 Overload (51) V L A SR
16 Max frequency (81) V L A YES
17 Min frequency (81) V L A SR
18 Generator contactor closed (ON) G F
19 Generator presence G F
MAINS
19 Mains presence V F
20 Overvoltage (59) V L
21 Undervoltage (27) dissymmetry (60) V L
22 Mains contactor closed G F
VARIOUS
23 Wait/Prog G L F
24 Acoustic alarm A
25 Emergency button active R F A YES
Legend
R = Red V = Green G = Yellow F = Fix
L = Flashing A = Acoustic alarm ON SI = Immediate stop SR = Delayed stop
27 = Min. voltage 5 9= Max. voltage 51 = Overload 81 = Min/max frequency
H.What happens in case of alarm with immediate stop?
• Immediate opening of the generator contactor.
• Activation of immediate stop.
• Activation of acoustic alarm.
• Memorization of alarm cause.
• Recording of all parameters and signalisations.
• Block status up to re-establishment
In case of alarm the display will automatically show the relative page and light the relative led.
Press ones the push button RESET to deactivate the acoustic alarm, pushing twice to deactivate the alarm status and re-
establish the normal functions of the electronic module.
I. When the voltage is restored within normal limits the mains re-enter delay timer (t2) is active and enables mains
stabilization before sending load on it.
L. After commutation, which has a pause of 1”, the cooling phase of the engine starts cc. 20’'(t4) and to which ends
the stop is activated and kept for about 10’’ .
M. Ready for a new cycle
N. With mains presence the fuel reserve, water level and overload protections are operating.
The manual operational mode is considered as an emergency back-up mode for the automatic functions. It also ensures the
operating efficiency with the micro-controller in an abnormal condition. The programming switch ensures the direct
commands that are not backed-up by electronic logics. This means that when the START push button is pressed for
example, the starting motor will be operated for as long as the push button is held down.
The following functions are possible:
1. Forced power supply from the mains CR;
2. Manual starting, the generator CG contact maker is opened;
3. The mains CR contact maker is opened and the power supply is forced from the generator;
4. Manual stoppage;
MANUAL STARTING
This provides the 15/54 commands that power all the generator utilities. It enables the start push button and once the
generator is running at a steady state the programming switch is set on the following function that enables the generator.
With the generator running all the safety devices are enabled. As these are however controlled entirely by the electronics its
failure could disable them.
MANUAL STOPPAGE
The stop push button is enabled at all times.
By moving the jumper, located on the right side of the module, on the pin
1 and 2 instead 2 and 3,the stop push button is enabled only in MANUAL
START mode.
WARNING
FILE VER DATE LANGUAGE PAGE
GCM01-MU-GB-12_en.doc LVI/03 16/09/2005 ING 10 of 33
If, after having powered the control panel the battery LED should fail to light up, check the POLARITY OF THE
BATTERY before operating any commands. Possible connection errors could cause electronic anomalies in the
MP01 module if commands are operated with the poles inverted.
COMMAND RELAYS
Three relays 16A command the starting, stopping and utilities 15/54. These are safeguarded by one single fuse; F1 (16A)
considering that only one relay is enabled at a time.
Two relays are free contact 10Aand command the contact maker of the commutation and generator (CG-CR).
On the right side of the module are available two trimmers, (not indicated to avoid Volt
wrong use) which enable the adjustment of mains voltage and generator measures. Rete
MOTOR PRE-HEATING
A single-phase power supply is foreseen that is safeguarded by fuses for the motor pre-heating system. The heater on it
must be fitted with built-in thermostat.
If required, specific plants to pre-heating system on the motor or generator are possible.
EMERGENCY
Pre-arrangement for the external emergency command enabled in all operational modes with immediate stoppage of the
motor, opening of the generator contact maker and triggering of the alarm.
The emergency device not only controls the control software of the circuit board but is also equipped with an electro-
mechanical circuit that totally ensures the stoppage of the unit and the opening of the generator contact maker.
+ BATT AC
RCG
PAE
CG
- BATT AC
T01
Functioning in manual mode: selecting MANUAL START
you have only one glow plug signal.
In the case more cycles are required it is necessary go back to MAN MAINS.
CRANK T06+t01
T06
15/54
RESET Rst
In remote controlled plants it’s necessary to have a command that re-establishes the circuits or closes the switches.
The output 11 is active for the time programmed in t06
Programming t07 = RST t06 = 0-20” output time active.
ANTITHEFT DEVICE
Only for GCM01 with serial output RS232C.
Only in remote controlled plants installed.
In case of disconnection of the generator the alarm status is given GC-M01
by remote control with GSM or MODEM. The conditions are
memorized in the alarm report.
21 20 14
FUNCTIONING
With the circuit cut above the generator in relation to the relay R1
of 30A that insulates the battery wiring, and the cable 14 which
enables the antitheft device, the module GCM01 is anyway
supplied by battery2 which supplies the remote control system R1
Functioning
BATT 2
2Ah
Programming T40 = fur
With T40 = at the input 14 FREE remains available for normal
alarms.
GEN SET
+ BATT 1 -
TEST FUNCTION
By configuring input 7 for the automatic test functioning TEST, which enables through remote control to put the generator in
automatic mode without cutting off mains power supply. If during the test running the mains fails, the generator immediately
supplies the users. Cutting off the command TEST, the generator stops automatically.
Programming: T13 = TST
The BLC function is disabled
LOCK FUNCTION
By configuring input 7 for the block function BLC, which enables through external command to put the module in a state of
forced lock mode; this function is very useful to put the module in night lock or weekend lock.
Programming T13 = BLC.
The TEST function is disabled
FUNCTION EJP
When JP1 is enabled, after the programmed time T12, the generator starts; with the command EJP2 the commutation from
mains to gen-set is immediate.
When these inputs are disabled, with connected mains and within normal operating limits, the output is switched to the
mains and the motor is stopped following a cooling delay.
M-01
The functions SCR and RES are disabled 8 7
Programming
T11 = EJP enables the function
T12 = starting delay of 0-28’
FUNCTIONING:
Command EJP1: the gen-set starts without commutation after t12 delay;
Command EJP2: immediate commutation;
EJP1 EJP2
30 min COMM.
SCR FUNCTION OR FORCED STARTING WITH OUTPUT
The input 8 is suitable for the SCR function. By configuring input T11 in SCR, when this is enabled, it starts the motor with
the forced output from the generator. As soon as this input is disabled, if the mains is connected and is within normal
operational limits the output is switched over to the mains and the motor is stopped following a cooling delay.
The EJP and RES functions are disabled M-01
8 7
PROG CONF PROG CONF
CONN FUNCTION
1 1 2 2
7- 8 EJP FRANCE T11 EJP T12 0 – 28’
SCR forced starting with
8 T11 SCR 1 2
output.
RES two GE alternated 0 – 255
8 T11 RES T34
(One in reserve to the other) Hours
7 BLC forced lock T13 BLC EJP1 EJP2
7 TST test running T13 TST SCR BLC
RES TST
RES FUNCTION FOR TWO GENERATORS THAT RUN ALTERNATELY
By configuring input 8 for the RES function, used in plants composed by two generators one in reserve to the other.
Two applications are foreseen:
1. Two gen-sets one in reserve to the other and in stand-by to mains;
2. Two gen-sets one in reserve to the other, as production central without mains.
The EJP and SCR are disabled
1 STAND-BY TO MAINS
To establish the PILOT generator put the programming switch in a position different from AUT (test or lock) for 3” and then
switch it back (AUT).
The FAILED START led begins flash to indicate that the PILOT generator and with fix light it indicates failed start.
It is possible to use the internal timer to program the automatic intervention of the power station composed by to gen-sets.
Programming the lock function with the internal timer it is possible to lock each generator for the programmed time.
Given that in case of disconnection of the module GC-M01 the timer loses the programming, it is advisable to supply the
plant (of two gen-sets) with two diods D1 and D2 of 40 A.
If you do not use the internal timer the diods are not necessary.
This circuit with diods on the battery is suitable only for plants without battery supplied by mains.
WIRING DIAGRAM
GC-M01 1 GC-M01 2
21 8 7 21 8 7
ON = STOP
OFF = START
D1 40A D2 40A
+ BATT 1 + BATT 2
T33 = Establishes the starting time of the generator, programmable from 0 to 23,50 hours
AUTOMATIC LOCK:
Enables to program time and days of the lock device, active even with mains failure.
Select t29 to program the day, then chose “tot” for the total lock and “par” for the partial lock. With “par” you enable the lock
start time in t30 and the lock stop time in t31. After d7 (Sunday) you will find the function “BLC”, press ENTER for the option
between ON to enable the lock function or OFF to disable the lock function.
Programming
T29 = 7 days the week divided in total lock “tot” or partial lock “par”, enabled by
BLC ON - OFF
D1 = Monday
D2 = Tuesday
D3 = tot = total day lock
D4 = par = partial lock, t30 and t31 enabled.
D5 =
D6 = t30 enables lock start
D7 = t31 disables lock end
BLC = ON enables the lock function OFF disables the lock function
T30 = 0 – 23,5 hours and tens to set the lock start in the selected days (t29)
T31 = 0 – 23,5 hours and tens to set the lock stop in the selected days (t29)
When the internal timer locks the generator, on the display appears BLC.
To using the generator in lock mode, use the manual commands.
ALARM REPORT
Memorizes all parameters (measures and alarms) at the moment of a failure, and enables to visualize the last 5 alarms.
It is active only with the programming switch in lock position.
To visualize the alarm report press at the same time and for 8”, “St1” appears, select the report from St1 to St5 with +/-
and enter with ENTER
ST1 = last report;
ST2 = the last but one; Ecc;
3.1. SETTINGS
The programming defines the kind of functioning that can be normal or articulated on need. To simplify the use GCM is
given with a standard configuration for a Disel generator group in emergency to the mains.
To reach the function programming, bring the switch N° 4 in ON position. All displayed measures can be modified. (Ex: 380V
into 395 or 378 or in other values)
The first displayed setting field is (t00). To enter press located on the frontal of the module; by entering in the field the
display shows the actual setting. To increase or decrease the adjusted value use + and -.
To confirm the chosen value and pass to the following field press The setting fields are 46 from T00 to T45. To move on
The following features are the minimum for the management of a stand-by generating set.
The fields in written round brackets are related fields to the same function.
NEW
N° DESCRIPTION VALUE FIELD
EJP Delay
T12 This is the starting delay (the relative input has to be programmed with the EJP 27’ 0 – 28’
function)
Overload delay
T28 When the threshold t27 is overload, the led wait starts flashing and at the end of the
(T27) time in t28 intervenes the overload alarm.
120” 30-255
DESCRIPTION Ref.
N° VALUE
Value400v
Engine working hours for maintenance.
It establishes after how many working hours the engine maintenance has 70 (x10) 0 – 255x10
T14 to be done. The GCM01 module signals with an acoustic and with a 700 working (2550)
lighting alarm . The defined value must be multiplied by 10. hours
Max. Mains voltage
T15 The generator is started. The value is in relation to the programmed + 10% Vn 440 V
normal working voltage (T09).
Min mains voltage
T16 The generator is started. The value is in relation to the programmed - 20% Vn 320 V
normal working voltage (T09).
Max. Generator voltage
T15 Alarm triggered and stoppage. The value is in relation to the programmed + 10% Vn 440 V
normal working voltage (T09).
Min. generator voltage
T16 Alarm triggered and stoppage. The value is in relation to the programmed - 20% Vn 320 V
normal working voltage (T09).
Hysteresis alarm threshold Min V
T17 It establishes the value of minimum voltage 30 Volts 0 –40 Volts
N° DESCRIPTION VALUE
T30(T29
“LOCK” beginning time 20 0,0-23,5
It establishes the lock beginning time in hours and a dozen minutes, for all the partial programming hours
-T31) days in t29.
T31(t29-
“LOCK” stopping time 7 0,0-23,5
It establishes the lock stopping time in hours and a dozen minutes, for all the partial programming hours
t30)
days in t29.
“Automatic test” test days selection OFF
T32(t33) It selects the test day on 4 weeks and starts or stops OFF all the functions of automatic test.
N° DESCRIPTION DEFAULT
T00 Starting attempts 5
T01 Starting time 5 Sec
T02 Mains enabling delay 30 Sec
T03 Generator enabling delay 5 Sec
T04 Stoppage delay 20 Sec
T05 Starting delay 1 Sec
T06 Glow plug pre-heating time or starter 5 Sec
T07 Function selection: PRC or STR CND
T08 Working frequency selection 50 Hz
T09 Working voltage selection 400
T10 AT value 100
T11 Function selection EJP or SCR or RES SCR
T12 Starting delay with EJP 27 Min
T13 Function selection: BLC or TST 70 (x10)
T14 Engine maintenance hours 10%
T15 Alarm percentage selection Max. V 20%
T16 Alarm percentage selection Min. V 10 V
T17 Hysteresis alarm threshold Min V 30 V
T18 Hysteresis alarm threshold Max V 10 V
T19 Calibration generator frequency reading 50 Hz
T20 Calibration generator three-phase voltage reading 400V
T21 Calibration generator current reading 100A
T22 Calibration of generator voltage reading 400V
T23 Calibration of battery voltage reading 12/24V
T24 Calibration of battery current reading 5A
T25 Max. Battery charger voltage 13,5/27V
T26 Max. Battery charger current 5A
T27 Overload current 0=OFF
T28 Overload delay 120’’
T29 “LOCK” days selection 0
T30 “LOCK” beginning time 20
T31 “LOCK” stopping time 7
T32 “Automatic test” test days selection OFF
T33 “Automatic test” beginning time 8
T34 Working hours of alternated gen-sets 4
T40 Alarm or antitheft function ALL
SERIAL CONNECTOR
RS232C
GC-M01
SW1 SELECTIONS
CONNECTOR
PROGRAM
1: ON 12Vdc OFF 24Vdc
2. ON SINGLE-PHASE OFF THREE-PHASE
3: ON 15- 16 POSITIVE INPUT OFF 15-16 NEGATIVE INPUT
4: ON PROGRAM MODE OFF FUNCTION MODE
OIL
Vac
STARTER - PREHEATING
16A
16A
16A
EMERGENCY
32
T
OVERLOAD
D-
TEST - EJP
LOCK
STOP NO
FUEL RESERVE
CR CG
31
D+
ALARM
S
..../5A
START
18/27Vac
STOP NC
CG CR
-B +B
LEVEL
CG CR
30
FREE
R
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
ON
OFF
On the higher part, is foreseen the output of the connector 9 poles of serial interfacing RS232.
N.B.:
The technical characteristics are subject to modifications without notice following technical
improvements.
FUNCTIONS
27 Min voltage
59 Max voltage
60 Dissymmetry
81 Protection for min/max frequency
50 Instant current or short-circuit
51 Max current with programmable delay
BCT CG CR -BATTERY
.../5A
CR CG IG
OVERLOAD
CG CR
18/27 Vac
5 6 28 29 1 2 3 4 9 10 30 31 32 17 26 27
BATTERY
KEYS CHARGER RR RG GEN. CURRENT THREE-PHASES
CG GENERATOR CONTACTOR VOLTAGE MEASURES SENSOR
CR MAINS CONTACTOR RTS
RR MAINS RELAY
+BATTERY
GCM-01
RG GENERATOR RELAY
SERIAL CONNECTOR
IG GENERATOR CIRCUIT BREAKER
RS232C
EV ELECTROVALVE
EPB EMERGENCY PUSH BUTTON
BCT BATTERY CHARGER TRANSFORMER
16A 16A 16A PRE
EMG EJP
HEATING BLC
DYN 15/54 CANDLES
STOP
STARTER
MAX.
TST SCR
100mA
STARTER
MAX.
RES
100mA
21 20 25 22 23 24 11 12 13 14 15 16 18 19 7 8
START
ALARM
FUEL RESERVE
FREE
EMERGENCY
STOP
BLOCK - TEST
WATER LEVEL
PREHEATING - STARTER
D- RA RS EV R S FR
MOTOR GROUND
STOP
OIL
HOLE
117
105
127
20 0
Ø
26 26
4 HOLES Ø 4 mm
4.1. POSITIONING
The control panel must have a protection rating (IP) suitable for the area in which it will be installed:
IP 42 (normal supply) for closed areas;
IP 55 in the case of possible splashing of water or for control panels exposed to rain.
WARNING!!!
It is advisable not to install the control panel further away than 20 meters form the generator.
QGE
GENERATING SET
CONTROL
PANEL
MAX 20mt
This requirement is due to the excessive currents caused by lightening that hits the public mains causing the voltage inside
the control panel to rise excessively if the connection line exceeds 20 meters.
If there is no other choice than installing the control panel further away than 20 meters, our engineering
department can provide you with various technical solutions.
WARNING!!
To ensure the reliability of the system all of its components must be connected to earth
FUEL TANK
QGE
GENERATING SET
EARTH
OTHER COMPONENTS
For further information contact a reliable installation engineer or our engineering department.
4.3. STARTING
It is advisable for the start command to install a servo-relay above the motor, so as to avoid that frequent voltage drops can
prevent the starting. Even with few wiring meters between panel board and generator.
FUS. 30A
START 3 + BATTERY
16A max
R
RELAY 30A 50
R
STARTING MOTOR
- BATTERY
Fig.: 3
Stoppage with ELECTROVALVE normally energised while the generator is running and while the utilities of the unit
are powered.
Connection 7 is defined 15/54; it emits the +B with a maximum current of 16A as the GE starting is commanded to stop
when the stoppage command is received.
15-54 10
OTHER MOTOR UTILITIES
16A max
ELECTRONIC
EV RPM
REGULATOR
FUS. 30A
4
+ BATT
16A max
R
RELAY 30A R EM
INJECTION PUMP
- BATT.
Operation: with the stopping command the electromagnet is energised and stops the motor. To establish the stoppage of
the motor the closure of the oil pressure switch is controlled, which after 20 seconds from when it closed automatically
disables the electromagnet thus avoiding settings and adjustments.
Fig. 5
THERMOSTAT PRESSURE SWITCH FUEL LEVEL
P
T
NA NC NC
- BATTERY
THE PARAMETERS INDICATED ARE NOT BINDING BUT SUBJECT TO TECHNICAL IMPROVEMENTS WITHOUT
PRIOR NOTICE.
The control panels that are subject to the electrical strength test are to be prepared baring in mind that the only connection
point with the electronic logic is established by the MAINS sensor (inputs 21R 22S 23T) to which a divider is connected
that is made up of
3 500 K ohm resistors for high voltage, for phase and connected to earth.
Therefore the R - S - T inputs are to be disconnected.
In cases in which the electrical system is started but not the generator, therefore its circuits and battery are practically not
powered, the powering of the electronics by the mains is to be avoided as this does not offer the control and safety devices
provided by the battery.
Therefore all fuses have to be disconnected, except F4 that supplies only the mains contact maker.
By starting the generator follow the servicing procedures.
WARNING considering that the battery charger generators output a voltage of between 50 and 150
Volts when disconnected from the battery while the generator is running, which is very destructive for the
electronics, the connections must strictly not be touched while the generator is running or the loose cables.
See the relative manual for the maintenance of the GENERATOR. The information provided herewith simply relates to
the electrical command and control parts of the generator.
WARNING!
The control panel is powered by the mains and by the generator. Before accessing it for maintenance purposes
disconnect the mains and stop the generator by setting the programming switch on “LOCKED”
Supposing that a load sufficient to exceed the maximum current that may be output is not available it is advisable to
modify the calibration of the overload to a value lower than the load current available (see setting section).
With the generator in automatic mode, disconnect the MAINS and when the CG generator contact maker has closed
enable the load. When the set current is exceeded, following the delay timing, the CG contact maker is opened and the
relative LED flashes, the alarm is triggered and the generator stops following the motor delay timing.
Reset the current calibration (maximum current of generator in “ALARM THRESHOLDS” section) after the test
has been completed.
The battery is kept efficient by the automatic battery charger, which controls its charge avoiding oxidation and
sulphating. It controls possible rising in voltage caused by the disconnection of internal components and also voltage
sagging causes by anomalies in the battery charger. The storage capacity, or rather the capacity of facing up to the
number of starting times sufficient to ensure the running efficiency of the generator is to be checked every six months in
the following manner:
Check with the battery fully charged, with a voltage greater than 13,5V for generators with 12V batteries and a voltage
greater than 27V for generators with 24V batteries.
With the generator in locked mode, disconnect the electromagnet the safety solenoid valve or the actuator or anything
else necessary to prevent the generator from starting. The power supply to the injection pump must be prevented so
that upon starting the motor turns without starting.
Set the programming switch on TEST, count 4 starting attempts at a rotation speed that is more or less the same from
the first to the fourth.
The same procedure can be performed by setting the programming switch on ENABLE START mode and manually
commanding the starting attempts for 5 seconds with pauses of 10 seconds for at least 5 times one after the other.
If starting fails after these 5 attempts (minimum 4) the batteries are to be replaced.
If the utility system is modified, check the scaling of the mains/generator line switching. The maximum load current must
not exceed the switching limit values indicated on the internal nameplate.
Nothing is working
Failed stoppage
Attempt to start
Battery led off
Failed starting