App Guide EntelliGuard - G 09 - 2020 Aplicacion
App Guide EntelliGuard - G 09 - 2020 Aplicacion
Circuit Breakers
Application Guide
—
Table of contents
01-08 Section 1. General Description 03-18 Table 3.1 Minimum Selective Clearing Times for an
01-08 Table 1.1 Device Standards and References EntelliGuard G Circuit Breaker Above Selected GE
01-08 Table 1.2 Device Ratings Circuit Breakers, and Related HRC Levels at Various
01-09 Table 1.3 Interrupting Rating Tier ANSI/UL1066 Fault Circuits
Devices, LVPCB 03-18 Above Other Power Circuit Breakers
01-09 Table 1.4 Interrupting Rating Tier ANSI/UL 1066 03-19 Terminology
Device, Non-Auto LVPCB 03-20 Long Time Protection
01-09 Table 1.5 Interrupting Rating Tier UL489 Devices, 03-20 Thermal Long Time Overcurrent
ICCB 03-21 Table 3.2 Thermal Characteristic: Nominal Clearing
01-09 Table 1.6 Interrupting Rating Tier UL 489 Device, and Commit Times for X Multipliers of Nominal
Molded Case Switches Pickup
01-10 Table 1.7 Endurance Rating – ANSI/UL 1066 Devices 03-22 Fuse-Shaped Steep Long Time Overcurrent
01-10 Table 1.8 Endurance Rating - UL 489 Devices 03-23 Table 3.3 Fuse Characteristic: Nominal Clearing and
01-10 Table 1.9 Endurance Rating - UL 489B DC Switches Commit Times for X Multipliers of Nominal Pickup
01-10 Altitudes and Closing Times 03-23 Thermal Memory
01-10 Dimensions and Weights 03-23 Short Time Protection
02-12 Section 2. Features and Characteristics 03-23 Short Time Pickup
02-12 Standard and Optional Features 03-24 Short Time Bands
02-12 Table 2.1 Enclosure Requirements 03-24 Table 3.4 Short Time Delay Bands
02-12 Reverse Feed 03-25 Short Time I 2 t Slopes
02-12 Two-Step Stored Energy Mechanism 03-25 Ground Fault Protection
02-12 Field Installable Trip Units and Accessories 03-26 Internal Residual Summation
02-13 Coils 03-26 External Zero Sequence Input
02-13 Breaker/Main Contact Status 03-26 Ground Fault Pickup Settings
02-13 Motor Operator 03-26 Table 3.5 Ground Fault Time Delay Bands
02-13 Electrical Closing Button 03-26 Table 3.6 Minimum Ground Fault Pickup and Clear
02-13 Ready to Close Indicator Time
02-13 Mounting Straps/Accessories 03-26 Ground Fault Protection Curves
02-13 Auxiliary Switches 03-27 Instantaneous Protection
02-13 Interlocks 03-27 Adjustable Selective Instantaneous
02-13 Breaker Status Indicators 03-28 Table 3.7 Maximum Adjustable Instantaneous Pickup
02-13 Rejection Feature for EntelliGuard G Circuit Breakers with Normal or
02-13 Through-Door Racking Extended Range Option
02-14 Padlocking Devices 03-28 Table 3.8 Time Current Curves
02-14 Key Interlock 03-28 High Set Instantaneous Overcurrent (HSIOC)
02-14 Shutters 03-29 Making Current Release (MCR)
02-14 Carriage Position Switch 03-29 Reduced Energy Let-Through (RELT) Instantaneous
02-14 Lifting Beam Trip
02-14 IP Covers 03-29 Reduced Energy Let-Through Switch Wiring
02-14 Mechanical Counter 03-30 Zone Selective Interlocking (ZSI)
02-14 Cable Interlocks (OEM Applications Only) 03-31 Universal Trip Rating Plugs
02-14 Bell Alarm Contact 03-32 Table 3.9 Trip Rating Plug Codes
03-15 Section 3. EntelliGuard TU Trip Unit System 03-32 Table 3.10 Trip Rating Plug Specifications
03-15 Reliability without Compromising Protection 03-33 Table 3.11 EntelliGuard G Rating Plug Logic (UL 489,
03-15 Arc Flash and the EntelliGuard TU Trip Unit UL 1066, IEC)
03-16 New for 2013…firmware versions 08.00.26 and later 03-34 Universal Spare Trip Unit
03-16 Selectivity with Molded Case Circuit Breakers and 03-34 Table 3.12 Universal Spare Trip Unit Options (User-
Other Devices Selected)
03-17 Above Downstream Feeders 03-34 Example Universal Trip Cat#: G1X00L4T6MRXXXX
03-17 The Waveform Recognition Selective Instantaneous 03-35 Table 3.13 Relay Functions Available in EntelliGuard G
Circuit Breakers with EntelliGuard TU Trip Units
4 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Table of contents
04-53 Table 4.31a Neutral Rogowski CTs (Loose Rogowski 06-88 Table 6.6 Operational Ratings, UL1066/ANSI Circuit
Coil and mounting hardware) Breakers
04-53 Table 4.31b Large Window Rogowski 06-88 Selecting a Circuit Breaker for an Application
04-53 Sealed Door Panel Escutcheon 06-88 Cable or Bus Size – Factor A
04-53 Mechanical Operations Counter 06-88 Ambient Temperature – Factor B
04-53 Table 4.32 Miscellaneous Accessories 06-88 Table 6.7 Ambient Temperature Rating - Factor B
04-54 Door Interlocks 06-88 Operating Frequency – Factor C
04-54 Table 4.33 Door Interlocks 06-89 Altitude – Factor “D”
04-54 Table 4.34 Back-connected Terminations for 06-89 Table 6.8 Altitude Rating – Factor D
Cassette 06-89 Load Class Rating – Factor E
04-57 Table 4.35 Back-connected Terminations 06-89 Table 6.9 Load Class Rating – Factor E
04-60 Flat Front Terminations 06-89 Safety – Factor F
04-60 Table 4.36 Optional Flat Front Terminations 06-89 Other Factors that Influence Circuit Breaker Sizing
04-62 Table 4.37 Cluster 100% vs. 80% Ratings
04-63 Table 4.38 Cluster Pad 06-89 Table 6.10 Circuit Breaker and Trip Parameters
04-65 Remote Racker 07-90 Section 7. Physical Data
04-65 Table 4.39 Remote Racker Catalog Listing 07-90 Dimensions and Weights
04-65 Grounding/Earthing Device (IEC Only) 07-91 Table 7.1 Drawing Index
04-65 Table 4.40 Earthing Devices (IEC only) 07-92 Dimensions & Weights
04-65 Rejection Device 07-92 Table 7.2 3-pole, UL/ANSI
04-65 Replacement Top Cover 07-93 Table 7.3 4-pole, UL/ANSI
04-65 Table 4.41 Replacement Top Covers 08-94 Section 8. Standards and References
05-66 Section 5. Catalog Numbering Guide 08-94 Organizations
05-66 EntelliGuard G ANSI/UL489 Circuit Breaker Catalog 08-94 Underwriters Laboratories® (UL)
Number Guide 08-94 National Electrical Manufactures Association (NEMA)
05-80 EntelliGuard TU Trip Unit for EntelliGuard G Breakers 08-94 Canadian Standards Association (CSA)
05-83 EntelliGuard TU Trip Unit Rating Plugs 08-94 Institute of Electrical and Electronics Engineers
06-84 Section 6. Application Data (IEEE)
06-84 Key Features 08-94 American National Standard Institute (ANSI)
06-84 UL1066 Low Voltage Power Circuit Breakers 08-94 International Electrotechnical Committee (IEC)
06-84 UL489 Stored Energy Insulated Case Circuit Breakers 08-95 National Electrical Code®
06-84 IEC Rated Circuit Breakers for IEC Equipment and 08-95 American Society for Testing and Materials (ASTM)
Applications 08-95 Military Standard (MIL-STD)
06-84 All Types 08-95 Seismic Qualifications to All Major Building Code
06-84 Ratings and Sizes Standards
06-85 Short Circuit Interrupting Ratings 08-95 Other
06-85 Table 6.1 First Half-Cycle Peak at Specific Fault X/R 08-96 EntelliGuard G Publications
Ratios (excerpted from UL489)
06-85 Withstand Ratings, Selective Waveform Recognition-,
RELT- and Override-Instantaneous Protection
06-86 Close and Latch Ratings and Making Current Release
(MCR) Instantaneous Trip
06-87 Table 6.2 EntelliGuard G Circuit Breaker Close and
Latch Ratings, UL489 Listed
06-87 Table 6.3 EntelliGuard G Circuit Breaker Close and
Latch Ratings, UL1066 Listed
06-87 Table 6.4 EntelliGuard G Non-Automatic Switch
Close, Latch, and Withstand Ratings, UL489 Listed
06-87 Operations
06-87 Table 6.5 Operational Ratings, UL 489 Circuit
Breakers
6 ENTELLIGUARD* G CIRCUIT BRE AKERS
— —
Table of figures Table of tables
01-11 Figure 1.1 Breaker construction 01-08 Table 1.1 Device Standards and References
01-11 Figure 1.2 Label 01-08 Table 1.2 Device Ratings
01-11 Figure 1.3 Label U Trip Unit 01-09 Table 1.3 Interrupting Rating Tier ANSI/
03-16 Figure 3.1 Arcing Current UL1066 Devices, LVPCB
03-17 Figure 3.2 Selectivity Curve 01-09 Table 1.4 Interrupting Rating Tier ANSI/UL
03-18 Figure 3.3 TCC for Two Circuit Breakers Implementing 1066 Device, Non-Auto LVPCB
Short Time, Instantaneous, and Threshold ZSI 01-09 Table 1.5 Interrupting Rating Tier UL489
03-20 Figure 3.4 Thermal Characteristic: Maximum and Devices, ICCB
Minimum Long Time Delay Bands for a 1000A Long 01-09 Table 1.6 Interrupting Rating Tier UL 489
Time Pickup Device, Molded Case Switches
03-22 Figure 3.5 Fuse Characteristic: Maximum and 01-10 Table 1.7 Endurance Rating – ANSI/UL 1066
Minimum Long Time Delay Bands for a 1000A Long Devices
Time Pickup 01-10 Table 1.8 Endurance Rating - UL 489 Devices
03-24 Figure 3.6 Short Time Pickup 01-10 Table 1.9 Endurance Rating - UL 489B DC
03-24 Figure 3.7 Short Time Transition Switches
03-25 Figure 3.8 Short Time Delay 02-12 Table 2.1 Enclosure Requirements
03-25 Figure 3.9 Short I 2 t (In or Out) 03-18 Table 3.1 Minimum Selective Clearing Times
03-27 Figure 3.10 Ground Fault Characteristics for an EntelliGuard G Circuit Breaker Above
03-30 Figure 3.11 Integrated Switch and LED, Spring Return Selected GE Circuit Breakers, and Related
from “Test” to “Off,” Latched in “On” HRC Levels at Various Fault Circuits
03-31 Figure 3.12 Zone Selective Interlocked CB, Upper 03-21 Table 3.2 Thermal Characteristic: Nominal
CB Shown “Unrestrained” Clearing and Commit Times for X Multipliers
03-31 Figure 3.13 Zone Selective Interlocked CB, Upper of Nominal Pickup
CB Shown “Restrained” 03-23 Table 3.3 Fuse Characteristic: Nominal
03-32 Figure 3.14 EntelliGuard Trip Unit Rating Plug Catalog Clearing and Commit Times for X Multipliers
Number of Nominal Pickup
04-41 Figure 4.1 A ccessory Mounting 03-24 Table 3.4 Short Time Delay Bands
04-44 Figure 4.2 Time Delay Module 03-26 Table 3.5 Ground Fault Time Delay Bands
04-48 Figure 4.3 Breaker-Mounted Key Interlock 03-26 Table 3.6 Minimum Ground Fault Pickup and
04-48 Figure 4.4 Cassette-Mounted Key Interlock Clear Time
04-64 Figure 4.5 Terminations for DC Switches UL 489B 03-28 Table 3.7 Maximum Adjustable Instantaneous
07-90 Figure 7.1, visit www.geindustrial.com. Pickup for EntelliGuard G Circuit Breakers
with Normal or Extended Range Option
03-28 Table 3.8 Time Current Curves
03-32 Table 3.9 Trip Rating Plug Codes
03-32 Table 3.10 Trip Rating Plug Specifications
03-33 Table 3.11 EntelliGuard G Rating Plug Logic
(UL 489, UL 1066, IEC)
03-34 Table 3.12 Universal Spare Trip Unit Options
(User-Selected)
03-35 Table 3.13 Relay Functions Available in
EntelliGuard G Circuit Breakers with
EntelliGuard TU Trip Units
03-35 Table 3.14 Voltage Unbalance Settings
03-36 Table 3.15 Current Unbalance Settings
03-36 Table 3.16 Undervoltage Settings
03-36 Table 3.17 Overvoltage Settings
03-36 Table 3.18 Power-Reversal Settings
03-37 Table 3.19 Input Assignments Possible
03-37 Table 3.20 Output Configuration
03-38 Table 3.21 EntelliGuard Trip Unit Summary
A P P L I C AT I O N G U I D E 7
03-40 Table 3.22 Metering Data Startup Levels 04-51 Table 4.28 Wiring Schematic for Block-B
for breaker with EntelliGuard Trip Unit (Three Layer Secondary Disconnect to be
with 24 VDC Added for GTU with Full I/O and
03-40 Table 3.23 Accuracy as a Percent of Additional Accessory Signals)
Sensor Rating 04-51 Table 4.29 Wiring Schematic for Block-C
04-42 Table 4.1 Motor Operators – Internal to the breaker, not used by
04-43 Table 4.2 Closing Coil Characteristics customer (Two Layer Intermediate
04-43 Table 4.2.1 Command Shunt Releases Secondary Disconnect at the Top for the
04-43 Table 4.3 Extended Range Shunt Trip for Side Mounted Secondary Disconnect)
UL Ground Fault and ANSI DC Rating 04-52 Table 4.30 Wiring Schematic
Applications Nomenclature Definitions
04-43 Table 4.4 Coil Signaling Contact Module 04-53 Table 4.31 Wiring Schematic
04-44 Table 4.5 UVR Operating Characteristics Nomenclature Definitions
04-44 Table 4.6 TDM Characteristics 04-53 Table 4.31a Neutral Rogowski CTs (Loose
04-45 Table 4.7 Remote Operation Coil Rogowski Coil and mounting hardware)
Combination 04-53 Table 4.31b Large Window Rogowski
04-45 Table 4.8 Ready to Close Contacts 04-53 Table 4.32 Miscellaneous Accessories
04-45 Table 4.9 Auxiliary Switches 04-54 Table 4.33 Door Interlocks
04-45 Table 4.10 Auxiliary Switch Ratings and 04-54 Table 4.34 Back-connected Terminations
Secondary Disconnect Points for Cassette
04-46 Table 4.11 Power Rated (3NO/3NC) (Ref 04-57 Table 4.35 Back-connected Terminations
Drawing 10099230) 04-60 Table 4.36 Optional Flat Front
04-46 Table 4.12 Power Rated (8NO/8NC) (Ref Terminations
Drawing 10099228) 04-62 Table 4.37 Cluster
04-46 Table 4.13 Power Rated (3NO/3NC) Low 04-63 Table 4.38 Cluster Pad
Signal (Hi-Fi) (2NO/2NC) (Ref Drawing 04-65 Table 4.39 Remote Racker Catalog Listing
10099232) 04-65 Table 4.40 Earthing Devices (IEC only)
04-47 Table 4.14 Power Rated (4NO/4NC) + Low 04-65 Table 4.41 Replacement Top Covers
Signal (Hi-Fi) (4NO/4NC) (Ref Drawing 06-85 Table 6.1 First Half-Cycle Peak at Specific
10099234) Fault X/R Ratios (excerpted from UL489)
04-47 Table 4.15 Key Interlocks and Door 06-87 Table 6.2 EntelliGuard G Circuit Breaker
Interlocks Close and Latch Ratings, UL489 Listed
04-48 Table 4.16 Carriage Position Switches 06-87 Table 6.3 EntelliGuard G Circuit Breaker
04-48 Table 4.17 Carriage Position Switch Close and Latch Ratings, UL1066 Listed
Ratings (Common NO/NC Contact 06-87 Table 6.4 EntelliGuard G Non-Automatic
Configuration) Switch Close, Latch, and Withstand
04-48 Table 4.18 Mechanical Interlock (Cable/ Ratings, UL489 Listed
Rod) 06-87 Table 6.5 Operational Ratings, UL 489
04-49 Table 4.19 Cables for Mechanical Circuit Breakers
Interlocks 06-88 Table 6.6 Operational Ratings, UL1066/
04-49 Table 4.20 Interlock Configurations ANSI Circuit Breakers
04-50 Table 4.21 Bell Alarm Switches 06-88 Table 6.7 Ambient Temperature Rating -
04-50 Table 4.22 Bell Alarm Lockout Kits for Trip Factor B
Units 06-89 Table 6.8 Altitude Rating – Factor D
04-50 Table 4.23 Bell Alarm Ratings 06-89 Table 6.9 Load Class Rating –
04-50 Table 4.24 Spring Charged Contact (1 NO) Factor E
04-50 Table 4.25 Secondary Disconnect Options 06-89 Table 6.10 Circuit Breaker and Trip
04-50 Table 4.26 Secondary Disconnect Block Parameters
Locations 07-91 Table 7.1 Drawing Index
04-51 Table 4.27 Wiring Schematic for Block-A 07-92 Table 7.2 3-pole, UL/ANSI
(Three Layer Secondary Disconnect with 07-93 Table 7.3 4-pole, UL/ANSI
Basic GTU and Basic Accessories)
8 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 1.
General description
EntelliGuard G circuit breakers are the newest line communications protocols. The ArcWatch* enabled
of low voltage power circuit breakers (LVPCBs) system delivers superior circuit protection without
evolved from the exceptional designs and practices compromising selectivity or arc flash protection.
of GE legacy breakers. EntelliGuard G breakers The EntelliGuard system is yet another evolution of
offer a truly global product platform that meets GE core competences in reliable electric power
industry standards throughout the Americas, distribution, circuit protection and arc flash
Europe and Asia (ANSI, UL, cUL, IEC, Lloyds protection.
Register of Shipping, etc.). EntelliGuard G 3-pole breakers are the standard in
Breakers are available to OEMs in 3- and 4-pole GE AKD-20 Low Voltage Switchgear. The breakers
designs from 400A to 6400A (IEC) with fault are suitable for 280Vac, 480Vac and 600Vac
interruption ratings up to 200kA. New, state-of- applications, and they provide advanced circuit
the-art EntelliGuard Trip Units enable the breakers protection, limit arc fault energy and preserve
with advanced technology that provides system system coordination without sacrificing any of
protection, local and remote monitoring, relaying these critical functions (Table 1.1; see Section 8
and communications. EntelliGuard Trip Units may for details).
be supplied with either Modbus or Profibus
1. Restricted
Table 1.4 Interrupting Rating Tier ANSI/UL 1066 Device, Non-Auto LVPCB
Envelope 1 Envelope 2 Envelope 2.5 Envelope 3
Type 254V – 635V 800 – 1200 800, 1600, 2000 800, 1600 – 3200 2000 – 4000 3200 – 5000
S1 42 X
N 42/65 X
M 65/100 X
U1 65 X
B 100 X
1. 3 pole only.
1. Icu=Ics=Icw
Table 1.6 Interrupting Rating Tier UL 489 Device, Molded Case Switches
Type 240V – 600V 800 – 1200 800 – 2000 800, 3000 2000, 3000, 4000 3000 – 6000
S1 42 X
N 42 X
M 65 X
U1 65 X
B 100 X
1. 3 pole only.
10 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 1.
General description
Table 1.7 Endurance Rating – ANSI/UL 1066 Devices
Rated Endurance
Minimum Mechanical Minimum Electrical Endurance Minimum Electrical Endurance
Envelope Max Amps Endurance at 480V at 600V
1 1600 16,000 10,000 7,500
1 2000 16,000 7,500 5,000
2 3200 11,000 5,000 5,000
2.5 4000 5,000 3,000 2,000
3 4000 7,000 3,000 2,000
3 5000 7,000 2,000 1,500
• Configurations available for 600V DC and 1000V DC with or without isolating both DC legs.
• See “Flat Front Terminations,” page 53, for Bus Bar Configurations. Note: Bus Bars must be ordered separately.
• Time Constant (L/R) = 15msec, Rated calibration temperature: 50 degree C.
• Suitable for use in Photovoltaic system in accordance with article 690 of the NEC.
1 9
3 10
4
11
12 1 B-disconnect
2 Secondary disconnects – combination terminals
3 Detailed, factory-assembled side label
5 13 4 EntelliGuard TU trip unit
5 Rating plug
14 6 Operating buttons: ON/OFF
7 Optional factory- installed interlocks — Drawout
6 15 Breaker’s Key Interlocks are installed in the Cassette
8 Complete, factory-assembled catalog number
16 9 A-disconnect, always provided
10 Accessory window (Close/Command Close Coils,
Shunt Trips, UVRs
7 17 11 Padlock provision
12 Retractable handle for manual spring charging
13 Electrically closed button
18
14 Spring discharge
15 Breaker status: OPEN/CLOSED Closing spring
status: CHARGED/DISCHARGED
19 16 Ready-to-close
8 17 Spring charged indicator
18 Mechanical operations counter
19 Tamper-proof breaker label
1 2 3 1
2
3
4
5
1 Main screen with…
2 Setup – allows
adjustment of
settings and
parameters
3 Meter – displays full
measurement values
4 5 6 7 8 4 Status – indicates
6 breaker main contact
position settings,
pick-up,
1 Product family 7
errors, RELT, firmware
2 Current rating version
3 Bar code with manufacturing data 5 Event log – shows
4 Voltage ratings history of trip, cause,
5 Short circuit ratings overcurrent level
6 Certification & standards 6 Cursor-driven
7 Manufacturing date setting/selection
8 Interruption tier color code (IEC only) system
7 Rating plug
12 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 2.
Features and characteristics
Standard and optional features
Thermal Performance
ANSI C37 and UL 489 designs are 100% rated up to
40ºC when applied in recommended enclosure
sizes. IEC 60947 versions are 100% rated in free air
up to 50ºC. IP31 enclosure/switchboard rating is
based on size, recommended up to 50ºC ambient
with rear vertical bus connection (Table 2.1).
Coils Interlocks
EntelliGuard G devices have provisions for four Standard interlocks include:
accessory operating coils. The four positions can • Drawout Breaker: prevents the breaker from
be filled by the following four devices: one Close being closed unless it is in the TEST or CONNECT
Coil (CC or CCC), one Shunt Trip Coil, one UVR positions
(Undervoltage Release), and the fourth position can • Drawout Breaker/Main Contacts: prevent
either be a Shunt Trip Coil or a UVR. The closing coil withdrawal/removal of the breaker unless the
is a “one-shot” electronic closed circuit. Shunt trip main contacts are OPEN. Access to the drawout
(ST) coils are continuous rated. Undervoltage relays mechanism racking screw is blocked when the
(UVR) are available with a fixed time delay (50ms at breaker is CLOSED.
down to 50% system voltage; 20ms below 50% • Spring Discharge Interlock: Automatically
system voltage). The time delay module (TDM) is discharges the closing springs when the breaker
available as a shipped-loose accessory for remote is moved from the DISCONNECT to the
installation (in equipment). Optional status contact WITHDRAWN position. This prevents withdrawing
modules for the ST, CC and UVRs provide coil status a breaker from the cubicle with the closing
(energize/de-energize) via the secondary springs charged.
disconnects and trip unit.
Breaker Status Indicators
Breaker/Main Contact Status Standard Indicators include:
OPEN/CLOSED, ON/OFF indication is provided on • The breaker status indicator shows the condition
the front cover. of the main contacts (OPEN, CLOSED).
• The status of the closing springs is indicated as
Motor Operator CHARGED or DISCHARGED.
Heavy duty, motor/gearbox unit; easily accessible • The drawout position indicator displays whether
with a full range of voltages. the breaker is in the CONNECT, TEST, or
DISCONNECT position.
Electrical Closing Button • The breaker also includes a switch that provides
Located on the front cover between the Open and main contact status indication that can be wired
Close button; used to electronically close the to a remote monitoring system.
breaker when a Command Close Coil is selected. • The optional Reduced Energy Let-Through (RELT)
is provided with an ON/OFF contact closure to
Ready to Close Indicator positively indicate whether the RELT setting is
Provides visible indication/readiness for close enabled or not.
operation.
Rejection Feature
Mounting Straps/Accessories A factory-installed rejection feature prevents
Kits are available to mount and connect fixed/ mismatching breakers and cassettes/
stationary breakers in either a rear connected substructures. This prevents (a) inserting a breaker
(Vertical) or a flat front connected. with a lower interrupting rating into a higher rated
cassette/substructure and (b) inserting a higher
Auxiliary Switches current rated breaker into a lower rated cassette/
Four available designs: substructure.
• Power rated (3NO+3NC) (Standard)
• Power rated (3NO+3NC) + low signal (Hi-Fi) Through-Door Racking
(2NO+2NC) The breaker racking mechanism is accessible
• Power rated (8NO+8NC) through the front of the cassette and permits
• Power rated (4NO+4NC) + low signal (Hi-Fi) safely disconnecting/withdrawing the circuit
(4NO+4NC) breaker without opening the door and exposing
personnel to live parts during the process.
14 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 2.
Features and characteristics
Padlocking Devices IP Covers
The padlocking device is standard on breakers and Optional IP54 covers (protects against harmful
allows up to three padlocks with 1/4" to 3/8" amounts of dust and splashing water) are available
diameter shanks to secure the breaker in the for all breaker sizes.
OPEN/TRIP FREE position. A padlock provision on
the front panel of the cassette/substructure Mechanical Counter
permits locking access to the racking screw. Provides local record of the cumulative number of
Racking access can be locked with the breaker in complete breaker closing operations.
the CONNECT, TEST, DISCONNECT position with up
to three padlocks. Cable Interlocks (OEM Applications Only)
Available for fixed and drawout breakers, these
Key Interlock units enable direct interlocking of EntelliGuard G
Up to four optional key interlocks are available circuit breakers.
(Kirk, Ronis, Profalux, Castell). Switchgear
applications utilize a Kirk key interlock mounted in Bell Alarm Contact
the cassette. A maximum of two key interlocks may Available with or without a mechanical lockout
fit in the cassette. feature, the bell alarm operates whenever the
breaker trips due to a protective function
Shutters (electrical fault).
Optional lockable shutters are available (factory Breakers ordered from the factory without Bell
installed). Alarm Accessory will have Automatic Reset
Functionality when the Bell Alarm Accessory is
Carriage Position Switch installed. To convert from Automatic to Manual
This optional cassette/substructure device permits Reset on the Bell Alarm, a new trip unit is required.
local or remote indication of the circuit breaker
status (CONNECTED, TEST, DISCONNECTED),
2NO/2NC single pole, double throw contacts are
available for each position.
Lifting Beam
Optional Lifting Beams/bars with separate slings
are available for all breaker sizes. A Universal
Lifting Beam is also available capable of lifting a 3
Pole Envelope 1
A P P L I C AT I O N G U I D E 15
—
Section 3.
Entelliguard TU Trip Unit System
The EntelliGuard TU Trip Unit offers optimum These requirements often seem to be, and
circuit protection and optimum system reliability sometimes are, in conflict, pitting the speed and
simultaneously with little or no compromise to sensitivity required to improve arc flash protection
either of these critical functions. Reliability and arc against the delays and deliberate decision making
flash protection, in one package, at the same time, required to maximize power system reliability. The
all the time. EntelliGuard TU, along with the EntelliGuard family
EntelliGuard TU series trip units are available as the of circuit breakers, offers flexible solutions for
standard controller for new production demanding circuit protection and circuit
EntelliGuard G ANSI/UL 1066, UL 489 and IEC preservation environments. The EntelliGuard TU is
circuit breakers. EntelliGuard TU designs are also designed to provide the utmost in system
available as direct, functional replacements for GE protection and reliability simultaneously, with little
PowerBreak*, PowerBreak II, WavePro*, AKR, and AK or no compromise.
circuit breakers. EntelliGuard TU trip units are also
available in kit form for many popular non-GE and Arc flach and the EntelliGuard TU Trip Unit
older GE low voltage power circuit breakers (Refer Reducing arc flash hazard should be a primary
to DEH-4567 and DET-722). The EntelliGuard TU concern in many power system designs. The best
technology is also available in GE's molded case way to ensure the lowest possible hazard for a
Spectra Breaker line 400A-1200A. Optional features particular distribution system is to consider the
of Spectra MET (microEntelliGuard*) include the hazard as the system is designed and make careful
innovative RELT and Zone Selective Interlocking- selection of the system’s topology, circuit sizes,
Instantaneous feature. New, on-board features and equipment sizes and protective devices to
communications capabilities enable equipment minimize hazard for the operating and maintenance
enhancements, improved operational performance personnel that will need to interact with the system
and life extension programs. Performance will vary for years to come.
based on associated circuit breaker and equipment The EntelliGuard TU, especially in conjunction with
conditions. All EntelliGuard TU Trip Units are the EntelliGuard G circuit breaker, provides
Conformal Coated for increased reliability in significant flexibility towards solving arc flash
humid/damp environments. hazard problems without excessive sacrifice of
This section describes the functions as system reliability, in terms of selectivity.
implemented in the EntelliGuard G UL 489 and The next few pages are an overview of the
ANSI/UL 1066 circuit breakers. References or EntelliGuard TU's novel features enabling Arc Flash
comparisons to other GE circuit breakers are for mitigation and selectivity at the same time. When
informational purposes only. the downstream breaker/fuse is current limiting,
the Waveform Recognition Selective Instantaneous
Reliability without compromising protection is used to achieve lower Instantaneous pickup
Reliable protection of circuits and equipment has settings while maintaining selectivity. This is very
always been the circuit breaker’s primary mission. effective for 250A and below devices. For Feeder
Providing appropriate protection of the devices above 250A in MCCs (600A for panels/
conductors, while preserving selective switchboards), the Instantaneous Zone Selective
coordination, has been the primary focus of most Interlocking (I-ZSI) feature is used to achieve
system designers. However, what was acceptable selectivity and arc flash mitigation at the same
in the past is no longer the standard today. time. The I-ZSI feature is available on Spectra MET
Modern economic reality, coupled with strict and EntelliGuard TU in the following breakers:
regulatory requirements, demand optimal system EntelliGuard G, Power Break II, WavePro, AK/AKR,
performance with increased sensitivity to the and Conversion Kits. By combining the Waveform
inherent power system hazards that face operating Recognition Selective Instantaneous and I-ZSI, a
and maintenance personnel. Safety agencies, local system with a 100KAIC bolted fault current can
authorities and owner-operators demand better achieve an 8 cal/cm2 or less incident energy level.
*) Indicates a trademark personnel protection and state-of-the-art One way to lower potential incident energy is to
of the General Electric
capabilities to minimize hazards while ensure that circuit breakers are able to interrupt
Company and/or its
subsidiaries. simultaneously preserving critical loads and using their Instantaneous trips for all expected
system capabilities. arcing faults. Figure 3.1 shows the expected arcing
16 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 3.
Entelliguard TU Trip Unit System
currents for 480V systems for various arc gaps Furthermore, EntelliGuard trip units have built-in
representative of switchgear (32mm), ZSI test capability as a standard feature on all the
switchboards (25mm), MCCs (25mm) and ones equipped with ZSI. It allows users to test
panelboards (13mm). These values were interconnected wiring and TIM modules to ensure
determined using IEEE standard 1548, Guide for the ZSI scheme is fully functional.
Performing Arc-Flash Hazard Calculations, 2002.
Selectivity with molded case circuit breakers and
other devices
Figure 3.1 Arcing Current The EntelliGuard TU trip unit’s Waveform
Recognition Selective Instantaneous provides a
50.0
unique selectivity capability. When used in
conjunction with current limiting devices
40.0 downstream, the trip unit may be set low, and still
maintain significant levels of selectivity. See
publication DET-760 for the list of the minimum
30.0
instantaneous settings above specific GE circuit
kA Arcing
Selectivity for an EntelliGuard TU ground fault Also listed is the Hazard Risk Category for various
function and a circuit breaker below may be available fault currents calculated at the listed
enhanced by the trip unit’s selective ground fault Short Time band clearing times and Instantaneous
function and zone selective interlocking. Figure 3.2 clearing times provided by the EntelliGuard TU trip
demonstrates an 800A circuit breaker under a unit’s Waveform Recognition Selective
1200A ground fault set to be fully selective. See Instantaneous and its Reduced Energy Let-Through
also DET-760 for the tables that identify the (RELT) Instantaneous trip. The Hazard Risk
maximum instantaneous pickup multipliers Category (HRC) levels shown are calculated for a
possible for various types and sizes of GE circuit solidly grounded, 480V system, 32mm arc gap, 18
breakers and a complete listing of all selectivity in. working distance and arc in box. Using the
functionalities. optimized Short Time band allows the system to
stay at HRC2 most of the time and always less than
HRC4. However, use of the RELT Instantaneous trip
Figure 3.2 Selectivity Curve
allows the system to protect at HRC1 or 2 for
1000.00
available fault currents as high as 90kA.
—
Section 3.
Entelliguard TU Trip Unit System
Table 3.1 Minimum Selective Clearing Times for an EntelliGuard G Circuit Breaker Above Selected GE Circuit Breakers, and
Related HRC Levels at Various Fault Circuits
GE Molded Case Circuit Minimum Clearing 480V, 32mm, 24in Working Distance, Arc in a Box - HRC @ Ibf=
Circuit Breaker Family Breaker Type EntelliGuard TU Short Time
35kA 42kA 50kA 60kA 75kA 90kA 100kA
Time Band
FB, FC, TEY, THQL TM, LP 0.025sec 0.08sec 2 2 2 2 3 3 3
TED, TEC TM-GP, MCP 0.025sec 0.08sec 2 2 2 2 3 3 3
TF, TJ, TK TM-GP 0.025sec 0.08sec 2 2 2 2 3 3 3
Spectra E, F, G Frame E-GP 0.025sec 0.08sec 2 2 2 2 3 3 3
Spectra K Frame E-GP 0.033sec 0.088sec 2 2 2 2 3 3 3
Spectra G, K with MVT trip AE-GP 0.025sec 0.08sec 2 2 2 2 3 3 3
Record Plus G Frame E, AE-GP 0.042sec 0.097sec 2 2 2 2 3 3 3
Record Plus E Frame E-GP 0.033sec 0.088sec 2 2 2 2 3 3 3
Power Break with MVT AE-GP 0.058sec 0.113sec 2 2 2 3 3 3 3
Instantaneous Clearing Time instantaneous 0.050sec 1 1 1 2 2 2 2
RELT Clearing Time RELT Instantaneous 0.042sec 1 1 1 1 2 2 2
TM = T hermal Magnetic. AE = Adjustable Electronic. GP = G eneral Purpose Application. HRC = H azard Risk Category
E = Electronic. LP = Lighting Panel Application. MCP = M otor Circuit Protector. (See NFPA 70E).
Above Other Power Circuit Breakers selectivity. A novel algorithm within the trip units
Using the EntelliGuard TU trip unit’s novel will arbitrate fault location and shift the upstream
Instantaneous Zone Selective Interlocking (I-ZSI), device in time and threshold to ensure the
the main circuit breaker also can be set to interrupt downstream device operates as set and that the
selectively for faults in its zone of protection. upstream device provides backup protection as
However, the pickup level must be nested to fast as possible in case the downstream device
prevent a nuisance trip at the main. Allowing for a fails to operate.
10% tolerance in the pickup current of both trips, The figure below shows the TCC for two circuit
the upper boundary of the main’s trip may be breakers implementing Short Time, Instantaneous,
estimated at approximately 11kA. Again, Figure 3.1 and Threshold Zone-Selective-Interlocking at the
shows that available fault currents above 25kA will same time. When the downstream trip unit senses
generally produce arcing currents above 11kA. a fault current it causes the upstream trip unit to
Table 3.1 shows a system with fault currents from shift both the short time and instantaneous
35kA to 100kA, the feeder and main circuit breaker thresholds to the right, as well as restraining the
will provide protection at HRC1 or HRC2 selectively operation in time to allow the downstream circuit
above most circuit breakers using short time breaker to protect its zone of protection,
bands. Coordinated instantaneous settings would selectively.
provide even better protection while still The user only sets one threshold for each function.
maintaining selectivity with select feeder breakers. The trip unit automatically calculates the needed
To this capability one can add the RELT rightward shift (23%). Similarly for Instantaneous-
instantaneous setting that provides more sensitive Zone–Selective-Interlocking, the user only selects
and faster protection when needed. to enable it and selects the protection current
Users have the option of T-ZSI for short time and threshold. The trip unit automatically calculates the
instantaneous protection functions when needed restraint in time to maintain selectivity
programing T-ZSI and I-ZSI enabled trip units when needed. For short time-Zone-Selective-
(firmware version 08.00.26 and later). T-ZSI allows Interlocking the user must select both the
the short time pickups of two circuit breakers to unrestrained protective timing and the restrained
completely overlap while still maintaining backup timing band
A P P L I C AT I O N G U I D E 19
Figure 3.3 TCC for Two Circuit Breakers Implementing Short Time, X: X is a multiplier that may be applied in
Instantaneous, and Threshold ZSI front of any rating value to denote a
fraction of that rating. Example: The
Long Time Pickup may be set at 0.5X of
In.
1000.00 1000.00
Second:
Note:
ICU, or the ultimate breaking capacity
In case of a non-adjustable overload release, this value is equal to nominal
per IEC 60947-2, is the breaking capacity
current In.
that a breaker can safely interrupt, but
may not remain operational after
interrupting one time.
—
Section 3.
Entelliguard TU Trip Unit System
Long time protection Figure 3.4 Thermal Characteristic: Maximum and
The EntelliGuard TU offers two different shapes for Minimum Long Time Delay Bands for a
Long Time protection curves. Each type of curve is 1000A Long Time Pickup
available with 22 different time delays. The shapes
may be described as thermal type I2t
characteristics and fuse-shaped I4t lines.
The nominal Long Time pickup is computed from
the trip rating plug value (In) multiplied by the Long
Time pickup setting. Long Time pickup setting
multipliers are user settings and may range from
0.5 to 1.0 in increments of 0.05.
The actual Long Time pickup is 112% of the nominal
setting (Ir). 112% is to compensate for the Long
Time Pickup Tolerance of ±10% that is drawing as
“actual value/1+ tolerance.” For a nominal 1000A
Long Time pickup, the actual trip setting is 1120A,
drawn as a vertical band between 1120/1.1 and
1120/0.9, or 1018A and 1244A.
Table 3.2 Thermal Characteristic: Nominal Clearing and Commit Times for X Multipliers of Nominal Pickup
1.5 7.2 10 12 15
X=
Commit Clear Commit Clear Commit Clear Commit Clear Commit Clear
Min CB 4.25 8.04 0.139 0.239 0.072 0.137 0.050 0.104 0.038 0.080
C-2 12.7 24.1 0.417 0.656 0.215 0.352 0.149 0.253 0.095 0.172
C-3 25.5 48.1 0.83 1.28 0.430 0.674 0.298 0.476 0.190 0.315
C-4 34.0 64.1 1.11 1.70 0.57 0.89 0.40 0.62 0.254 0.410
C-5 51.0 96.2 1.67 2.53 0.86 1.32 0.60 0.92 0.38 0.60
C-6 67.9 128 2.22 3.4 1.15 1.75 0.79 1.22 0.51 0.79
C-7 84.9 160 2.78 4.2 1.43 2.18 0.99 1.52 0.63 0.98
C-8 102 192 3.33 5.0 1.72 2.61 1.19 1.81 0.76 1.17
C-9 119 224 3.89 5.9 2.01 3.03 1.39 2.11 0.89 1.36
C-10 136 256 4.44 6.7 2.29 3.46 1.59 2.41 1.02 1.55
C-11 153 289 5.00 7.5 2.58 3.89 1.79 2.71 1.14 1.74
C-12 170 321 5.56 8.4 2.87 4.32 1.99 3.00 1.27 1.93
C-13 204 385 6.67 10.0 3.44 5.18 2.38 3.60 1.52 2.31
C-14 238 449 7.78 11.7 4.01 6.04 2.78 4.19 1.78 2.69
C-15 272 513 8.89 13.4 4.59 6.90 3.18 4.79 2.03 3.07
C-16 306 577 10.0 15.0 5.16 7.76 3.58 5.38 2.29 3.45
C-17 340 641 11.1 16.7 5.73 8.61 3.97 5.98 2.54 3.83
C-18 374 705 12.2 18.4 6.30 9.47 4.37 6.57 2.79 4.21
C-19 408 769 13.3 20.0 6.88 10.3 4.77 7.17 3.05 4.59
C-20 442 833 14.4 21.7 7.45 11.2 5.17 7.76 3.30 4.97
C-21 476 898 15.6 23.4 8.02 12.0 5.56 8.36 3.56 5.35
Max CB 510 962 16.7 25.1 8.60 12.9 5.96 8.95 3.81 5.73
• Algorithm will not commit below 1.5 cycles, clearing time will not be less than 0.08sec.
• Maximum LT curve is 15XLTPU for Envelope 1 and 2 devices, 10XLTPU for Envelope 3 devices.
• Actual Long Time pickup is 112% of nominal pickup.
22 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 3.
Entelliguard TU Trip Unit System
Fuse-shaped steep long time overcurrent Figure 3.5 Fuse Characteristic: Maximum and
The optional steeper fuse characteristic is a Minimum Long Time Delay Bands for a
straight line K=I4t shape for application in systems 1000A Long Time Pickup
where fuses and circuit breakers are used together.
Twenty-two different time bands are available in
each trip unit.
Figure 3.5 displays minimum and maximum bands.
Table 3.3 displays the nominal time delays for each
of the 22 bands at various multiples of nominal
current pickup.
Drawn bands also include a 30 ms constant time,
which accounts for the slight widening evident in
the time current curve at the lower (right) end of
the faster (lower) time bands.
Table 3.3 Fuse Characteristic: Nominal Clearing and Commit Times for X Multipliers of Nominal Pickup
1.5 7.2 10 12 15
X=
Commit Clear Commit Clear Commit Clear Commit Clear Commit Clear
Min Fuse 0.675 1.51 0.025 0.080 0.025 0.080 0.025 0.080 0.025 0.080
F-2 1.96 4.37 0.025 0.080 0.025 0.080 0.025 0.080 0.025 0.080
F-3 3.56 7.95 0.025 0.080 0.025 0.080 0.025 0.080 0.025 0.080
F-4 5.57 12.4 0.025 0.080 0.025 0.080 0.025 0.080 0.025 0.080
F-5 8.07 18.0 0.025 0.080 0.025 0.080 0.025 0.080 0.025 0.080
F-6 11.2 25.0 0.025 0.080 0.025 0.080 0.025 0.080 0.025 0.080
F-7 15.1 33.7 0.028 0.080 0.025 0.080 0.025 0.080 0.025 0.080
F-8 20.0 44.7 0.038 0.084 0.025 0.080 0.025 0.080 0.025 0.080
F-9 26.1 58.3 0.049 0.110 0.025 0.080 0.025 0.080 0.025 0.080
F-10 33.8 75.4 0.064 0.142 0.025 0.080 0.025 0.080 0.025 0.080
F-11 43.3 96.7 0.082 0.182 0.025 0.080 0.025 0.080 0.025 0.080
F-12 55.3 123 0.104 0.232 0.028 0.080 0.025 0.080 0.025 0.080
F-13 70.2 157 0.132 0.295 0.036 0.080 0.025 0.080 0.025 0.080
F-14 88.9 198 0.167 0.374 0.045 0.100 0.025 0.080 0.025 0.080
F-15 112 251 0.211 0.472 0.057 0.127 0.027 0.080 0.025 0.080
F-16 141 316 0.266 0.595 0.072 0.160 0.035 0.080 0.025 0.080
F-17 178 397 0.335 0.748 0.090 0.201 0.043 0.097 0.025 0.080
F-18 224 499 0.421 0.940 0.113 0.252 0.055 0.122 0.025 0.080
F-19 280 626 0.528 1.179 0.142 0.317 0.068 0.153 0.028 0.080
F-20 352 785 0.663 1.479 0.178 0.397 0.086 0.192 0.035 0.080
F-21 441 984 0.830 1.853 0.223 0.498 0.108 0.240 0.044 0.098
Max Fuse 540 1204 1.017 2.269 0.273 0.610 0.132 0.294 0.054 0.120
• Algorithm will not commit below 1.5 cycles, clearing time will not be less than 0.08sec.
• Maximum LT curve is 15XLTPU for Envelope 1 and 2 devices, 10XLTPU for Envelope 3 devices.
• Actual Long Time pickup is 112% of nominal pickup.
—
Section 3.
Entelliguard TU Trip Unit System
An example of this may be seen in Figure 3.6 for the Figure 3.7 Short Time Transition
combination of Long Time Delay Band and Short
Time Delay Band shown in Figure 3.7, any Short
Time pickup setting larger than 6X will result in the
Long Time band intersecting with the horizontal
Short Time delay band rather the vertical Short
Time pickup.
Figure 3.6 Short Time Pickup Table 3.4 Short Time Delay Bands
Figure 3.8 Short Time Delay Figure 3.9 Short I 2t (In or Out)
Short Time I 2t Slopes The maximum (upper) Short Time I2t band may not
The EntelliGuard Trip Unit offers three different be used with the minimum Long Time thermal
Short Time I2t characteristics to allow optimized band. Use of the fuse shaped Long Time bands also
settings for selectivity and fast protection inhibits use of the Short Time I2t bands. Only the
whenever possible. When using the EntelliGuard definite Short Time pickup characteristic may be
Trip Unit in systems that also employ older GE MVT used with the fuse shaped Long Time curves.
trip units, the EntelliGuard Trip Unit’s maximum I2t
characteristic is equal to the Short Time I2t Ground fault protection
characteristic in the MVT trip. The EntelliGuard TU trip unit offers the ultimate in
The position of the I2t slopes varies with the Long Ground Fault protection. Each trip unit may be
Time pickup of the respective circuit breaker. The provided with the ability to accept a neutral sensor
intersection of the Short Time pickup and the Short signal and generate an internal Zero Sequence
Time delay band with the I2t slope varies with the phasor for Ground Fault protection. It may also be
Short Time pickup and time delay band. equipped with the ability to accept a Zero
The three positions for the Short Time It band are Sequence phasor signal from an external Zero
shown in Figure 3.9. The bands may be defined by Sequence CT or residual summation scheme using
the formula K = I2t, where K equals 18, 8 and 2 current transformers. Either Ground Fault method
times the nominal Long Time pickup squared. A may be used to provide Ground Fault trip or Ground
30msec fixed time is added to account for circuit Fault alarm. Four pole circuit breakers may also
breaker mechanical operation, clearing time and provide Ground Fault protection based on an
variance. Pickup tolerance is 10% of current. external Zero Sequence input signal or a residual
sum of all four internal sensors.
26 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 3.
Entelliguard TU Trip Unit System
Internal residual summation Ground fault time delay bands
The EntelliGuard TU trip unit uses internal air core Ground Fault Time Delay Bands used in the Entelli-
sensors for current sensing, and the signals are Guard G circuit breakers range from 42msec to
residually summed using advanced digital 942msec.
electronics. A neutral sensor may be located The available minimum settings per circuit breaker
remotely and connected to the trip unit. The type are shown in Table 3.6. The maximum Time
connection is limited to 10m (33ft). Due to the air Delay Band setting for all circuit breakers is
core sensor’s ability to handle a wide range of 0.940sec with a 1sec clear.
primary currents without distortion, Ground Fault
sensing is accurate for a wide range of phase and Table 3.6 Minimum Ground Fault Pickup and
current inputs. Clear Time
Setting EntelliGuard G
External zero sequence input Minimum pickup 0.042 sec
The EntelliGuard TU trip unit is able to accept input Minimum clear 0.097 sec
from an externally calculated Ground Fault current.
Maximum pick 0.940 sec
The Ground Fault current may be derived using a
Maximum clear 1.000 sec
single Zero Sequence CT or multiple phase CTs
connected in a residual summation scheme.
External CE marked Zero Sequence or ground Ground fault protection curves
return CTs are available for IEC applications, but are The EntelliGuard TU trip unit offers four different
not UL Listed. Phase CTs used for a summation shapes for the ground fault function:
connection are UL Listed. Applications for this • Definite time with adjustable time delay.
capability include sensing at the ground return • I2t slope with adjustable time delay.
connection for a transformer or generator as well • I4t slope (fuse shaped) with adjustable time
as application in multiple source grounded delay.
systems. • Selective double break I2t with adjustable time
delay.
Ground fault pickup settings The definite time and I2t characteristics provide
All UL 489 and UL 1066 circuit breakers are limited the traditional GF curve shapes. The I4t
to a maximum nominal pickup setting of 1200A per characteristic provides a shape more in line with
the UL standard. The minimum setting is 20% of downstream fuses. GE’s novel selective double
sensor size. The available maximum settings per break I2t characteristic provides the most selective
sensor may be seen in Table 3.5. setting possible while still meeting the applicable
UL and NEC standards. In many cases, an 800A
Table 3.5 Ground Fault Time Delay Bands circuit breaker may be used under a 1200A ground
Sensor Minimum Maximum fault curve selectively (Figure 3.10).
400 0.2 1.0
600 0.2 1.0
800 0.2 1.0
1200 0.2 1.0
1600 0.2 0.75
2000 0.2 0.60
2500 0.2 0.48
3000 0.2 0.40
3200 0.2 0.37
4000 0.2 0.30
5000 0.2 0.24
6000 0.2 0.20
A P P L I C AT I O N G U I D E 27
—
Section 3.
Entelliguard TU Trip Unit System
Table 3.7 Maximum Adjustable Instantaneous Pickup for EntelliGuard G Circuit Breakers with Normal or Extended Range
Option
“In” (Plug Withstand Rating
Rating, A) 42 50 65 85 100
Normal Extended Normal Extended Normal Extended Normal Extended Normal Extended
Range Range Range Range Range Range 1 Range Range 1 Range Range 1
150-2,000 15 15 15 30 15 30 15 30
2,200 15 15 28 15 30 15 30
2,400 15 15 25 15 30 15 30
2,500 15 15 24 15 30 15 30
3,000 15 15 20 15 26 15 30
3,200 15 19 15 25 15 29
3,600 15 17 15 22 15 26
4,000 15 15 15 20 15 23
5,000 15 16 15 19
6,000 13
The Adjustable Selective Instantaneous will clear a High set instantaneous overcurrent (HSIOC)
fault in three cycles when used in 60Hz or 50Hz The EntelliGuard TU trip unit’s HSIOC pickup is
applications. Zone Selective Interlocking (I-ZSI) similar to the fixed override used by other trip units
may be used with this Instantaneous function, and circuit breakers in the industry. In EntelliGuard
allowing several breakers with overlapping G, the HSIOC setting is changed automatically by
Instantaneous protection to be selective with each the trip unit if the normal adjustable Instantaneous
other. Because each circuit breaker is set to trip is turned off (LVPCB only). When adjustable
Instantaneously for faults within their respective Instantaneous setting is turned off, HSIOC nominal
zones of protection, fast protection and selectivity setting becomes 98% of the circuit breaker’s Short
are achieved simultaneously. Time withstand setting. In all other cases, in the
The special selective Instantaneous algorithm EntelliGuard G family of circuit breakers, the HSIOC
allows any circuit breaker above current limiting is set high enough to allow full selectivity up to the
devices to be set with a relatively low circuit breaker’s short time withstand rating.
Instantaneous pickup and still achieve significant For circuit breakers with an HSIOC trip function,
selectivity. The system may be able to provide the location of the HSIOC trip is shown by the line
Instantaneous protection for most faults, including that reaches the 0.01sec axis at the bottom of the
high impedance arcing fault, while maintaining TCC. The location of that line is shown in Section 5.:
significant levels of selectivity. Figure 3.12 and Catalog Numbering Guide, “Digit 5 – EntelliGuard G
Figure 3.13 later in this document demonstrate the Short Circuit and Interrupting Ratings." In many
performance of the Instantaneous ZSI capability. applications, the EntelliGuard G circuit breaker with
an EntelliGuard TU trip unit will be completely
selective up to the HSIOC pickup or the circuit
Table 3.8 Time Current Curves breaker’s full short circuit rating, even with the
Breaker Type TCC adjustable Instantaneous on.
EntelliGuard G: Selective Instantaneous & DES-094
RELT
Power CB: Selective Instantaneous & RELT DES-101
Power Break: Instantaneous DES-099
Power Break II: Selective Instantaneous DES-100
and HSIOC (Override)
A P P L I C AT I O N G U I D E 29
Making current release (mcr) When the EntelliGuard TU trip unit has the RELT
This form of Instantaneous protection is provided Instantaneous pickup enabled, the trip unit
on all EntelliGuard G circuit breakers. This function provides a feedback signal via an optically isolated
provides protection in case the circuit breaker is dry contact and serial communication. This
closed on an unusually high current. A circuit provides positive feedback that the trip unit has
breaker that experiences 15 times (15x) or more its received and reacted to the RELT Enable command.
plug rating is possibly closing in on a fault caused The EntelliGuard TU trip unit’s RELT capability
by incorrectly wired conductors, forgotten provides the ultimate in user flexibility for wiring
grounding cables or some other type of unusual and controlling an alternate Instantaneous setting
low impedance fault. for temporary use to reduce personnel hazard. The
Alternatively, it is closing on a very low impedance RELT Instantaneous pickup clears fault current in
arcing fault. In either case, there is a possibility 42msec or less at 60Hz.
that equipment may be damaged by the high fault RELT capability may be provided on a trip unit with
current or an arc flash hazard has been or without control power. If 24V is provided to the
inadvertently created. The MCR provides very fast RELT input, the trip unit will use the RELT
protection when the circuit breaker is closed and Instantaneous trip setting. However, without
for the first six cycles thereafter. After the six control power connected to the trip unit
cycles have elapsed, the MCR is turned off and the permanently, indication that the trip unit is in the
circuit breaker reverts to its adjustable RELT mode may not be reliably communicated. If
Instantaneous pickup and HSIOC if provided. The reliable communication that the trip unit is in the
MCR will clear fault current in 40msec or less. RELT mode is desired, it is suggested that the trip
unit be permanently connected to 24Vdc control
Reduced energy let-through (RELT) instantaneous power.
trip
The EntelliGuard TU trip unit provides an optional Reduced energy let-through switch wiring
second, user-adjustable, RELT Instantaneous trip, The RELT switch may be connected to a manually
which allows a circuit breaker to be temporarily set operated two-position switch, a remote sensor, or
to a more sensitive pickup to provide better both simultaneously. The EntelliGuard TU trip unit
protection, only when better protection is needed provides a feedback capability directly from the
and some selectivity may be sacrificed. The RELT trip so the user is able to verify that the signal was
pickup is adjustable from 1.5X to 15X of plug rating, received by the trip unit and the settings have
independently of the normal adjustable selective changed. Optionally, an indicating light may also be
Instantaneous. It may be set higher or lower than connected to the source of control power so the
the selective Instantaneous. user knows if control power is available to change
The user must make two entries at the trip unit: (1) the setting. The trip unit does not require its own
Pickup settings (1.5-15X of the plug) and (2) ON, control power to accept a RELT input and change
OFF or REMOTE. ON/OFF enables or disables the the Instantaneous trip pickup according to the user
pickup setting. REMOTE allows the RELT settings. However, if control power is available to
Instantaneous pickup to be enabled via application the trip unit, the feedback signal will function
of 24Vdc or Vac at the RELT input terminals or serial immediately, rather than when the trip unit
communications via the Modbus or Profibus becomes self-powered through its load current
communication port. The RELT pickup may be (Figure 3.11).
enabled via serial communication or remote 24V
signal, but both need to be indicating “OFF” for the
2
RELT, a.k.a.
RELT Instantaneous pickup to be disabled. The
maintenance RELT input command may be wired to a manual
switch, fullfills the
requirements of the
switch, automatic sensor or, via external logic, to
NEC, article 240.87. one or more signal sources.
30 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 3.
Entelliguard TU Trip Unit System
Figure 3.11 Integrated Switch and LED, Spring Re- Zone selective interlocking (ZSI)
turn from “Test” to “Off,” Latched in The EntelliGuard TU trip unit’s ZSI capability differs
“On” from that found in other circuit breaker trips in two
significant ways:
1. It allows independent and separate settings of
the unrestrained (in zone protection) and the
restrained (back up protection) bands.
2. It provides simultaneous and independent ZSI of
both the Short Time and Instantaneous
protection. This allows each circuit breaker to
zone interlock with upper tier circuit breakers
between ST band to ST band, Instantaneous to
Instantaneous, or Instantaneous to Short Time.
T-ZSI is available with GTU firmware version Figure 3.13 Zone Selective Interlocked CB, Upper
08.00.26 and above. CB Shown “Restrained”
Short Time and Ground Fault bands for zone
interlocked circuit breakers may be set to any band
available to the trip. Figure 3.12 shows two circuit
breakers set to protect at their unrestrained
settings. Figure 3.13 shows the same two circuit
breakers while a fault is detected below the lower
circuit breaker in the system and after a restraint
signal is received by the upper circuit breaker’s trip
unit. The upper circuit breaker’s Short Time band
has shifted from the user setting of 0.025sec to a
user set restrained band of 0.092sec. The
Instantaneous has shifted from the adjustable
selective Instantaneous band clearing in 0.050sec
to the fixed restrained band of 0.058sec, clearing in
0.113sec. This allows the lower circuit breaker to
clear faults within their zone of protection above
7,000A RMS and 11,000A RMS respectively, clearing
under 100msec, while maintaining full selectivity
for faults up to 85,000A.
Note:
For I-ZSI functionalities on EntelliGuard TU trip
units in ANSI and UL EntelliGuard G circuit breakers,
see publication DET-760.
Figure 3.12 Zone Selective Interlocked CB, Upper Universal trip rating plugs
CB Shown “Unrestrained” The EntelliGuard TU trip system is composed of
trip units and trip rating plugs along with the
sensors and wiring provided in the EntelliGuard G
circuit breaker to support the trip. Rating plugs are
used to lower the Long Time adjustment range of
the sensor provided in the circuit breaker.
The EntelliGuard TU trip rating plugs are unique in
that they can be used with multiple trip units and
circuit breakers within a specific sensor range,
rather than only with a single specific sensor. The
trip rating plug catalog number, shown in Figure
3.14, identifies the rating as well as the minimum
and maximum sensor rating the plug may be used
with. Table 3.9 lists the two-digit codes used
within the trip rating plug catalog numbers and the
sensor current ratings to which they are mapped.
Table 3.10 lists trip rating plugs available for each
sensor.
32 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 3.
Entelliguard TU Trip Unit System
Figure 3.14 EntelliGuard Trip Unit Rating Plug Table 3.10 Trip Rating Plug Specifications
Catalog Number
Trip Plug Catalog Plug May Be Used With
Number Rating Minimum Maximum
Sensor Sensor
GTP0060U0101 60A1 150A 3 150A3
GTP0080U0101 80A 1
150A 3 200A 4
GTP0100U0103 100A 2 150A 3 200A 4
GTP0125U0103 125A1 150A 3 200A 4
GTP0150U0404 150A 150AV 400A
GTP0200U0404 200A 200A 4 400A
GTP0225U0406 225A 400A 600A
GTP0250U0407 250A 400A 630A 5
GTP0300U0408 300A 400A 800A
GTP0350U0408 350A 400A 800A
GTP0400U0410 400A 400A 1000A
Table 3.9 Trip Rating Plug Codes GTP0450U0612 450A 600A 1200A
GTP0500U0613 500A 600A 1250A 5
Code Sensor Rating Code Sensor Rating GTP0600U0616 600A 600A 1600A
01 150A1 16 1600A GTP0700U0816 700A 800A 1600A
02 200A2 20 2000A GTP0750U0820 750A 800A 2000A
03 225A4 25 2500A GTP0800U0820 800A 800A 2000A
04 400A 30 3000A GTP0900U1020 900A 1000A 2000A
06 600A 32 3200A GTP1000U1025 1000A 1000A 2500A
07 630A3 40 4000A GTP1100U1225 1100A 1200A 2500A
08 800A 50 5000A GTP1200U1232 1200A 1200A 3200A
10 1000A 60 6000A GTP1500U1640 1500A 1600A 4000A
12 1200A 64 6400A3 GTP1600U1640 1600A 1600A 4000A
13 1250A3 GTP1900U2050 1900A 2000A 5000A
1 Sensor available in WavePro and AKR only. GTP2000U2050 2000A 2000A 5000A
2 Sensor available in Power Break only.
3 Sensor available in IEC listed circuit breaker only.
GTP2200U2550 2200A 2500A 5000A
4 Used on Conv Kits GTP2400U2564 2400A 2500A 6400A 5
GTP2500U2564 2500A 2500A 6400A 5
GTP3000U3064 3000A 3000A 6400A 5
GTP3200U3264 3200A 3200A 6400A 5
GTP3600U4064 3600A 4000A 6400A 5
GTP4000U4064 4000A 4000A 6400A 5
GTP4000K4040 6
4000A 4000A 4000A
GTP5000U5064 5000A 5000A 6400A 5
GTP6000U6064 6000A 6000A 6400AV
Table 3.11 EntelliGuard G Rating Plug Logic (UL 489, UL 1066, IEC)
—
Section 3.
Entelliguard TU Trip Unit System
Universal Spare Trip Unit Table 3.12 Universal Spare Trip Unit Options
EntelliGuard G circuit breakers will accept a (User-Selected)
Universal Spare Trip Unit. This unique trip unit may Feature # Option
be used in any EntelliGuard G circuit breaker Long Time 1 Standard (Circuit Breaker Curves)
regardless of frame size, sensor size, short circuit 2 Standard and Fuse Curves
rating or whether the circuit breaker is listed under
Instantaneous 1 Standard
UL 489, ANSI/UL 1066 or IEC 947 standards. Should
2 Extended Range1
any circuit breaker’s trip unit fail to operate for any
Ground Fault 2
1 None
reason, this one universal trip unit may be used as a
2 Standard (Internal GF)
replacement.
3 Ground Input
Once an EntelliGuard TU trip unit, including the
Arc Flash Protection 1 No RELT
Universal Spare Trip Unit, is associated with a
2 RELT
specific EntelliGuard G circuit breaker, it may only
Zone Selective 1 Short Time and Ground Fault
be used with that specific circuit breaker. If
Interlocking 2 Short Time, Ground Fault,
swapping between EntelliGuard G circuit breakers
Instantaneous, and Threshold
is required, a trip unit may only be swapped
Communications 1 None
between circuit breakers with equal sensor ratings,
2 Modbus
short circuit ratings and standard listing. Before
3 Profibus
the circuit breaker may be used with a swapped or
Metering 1 Standard (ammeter)
new trip unit, the trip unit must be mapped to the
2 Advanced (A, V, E and P)
circuit breaker.
3 Diagnostic (Advanced and WFC)
The Re-mapping procedure is done by Pressing
simultaneously the "Right", "Left", and "Up" Arrow 1. Available in ANSI/UL1066 CB only.
2. Mains and ties in solidly grounded multiple source substations will
all at the same time (should be able to do with one usually require ground input type ground fault protection. Feeders
hand). "BIM OK" will be flashing in the upper left will use standard internal ground fault protection.
Table 3.13 Relay Functions Available in EntelliGuard G Circuit Breakers with EntelliGuard TU Trip Units
—
Section 3.
Entelliguard TU Trip Unit System
Current unbalance relay Power-reversal relay
This function compares the true RMS current in the This function measures the direction of power flow
highest or lowest phase with the average of all through the breaker and initiates a trip if a suffi-
three phases and initiates a trip if the difference cient magnitude of reverse power is detected (Ta-
exceeds the set point (Table 3.15). ble 3.18).
be set above the ON threshold. If the highest Outputs for EntelliGuard G Circuit Breakers
measured phase current goes above the current The number of outputs available varies by breaker.
alarm 1 or current alarm 2 ON set-point, and then The EntelliGuard G circuit breaker has three. These
remains above the set-point for more than 60sec, outputs are relay contact outputs to secondary
the output will close if assigned to either of these disconnect. Each output can be configured per
alarms. If the current falls below the current alarm 1 Table 3.20.
or current alarm 2 set-point for more than 60sec,
the output, if assigned to the current alarm, will
Table 3.20 Output Configuration
open. This is a definite time function with a 60sec
delay and a 60sec cool down period. Both periods Function Group #Summary Description
Note:
When RELT is Optioned, Input1 is dedicated to
RELT. Contacts are rated for 30 VDC/25 VAC MAX, 1
Amp.
38 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 3.
Entelliguard TU Trip Unit System
Circuit breaker self-timing and continuously monitor if the circuit breaker
Trip units implementing software revision 08.00.26 mechanism is showing any signs of slowing due to
and newer (post September 2013) will include wear, lack of lubrication, or other conditions. The
standard tripping mechanism self-timing. This time recorded does not include protective
feature will consist of 8 Modbus registers with algorithm time, or current interruption (arcing)
values. One register will be populated at the time. It includes a proxy for the mechanism
factory where the trip and circuit breaker are mechanical movement time measured from the
combined and the next two registers, when the time the operating solenoid receives a trip signal to
breaker is tripped with auxiliary power. The other the time the contact arms have finished moving
five Modbus registers will include the same and fully opened the contact tips. The time
operating timing for the last 5 tripping operations. measured should not be considered an exact
When an 8th operation is measured, the first of the representation for the operating time, but should
5 registers with tripping operation time be considered as a proxy for the operation time
information will be refreshed in a First-In-First-Out that also includes additional time for the signal
(FIFO) fashion. The first three Modbus registers will switch and driving mechanism for the switch.
remain as benchmark times for comparison
purposes. Entelliguard trip unit performance characteristics
A Power Management Control System (PMCS) can Table 3.21 provides an overview of the trip unit
pull the information from these Modbus registers features, characteristics, specifications and
accuracy.
—
Section 3.
Entelliguard TU Trip Unit System
All Settings can be performed via the front of the
trip unit. Free setup software is downloadable
from geindustrial.com. Download and upload trip
unit settings. Ability to download and view the
waveform captured by the trip unit. Also has the
ability to store settings in an Offline file and then
compare it to the current settings. Requires the
EntelliGuard TU Test Kit, GTUTK20.
Table 3.22 Metering Data Startup Levels for breaker with EntelliGuard Trip Unit with 24 VDC
Parameter Phase Unit Startup Level
Current Phase A,B,C, neutral A > 3 % Rating Plug Current
Voltage Phase L1,L2,L3 V > 15 V for all Voltage Ranges
Real Power Phase L1,L2,L3 and total kW > 7% Rating Plug Current or > 15 Volts
Reactive Power Phase L1,L2,L3 and total kVAR > 7% Rating Plug Current or > 15 Volts
Apparent Power Phase L1,L2,L3 and total kVA > 7% Rating Plug Current or > 15 Volts
Total Auto-ranging from 0.00 kWH to > 7% Rating Plug Current or > 15 Volts
Peak Demand Power
999mWH
Phase A,B,C and total Auto-ranging from 0.00 kWH to > 7% Rating Plug Current or > 15 Volts
Energy
999mWH
Frequency Hz > 10% of Line Voltage
Power Factor % > 7% Rating Plug Current or > 15 Volts
Note: Metering Data for breaker with EntelliGuard Trip Unit without 24 VDC requires 20% sensor current and then all metering will be available
Note: For selec ted sensor per formance charac ter istics see
publicat ions DES - 0 9 0, DES - 0 91 , DES - 0 92, DES - 0 93 , DES - 0 9 4
A P P L I C AT I O N G U I D E 41
—
Section 4.
Accessories
A wide range of optional accessories are Figure 4.1 Accessory Mounting
interchangeable across all EntelliGuard G power
circuit breakers, regardless of nominal rating or
envelope/frame size. As shown in Figure 4.1, each
accessory incorporates easy-fit design features for
quick installation, either at the factory or in the
field.
Note:
Replacement accessories have an “R” at the end of
the catalog number as shown in the tables. All coils
are conformal coated for increased reliability in
humid/damp environments
—
Section 4.
Accessories
Table 4.1 Motor Operators
Envelope Power Nominal Control IEC Range (85% ANSI Range UL Range Cat No.
Consumption Voltage to 110%) (85% to 110%)
24Vdc/30Vdc 20.4V to 26.4V 20.4V to 26.4V GM01024DR
48Vdc 40.8V to 52.87V 38V to 56V 40.8V to 52.87V GM01048DR
60Vdc 51V to 66V 51V to 66V GM01060DR
DC – 300W
72Vdc 61.2V to 79.2V 61.2V to 79.2V GM01072DR
110Vdc/130Vdc 106.25V to 137.5V 100V to 140V 106.25V to 137.5V GM01110DR
1
250Vdc 212.5V to 275V 200V to 280V 212.5V to 275V GM01250DR
48Vac 40.8V to 52.87V 40.8V to 52.87V GM01048AR
120Vac 102V to 132V 104V to 127V 102V to 132V GM01120AR
AC – 350VA
240Vac 204V to 264V 208V to 254V 204V to 264V GM01240AR
277Vac 235.5V to 304.7V 235.5V to 304.7V GM01277AR
24Vdc/30Vdc 20.4V to 26.4V 20.4V to 26.4V GM02024DR
48Vdc 40.8V to 52.87V 38V to 56V 40.8V to 52.87V GM02048DR
60Vdc 51V to 66V 51V to 66V GM02060DR
DC – 480W
72Vdc 61.2V to 79.2V 61.2V to 79.2V GM02072DR
110Vdc/130Vdc 106.25V to 137.5V 100V to 140V 106.25V to 137.5V GM02110DR
2, 2.5, 3
250Vdc 212.5V to 275V 200V to 280V 212.5V to 275V GM02250DR
48Vac 40.8V to 52.87V 40.8V to 52.87V GM02048AR
120Vac 102V to 132V 104V to 127V 102V to 132V GM02120AR
AC – 560VA
240Vac 204V to 264V 208V to 254V 204V to 264V GM02240AR
277Vac 235.5V to 304.7V 235.5V to 304.7V GM02277AR
• Spring charge contact is power rated only, as shown below. • Spring charge time = 3sec max.
• Recommended fuse amps: contact factory.
AC Ratings DC Ratings • Duty cycle = 2/min.
• Envelope 1 motors: running VA ~ 300VA; inrush = 2 to 3 times.
Voltage Amps Voltage Amps • Envelope 2 and 3 motors: running VA ~ 450VA; inrush = 2 to 3 times.
110-130V AC21-15A 24V DC21-15A
AC23-10A 110-130V DC21-10A
220-240V AC21-10A 250V DC21-5A
AC23-5A
A P P L I C AT I O N G U I D E 43
Table 4.2 Closing Coil Characteristics Table 4.3 Extended Range Shunt Trip for UL
Type Power Nominal Control Catalog Ground Fault and ANSI DC Rating
Consumption Voltage Number Applications
24V DC21-15A Catalog Number Nominal Control Rating
24Vdc GCCN024DR Voltage
DC: 350W, GSST024DR 24Vdc Momentary
48Vac/dc GCCN048R
20 W (sealed)
Closing 60 to 72Vdc GCCN060DR 110Vdc – 130Vdc
GSST120R Momentary
Coil AC: 350W 110Vac – 130Vac
110-130 Vac/dc GCCN120R
(inrush), 220Vdc – 240Vac
208Vac GCCN208AR GSST240R Momentary
20W (sealed) 220Vac – 240Vac
220Vdc/240Vac GCCN240R GSTG024DR 24Vdc Continuous
250Vdc/277Vac GCCN277R GSTG048R 48Vac/dc Continuous
DC: 350W, 24Vdc GCCC024DR GSTG072R 70Vdc - 72Vdc Continuous
Command
20W (sealed) 48Vac/dc GCCC048R 110Vdc – 125Vdc/
Operated GSTG120R Continuous
AC: 350W 120Vac – 125Vac
Closing 60 to 72Vdc GCCC060DR
(inrush),
Coil 110-130 Vac/dc GCCC120R GSTG208AR 208 Vac Continuous
20W (sealed)
208Vac GCCC208AR GSTG240R 220Vdc/240Vac Continuous
GSTG250DR 250Vdc/277Vac Continuous
• Duty cycle = 2/min.
• Closing coil inrush = 350VA. • Pickup range = 55%-110%
• DC signal to contact make: • Duty cycle = 2/min.
• Envelopes 1 & 2 – 45 msec. • Inrush = 480VA (ac), 480W (dc)
• Envelope 3 – 80 msec. • Holding = 60VA (ac), 50W (dc).
• Momentary rated shunt trip requires wiring one or more normally
open (NO) breaker aux contacts in series with the accessory to
Table 4.2.1 Command Shunt Releases avoid coil damage.
• DC signal to contacts parting – 20 msec.
• Potential arcing time – 16 msec.
Nominal Control Voltage Catalog Number
Factory Fitted: Field Installable:
24V DC - GCST024D 24V DC - GCST024DR Status indication switch (coil signaling contact)
30V DC - GCST030D 30V DC - GCST030DR A plug-in module is available to provide status
48V AC-DC - GCST048 48V AC-DC - GCST048R indication via the secondary disconnects and trip
120V AC-DC - GCST120 120V AC-DC - GCST120R unit. Coil Signaling Contacts are available for
240V AC-DC - GCST240 240V AC-DC - GCST240R closing coils, shunt trips and undervoltage releases
277V AC-DC - GCST277 277V AC-DC - GCST277R (Table 4.4). Contact is mounted on top of the
Accessory Device. One of the low-signal (Hi-Fi)
contacts is always wired to the trip unit.
Command operation module
This module energizes the closing coil to cause the
breaker to close whenever control power is applied
Table 4.4 Coil Signaling Contact Module
to the accessory and when commanded from the
breaker trip unit or breaker front panel push button Type and
Rating Cat. No.
(electrical closing). Configuration
120Vac 6A
AC
250Vac 6A
Shunt trip 1 Power rated + 125Vac 0.5A
Energizing the shunt trip (ST), via local or remote 1 Low signal (Hi-Fi) DC GCSP1R
(1NO contact each) 250Vdc 0.25A
input, will instantaneously activate the circuit
AC 125Vac 0.1A
breaker mechanism, ensuring a rapid open
DC 30Vdc 0.1A
operation. The shunt trip is continuously rated and 2 Low signal (Hi-Fi)
does not require an auxiliary switch in series with AC 125Vac 0.1A GCSP2R
(1NO contact each)
the coil. The shunt trip is a straightforward, field
• DC signal to switch change:
installable accessory available in wide range of • Shunt trip & close coil – 12 msec
voltages. See Table 4.3. • UVR – 60 msec
44 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 4.
Accessories
Undervoltage release (UVR) with fixed time delay Time delay module (TDM) for uvr (externally
The UVR instantaneously activates the circuit mounted)
breaker trip mechanism when the source voltage The de-energized operation of the Undervoltage
drops below the low voltage threshold. The UVR is release can be delayed. This optional, externally
also a simple, field installable device. mounted module has an adjustable time delay of 0
sec to 3 sec. The device can be implemented to
Note: prevent undesired breaker tripping due to
This accessory acts as a permissive; it is a no- momentary voltage interruptions and is connected
voltage/no-close device. The circuit breaker cannot in series with the Undervoltage release. The time
be closed (manually or electrically) unless the delay is in addition to the time delay from the
undervoltage release coil is energized above the breaker mounted UVR accessory. The time delay
required threshold. The undervoltage release with module starts counting at 50% of rated voltage
fixed time delay is specifically intended for (Figure 4.2 and Table 4.6).
applications where a delay period (ride-through) is
required due to potential voltage events. The Figure 4.2 Time Delay Module
delays are 50msec when system voltage drops to
50% and 20msec when system voltage drops below
50% (Table 4.5).
—
Section 4.
Accessories
Table 4.11 Power Rated (3NO/3NC) (Ref Drawing 10099230)
Normally Open Normally Closed
Secondary Secondary
Switch Contact Connector Switch Contact Connector
Disconnect Disconnect
1 A25 3 A19
2 A24 4 A18
5 A23 7 A17
PL1 PL2 Power Rated
6 A22 8 A16
9 A21 11 A15
10 A20 12 A14
Table 4.13 Power Rated (3NO/3NC) Low Signal (Hi-Fi) (2NO/2NC) (Ref Drawing 10099232)
Normally Open Normally Closed
Secondary Secondary
Switch Contact Connector Switch Contact Connector
Disconnect Disconnect
1 A25 3 A19
2 A24 4 A18
5 A23 7 A17
PL3 PL6 Power Rated
6 A22 8 A16
9 A21 11 A15
10 A20 12 A14
13 B26 15 B13
PL1 PL4
14 B25 16 B12
Hi-Fi
17 B24 19 B11
PL2 PL5
18 B23 B10
A P P L I C AT I O N G U I D E 47
Table 4.14 Power Rated (4NO/4NC) + Low Signal (Hi-Fi) (4NO/4NC) (Ref Drawing 10099234)
Normally Open Normally Closed
Secondary Secondary
Switch Contact Connector Switch Contact Connector
Disconnect Disconnect
1 A25 3 A19
2 A24 4 A18
5 A23 7 A17
PL1 PL5
6 A22 8 A16
Power Rated
9 A21 11 A15
10 A20 12 A14
13 B26 15 B13
PL2 PL6
14 B25 16 B12
17 B24 19 B11
PL4 PL8
18 B23 20 B10
21 B22 23 B9
22 B21 24 B8
Hi-Fi
25 B20 27 B7
PL3 PL7
26 B19 28 B6
29 B18 31 B5
30 B17 32 B4
Circuit breaker - key interlock facility Table 4.15 Key Interlocks and Door Interlocks
This option supplies factory-installed or field Catalog Number
installable key interlock mounting provisions Description Breaker Cassette
(baseplates and mechanism) on the front of the Mounted1 Mounted2
breaker fascia. Key interlocks ensure that a circuit Mounting Provision for Kirk Locks GBKRKR GCKRKR
breaker cannot be closed unless the dedicated key Cylinder lock and keys for Kirk GKRK —3
has been inserted and secured within the lock. Mounting Provision for Ronis Locks GBRONR GCRONR
Circuit breakers accept ready-to-fit interlocking Cylinder lock and keys for Ronis GRON GRON
device kits such as Castell, Ronis, Kirk and Profalux Mounting Provision for Castell Locks GBCAS
for installation between related, separate circuit Cylinder lock and keys for Castell GCAS
breakers. Mounting Provision for Profalux Locks GBPRO GCPRO
Cylinder lock and keys for Profalux GPRO GPRO
Key Interlock Conversion Kit4 GCCONV
Door interlock (left side) GLHDR
Door interlock (right side) GRHDR
—
Section 4.
Accessories
Figure 4.3 Breaker-Mounted Key Interlock Table 4.17 Carriage Position Switch Ratings
(Common NO/NC Contact
Configuration)
Ratings
AC 120Vac 6A
250Vac 6A
DC 125Vac 0.5A
0.25A
Cassette/substructure
The drawout mechanism allows the breaker to be
racked in four distinct positions (CONNECTED,
A Key interlock mounting locations
TEST, DISCONNECTED, WITHDRAWN).
Type A
1 from 2 interlock
2 cable configuration
Interlocking between two circuit breakers
Type B
1 from 3 interlock
6 cable configuration
Interlocking among three circuit breakers
Available on request.
Only 1 of 3 breakers can be closed.
Type C
2 from 3 interlock
6 cable configuration
Interlocking among three circuit breakers
Available on request.
• Any two from three breakers can be closed.
• Any one from three breakers can be closed.
• Two breakers must be closed to prevent the third
breaker from closing
Type D
1 from 3 interlock
4 cable configuration
Interlocking between three circuit breakers
—
Section 4.
Accessories
Bell alarm with lockout Secondary disconnects (factory-installed/field
The Bell Alarm provides remote indication that the installable)
circuit breaker has opened because of an electrical Inputs and outputs to the circuit breaker are wired
fault. The Lockout feature is integral to the trip through secondary disconnects located on either
unit. When a Bell Alarm is supplied with the breaker, the top or the side (Envelope 1 only) of the breaker.
the Trip Unit dial is set and locked to the manual The plug-style secondary disconnects engage
position. In order to re-close the breaker, the mating disconnects in the breaker cubicle when the
Lockout button must be pushed in/reset on the breaker is in the TEST or CONNECT position. Up to
Trip Unit 1-Form C contact (Table 4.21 and Table 78 points are available so that all breaker
4.23). accessories can be wired to dedicated disconnect
See “Bell Alarm Contact” on page 8 for more detail. points (Table 4.26 through Table 4.31).
A kit is also available for converting to automatic Side mounted fixed breakers and drawout breakers
lockout reset (see Table 4.22). and cassettes that come with breaker block B are
always mounted at the factory. Top mounted fixed
Table 4.21 Bell Alarm Switches breakers and drawout breakers come with the
Switch Configuration Cat. No. block B mounted on the breaker, if required by
1 Form C, Power Rated GBAT1R accessories selected. For drawout breaker
1 Form C, Signal Rated GBATS1R
cassettes, block B must be ordered separately,
2 Form C, Power Rated GBAT2R
catalog number GSDWCR
Charging spring status indicator Table 4.26 Secondary Disconnect Block Locations
Factory-installed on the motor, this auxiliary switch Top Disconnect
indicates that the circuit breaker is charged and is Block B Block A
standard with the spring-charging motor (Table
120Vac 6A
Block A
4.24).
Side Disconnect
Block B 6A
Table 4.24 Spring Charged Contact (1 NO)
Ratings Catalog Number 125Vdc 0.5A
Block B
120Vac 6A
AC 250Vdc 0.25A
250Vac 6A
GSCC1R
125Vdc 0.5A
DC
250Vdc 0.25A
A P P L I C AT I O N G U I D E 51
Table 4.27 Wiring Schematic for Block-A (Three Layer Secondary Disconnect with Basic GTU and Basic Accessories)
A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13
Spr NO/ Spr NO/
Motor Motor ST1 ST1 UV1 UV1 CC COM CC IMM CC CMD ST2/ UV2 ST2/ UV2
RTC NO RTC NO
Max. Current (I) 14.8A 14.8A 10A 10A 1.9A 1.9A 1.9A 1.9A 1.9A 1.9A 1.9A 1.9A 1.9A
440V 440V 240V 240V 440V 440V 440V 440V 440V 440V 440V 440V 440V
Max. Voltage (V) A14 A15 A16 A17 A18 A19 A20 A21 A22 A23 A24 A25 A26
NC3 NC3 NC2 NC2 NC1 NC1 NO3 NO3 NO2 NO2 NO1 NO1
Max. Current (I) 15A 15A 15A 15A 15A 15A 15A 15A 15A 15A 1A 15A
440V 440V 440V 440V 440V 440V 440V 440V 440V 440V 440V 440V
Max. Voltage (V) A27 A28 A29 A30 A31 A32 A33 A34 A35 A36 A37 A38 A39
O/P1a O/P1b O/P2a O/P2b 24 V+ 24 V- BA NC BA NO BA COM N-RC- N-RC+ Eleg-CT Eleg-CT
Max. Current (I) 1A 1A 1A 1A <500mA <500mA 10A 10A 10A <50mA <50mA 5A 5A
30Vdc/ 30Vdc/ 30Vdc/ 30Vdc/
Max. Voltage (V) 30V 30V 240V 240V 240V 480mV 480mV 2V 2V
25Vac 25Vac 25Vac 25Vac
Table 4.28 Wiring Schematic for Block-B (Three Layer Secondary Disconnect to be Added for GTU with Full I/O and Additional
Accessory Signals)
B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B13
I/P ST1 NO/ ST1 COM/ UV1 NO/ UV1 COM/
INPUT1 INPUT2 NC6 NC6 NC5 NC5 NC4 NC4
COM NC8 NC8 NC7 NC7
Max. Current (I) <50mA <50mA <50mA 10A/15A 10A/15A 10A/15A 10A/15A 15A 15A 15A 15A 15A 15A
30Vdc/ 30Vdc/ 30Vdc/ 240V/ 240V/ 240V/ 240V/
440V 440V 440V 440V 440V 440V
25Vac 25Vac 25Vac 440V 440V 440V 440V
B14 B15 B16 B17 B18 B19 B20 B21 B22 B23 B24 B25 B26
Max. Voltage (V)
ST2 NO/ ST2 COM/
CC NO/ CC COM/
BA2 NC BA2 NO BA2 COM UV2 NO/ UV2 COM/ NO6 NO6 NO5 NO5 NO4 NO4
NO8 NO8
NO7 NO7
10A/ 10A/ 10A/ 10A/
Max. Current (I) <50mA <500mA - 15A 15A 15A 15A 15A 15 A
15A 15A 15A 15A
240V/ 240V/ 240V/ 240V/
5V 0.1V - 440V 440V 440V 440V 440V 440V
440V 440V 440V 440V
B27 B28 B29 B30 B31 B32 B33 B34 B35 B36 B37 B38 B39
Max. Voltage (V)
ZSI ZSI ZSI ZSI ISO 5V GND
TX EN 1 RX TX Volt-A Volt-B Volt-C
out+ out+ out+ out+ GND ISO Volt-IN
Max. Current (I) <50mA <50mA <50mA <50mA <500mA <500 mA <50mA <50mA <50mA <500mA <50mA <50mA <50mA
Max. Voltage (V) 28Vdc 28Vdc 30Vdc 30Vdc 0.1V 5V 5V 5V 5V 0.1V 1.76V 1.76V 1.76V
Table 4.29 Wiring Schematic for Block-C – Internal to the breaker, not used by customer (Two Layer Intermediate Secondary
Disconnect at the Top for the Side Mounted Secondary Disconnect)
C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 C12 C13 C14 C15 C16 C17 C18 C19 C20 C21
ST2/ ST2/
BA BA BA ST1 ST1 UV1 UV1 CC CC
UV2 UV2 NO5 NO5 NO4 NO4 NC3 NC3 NC2 NC2 NC1 NC1
NC NO COM NO COM NO COM NO COM
NO COM
C22 C23 C24 C25 C26 C27 C28 C29 C30 C31 C32 C33 C34 C35 C36 C37 C38 C39 C40 C41 C42
Spr Spr
NO/ NO/ CC CC CC ST2/ ST2/
ST1 ST1 UV1 UV1 NC5 NC5 NC4 NC4 NO3 NO3 NO2 NO2 NO1 NO1
RTC RTC COM IMM CMD UV2 UV2
NO NO
52 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 4.
Accessories
Table 4.30 Wiring Schematic Nomenclature Definitions
Pin Nomenclature Description Pin Nomenclature Description
A1 Motor B14
power input to motor operator
A2 Motor B15
A3 SPR NO/RTC NO spring charge status contact/ ready to
B16
A4 SPR NO/RTC NO close signaling contact
A5 ST1 B17 CC NO/NO8 closing coil signaling contact/normally
power input to shunt trip 1 B18 CC COM/NO8 open contact 8
A6 ST1
A7 UV1 ST2 NO/UV2
undervoltage release 1 B19 shunt trip 2 signaling contact/
A8 UV1 NO/NO7
undervoltage release 2 signaling contact/
ST2 COM/UV2
closing coil neutral wire-common B20 normally open contact 7
A9 CC COM COM/NO7
(CC or CCC)
B21 NO6
closing coil (CC), continuous control normally open contact 6
A10 CC IMM B22 NO6
power (CCC)
B23 NO5
A11 CC CMD closing coil close signal (CCC) normally open contact 5
B24 NO5
A12 ST2/UV2 power input to shunt trip 2/ undervoltage B25 NO4
A13 ST2/UV2 release 2 normally open contact 4
B26 NO4
A14 NC3 B27 ZSI out+
normally closed contact 3 zone selective interlock output
A15 NC3 B28 ZSI out-
A16 NC2 B29 ZSI in+
normally closed contact 2 zone selective interlock input
A17 NC2 B30 ZSI in-
A18 NC1 B31 ISO GND
normally closed contact 1
A19 NC1 B32 5V Iso
A20 NO3 B33 TX EN 1 trip unit communication
normally open contact 3
A21 NO3 B34 RX
A22 NO2 B35 TX
normally open contact 2
A23 NO2 B36 Voltage Input GND ground point for voltage input to trip unit
A24 NO1 B37 Volt-A
normally open contact 1
A25 NO1 B38 Volt-B system phase voltage signals
A26 B39 Volt-C
A27 O/P1a relay output 1 from trip unit
A28 O/P1b relay output 1 from trip unit
A29 O/P2a relay output 2 from trip unit
A30 O/P2b relay output 2 from trip unit
Ground fault
A31 24 V+
auxiliary power supply to trip unit The EntelliGuard TU Trip Unit provides a non-core CT input for
A32 24 V-
A33 BA NC zero sequence or residual summation current. The expected
A34 BA NO bell alarm switch ratio is 1A = 100%.
A35 BA COM
A36 N-RC-
neutral Rogowski coil Neutral rogowski
A37 N-RC+
A38 Eleg-CT
The Neutral Rogoswki CTs are used to measure the Neutral
earth leg CT (multi-source ground fault)
A39 Eleg-CT Current and is required when Internal Ground Fault is selected
B1 Input 1 relay input to trip unit on the trip unit. There are two types available:
B2 Input 2 relay input to trip unit 1. Encased with Terminal Screws: The Rogowski coil is
B3 I/P COM relay input to trip unit encased with two terminal screws. No additional mounting
B4 ST1 NO/NC8 shunt trip 1 signaling contact/normally hardware is required as the encasing is molded to the
B5 ST1 COM/NC8 open contact 8 mounting dimensions (Table 4.31)
B6 UV1 NO/NC7 undervoltage release 1 signaling contact/ 2. Loose Rogowski Coil with separate mounting hardware:
B7 UV1 COM/NC7 normally closed contact 7
The coil and mounting hardware are separate.
B8 NC6
normally closed contact 6 The coil comes with the two wire leads for connection to a
B9 NC6
B10 NC5 terminal block. See Table 4.31a.
normally closed contact 5
B11 NC5 3. Large Window Rogowski CTs: The Rogowski coil provides a
B12 NC4 larger window (6.57 x 2.56 inches) for larger busbars. See
normally closed contact 4
B13 NC4
Table 4-31b.
A P P L I C AT I O N G U I D E 53
Table 4.31 Neutral Rogowski CTs (Encased with Table 4.31b Large Window Rogowski
Terminal Screws)
Current Rating Cat. No.
Envelope Current Rating Cat. No. 1000A - G101 NRC
400 A G04HNRCE 1200/1250A G131NRC
630 A G07HNRCE 2000A G201NRC
800 A G08HNRCE 2500A G251NRC
1
1200/1250 A G13HNRCE 3000/3200A G321NRC
1600 A G16HNRCE 4000A G401NRC
2000 A G20HNRCE 5000A G501NRC
400 A G04MNRCE 6000A G601NRC
630 A G07MNRCE
800 A G08MNRCE
1200/1250 A G13MNRCE Sealed door panel escutcheon
2 An optional complete IP54 front door panel is
1600 A G16MNRCE
2000 A G20MNRCE available when a higher degree of protection is
2500 A G25MNRCE
needed (Table 4.32).
3000/3200 A G32MNRCE
Mechanical operations counter
3000/3200 A (1600 A x 2) G32LNRCE
Used with either manual or motor charged circuit
4000 A (2000 A x 2) G40LNRCE
3 breakers, the counter provides an accurate record
5000 A (2500 A x 2) G50LNRCE
of the cumulative number of complete breaker
6000/6400 A (3200 A x 2) G64LNRCE
closing operations (Table 4.32).
Table 4.31a Neutral Rogowski CTs (Loose Ro- Table 4.32 Miscellaneous Accessories
gowski Coil and mounting hardware)
Description Cat. No.
Envelope Current Rating Cat. No. Racking handles:
400 A G04HNRC OEM breakers GRHNR
AKD-20 breakers ENTGRH
630 A G07HNRC
IP54 Door Escutcheon, GGDEFD
800 A G08HNRC Fixed and Drawout
1
1200/1250 A G13HNRC Mechanical Operations Counter GMCNR
1600 A G16HNRC ACB Lifting Truck GE-1000
2000 A G20HNRC Breaker lifting Beams
400 A G04MNRC for 3P Envelope 1 and 2 GLD3F12
for 3P Envelope 3 GLD3F3
630 A G07MNRC for 4P Envelope 1 and 2 GLD4F12
800 A G08MNRC for 4P Envelope 3 GLD4F3
1200/1250 A G13MNRC Door Flange – Fixed Breaker GDPRF
2 Door Flange – Withdrawable Breaker GDPRW
1600 A G16MNRC
2000 A G20MNRC Contact Wear Indicator GCNTW
3000/3200 A G32MNRC
3000/3200 A (1600 A x 2) G32LNRC
4000 A (2000 A x 2) G40LNRC
3
5000 A (2000 A x 2) G50LNRC
6000/6400 A (3200 A x 2) G64LNRC
54 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 4.
Accessories
Door interlocks
See Table 4.33.
3 Pole GBB216TBBC3 6
Up to 1600 A
4 Pole GBB216TBBC4 8
3 Pole GBB220TBBC3 6
2000 A
4 Pole GBB220TBBC4 8
3 Pole GBB216TBBC3 6
2 Up to 1600 A
4 Pole GBB216TBBC4 8
A P P L I C AT I O N G U I D E 55
3 Pole GBB220TBBC3 6
2000 A
4 Pole GBB220TBBC4 8
3 Pole GBB230TBBC3 6
2500A &
2 3000A UL GBB230TBBC4 8
3 Pole
GBB216TBBC3 6
(Bottom Side)
3 Pole
3200A ANSI (Bottom Side) GBB232TBC3
4 Pole
(Top Side) GBB216TBBC4 8
56 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 4.
Accessories
Envelope Size Description Type Catalog Number Drawing Qty/kit
4 Pole
2 GBB232BBC4 4
(Bottom Side)
3 Pole
2.5 Up to 4000A GBBN40TBC3 6
(Top/Bottom)
3 Pole
(Top Side,
2 per pole) GBB360TBC3 6
3 Pole
GBB360BBC3 6
(Bottom Side)
3000A – 6000A
3
4 Pole
(Top Side, GBB360TBC4 8
2 per pole)
4 Pole
(Bottom Side, GBB360BBC4 8
2 per pole)
A P P L I C AT I O N G U I D E 57
3 Pole
GBB112TBB3 3
(Top Side)
3 Pole
GBB112BBB3 3
(Bottom Side)
Up to 1200 A – 5th
character “S” only
4-Pole
GBB112TBB4 4
(Top Side)
1
4-Pole
GBB112BBB4 4
(Bottom Side)
3 Pole GBB116TBB3 6
Up to 1600 A
4 Pole GBB116TBB4 8
3 Pole GBB120TBB3 6
1 2000 A
4 Pole GBB120TBB4 8
—
Section 4.
Accessories
Envelope Size Description Type Catalog Number Drawing Qty/kit
4 Pole GBB220TBB4 8
3 Pole GBB230TBB3 6
3000A UL
4-Pole GBB230TBB4 8
3 Pole
2 GBB232TBB3 3
(Top Side)
3 Pole
(Bottom Side) GBB232BBB3 3
3200A ANSI
4 Pole
GBB232TBB4 4
(Top/Bottom)
4 Pole
(Bottom Side) GBB232BBB4 4
3 Pole
2.5 Up to 4000 A (Top/Bottom) GBBN40TBB3 6
A P P L I C AT I O N G U I D E 59
3 Pole GBB340TBB3 6
Up to 4000 A
3 Pole GBB340TBB4 8
3 Pole
(Top Side)
GBB360TBB3 3
3 Pole
GBB360BBB3 3
(Bottom Side)
6000A
4 Pole
GBB360TBB4 4
(Top Side)
4 Pole
GBB360BBB4 4
(Bottom Side)
60 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 4.
Accessories
Flat front terminations
The EntelliGuard G Fixed mounted breaker comes standard with Back-connected Terminations. Optional
Flat Front terminations are available for front access mounting (Table 4.36).
—
Section 4.
Accessories
Table 4.37 Cluster
2.5
1. Used for breakers with the following nomenclature: 6th digit being “S” or a combination of the following:
• 3rd and 4th digit being 04, 06, 08, 16, or 20
• 5th digit being (“E” or “M”)
• 6th digit not equal to “D”
A P P L I C AT I O N G U I D E 63
2.5
Cluster Pad (two sets per phase) GBB120TBD 2
1. Used for breakers with the following nomenclature: 6th digit being “S” or a combination of the following:
• 3rd and 4th digit being 04, 06, 08,16, or 20
• 5th digit being “E” or “M”
• 6th digit not equal to “D”
64 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 4.
Accessories
Figure 4.5 Terminations for DC Switches UL 489B
Isometric view
Application Circuit diagram Catalog number
of termination
3P, Env2
600C DC
Stationary GBB2TBF2DC
Without neutral isolation Drawout GBB230TBBC2DC
3P, Env2
1000C DC
Stationary GBB2TBF3DC
Without neutral isolation Drawout GBB230TBBC3DC
3P, Env2
1000C DC
Without neutral isolation Stationary GBB2TBF4DC
Drawout GBB230TBBC4DC
4P, Env2
scale:2.1
A P P L I C AT I O N G U I D E 65
All EntelliGuard G circuit breakers can be fitted with ENTELLI Breakers EGECOVER
a grounding/earthing device, which has a short RETRO Breakers EGRCOVER
circuit rating equal to the breaker withstand rating. UL Breakers EGUCOVER
This permits either the feeder cables or the busbar
• Special handling and order entry are required to preserve UL
to be safely grounded and locked during system Listing of the breaker. Contact Post Sales Service for details and
order entry assistance.
maintenance operations (Table 4.40).
—
Section 5.
Digit
Sample
1
G
Mounting
Catalog numbering guide
7
H
ENTELLIGUARD* G CIRCUIT BRE AKERS
Closing Devices
9
R
Shunt Trip
X
10
UVR
5
11
Mechanical Interlock
L4
ZSI
6
19
Rating Plug
A P P L I C AT I O N G U I D E 67
—
Section 5.
Catalog numbering guide
Digit 5 – EntelliGuard G Short Circuit and Interrupting Ratings
Interrupting Rating Tier ANSI/UL1066 Devices, LVPCB
1/2S Override Override
Code 254V 508V 635V HSIOC Code
Withstand No Inst. w/Inst.
S 1
65,000 65,000 50,000 50,000 50,000 49,000 53,500 S
N 65,000 65,000 65,000 65,000 N
H 85,000 85,000 65,000 65,000 65,000 63,700 69,500 H
P1 100,000 100,000 65,000 65,000 65,000 63,700 69,550 P
E 85,000 85,000 85,000 85,000 E
M 100,000 100,000 100,000 85,000 85,000 83,800 90,950 M
U1 130,000 100,000 100,000 100,000 100,000 98,000 107,000 U
L 150,000 150,000 100,000 100,000 100,000 98,000 107,000 L
W 200,000 200,000 100,000 100,000 100,000 98,000 107,000 W
Interrupting Rating Tier UL489 Devices ICCB
690V 1/2S Override Override
240V 480V 600V HSIOC 400-1200
(IEC 60947-2) Withstand No Inst. w/Inst.
S1 65,000 65,000 50,000 40,0003 42,000 42,000 44,940 S
N 65,000 65,000 65,000 50,0003 42,000 42,000 44,940 N
H 85,000 85,000 65,000 50,000 50,000 53,500 H
P1 100,000 100,000 65,000 50,000 50,000 53,500 P
M 100,000 100,000 100,000 85,0003 65,000 65,000 69,550 M
U1 130,000 100,000 100,000 85,000 85,000 90,950 U
L 150,000 150,000 100,000 100,0003 85,000 85,000 90,950 L
W 200,000 200,000 100,000 85,000 85,000 90,950 W
Close and Latch ratings (MCR set accordingly)
UL/ANSI 1 42,000
UL/ANSI 2 65,000
UL/ANSI 2.5 85,000
UL/ANSI 3 100,000
S N H M E L
IEC 1 42,000 42,000 42,000
IEC 2 50,000 50,000 65,000 65,000
IEC 3 100,000 100,000
ANSI Non-Automatic Switches 30 Cycle Withstand Ratings
254V 580V 635V
S 1
42,000 42,000 42,000 S
N 42,000 42,000 42,000 N
M 65,000 65,000 65,000 Note: Non-automatic switches are provided M
with no internal sensing or tripping
U1 85,000 85,000 85,000 U
mechanism and cannot be applied
B 100,000 100,000 100,000 above their respective withstand levels. B
UL489 Non-Automatic Switches If a non-automatic device is required at
ratings above the available switches is
254V 580V 635V required, it is recommended that a
S1 42,000 42,000 42,000 circuit breaker set with maximum S
setting be employed using external
N 42,000 42,000 42,000 N
control or protection as required by the
M 65,000 65,000 65,000 application. M
U1 85,000 85,000 85,000 U
B 100,000 100,000 100,000 B
1. Available as 3-pole only
2. Restricted
3. Icu = Ics = Icw
A P P L I C AT I O N G U I D E 69
X
X X
X
X
X X
X
X X
X X
Notes: Override has 7 % pick up tolerance. Nominal setting is 98% of Icw if no other instantaneous is on, or 107%
of Icw if any other instantaneous is on.
UL 489 CB always has other instantaneous protection on. MCR set at 78% Close and Latch rating with -10%
tolerance.
—
Section 5.
Catalog numbering guide
Digit 6 – Mounting Type Poles Digit 8 – Closing Devices
Designation Mounting Poles Code Closing Coil Type Code
3 1 24Vdc A
drawout 4, right 2 30Vdc B
4, left 3 48Vac/dc C
3 4 60 – 72Vdc D
Closing Coil (CC)1
OEM 4, right 5 110Vdc/130Vdc; 120Vac E
4, left 6 208Vac F
stationary
3, no rear copper X 220Vdc; 240Vac G
4, right, no rear copper Y 250Vdc; 277Vac H
4, left, no rear copper Z 24Vdc M
drawout 3 D1 30Vdc N
GE
drawout 3 S1 48Vac/dc P
Equipment Command Operated
stationary 3 F 60 – 72 Vdc Q
Closing Coil (CCC)2
110Vdc/130Vdc; 120Vac R
1. Use code “S” (single cluster construction) for new orders of
Envelope 2, 2000A and less, interruptions rating tier E and M; 208Vac S
otherwise, use “D” 220Vdc; 240Vac T
• Right, Left indicates the location of the fourth pole, typically used
to switch the neutral. Blank/none X
• Stationary and drawout breakers come with and without back
connected terminations. Optional flat front terminations are 1. The Closing Coil (CC) permits either local or remote release of the
available. See “Flat Front Terminations,” page 53. spring charged closing mechanism by electrical operation.
• P type circuit breaker available only in 3-pole. 2. The Command Operated Closing Coil (CCC) includes an additional
anti-pumping safety feature to ensure that the electrical closing
signal must be released before further closure is attempted, a shut
off is initiated if the closing signal is maintained.
Digit 7 – Spring Charging Motor • Manual button through breaker cover is included as standard
assembly.
Spring Charging Motor (EO) Code
• When a Spring Charging Motor is selected (Digit 7), a Closing
24/30Vdc A Device must be selected from Closing Devices for Digit 8, and a
Shunt Trip Device must be selected from Shunt Trip 1 Devices for
48Vdc B
Digit 9.
60Vdc C • Select one device only.
DC
72Vdc D
110/130Vdc E Digit 9 – Shunt Trip 1
250Vdc F Extended Range Shunt Code Ratings
48Vac G Trip (ANSI/UL)1
120Vac H 24Vdc F Momentary
AC
240Vac J 110-130Vdc/ac J Momentary
Blank/none 1
X 24Vdc M Continuous
48Vac/dc P Continuous
1. An “X” (Blank/None) denotes a Manually Operated device (MO)
70 – 72Vdc Q Continuous
Spring Charge Contact, GSCC1, included with all Motor Operators.
• When a Spring Charging Motor is selected, a Closing Device must 110/125Vdc; 120Vac R Continuous
be selected from Closing Devices for Digit 8, and a Shunt Trip
Device must be selected from Shunt Trip 1 Devices for Digit 9. 208Vac S Continuous
• Shunt Trip 1 with a coil voltage different from the Spring Charge 220Vdc; 240Vac T Continuous
Motor may be user-selected.
250Vdc; 277 Vac V Continuous
Blank/none X
1. The UVR with Fixed Time Delay is specifically intended for 70 – 72Vdc Q
2nd Extended
applications where a delay period, or “ride-through,” is required Range Shunt Trip 110/125Vdc; 120Vac R
due to potential voltage events. The design delays are 50 msec
(ANSI/UL) 2 208Vac S
when system voltage drops to 50% and 20 msec when system
voltage drops below 50%. 240Vac T
• An optional External UVR Time Delay Module is available in a 1 – 3
sec delay. 250Vdc V
• Select one device only.
Blank/none X
1. The UVR with Fixed Time Delay is specifically intended for
applications where a delay period, or “ride-through,” is required
due to potential voltage events. The design delays are 50 msec
when system voltage drops to 50% and 20 msec when system
voltage drops below 50%.
2. The Extended Range Shunt Trip is specifically intended and
required for UL ANSI Ground Fault applications. The pickup range
is 55-110% of the ST coil voltage.
• An optional External UVR Time Delay Module is available in a 1 –
3sec delay.
• Select one device only.
72 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 5.
Catalog numbering guide
Digit 12 – Auxiliary Switch
Contact Configuration Code
Auxiliary Switch, 3NO+3NC (Power Rated)1 STANDARD/INCLUDED 2
Auxiliary Switch, 8NO+8NC (Power Rated) 4 4
Aux. Switch, 3NO/3NC (Power Rated) + 2NO/2NC low signal (Hi-Fi) 6
Aux. Switch, 4NO/4NC (Power Rated) + 4NO/4NC low signal (Hi-Fi) 4 8
Auxiliary Switch, 3NO+3NC CSC, PR, (1 NO on SD) – Close Coil or CCC A
(Power Rated) CSC, Hi-Fi via Trip Unit – Close Coil or CCC2,3 B
CSC, PR, (1 NO on SD) – 1st Shunt Trip C
CSC, Hi-Fi via Trip Unit – 1st Shunt Trip2,3 D
CSC, PR, (1 NO on SD) – 1st UVR E
CSC, Hi-Fi via Trip Unit – 1st UVR2,3 F
CSC, PR, (1 NO on SD) – 2nd ST or 2nd UVR G
CSC, Hi-Fi via Trip Unit – 2nd ST or 2nd UVR2,3 H
Aux. Switch, 3NO/3NC (PR) + 2NO/2NC CSC, PR, (1 NO on SD) – Close Coil or CCC J
Low Signal (Hi-Fi) CSC, Hi-Fi via Trip Unit – Close Coil or CCC2,3 K
CSC, PR, (1 NO on SD) – 1st Shunt Trip L
CSC, Hi-Fi via Trip Unit – 1st Shunt Trip2,3 M
CSC, PR, (1 NO on SD) – 1st UVR N
CSC, Hi-Fi via Trip Unit – 1st UVR2,3 P
CSC, PR, (1 NO on SD) – 2nd ST or 2nd UVR Q
CSC, Hi-Fi via Trip Unit – 2nd ST or 2nd UVR2,3 R
Auxiliary Switch, 3NO+3NC CSC, PR, (1 NO on SD) – All Installed Devices S
(Power Rated) CSC, Hi-Fi via Trip Unit – All Installed Devices2,3 T
Aux. Switch, 3NO/3NC (PR) + 2NO/2NC CSC, PR, (1 NO on SD) – All Installed Devices U
Low Signal (Hi-Fi) CSC, Hi-Fi via Trip Unit – All Installed Devices2,3 V
BACL Power Rated (1NO/1NC) & RTC Signal Rated (Hi-Fi) through Trip Unit F 1,2,3
Pushbutton Padlock Device L
BACL Power Rated (1NO/1NC), MOC & RTC Power Rated on SD G3 Profalux Key Lock Provision and Push Button Padlock 4
BACL Power Rated (1NO/1NC), MOC & RTC Signal Rated (Hi-Fi) through Trip Unit J1,2 Device
Ronis Key Lock Provision and Push Button Padlock 3
BACL Power Rated (1NO/1NC), MOC & RTC Signal Rated on SD H3
Device
BACL Power Rated (2NO/2NC) & MOC 7 Kirk Key Lock Proviion and Push Button Padlock 2
BACL Power Rated (2NO/2NC), MOC & RTC Power Rated on SD 8 Device
BACL Power Rated (2NO/2NC), MOC & RTC Signal Rated (Hi-Fi) through Trip Unit Q Castell Key Lock Provision and Push Button Padlock 1
Device
BACL Power Rated (2NO/2NC), MOC & RTC Signal Rated on SD 9
Profalux Key Lock Q
BACL Signal Rated N
Ronis Key Lock S
BACL Signal Rated & MOC T
Kirk Key Lock D
BACL Signal Rated & RTC Power Rated Contacts on SD P
Castell Key Lock F
BACL Signal Rated & RTC Signal Rated (Hi-Fi) Contacts on SD R
Profalux Key Lock and Push Button Padlock Device 6
BACL Signal Rated & RTC Signal Rated (Hi-Fi) through Trip Unit S
Ronis Key Lock and Push Button Padlock Device 7
BACL Signal Rated, MOC and RTC Power Rated on SD U
Kirk Key Lock and Push Button Padlock Device J
BACL Signal Rated, MOC & RTC Signal Rated (Hi-Fi) through Trip Unit Y
Castell Key Lock and Push Button Padlock Device N
BACL Signal Rated, MOC & RTC Signal Rated on SD V
Blank/none X
MOC B
• This option provides factory installed interlocking devices for
MOC and RTC Power Rated (1NO) on SD K installation between separate circuit breakers (baseplates and
MOC and RTC Signal Rated (1NO) on SD1 L mechanism). This safeguard ensures that a circuit breaker cannot
be closed unless the dedicated key has been inserted and secured
MOC and RTC Signal Rated (Hi-Fi)(1NO) through Trip Unit M1,2 within the lock.
• If selecting a Draw Out Breaker (Digit 6), the key interlock must be
RTC Power Rated Contacts (1NC) on SD 4
mounted on the cassette (see Table 4.15). This enables the ability
RTC Power Rated Contacts (1NO) on SD 1 to swap breakers without having to change the key interlocks.
BACL = Bell Alarm Contact with Lockout Hi-Fi = High Fidelity Mechanical Interlocks are field mountable only.
MOC = Mechanical Operations Counter RTC = Ready To Close Contacts
SD = Secondary Disconnect
1. To output the RTC contact output via Trip Unit a communications package must be selected in • Some installations use multiple power sources that are required
Advanced Features (Code 19/Step 16); which requires Secondary Disconnect Block B. to supply energy simultaneously, alternately, or, in a specified
2. If a UL or ANSI Switch is selected, the (Hi-Fi Through Trip Unit) is not valid. sequence. EntelliGuard G Circuit Breakers can be used to
3. Bell Alarm Contact with Lockout comes with the Trip Unit set to Manual LO Enabled. interconnect these sources and be electrically and mechanically
• The term “Hi-Fi” refers to gold-plated contacts use for signal level outputs (10mA minimum – interlocked to provide the necessary transition and protection.
100mA maximum, 5-30Vdc, 125vac). Mechanical Interlocks are available for fixed and draw out circuit
• Option “B”, “I”, “2”, “3”, “K”, “L”, “M”, and “X” are the only valid options when a Switch is selected in breakers. The interlocks enable directly interlocking breakers
Digit 2. that are mounted side by side or in vertical stacks. The interlocks
consist of two components: (A) The factory-installed bracket fitted
to the breaker (fixed breakers) or the cassette (drawout breakers),
and (B) The field-installable interconnecting cables available in
lengths of 1.0, 1.6, 2.0, 2.5, 3.0, 3.5 and 4.0m (ordered separately).
Refer to Section 4. for interlocking schemes.
• Contact factory for availability.
74 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 5.
Catalog numbering guide
Digits 16 & 17 – Overcurrent Protection Package
Type Over Current (OC) Protection Package Code
LSI (S, switchable) (I, switchable ANSI only) L3
LSIG (S, switchable) (I, switchable ANSI only) L4
LSIGA (S, switchable) (I, switchable ANSI only) (G, Alarm Only) L5
EntelliGuard G Standard Range
LSIC (S, switchable) (I, switchable ANSI only) L6
ANSI/UL OC Instantaneous
LSICA (S, switchable) (I, switchable ANSI only) (C, Alarm Only) L7
Protection with
Fuse Settings LSIGDA (S, G, A switchable) (I, switchable ANSI only) L8
LSIGCDA (S, G, C, A all switchable) (I, switchable ANSI only) L9
LSHGDA (S, G, A switchable) (H, switchable ANSI only) LH
LSHGCDA (S, G, C, A all switchable) (H, switchable ANSI only) LK
JSI (S, switchable) (I, switchable ANSI only) J3
JSIG (S, switchable) (I, switchable ANSI only) J4
JSIGA (S, switchable) (I, switchable ANSI only) (G, Alarm Only) J5
EntelliGuard G Standard Range
JSIC (S, switchable) (I, switchable ANSI only) J6
ANSI/UL OC Instantaneous
JSICA (S, switchable) (I, switchable ANSI only) (C, Alarm Only) J7
Protection with
Fuse Settings JSIGDA (S, G, A all switchable) (I, switchable ANSI only) J8
JSIGCDA (S, G, C, A all switchable) (I, switchable ANSI only) J9
From 1/1/12:
Included in l Extended Range JSH (S, switchable) (H, switchable ANSI only) JC
type trip units Adjustable JSHG (S, switchable) (H, switchable ANSI only) JD
Instantaneous
JSHGA (S, switchable) (H, switchable ANSI only) (G, Alarm Only) JE
(For reference only)
JSHC (S, switchable) (H, switchable ANSI only) JF
JSHCA (S, switchable) (H, switchable ANSI only) (C, Alarm Only) JG
JSHGDA (S, G, A all switchable) (H, switchable ANSI only) JH
JSHGCDA (S, G, C, A all switchable) (H, switchable ANSI only) JK
None – (For Switch Only) XX
—
Section 5.
Catalog numbering guide
EntelliGuard G ANSI/UL489 circuit breaker Digits 3 & 4 – Cassette Current Rating1
catalog number guide Circuit Breaker/Switch DC Switch
Current Rating (A)
Sample G A 16 M 2 S ANSI UL489 UL489B
Digit 1 2 3&4 5 6 7 800 082 082 082
1200 12 3
12 3
Circuit Breaker Cassette Family
Current Rating
# of Poles
Shutters
1600 16 16 16
2000 20 20 20
3000 30 30
3200 32
5000 50
6000 60
—
Section 5.
Catalog numbering guide
Digit 5 – Cassette Envelope Size
Interrupting Rating Tier ANSI/UL1066 Devices, LVPCB
1/2S Override Override
Code 254V 508V 635V HSIOC Code
Withstand No Inst. w/Inst.
S 1
65,000 65,000 50,000 50,000 50,000 49,000 53,500 S
N 65,000 65,000 65,000 65,000 N
H 85,000 85,000 65,000 65,000 65,000 63,700 69,500 H
P1 100,000 100,000 65,000 65,000 65,000 63,700 69,550 P
E 85,000 85,000 85,000 85,000 E
M 100,000 100,000 100,000 85,000 85,000 83,800 90,950 M
U1 130,000 100,000 100,000 100,000 100,000 98,000 107,000 U
B 100,000 100,000 100,000 100,000 B
L 150,000 150,000 100,000 100,000 100,000 98,000 107,000 L
W 200,000 200,000 100,000 100,000 100,000 98,000 107,000 W
Interrupting Rating Tier UL489 Devices ICCB
690V 1/2S Override Override
240V 480V 600V HSIOC 400-1200
(IEC 60947-2) Withstand No Inst. w/Inst.
S1 65,000 65,000 50,000 40,0003 42,000 42,000 44,940 S
N 65,000 65,000 65,000 50,0003 42,000 42,000 44,940 N
H 85,000 85,000 65,000 50,000 50,000 53,500 H
P1 100,000 100,000 65,000 50,000 50,000 53,500 P
M 100,000 100,000 100,000 85,0003 65,000 65,000 69,550 M
U1 130,000 100,000 100,000 85,000 85,000 90,950 U
L 150,000 150,000 100,000 100,0003 85,000 85,000 90,950 L
W 200,000 200,000 100,000 85,000 85,000 90,950 W
ANSI Non-Automatic Switches 30 Cycle Withstand Ratings
254V 580V 635V
S1 42,000 42,000 42,000 S
N 42,000 42,000 42,000 N
M 65,000 65,000 65,000 Note: Non-automatic switches are provided M
with no internal sensing or tripping
U 1
85,000 85,000 85,000 U
mechanism and cannot be applied
B 100,000 100,000 100,000 above their respective withstand levels. B
UL489 Non-Automatic Switches If a non-automatic device is required at
ratings above the available switches is
254V 580V 635V required, it is recommended that a
S1 42,000 42,000 42,000 circuit breaker set with maximum S
settings be employed using external
N 42,000 42,000 42,000 N
control or protection as required by the
M 65,000 65,000 65,000 application. M
U 1
85,000 85,000 85,000 U
B 100,000 100,000 100,000 B
1. Available as 3-pole only
2. Restricted
3. Icu = Ics = Icw
A P P L I C AT I O N G U I D E 79
X
X X
X X
X
X X
X
X X
X X
Envelope 1 Envelope 2 Envelope 2.5 Envelope 3
800-1200 800-2000 800-3200 800-4000 3200-5000
X
X
X
X
X
Envelope 1 Envelope 2 Envelope 2.5 Envelope 3
800-1200 800-2000 800-3000 800-4000 3000-6000
X
X
X
X
X
—
Section 5.
Catalog numbering guide
EntelliGuard TU trip unit for EntelliGuard G breakers Circuit Breaker Type Code
Sample GG M 16 L4 X 6 A XXXX Power Break 1 (UL) GA
Digit 1&2 3 4&5 6&7 8 9 10 11-14 Power Break 2 (UL) GB
AKR (ANSI) GC
EntelliGuard Trip Unit Form
Frame Rating
Sensor Rating
ZSI
Future Use
WP (ANSI) GW
Mpact Low (IEC) GL
Mpact 24-48V (IEC) GH
Mpact 120-240V (IEC) GQ
EntelliGuard G ACB (ANSI) GG
EntelliGuard G ACB (UL) GU
EntelliGuard G ACB (IEC) GT
EntelliGuard G Universal Spare Trip G1
Type A Conversion Kits (ANSI) G2
EntelliGuard G Switch (IEC) G3
• This Application Guide documents the EntelliGuard TU Trip Unit
for EntelliGuard G Circuit Breakers.
• GE Legacy ANSI, UL Circuit Breakers are documented in DEH-4567.
—
Section 5.
Catalog numbering guide
Digits 6 & 7 – Overcurrent Protection Package (for EntelliGuard G Breakers)
Type Over Current (OC) Protection Package Code
LSI (S, switchable) (I, switchable ANSI only) L3
LSIG (S, switchable) (I, switchable ANSI only) L4
LSIGA (S, switchable) (I, switchable ANSI only) (G, alarm only) L5
Standard Range
LSIC (S, switchable) (I, switchable ANSI only) L6
Instantaneous
LSICA (S, switchable) (I, switchable ANSI only) (C, alarm only) L7
LSIGDA (S, G, A switchable) (I, switchable ANSI only) L8
EntelliGuard G
ANSI/UL OC LSIGCDA (S, G, C, A all switchable) (I, switchable ANSI only) L9
Protection with LSH (S, switchable) (H, switchable ANSI only) LC
Fuse Settings
LSHG (S, switchable) (H, switchable ANSI only) LD
LSHGA (S, switchable) (H, switchable ANSI only) (G, alarm only) LE
Extended Range
Adjustable LSHC (S, switchable) (H, switchable ANSI only) LF
Instantaneous LSHCA (S, switchable) (H, switchable ANSI only) (C, alarm only) LG
LSHGDA (S, G, A switchable) (H, switchable ANSI only) LH
LSHGCDA (S, G, C, A all switchable) (H, switchable ANSI only) LK
JSI (S, switchable) (I, switchable ANSI only) J3
JSIG (S, switchable) (I, switchable ANSI only) J4
JSIGA (S, switchable) (I, switchable ANSI only) (G, Alarm Only) J5
Standard Range
JSIC (S, switchable) (I, switchable ANSI only) J6
Instantaneous
EntelliGuard G ANSI/UL JSICA (S, switchable) (I, switchable ANSI only) (C, Alarm Only) J7
OC Protection with Fuse JSIGDA (S, G, A all switchable) (I, switchable ANSI only) J8
Settings
JSIGCDA (S, G, C, A all switchable) (I, switchable ANSI only) J9
FROM 1/1/12: Extended Range JSH (S, switchable) (H, switchable ANSI only) JC
INCLUDED IN L TYPE Adjustable JSHG (S, switchable) (H, switchable ANSI only) JD
TRIP UNITS Instantaneous
JSHGA (S, switchable) (H, switchable ANSI only) (G, Alarm Only) JE
JSHC (S, switchable) (H, switchable ANSI only) JF
JSHCA (S, switchable) (H, switchable ANSI only) (C, Alarm Only) JG
JSHGDA (S, G, A all switchable) (H, switchable ANSI only) JH
JSHGCDA (S, G, C, A all switchable) (H, switchable ANSI only) JK
None (for switch only) XX
Digit 8 – Zone Selective Interlocking (ZSI) EntelliGuard TU Trip Unit Rating Plugs
Zone Selective Interlocking Code Sample GTP 1600 U 16 40
Z + I- ZSI + T-ZSI1; user selectable T Digit 1,2,3,4 5,6,7,8 9 10,11 12,13
Blank/None X
—
Section 6.
Application data
The EntelliGuard G family of circuit breakers and All Types
related switching devices is a truly global line of • Stationary mounting capability with rear or front
protection and switching devices. It was designed connections.
from the ground up to provide reliable protection • Drawout mounting with cassette and automatic
and operation in a wide range of power distribution shutter mechanism.
systems. Combined with the EntelliGuard TU family • Complete closed door operation capability –
of trip devices, EntelliGuard G circuit breakers UL489, ANSI or IEC.
provide superior protection and reliability with a • Two-step stored energy mechanism for manual or
maximum of flexibility and a minimum of electrically operated circuit breakers, suitable for
compromise for your power protection and fast throw-over or generator paralleling
switching needs. applications
This section provides an overview of the circuit • Remote racking device allowing maintenance
breaker’s capability under UL 489 and UL 1066 personnel to rack circuit breakers in and out while
standards. standing outside the arc flash boundary.
• 3 and 4 pole configurations with the neutral on
either side.
Key features • Suitable for UL1008 transfer switch applications
There are three product families: • Alternate, settable and remote controllable
UL1066 Low Voltage Power Circuit Breakers instantaneous pickup with positive feedback.
• 800-5000A frames in three physical sizes. • GE’s novel fully controllable ZSI restrained and
• 400-5000A sensors with rating plugs as low as unrestrained settings.
150A and trip settings as low as 75A. • GE’s novel fully selective instantaneous trip with
• Short circuit ratings as high as 150kA at 480V selectivity enhancing ZSI capability.
(tested at 508V). • Field installable accessories with labels that may
• Withstand capability and selectivity as high as be seen through the circuit breaker’s escutcheon.
100kA • Easily accessible terminal contacts at the top or
• Continuously adjustable selective instantaneous side of circuit breaker for use by installer –
as high as 30X the circuit breaker’s rating. permanently labeled, color coded and interlocked
UL489 Stored Energy Insulated Case Circuit with harnesses for fast, efficient, mistake-proof
Breakers wiring.
• 800-6000A frames in three physical sizes. • Advanced protection algorithms that allow
• 400-6000A sensors with rating plugs as low as maximum selectivity and protection at the same
150A and trip settings as low as 75A. time with minimized need to sacrifice protection
• Short circuit ratings as high as 150kA at 480V. to get system reliability or vice versa.
• Withstand capability and selectivity as high as • Trip curves and algorithms to optimally
85kA. accommodate downstream fuses, older slower
• Continuously adjustable selective instantaneous power circuit breakers, ultra-fast current limiting
to 15X on all but the largest circuit breakers. devices or other EntelliGuard circuit breakers
• Drawout and stationary mounted, 100% rated. without sacrificing any more protection than
IEC Rated Circuit Breakers for IEC Equipment and absolutely necessary to achieve significant
Applications selectivity.
• 800-6400A frames in three physical sizes.
• 400-6400A sensors adjustable to 20% of sensor Ratings and sizes
size. The EntelliGuard G family of overcurrent devices is
• Short circuit ratings as high as 150kA at 440V, available in 3 or 4 pole versions, in 3 physical sizes
100kA at 690V, 80kA at 1000V. referred to as “envelopes” 1, 2 and 3. Four pole
• Rated breaking capacity 100%, Ics = Icu for all versions may have the neutral on the right- or left-
frames. most pole. The envelope and the number of poles
• Withstand capability and selectivity as high as are the main determinants for physical size and the
100kA for 1sec. space the device will require when installed in
• Continuously adjustable selective instantaneous equipment or enclosures.
as high as 30X the circuit breaker’s rating.
A P P L I C AT I O N G U I D E 85
The circuit breakers and switches are further Table 6.1 First Half-Cycle Peak at Specific Fault
divided into “frame” sizes. The frame sizes follow X/R Ratios (excerpted from UL489)
the guidelines defined under the applicable UL, IEC Power Factor X/R ratio Maximum Peak
and ANSI standards as shown in the various ratings at 1/2 Cycle
with short circuit ratings as high as 150kA at 480V, 19% 5.2 2.21
and withstand ratings as high as 100kA. UL1066 20% 4.9 2.18
and ANSI C32 ratings are based on various tests 100% 0.0 1.41
performed at rated voltage plus 6%. Hence it is
Consider a system where the fault current has an
common to see low voltage circuit breakers listed
X/R ratio of 10 and the calculated RMS value is
as suitable for 254, 508 and 635V. Any UL 1066
92,000. A circuit breaker with a stated interrupting
listed device must be tested at these higher
capability of 100,000 is being considered. Since the
voltages if listed at the normal nominal voltage of
fault’s X/R ratio is higher than the UL489 rating at
240, 480 and 600V. UL489 circuit breakers are
4.9, the circuit breaker’s rating, 100kA, must be
tested at the nominal voltage. Both circuit breakers
multiplied by 2.18/2.46 (from Table 6.1). The ratio is
are subject to dielectric testing after interrupting
.89. Hence, the circuit breaker must be considered
faults to ensure the ability to sustain voltage.
as if it is only rated for 89,000A. The UL489 100kA
Short circuit interrupting ratings are a
rated circuit breaker is not suitable for the
measurement of the circuit breaker’s ability to
application because its de-rated 89kA rating is
interrupt a particular value of fault current at a
below the available fault current of 92kA.
maximum power factor (also expressed as X/R
Consider an equivalent UL1066 circuit breaker
ratio). For fault currents above 20,000A RMS,
tested at an X/R ratio of 6.6. The UL1066 circuit
UL489 circuit breakers are tested at 20% power
breaker must be de-rated by 2.31/2.46, which yields
factor and UL1066 circuit breakers are tested at
0.94. The UL1066 circuit breaker is then de-rated to
15% power factor. When fault currents have power
0.94 times 100kA. The UL1066 circuit breaker is
factors lower (higher X/R) than the test power
rated higher than the available fault current of 92kA
factor, the circuit breaker’s short circuit rating
and hence could be considered for the application.
must be adjusted to compensate for the fault’s
lower PF. The adjustment is performed as shown in
Withstand ratings, selective waveform
Figure 6.1. Table 6.2 shows various asymmetrical
recognition-, relt- and override-instantaneous
peak ratios for various power factors and X/R
protection
ratios. A power factor of 100% yields a symmetrical
Instantaneous adjustment capability for any circuit
fault and hence the peak over RMS ratio is 1.41.
breaker is intrinsically connected to the circuit
Figure 6.1 Short Circuit Rating Adjustment breaker’s withstand rating and the trip system’s
Equation sensing methods. In the case of the EntelliGuard G
CB’s Test Peak = Derate Ratio family of circuit breakers, high withstand ratings
Fault Peak allow for a broad range of instantaneous trip options.
86 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 6.
Application data
The trip system relies on high accuracy air core 100% of the stated circuit breaker’s withstand
sensors not encumbered by the saturation rating is possible.
concerns associated with iron core sensors used in In UL1066 LVPCBs, maximum selective capability is
many other trip systems. This allows the achieved by using the adjustable instantaneous
EntelliGuard trip system to take full advantage of algorithm, even if it is set at maximum. When the
the circuit breaker’s withstand rating, providing adjustable instantaneous is enabled, regardless of
adjustable settings and full selectivity right up to setting, the override protection is set so that it will
the circuit breaker’s high withstand level. not trip for faults below the circuit breaker’s
EntelliGuard G circuit breakers, in conjunction with withstand rating. If the adjustable instantaneous is
EntelliGuard TU trip units with GE’s unique disabled (turned off), then the override
“selective instantaneous” algorithm, allow automatically adjusts downward by approximately
selectivity capability as high as 100kA with 9%. This lowers the maximum selective capability
instantaneous on, and set at surprisingly low to 91% of the circuit breaker’s withstand rating.
values. The EntelliGuard family of devices provides The EntelliGuard G LVPCB may be selective up to
multiple solutions for your selectivity and the full withstand current with adjustable
protection problems. instantaneous on and 91% of withstand rating with
Low Voltage Power Circuit Breakers (LVPCBs) listed adjustable instantaneous off.
to UL1066 have defined fault current withstand The EntelliGuard TU trip unit also offers a second
currents. EntelliGuard G UL489 Insulated Case adjustable instantaneous trip called the Reduced
Circuit Breakers also have substantial withstand Energy Let-Through (RELT) instantaneous pickup.
ratings. The stated withstand current (Icw) allows This trip offers a faster algorithm suitable for
the instantaneous protection of LVPCBs to be application as alternate instantaneous pickup
turned off or set at very high values, and it’s what setting for temporary use when faster and more
allows the short time bands of both types of circuit sensitive instantaneous protection is desired. The
breakers to be delayed as much as 0.5sec. RELT setting is determined by the user and may be
EntelliGuard G UL1066 LVPCBs with EntelliGuard TU adjusted from 1.5X to 15X rating plug. Once set, the
trip units are available with two different RELT function may be enabled or disabled locally at
instantaneous adjustment ranges to take full the trip unit or remotely via a 24Vac/dc signal, or
advantage of this capability. serial communications.
The standard instantaneous adjustment range is When the trip unit receives a RELT enable
2-15X, adjustable in 1/2X increments on all UL 489 command, it issues a feedback signal indicating the
and UL1066 circuit breakers. EntelliGuard TU trips RELT setting is now active. The user may connect
offer, for UL1066 LVPCBs only, an extended the RELT enable input to any 24Vac/dc source, such
Instantaneous adjustment range that allows the as a manual switch, automatic sensor, or both. The
instantaneous pickup to be continuously adjusted feedback signal may be connected to any desired
up to 30X, adjustable in 1X increments above 15X signaling means with the proper ratings. For
the rating plug. The maximum adjustable pickup further details see Section 3. of this application
setting is limited to approximately 95% of the guide.
circuit breaker’s withstand rating, or 30X trip plug
current rating, whichever is lower. Close and latch ratings and making current
The EntelliGuard G’s wide range of instantaneous release (MCR) instantaneous TRIP
adjustability allows for maximum flexibility in EntelliGuard G circuit breakers have defined close
providing the settings that are required for and latch ratings as shown in Table 6.2 through
selectivity or for optimum protection. Its capability Table 6.4. The close and latch rating is a
is limited by its withstand rating and the measurement of the circuit breaker’s ability to
instantaneous override. An instantaneous override close and latch closed on a fault. This value must be
is used in some circuit breakers to ensure that, if a high enough to allow a circuit breaker to handle
fault exceeds the circuit breakers withstand large transient inrush currents associated with
capability, the circuit breaker trips quickly. In all certain types of loads, such as energy efficient
UL489 EntelliGuard circuit breakers, the override motors or large capacitor banks.
protection is designed such that selectivity up to
A P P L I C AT I O N G U I D E 87
Operations
Operations
Operations
Mechanical
2 800 - 3000 N, E, M 65
Electrical
Electrical
Envelope Frame
at 508V
at 635V
2.5 800 – 4000 U 85
3 4000 - 6000 M, B 85
L 100 400-1600A 12500 10000 7500
1
2000A 12500 7500 5000
Table 6.4 EntelliGuard G Non-Automatic Switch
2 400-3000A 10000 5000 5000
Close, Latch, and Withstand Ratings,
2.5 800 – 4000 5000 3000 2000
UL489 Listed
3000-4000A 5000 3000 2000
Envelope Amps Type Close and Latch 3
Rating (kA) 6000A 5000 1500 1000
1 800 - 2000 N 42
2 800-3000 M 65 Table 6.6 Operational Ratings, UL1066/ANSI Cir-
2.5 2000 – 4000 U 85 cuit Breakers
3 4000 - 6000 B 100
Operations
Operations
Operations
Mechanical
L 100
Electrical
Electrical
Envelope Frame
at 508V
at 635V
EntelliGuard G circuit breakers are provided with
values that are high relative to the circuit breaker’s 400-1600A 12500 10000 7500
load carrying capacity. The trip system provides a 1
2000A 12500 7500 5000
type of instantaneous protection called a Making
2 400-3200A 10000 5000 5000
Current Release (MCR) to provide more sensitive
2.5 800 – 4000 5000 3000 2000
protection when closing. Should the trip system
3200- 5000 3000 2000
measure higher current than the MCR setting, it is
3 4000A
very likely that the circuit breaker has been closed
5000A 5000 2000 1500
on a bolted fault, or low impedance, arcing fault. If
that is the case, the MCR instantaneous will provide
very fast protection, minimizing damage and Per industry standards, operations are listed based
hazard. on no maintenance during the testing. However, if
some maintenance is done of some of the current
carrying parts and arc chute, then over 20,000
electrical and mechanical operations are possible.
88 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 6.
Application data
Selecting a circuit breaker for an application lubrication problems or mechanical binding of
There are six application factors to consider in internal parts due to differential contraction). The
selecting current rating for a circuit breaker: ambient temperature around an EntelliGuard G
1. Size of the cable or bus used in the line and load breaker should not be less than -20°C nor exceed
connections. 70°C.
2. Actual installed ambient temperature. Ambient temperature always refers to the
3. System operating frequency. temperature of the air immediately surrounding the
4. Altitude of the installation. breaker and not the temperature of the air outside
5. Type of loading of the protected circuit. the breaker’s enclosure. Room or outside air
6. Design safety factor. temperatures only establish the thermal floor to
which all other heating is added.
The following simple relationship combines these To convert breaker ambient from room ambient, it
six application factors into a single equation: is necessary to know the temperature rise within
CR = IA x A x B x C x D x E x F the equipment housing the breaker. Temperature
CR Required circuit breaker current rating, amps rise is a function of several variables, including
IA Actual load current, amps heating caused by other equipment, ventilation,
A Cable or bus sizing factor solar heating, factors relating to group mounting
B Ambient temperature rating factor and the free surface area of the breaker’s
C Frequency rating factor enclosure. Once the device’s ambient temperature
D Altitude rating factor is determined, select Factor B from Table 6.7.
E Load class rating factor
F Safety factor Table 6.7 Ambient Temperature Rating-Factor B
Ambient Maximum Wire AC DC
Cable or Bus Size – Factor A Temperature, °C1 Insulating Rating C2 Factor B Factor B
The thermal design of a circuit breaker takes into 25 75 1 1
account the ability of the line and load cables or 40 90 1 1
buses to act as heat sinks. For UL489 Listed circuit 50 105 1 11
breakers, UL has assigned specific cable or bus 60 125 1.1 1.15
sizes for each current rating. Generally, these 70 125 1.15
assignments are coordinated with specific 1 Average air temperature over a 24-hour period outside the
conductor temperature ratings. When using a breaker’s insulated case, but inside the enclosure.
2 Cable (wire) must be based on 75°C current rating per Table 3.10-
conductor with an increased temperature rating, 16, current National Electrical Code.
the higher rating decreases both the cross-
sectional area and its ability to conduct heat from
the circuit breaker. If an EntelliGuard G circuit
breaker is used with cables directly connected,
Operating Frequency – Factor C
contact your GE application engineer for
All UL EntelliGuard circuit breakers may be applied
information to ensure proper cabling information.
at their published ratings on 50Hz and 60Hz power
Cable with insulation ratings above 75°C may be
systems. At nominal system frequencies less than
used, providing it is sized to 75°C ampacity per the
50Hz but above direct current, digital solid-state
NEC or other applicable codes.
trip may become inaccurate. On direct current sys-
tems, digital solid-state trip units are completely
Ambient Temperature – Factor B
inoperative. EntelliGuard G circuit breakers may be
Ambient temperatures have a wide effect on the
used on DC applications, but EntelliGuard TU trip
rating of the breaker-cable system. While the
units may not.
internal sensing and tripping circuitry in
System operating frequencies above 60Hz may
EntelliGuard TU trip units are ambient insensitive,
change the performance and ratings of circuit
high-ambient temperatures may cause internal
breakers by heating metallic parts and significantly
components to exceed operating temperature
reducing interrupting capacity. EntelliGuard TU trip
limits. Low temperatures substantially increase the
units are not suitable for applications at 400Hz.
current-carrying capabilities of the breaker-cable
system until other limiting factors occur (e.g.,
A P P L I C AT I O N G U I D E 89
For operating frequencies of both 50Hz and 60Hz, Table 6.9 Load Class Rating – Factor E
the operating frequency rating Factor C = 1.00. For Load Type Factor E
operating frequencies other than 50Hz and 60Hz, Switching Electromagnets 1.5
contact your GE applications engineer. Single Motor Branch Circuit Protection
1.5
(Normal Duty) 1
Altitude – Factor “D” Switching Capacitors 1.5
EntelliGuard G UL circuit breakers are designed for Single Motor Branch Circuit Protection >3,001
operation at altitudes from sea level to 6000ft (Heavy Duty) 1 1.75
(1800m). Reduced air densities at altitudes above All Other load Types (Normal Duty) 1
6000ft affect the ability of the circuit breaker to 1. Use this factor to either plugging duty or starting more than 25
times per hour, where the rms current cannot be easily calculated.
both transfer heat and interrupt short circuits.
Determine the altitude of the breaker’s installation,
and select the altitude rating - factor D from Table Safety – Factor F
6.8. A safety factor is used to provide a design margin
between the rating of a circuit breaker and the
Table 6.8 Altitude Rating – Factor D
derived operating current using all of the
Altitude Factor B applicable selection factors. A safety factor of at
Feet Meters least 10% is often used to ensure the circuit
100 - 6,000 30 - 1,800 1 breaker is adequately sized. In addition it may be
6,001 - 10,000 1,801 - 3,000 1.04 useful to consider future growth.
>10,001 >3,001 1.08
Other Factors that Influence Circuit Breaker Sizing
Load Class Rating – Factor E 100% vs. 80% Ratings
The type of load and its duty cycle must be All EntelliGuard G circuit breakers are 100% rated.
considered in the application of EntelliGuard G Circuit breakers that are 100% rated are not
circuit breakers. Loads such as capacitors and required to be sized at 125% of the expected load.
electromagnets require a substantial and However, it is recommended that a safety factor, as
continuous de-rating factor if the breaker is described above, always be considered when
normally used to switch the load. With loads such selecting overcurrent device sizes.
as resistance welders, the breaker’s continuous An important consideration may be the circuit
current rating must be no less than 125% of the breaker’s desired selective and protection
welder’s 100% duty-cycle rating. performance within the context of the system
In general, circuit breakers are intended for the where it is installed. Certain settings are functions
protection of insulated cable. Where a circuit of the trip plugs, others of the sensors. In Table
breaker is intended to protect load equipment, 3.10 you will find the sensors available on a per
prudent engineering practices call for obtaining frame basis. Table 3.9 identifies the trip rating
factory review and concurrence with the selection plugs available for each sensor. Table 6.10 identifies
of a specific protective device. Load class selection the relationship between specific circuit breakers
Factor E for typical applications are listed in Table and trip parameters.
6.9.
—
Section 7.
Physical data
Dimensions and weights
To download detailed dimensional drawings like those shown in
—
Section 7.
Physical data
Description Mounting Location of Assembly #
Secondary Disconnect
800 - 4000A, Type U, 3-pole, fixed, ANSI/UL Top 10114225
800 - 4000A, Type U, 3-pole, Drawout, ANSI/UL Top 10114226
800 - 4000A, Type U, 3-pole, Front access, UL Top 200059613
3000 - 6000A, Type W, 3-pole, Drawout, ANSI/UL Top 10112605
3000 - 6000A, Type W, 4-pole, Drawout, ANSI/UL Top 10112606
Note: For latest drawings (including those for Type S and P), visit www.geindustrial.com.
—
Section 8.
Standards and references
Organizations American National Standard Institute (ANSI)
ANSI C37.13/1990 - Low-Voltage AC Power Circuit
Underwriters Laboratories® (UL) Breaker Used in Enclosures (600-Volt Insulation
UL 489 and UL 489-SB2 - Standard for Molded Case Class)
Circuit Breakers and Circuit Breaker Enclosures
UL 1066 - Standard for Safety Low-Voltage AC and ANSI C37.16/2000 - Recommendations for Low
DC Power Circuit Breakers Used in Enclosures Voltage Power Circuit Breakers and AC Power
Circuit Protectors, Preferred Ratings, Related
Order from: Requirements, and Application
UL Publication Stock
333 Pfingsten Road ANSI C37.17/1990 - American National Standard for
Northbrook, IL 60062 USA Trip Devices for AC and General Purpose DC Low
Voltage Power Circuit Breakers
National Electrical Manufactures Association
(NEMA) ANSI C37.20.1/2000 - Metal-Enclosed Low-Voltage
AB-1/2002 Standards Publication - Molded Case Power Circuit Breaker Switchgear
Circuit Breakers and Molded Case Switches ANSI C37.50/1989 (R1995) – Test Procedures for
SG3/1995 - Standards and Ratings for the Low-Voltage AC Power Circuit Breakers Used in
Application of Low-Voltage Power Circuit Breakers Enclosures
SG5/1995 – Power Switchgear Assemblies
ANSI/IEEE C37.90.1/1993 - IEEE Standard Surge
Order from: Withstand Capability (SWC) Tests for Protective
NEMA Publication Relays and Relay Systems
155 East 44th Street
New York, NY 10017 USA ANSI/IEEE C37.90.2/1993 - Withstand Capability of
Relay Systems to Radiated Electromagnetic
Canadian Standards Association (CSA) Interference from Transceiver
CSA 22.2 NO 5.1 – Standards for Branch Circuit
Protection Order from:
ANSI
Order from: 11 West 42nd Street,
Canadian Standards Association New York, NY 10036 USA
178 Rexdale Blvd.
Rexdale, Ontario, Canada M9WR3 International Electrotechnical Committee (IEC)
IEC 60947-1 (Ed. 4/2004) - Electrical Equipment for
Institute of Electrical and Electronics Engineers Low Voltage, High Power Switching Equipment
(IEEE) (Also applies to Electromagnetic Compatibility
IEEE 693 – Recommended Practices for Seismic
Design of Substations IEC 60947-2 (Ed. 4/2006) - Electrical Equipment for
Low Voltage, High Power Switching Equipment
Order from: (Also applies to Electromagnetic Compatibility
IEEE
345 East 47th Street, IEC 60947-3 (Ed. 4, Am 1, Am 2/2002) - Electrical
New York, NY 10017 USA equipment for Low voltage, high power switching
equipment (Also applies to Electromagnetic
Compatibility
A P P L I C AT I O N G U I D E 95
Order from:
ASTM
1916 Race Street Philadelphia,
PA 19103 USA
96 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Section 8.
Standards and references
EntelliGuard G Publications
Publications Pub #
Secondary Disconnects - Fixed DEH-41417
Command Close Coil DEH-41418
Ready To Close (RTC) DEH-41419
Coil Signaling Contacts DEH-41420
DEH-41430
DEH-41431
Back Connected Terminations for Cassette DEH-41433
DEH-41434
DEH-41437
DEH-41439
DEH-41440
DEH-41441
DEH-41442
Back Connected Terminations for Breaker
DEH-41443
DEH-41444
DEH-41445
DEH-41608
Contact Wear Indicator DEH-41446
DEH-41447
DEH-41448
Cluster pad Assembly
DEH-41449
DEH-41450
Mechanical Interlocks (Fixed) DEH-41451
Mechanical Interlocks (Drawout) DEH-41455
Cassette Interlock User Manual DEH-41459
Clusters DEH-41460
Flat Front Termination ANSI/UL DEH-41463
Remote Racking Operator DEH-41467
Key Interlock Casste Mounted DEH-41500
CVCB Coil Signal Status DEH-41517
Neutral Sensor Kit – Rogowski DEH-41387
24 Vdc Power Supply GEH-6492
Arc Chute Kit DEH-41389
Earthing Device Kit DEH-41379
EntelliGuard TU Rating Plugs DEH-41318
Anti-Bounce System DEH-41667
Gas Channel Assembly DEH-41668
EntelliGuard TU Lock Out Kit Installation DEH-41688
EntelliGuard TU Test Kit DEH-4568
EntelliGuard TU Trip Unit IOM DEH-4567
98 ENTELLIGUARD* G CIRCUIT BRE AKERS
—
Notes:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A P P L I C AT I O N G U I D E 99
—
Notes:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
—
ABB S.p.A.
Via Pescaria, 5
24123 Bergamo
Phone: +39 035 395.111
Fax : +39 035 395.306-433
www.geindustrial.com
1SDC200092D0201 - 2020.09