LKSM-HF: Armoured Power and Control Cable 0,6/1kV
LKSM-HF: Armoured Power and Control Cable 0,6/1kV
LKSM-HF
0,6/1kV CABLES
DESIGN: STANDARDS:
IEC 60092-353, design
1. Conductor
- stranded copper conductor 1,0-10mm2 IEC 60228, class 2
- stranded copper conductor 16-300mm2 IEC 60228, class 5 (Flex)
- tinned stranded copper conductor on request
2. Insulation
- XLPE plastic IEC 60092-360 Flame-
retardant
3. Bedding Fire-
- filler tape resistant
4. Armour Halogen-
- copper wire braid, coverage > 90% IEC 60092-350 free
- tinned copper wire braid on request Low smoke
5/2016
5. Sheath emission
- polyolefine plastic, SHF1 IEC 60092-360 Oil resistant
(only SHF2)
- on request, thermosetting polyolefine, SHF2
- standard colour black, other colours on request
Application: For fixed installation in most areas and on open deck in ships
and offshore units.
Main characteristics
Rated voltage AC 0,6/1kV (1,2kV)
DC 0,9/1,5kV (if voltage to earth does not exceed 0,9kV)
Maximum conductor
temperature + 90 °C
Flame-retardant IEC 60332-1-2 -test for single insulated wire and cable
IEC 60332-3-22 -test for bunched wires and cables,
category A
Halogen-free IEC 60754 series
Smoke emission IEC 61034 series
Oil resistance (only SHF2) IEC 60811-404 conditions according to 60092-360/SHF2
0,6/1kV CABLES
LKSM-HF 0,6/1kV Number of Cross- Nominal Current Min. bending
conductors & section of outer Approximate Rating A radius fixed
Part number cross-section armour diameter weight kg/km at +45°C installation
Normal G-type n x mm2 mm2 mm mm
5/2016
26247 27078 1x300 Flex 18,7 34,0 3270 582 205
25956 – 2x1,0 3,6 9,0 112 15 55
25770 – 2x1,5 3,8 9,5 131 20 60
25785 – 2x2,5 4,3 10,5 160 26 65
25801 – 2x4 5,2 12,0 214 34 75
25803 – 2x6 5,4 13,0 320 44 80
25805 – 2x10 8,7 15,5 481 61 95
26254 – 2x16 Flex 10,0 18,0 630 80 110
26255 – 2x25 Flex 12,3 23,0 965 105 140
26256 – 2x35 Flex 14,0 24,5 1210 130 150
26257 – 2x50 Flex 16,3 28,5 1635 167 175
26258 – 2x70 Flex 18,7 33,0 2225 204 200
26259 – 2x95 Flex 21,2 36,5 2805 241 220
25957 – 3x1,0 3,7 9,5 129 13 60
25772 25773 3x1,5 4,1 10,0 155 16 65
25786 25787 3x2,5 5,2 11,0 200 21 70
25802 25880 3x4 5,3 12,5 264 28 80
25804 25882 3x6 5,8 14,0 376 36 85
25806 25884 3x10 9,3 16,5 574 50 100
26271 26272 3x16 Flex 10,7 19,0 755 66 115
26273 26274 3x25 Flex 13,2 24,5 1155 86 150
26275 26276 3x35 Flex 15,0 26,0 1485 107 160
26277 26278 3x50 Flex 17,5 30,5 2050 137 185
26279 26280 3x70 Flex 20,2 35,5 2790 168 215
26281 26282 3x95 Flex 22,8 39,0 3555 199 235
26283 26284 3x120 Flex 35,1 44,0 4570 232 265
26285 26286 3x150 Flex 39,3 50,0 5720 267 305
26287 26288 3x185 Flex 43,4 55,0 6955 300 335
26295 26296 3x240 Flex 50,7 62,0 9150 355 375
G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G1,5
Part number for oil resistant SHF2 cable: Table continues on next page
4 + code from above table ➞ 4xxxxx
12
0,6/1kV CABLES
G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G16
0,6/1kV CABLES
LKSM-HF 0,6/1kV Number of Cross- Nominal Current Min. bending
conductors & section of outer Approximate Rating A radius fixed
Part number cross-section armour diameter weight kg/km at +45°C installation
Normal G-type n x mm2 mm2 mm mm
5/2016
25798 25799 24x2,5 15,7 26,0 1070 10 160
25768 25769 27x2,5 16,1 27,0 1165 10 165
26040 – 30x2,5 16,7 27,5 1265 10 170
25849 25850 37x2,5 18,1 30,0 1524 9 185
Other sizes on request.
G-type is with yellow/green earth conductor and marking on sheath is, for example, 3G16