0% found this document useful (0 votes)
257 views

Three Story Condominium Building: Engr. Najeb B. Pendiaman

This document summarizes the design standards and plans for a proposed three story condominium building. It includes sections on design standards, architectural plans, schedules, load calculations, assumed structural elements, wind and earthquake loads, slab design, reinforcement, and footing design. Design standards address density, setbacks, site design, structure design, landscaping, and compatibility with surroundings. Architectural plans show perspectives, floor plans, elevations, framing plans, and vicinity map. Load calculations determine dead and live loads based on NSCP 2015 tables.

Uploaded by

joshua ablin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
257 views

Three Story Condominium Building: Engr. Najeb B. Pendiaman

This document summarizes the design standards and plans for a proposed three story condominium building. It includes sections on design standards, architectural plans, schedules, load calculations, assumed structural elements, wind and earthquake loads, slab design, reinforcement, and footing design. Design standards address density, setbacks, site design, structure design, landscaping, and compatibility with surroundings. Architectural plans show perspectives, floor plans, elevations, framing plans, and vicinity map. Load calculations determine dead and live loads based on NSCP 2015 tables.

Uploaded by

joshua ablin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 57

THREE STORY

CONDOMINIUM
BUILDING

A Requirement Presented to
Engr. Najeb B. Pendiaman
Faculty of Department of Civil Engineering
College of Engineering
Mindanao State University – Marawi City

In Partial Fulfillment of the


Requirement for the Course
CVE 196 – CE Project 2
2nd Semester, 2021-2022

Submitted by:
Ruben S. Casinillo, Jr.
Joshua Rodrigo C. Ablin
May 27, 2022
TABLE OF CONTENT

Title Page
Condominium Design Standard 1
Architectural Plan 3
Schedules 9
Load Calculations 11
Assumed Slab Thickness, Beam Size, and Column Size 17
Wind Load 20
Earthquake Load 31
Slab Design 39
Spacing Reinforcement Bar 45
Design Footing 47
ETabs Parameters 50
Condominium Design Standards
The following standards shall apply to all condominium projects citywide, including specific plan
areas, which are approved after the effective date of the ordinance codified in this section. This section
provides minimum design and development standards for condominiums which are subject to approval of
a development plan permit in compliance with Chapter 17.42 and which shall be constructed in the
following manner:

     A.      Density. The maximum density of the underlying zoning district may be allowed only with
demonstration that the project meets or exceeds city standards and that superior design elements are
utilized.
     B.      Building Setbacks.
     1.      Structures shall be located on the project property to meet the requirements of the zoning district
for setbacks and distances between buildings except as provided herein. Setback requirements shall be
measured from the subdivision boundaries, common area boundaries and curb face of private streets
whichever is nearest as applicable. Where condominium structures are not located along a street, and are
located behind other structures, or where there are structures back to back, there shall be a minimum fifty-
foot separation between buildings and there shall be an unobstructed, minimum twenty-four foot wide
separation distance between buildings along the street, where it would be necessary to bring a fire truck to
a location within one-hundred sixty-five feet of any portion of the exterior walls of any condominium
structure.
     2.      In calculating the additional setbacks required for building heights above twenty feet, where
there is no property line from which to measure setbacks, the required separation distances between
buildings shall be increased pursuant to Section 17.20.100.
     C.      Site Design.
     1.      There should be an efficient and harmonious grouping of structures and space which encourages
the individuality of separate condominium dwelling units within a unifying design concept.
     2.      The applicant shall utilize site planning techniques and architectural treatments to reduce the
impact of building mass. Use of varied building heights, building articulation, landscaping, walls and
fences, screening and other similar techniques may be employed to achieve the goal of reduction of
building mass impacts.
     3.      All condominium lots shall be situated in such a way that noise impacts will be mitigated.
Dwellings shall be sound attenuated against present and projected noise to mitigate noise impacts on
outdoor living areas and in all habitable rooms.
     4.      Buildings shall be placed in a manner to allow streetscape building diversity. Clusters of
condominiums shall be sited in a manner that respects the natural topography and that avoids excessive
massing. Front setbacks of structures shall be varied by increasing some setbacks to the extent necessary
to create an interesting appearance from the street.
     5.      Private drives serving the clusters of single-family homes shall be curvilinear, either following
the natural contours, or in the event of a flat site, to avoid long straight-aways.
     6.      Condominium structures shall be offset to avoid linear arrangement of homes between clusters
and across streets.
     7.      The project shall establish safe, direct and convenient access to common amenity areas.

1
    
 8.      Private driveways serving four or less dwelling units having no parking within the travelway shall
have a minimum paved width of twenty-four feet.
     D.      Structure Design.
     1.      Building design shall integrate and equitably distribute details on sides of proposed structures
which face private streets, common areas and public rights-of-way as follows:
     a.      Light and shadow achieved through openings, projections, recesses and details;
     b.      Avoidance of large blank façades;
     c.       Roof lines shall vary by use of varying roof structural configurations and slopes.
     2.      Rear building elevations shall incorporate design features consistent with front building
elevations.
     E.      Landscaping.
     1.      Hierarchy of the circulation system shall be reinforced by landscaping. Project plans shall
identify opportunities and techniques for the creation of focal points where appropriate. Such
opportunities may include, but shall not be limited to, use of attractive hardscape elements, specimen
trees, water features or unusual plant groupings.
     2.      The use of special landscape treatments and/or thematic elements shall be used to embellish
distinguishable features of the condominium project.
     3.      The applicant shall enhance entry view corridors. Design treatments which enhance project
entries through the use of raised medians, additional landscaping, landscape theme and location of
recreational amenities may be required.
     4.      It shall be demonstrated that trees will be distributed on slopes, common areas and/or lots and
along private streets so as to interrupt and soften the silhouette of structures visible from outside the
project.
     5.      The natural vegetation and topography should be preserved where such natural features
contribute to the attractiveness of the project and compatibility within the neighborhood or district.
     F.      Compatibility with Surrounding Development.
     1.      The applicant shall design the project to create project edges which are compatible with adjacent
residential communities, which have been previously approved by the city. Similar structure heights,
comparable or more attractive perimeter walls, architectural features and landscaping improvements shall
be designed.
     2.      The design of the condominium structures and overall site plan should be compatible with the
physical characteristics of the site, with buildings adjacent to the site, and with the character of the
neighborhood or district. Design compatibility of buildings includes harmonious building style, form,
size, color, materials and relationship to site topography. A compatible design plan is one which preserves
the existing neighborhood character, facilitates efficient and convenient circulation, is functionally related
to the natural topography, utilizes natural characteristics of the site, and is an asset to the community.
     3.      Due consideration should be given to the impact of condominium development on the
neighborhood or district in which property is located. Development should be designed to minimize view
obstruction.

2
Architectural Plan
I. Perspective View

II.

Ground Floor Plan

3
III. 2nd and 3rd Floor Plan

IV. Rooftop Plan

4
V. Front and Back Elevation

5
VI. Left and Right Elevation

II. Foundation Plan

6
VIII. 2nd and 3rd Floor Framing Plan

IX. Roof Deck Framing Plan

7
XII. Vicinity Map

8
Schedules
I. Schedule of Beam

II. Schedule of Column

9
III. Schedule of Slab

IV. Schedule of Footing

10
Load Calculation
Dead Load
For the purpose of this design, NSCP 2015 Table 204-1 and 204-2 for the Minimum Design
Dead Load (KPa) is used.

11
12
Dead Load Parameters
 From Table 204-1 Minimum Densities for Loads from Materials
o Concrete Self Weight 23.6 kN/m3
 From Table 204-2 Minimum Design Dead Load
o Ceiling
 Gypsum board (0.5 in) 0.010 kPa
 Mechanical Duct Allowance 0.200 kPa
 Plaster on Tiles or Concrete 0.240 kPa
 Covering (Roof and Wall)
o Cement Tile 0.770 kPa
o Waterproofing Membranes
 Bituminous, Smooth Surface 0.070 kPa
 Liquid, applied 0.050 kPa
 Floor and Floor Finishes
o Ceramic or quarry tile (20 mm) 0.770 kPa
o Concrete Fill Finish (20 mm) 0.460 kPa
 Frame Walls
o Windows, glass, frames and sash 0.380 kPa
 Member Loads
o Exterior Walls (150 CHB) 3.11 kN/m per meter height
o Interior Wall (100mm CHB) 2.98 kN/m per meter height
 Elevator (Neglect for now)
 Slab Weight (100 mm height) 2.36 kN/m2

13
Live Load
For the purpose of this design, NSCP 2015 Table 205-1 for Minimum Uniform and
Concentrated Live Loads and Table 205-2 for Special Loads is used

14
15
Live Load Parameters
Under Table 205-1 Minimum Uniform and Concentrative Live Loads (kPa)
 Residential Areas
o Basic floor area 1.900 kPa
o Exterior balcony 2.900 kPa
o Storage 1.900 kPa
 Rest Room 1.900 kPa
 Roof deck
o Same as area served or occupancy 1.900 kPa.
 Stairs
o Exit Facilities 4.800 kPa

16
Assumed Slab Thickness, Beam Size, and Column Size
Assumed Slab Thickness
Since all the long-to-short span ratio (L/b) of the slabs are less than 2, then all the slabs
are considered a two-way slab.

 Slab Thickness 100 mm


 Slab Self-Weight 2.36 kN/m2

Beam Size and Column Size


Beam Group Beam Dimension (b x h) (mm)
B1 300 x 450
B2 350 x 450
B3 300 x 400
B4 250 x 400
Column Group Column Dimension (b x h) (mm)
C1 400 x 400
C2 300 x 300
C3 250 x 250

17
Design of Beams and Columns
Beam Reinforcement Design
Longitudinal Reinforcement
No. of Rebar to be Use =
Area∨Rebar
Sample Solution
Longitudinal Reinforcement (TOP) = 542 mm2 (Base on Etabs)
Longitudinal Reinforcement (BOTTOM) = 425 mm2 (Base on Etabs)
Area of Rebar (16) = 201.1 mm2
542
No. of Rebar to be Use = = 2.70 = 3 rebars at top
201.1
425
= = 2.11 = 3 rebars at bottom
201.1

Beam Stirrups Design


Stirrups Diameter (d) = 10 mm
Width of Beam = 300 mm
Depth of Beam = 450 mm
Length of Beam = 4000 mm
No. of legged Stirrups =2
( No . of Legged Stirrups )∗π∗d 2
Area of Shear Reinforcement =
4
Shear Reinforcing = 839.48 mm2/m (base on the data in Etabs)

Sample Computation Spacing of Rebar:

2∗π∗10 2
Area of Shear Reinforcement = = 157.08 mm2
4
1000 x Area of Shear Reinforcement
Spacing Required = =
Shear Reinforcing
1000 X 157.08
839.48

18
Spacing Required = 187.12 mm
Spacing to be Use = 150 mm

Computing Number of Rebar to be used on Beam


Calculation of Length or Beam to be applied with stirrups:
Total Beam Length
L(Cont.) =
3
Total Beam Length
L(Disc.) =
4
L(Center.) = Total Length – (Sum of calculated Lengths on both sides of the beam)
Calculated Beam Length
No. of Stirrups = be Use ¿+1
Spacing¿
Sample Computation:
Assume Continuous Beam:
4000
L(Cont.) = = 1333.33 mm
3
1333.33
No. of Stirrups = +1 = 9.88 = 10
150

Column Ties Spacing Computation


Smallest Value among the three:
=16 * Diameter of Rebar
= 48 * Diameter of Tie Bar
= Smallest Column Dimension
Sample:
For C1 = 400 x 400
= 16 * 16 = 256 = 250
= 45 * 10 = 450
= 400

19
Tie Spacing = 250 mm

Wind Load
To compute the wind load of the structure, steps provided in Table 207B.2-1 MWFRS
Wind Load for Enclosed, Partially Enclosed and Open Building of All Heights is used.

20
Nature of Occupancy
For the purpose of design, each structure shall be placed in one of the occupancy
categories listed in Table 103-1 of the National Structural Code of the Philippines. Based on the
function of the building, the structure falls under Occupancy Category IV: Standard Occupancy
Structure.

21
Wind Load
Basic Wind Load
Following map will be used to identify the basic wind speed for a building under standard
occupancy structure. Cabadbaran City is in the contour line of 310 kph wind basic velocity.

22
Wind Load Parameter
Wind Direction Factor (Kd)
The following table shows that the building structure has a wind directionality factor, Kd
of 0.85.

Exposure Factor
The structure falls under the category of Exposure B.

23
Topographic Factor (Kzt)
For simplicity of the design, kzt = 1.0 will be used.

Gust Effect Factor (G)


The gust-effect factor for a rigid building or other structures is permitted to be taken as
0.85.

24
Enclosure Classification
The structure is considered as an enclosed building as per defined in the NSCP 2015.

Internal Pressure Coefficient (GCpi)


The following table shows that the internal pressure coefficient, GCpi for an enclosed
building are (is) +0.18 and -0.18.

25
Velocity Pressure Exposure Coefficient, KZ or Kh

The following table will be used to determine the velocity pressure exposure coefficient,
Kz or Kh of every elevation.

Exposure B
o Elevation, z = 11,900 mm Kz = 0.7580
o Elevation, z = 7,200 mm Kz = 0.6520
o Elevation, z = 4,000 mm Kz = 0.5700

26
Velocity Pressure (qz or qh)

The Equation 207B.3-1 will be used to determine the velocity exposure of every
elevation.

For Exposure B
 Elevation, z = 11.9 m (level 3) qz = 2.929 kN/m2
 Elevation, z = 7.2 m (level 2) qz = 2.519 kN/m2
 Elevation, z = 4.0m (level 1) qz = 2.202 kN/m2

External Pressure Coefficient (Cp or C ) n

Since the structure is designed with roof deck, the following table shows external
pressure coefficient, Cp of walls.

27
The plan shown below is the structure’s horizontal dimension where the wind direction is
parallel to the transverse frame.

Value of L/B:

 Wind Parallel to Transverse Frame L/B = 36/16 = 2.25


 Wind Parallel to Longitudinal Frame L/B = 16/36 = 0.44

For the structure, the following will be used:


 Wind Wall (Cp) 0.800
 Leeward Wall (Cp)
o Wind parallel to traverse frame -0.270
o Wind parallel to longitudinal frame -0.460
 Side wall (Cp) -0.700

28
Calculated Total Wind Pressure, p (Windward + Leeward)
The total wind pressure on each building surface of the structure is calculated based on
Equation 207B.4-1.

29
 Wind Parallel to Traverse Frame
o Elevation, z = 11.90 m (level 3) 2.10 kPa
o Elevation, z = 7.200 m (level 2) 1.95 kPa
o Elevation, z = 4.000 m (level 1) 1.86 kPa
 Wind Parallel to Longitudinal Frame
o Elevation, z = 11.90m (level 3) 1.78 kPa
o Elevation, z = 7.200m (level 2) 1.63 kPa
o Elevation, z = 4.000m (level 1) 1.54 kPa
Distribution of Wind Force on each Frames
 Frame A and D (Outer Transverse Frame)
o Level 3 18.92 kN
o Level 2 17.59 kN
o Level 1 16.76 kN
 Frame B and C (Inner Transverse Frame)
o Level 3 37.84 kN
o Level 2 35.18 kN
o Level 1 33.52 kN
 Frame 1 and 3 (Outer Longitudinal Frame)
o Level 3 10.67 kN
o Level 2 9.79 kN
o Level 1 9.23 kN
 Frame 2 (Inner Longitudinal Frame)
o Level 3 21.35 kN
o Level 2 19.57 kN
o Level 1 18.46 kN

30
Earthquake Loads

Occupancy Category

For the purpose of earthquake-resistant design, each structure shall be placed in one of
the occupancy categories listed in Table 103-1 of the National Structural Code of the Philippines.
NSCP Table 208-1 assigns importance factors, I and I p. In this design we will use the 1.00 as the
value of importance factor for standard occupancy structures.

Site Geology and Soil Characteristics


Each site shall be assigned a soil profile type based on properly substantiated
geotechnical data using the site categorization procedure set forth by Section 208 and Table 208-

2 of NSCP.

31
Where the following soil profile type are define as follows:

For the purpose of this design, a soil type Sc is to be used.

Seismic Zone

The Philippine archipelago is divided into two seismic zones only as shown in figure
208.1 of the National Structural Code of the Philippines. Each structure shall be assigned a
seismic zone factor, Z, in accordance with Table 208-3 of the NSCP. In this design, our seismic
zone is ZONE 4 with a seismic zone factor, Z of 0.40.

32
Seismic Source Type
NSCP table 208-4 defines the types of seismic source. On the other hand, the location
and type of seismic sources to be used for design shall be established based on approved
geological data. In this design, the structure is approximated to be 5km from the Surigao Fault
System as shown in the map. Seismic Source Type A is assumed.

In Seismic Zone 4, each site shall be assigned near-source factors in accordance with
Tables 208-5 and 208-6 on the Seismic Source Type as set forth in Section 208.4.4.2 of the
National Structural Code of the Philippines.

33
Hence, the close distance to known seismic source is approximately 7.0 km for seismic
source type B as shown, for this purpose the Near-Source Factor Na is 1.20 and Nv is 1.60.

Seismic Design Coefficient


Each structure shall be assigned a seismic coefficient, Ca, in accordance with NSCP Table
208-7 and a seismic coefficient, Cv, in accordance with NSCP Table 208-8. In this design,
seismic coefficient Ca is 0.48 and seismic coefficient Cv is 0.90 .

34
Coefficient R and ΩO
The value for coefficient R and Ωo shall be taken from NSCP table208-11. In this design,
R has 8.5 value and Ωo has 2.8 value as assumed.

35
Structure Period

As per NSCP, the value of T shall be determined by two methods as specified in section
208.5.5.2. For this specific purpose, method A shall be used.
Method A:

hn = 11.4 m (measurement from the foundation top floor level)


Therefore, the Structure Period (T) shall be:
3/4
T = 0.0731 (11.4) = 0.454

 Earthquake Load Parameter (Summary)


o Seismic Importance Factor, I: 1.00
o Soil Profile Type: Sc
o Seismic Source Type: A
o Seismic Zone: 4
o Seismic Zone Factor, Z: 0.40
o Distance to Seismic Source: 5.0 km
o Near-Source Factor, Na: 1.20
o Near-Source Factor, Nv: 1.60
o Seismic Coefficient, Ca: 0.40
o Seismic Coefficient, Cv: 0.90
o Seismic Force Over-strength Factor, Ω0: 2.8
o Seismic Force Resisting Coefficient, R: 8.5
o Structure Period, T: 0.454

36
Seismic Load Calculation
Total Structure Weight
 Roof Deck Dead Load (kN)
o Parapet Wall 557.67
o Floor Dead Load 1746.36
o Beam Weight 1269.68
o Column Weight 184.36

Total: 3758.07
 3rd Floor Level
o Interior Wall 1793.36
o Exterior Wall 1044.96
o Floor Dead Load 2132.46
o Beam Weight 1269.68
o Column Weight 407.81

Total: 6648.27
 2nd Floor Level
o Interior Wall 1793.36
o Exterior Wall 1044.96
o Floor Dead Load 2132.46
o Beam Weight 1269.68
o Column Weight 407.81

Total: 6648.27
Total Dead Load of the Structure: 10,406.34 kN

37
Base Shear Calculation

o Base Shear (V) 2426.98 kN

o (V), Upper Limit 1224.98 kN


o Base Shear (V), Lower Limit 1030.23 kN
o Base Shear (V), Lowest Limit (Sz = 4) 626.83 kN
o USED BASE SHEAR (V) 1224.98 kN

38
SLAB DESIGN
One-Way or Two-Way Slab?
The table shows all the slab dimensions of the structure: 2nd floor to the Roof deck.
As a result, all the slabs will be designed as a Two-Way Slab.

La(mm) Lb(mm) lb/la Remarks


4000 4000 1 Two-way Slab
3000 4000 1.33 Two-way Slab
2500 4000 1.6 Two-way Slab

Where:
La = Shorter length of the Slab
Lb = Longer Length of the Slab

Thickness of the Slab

Using the ACI moment coefficient method, the overall thickness of the slab is
100mm.

Using 4000x4000 slab since it has the longest spans:


h = (1/180) (panel parameter)
h = (1/180) (4000x4)
h = 88.88 mm
h = 100 mm

ASSIGN LOAD TO THE SLAB


Total Dead Load
For 2nd and 3rd Floor Level
 From table 2014-1 Minimum Densities for Loads from Material
o Concrete Self-Weight 23.6 kN/m3
o Slab Weight 2.36 kPa
 From Table 204-2 Minimum Design Dead Load
o Ceiling
 Gypsum Board (0.5 in) 0.010 kPa
 Mechanical Duct Allowance 0.200 kPa
 Plaster on Tiles or Concrete 0.240 kPa

39
o Floor Finishes
 Ceramic or Quarry Tile (20 mm) 0.770 kPa
 Concrete Fill Finish 0.460 kPa
o Frame Partition/Frame Walls
 Windows, glass, frames, and sash 0.380 kPa
 Total Dead Load 4.420 kPa

For Rooftop Level


 Slab Weight 2.360 kPa
 Ceiling
o Gypsum Board (0.5 in) 0.010 kPa
o Mechanical Duct Allowance 0.200 kPa
o Plaster on Tiles or Concrete 0.240 kPa
 Floor Finish
o Concrete Fill Finish 0.460 kPa
 Covering
o Bituminous, Smooth Surface 0.070 kPa
o Liquid, Applied 0.050 kPa
 Total Dead Load (RTL) 3.390 kPa

Total Live Load


For 2nd and 3rd Floor Level
 Under Table 205-1 Minimum Uniform and Concentrative Live Load
o Residential Areas
 Basic Floor Area 1.900 kPa
 Exterior Balcony 2.900 kPa
 Rest Room 1.900 kPa
 Storage 1.900 kPa
o Stairs
 Exit Facility 4.800 kPa
 Total Live Load 13.40 kPa
For Rooftop Level
 Roof Deck
o Same area served or occupancy 1.900 kPa
 Total Live Load (RTL) 1.900 kPa

40
Load Combination
2nd Floor and 3rd Floor Level
 U = 1.4(D) 6.118 kPa
 U = 1.2(D) + 1.6(L) 26.74 kPa

Rooftop Level
 U = 1.4(D) 4.750 kPa
 U = 1.2(D) + 1.6(L) 7.108 kPa

Assuming 1 meter wide strip:


 For 2nd and 3rd Floor Level
o Dead Load 4.420 kN/m
o Live Load 13.400 kN/m
o U 26.744 kN/m
 For Rooftop Level
o Dead Load 3.390 kN/m
o Live Load 1.900 kN/m
o U 7.108 kN/m

41
ULTIMATE MOMENT LOAD, MU (ACI moment coefficient method)

Shown below are the slabs labelled according to the different cases, for 2nd floor to the
roof deck, which will be used to determine the coefficients for moments in slabs. Dimensions are
shown according to the clear span of both long and short spans.

Case 2:
4000 x 3000 mm
4000 x 2500 mm
Case 4
4000 x 4000 mm
Case 9
4000 x 4000 mm

42
4000 x 3000 mm
4000 x 2500 mm

Sample Computation:
Case 4: 4000 x 4000 mm
Solution:
m = 4000/4000 = 1
Coefficients:
 Table 1 – Coefficient for Negative Moments in Slabs
o Ca,neg 0.050
o Cb, neg 0.050
 Table 2 – Coefficient for Dead Load Positive Moments in Slabs
o Ca,DL 0.027
o Cb, DL 0.027
 Table 3 – Coefficient for Live Load Positive Moments in Slabs.
o Ca, LL 0.032
o Cb, LL 0.032

Moments
 For shorter length (la)
o Mneg(Cont.) = Ca,negwula2 = 0.050*26.744*42 = 26.102 kN.m
M ¬(Cont .)
o Mneg(Disc.) = = 8.701 kN.m
3
o Mpos = Ca,DLwDLla2 + Ca,LLwLLla2
o Mpos = (0.27)(4.42)(4)2 + (0.32)(13.40)(4)2 = 7.746 kN.m
 For longer length (lb)
o Mneg(Cont.) = Cb,negwulb2 = 0.050*26.744*42 = 14.121 kN.m
M ¬(Cont .)
o Mneg(Disc.) = = 4.707 kN.m
3
o Mpos = Cb,DLwDLlb2 + CbLLwLLlb2
o Mpos = (0.027)(4.42)(4)2 + (0.032)(13.40)(4)2 = 7.146 kN.m

43
44
SPACING REINFORCEMENT BAR
Solve Ru:
Mu
Ru =
Φb d 2
Where:
Mu = Factor Moment (N.mm)
b = 1000 mm
ɸ = .90 (for flexural reinforcement slab)
d(short) = h – clear cover – db/2
d(long) = h – clear cover – 3db/2
db = 12 mm ɸ (nominal diameter of bars)
Clear cover = 20mm

Solving Steel Ratio (ρ):


f 'c
ρ = 0.85 ¿
fy
Where:
fy = 280 MPa
f’c = 21 MPa

Solving for Spacing (S):


Asbars
S=
ρd
Where:
S = center-to-center Spacing of the re-bars of the slab
π 2 π
Asbar = d b = ( 12mm )2 = 113.10 mm2
4 4

45
The least of the following will be used as Snew:
Snew = 2(h) = 2(100) = 200 mm
= 3(h) = 3(100) = 300 mm
= 450 mm
= solved value of S

The new S must be the greater than the greatest of the following:
S = 50 mm + 12 mm = 62 mm
= 2db = 24 mm
4
= d
3 agg

Sample Solution:
@ Slab A; short-span (la), Mpositive
12
dshort = 100 – 20 - = 74
2
6
6.327∗10
Ru = 2 = 1.284
0.9∗1000∗74

21
ρ = 0.85 ¿ = 0.00476
280
113.10
S= = 321.08
0.00476(74)
S = 200 mm

46
Design of Footing

Material Properties:
Reinforced Yield Strength of Stee (fy) 280 MPa
Concrete Compressive Strength (f’c) 27.58 MPa
Concrete Unit Weight (γc) 23.6 kN/m3

Soil Properties:
Allowable Soil Pressure (SBC) 200 kPa
Soil Unit Weight (γs) 20 kPa
Depth of Excavation (h) 1 meter
Column Footing
Column Width 400
Column Length 400

Sample Computation (Isolated Footing Design)


For F1:
P (Factored) = 275 kN
P = Pf/1.5 = 183.33 kN
f’c = 27.58 MPa
Fy = 275.79 MPa
Bar Diameter = 12.00 mm
Column Width= 400 mm
SBC = 250 kN/m2
Footing Depth = 1000 mm
Sample Solution:

47
Area of Footing Required:
0.10 ( P )+ P 0.10 (183.33 )+183.33
= = = 1 m2 = 1000 mm2
SBC 200

Footing Dimension:
= √ Area of Fooring Required = √ 1.00 = 1 m
Therefore Footing Dimension = 1m x 1m
Thickness of the Footing:
l f −l c 2 1
Factor Moment (Mu) = P * lf * ( ) * ; lf = length of footing, lc = length of
2 2
column
1−0.4 2 1
= 183.33 * 1 * ( ) * = 8.25 kN.m
2 2

Thickness of footing (d) =


√ Mu
'
0.138∗f c∗l f


6
= 8.25 x 10 = 50 mm = 200 mm
0.138∗27.58 .∗1000
- Footing Thickness must be at least 200 mm (NSCP 2015: 414.3.2.1)
Check for 2-way Shear
Factored Soil Pressure (q) = P/Area of Footing Required
= 183.33/1000 = 0.183 MPa
Factored Shear Force = (q(lf2 – (lc + d)2) )/1000
= (0.183(10002 – (400 + 200)2))/1000 = 117.12 kN

Concrete Shear Strength (γc) = 0.25 √ f ' c = 0.25 √ 27.58 = 1.31

Concrete Shear Resistance = 4(lc + d) * d * γc


= (4(400 + 200) * 200 * 1.31)/1000 = 628.8 kN
Concrete Resistance > Factored Shear Force OK!
Checking Gross Bearing Capacity
Concrete Unit Weight = 23.6 kN/m3

48
Soil Unit Weight = 18 kN/m3
Gross Bearing Capacity = (23.6*1*1*0.20) + (20 *(1-0.20)*1*1) + 183.33
= 204.054 kPa
Gross Bearing Capacity < Gross Bearing Capacity OK!

Final Total Thickness of Footing (df) = Assumed Footing Thickness + Clear Cover + Diameter
of Rebar + Diameter of Rebar/2
= 200 + 50 + 12 +12/2 = 268 mm
= 300 mm is used as Thickness of Footing
Find Area of Steel Reinforcement
l f −l c
l f −l c
Mu = q(lf * * 2 )
2
2
1−0.40
1−0.40
= 0.183(1 * * 2 )
2
2
= 8.235 kN.m
Number of bars to be used
Ast fy
Mu = 0.87 fy Ast d (1− )
bdf ' c
Ast = 173.11 mm2
Ast (min) = 0.12/100 * lc *df
= 0.12/100 * 1000 * 300
= 360 mm2
Therefore use Ast = 360 mm2
Number of bars to be used = Ast / Area or rebar = 360/113.10 = 3.18 = 4

1000−50−50−12
Spacing = = 296 mm or use 250 mm spacing c/c
4−1

49
ETab Parameters

Column and Beam Design

The The model is set to the following codes specifically the Concrete Design Code which
is ACI 318-14.

The materials are


defined such as A615Gr40 (for
rebar), 4000Psi and 3000 Psi for
concrete).

50
51
Beams and Columns used are the dimensions stated earlier in the paper.

52
53
54
55

You might also like