Cyclic Fatigue Resistance of VDW - ROTATE and Reciproc Blue Nickel-Titanium Files at Root Canal Temperature
Cyclic Fatigue Resistance of VDW - ROTATE and Reciproc Blue Nickel-Titanium Files at Root Canal Temperature
doi:10.34172/joddd.2020.032
https://joddd.tbzmed.ac.ir
Original Article
N
also manufactured by VDW. This innovative system
ickel‒Titanium (NiTi) instruments with
offers a wide range of instruments for different
superelasticity and shape memory have been
clinical cases: (15/.04), (20/.05), (25/.04), (25/.06),
preferred by clinicians, especially in the preparation
(30/.04), (35/.04), (40/.04), (50/.04), (60/.04),
of curved root canals since their first use by Walia et
(30/.06), (35/.06), and (40/.06). Instruments with an
al1 in 1988. Despite the increased physical properties
S-shaped cross-section are used with clockwise (CW)
of NiTi instruments, instrument fracture in the root
rotary motion, as indicated by the system name.7
canal, albeit infrequent, has been a serious concern
The most important difference between these two
for clinicians.2,3 Cyclic fatigue, one of the two main
similar instrument systems produced by the same
instrument fracture mechanisms, results from stress
manufacturer is that one is a reciprocal single-file
due to successive tension/compression periods at the
system, and the other is a rotary multi-file system. In
canal’s most inclined point.4
addition, these instrument systems perform cutting
In recent years, manufacturers have developed
by rotating in different directions.
production techniques that are patented and
In the first instance, after the glide path was
not fully disclosed to achieve better mechanical
performed, the canal preparation in the reciprocal
properties in NiTi instruments, such as fracture
motion was completed with a single NiTi instrument
resistance, cutting efficiency, and flexibility. The
by Yared.8 After this, the reciprocal motion became
Reciproc Blue system (VDW, Munich, Germany), a
increasingly popular, and instruments designed to be
single-instrument system, has a similar morphology
used in reciprocal movement became commercially
to the previous Reciproc system. However, unlike
available. When researchers compared reciprocal
the Reciproc system produced with M-wire
and rotary movements, it was seen that the
technology, the Reciproc Blue system is produced
reciprocal movement had some advantages in some
with a new heat treatment technology. As a result,
parameters.9
the system has a blue titanium oxide layer on its
Studies that examined the effect of continuous
surface, with increased flexibility and cyclic fatigue
rotation and reciprocal movements with different
resistance.5,6 The VDW.ROTATE system (VDW,
*Corresponding author: Ahmet Demirhan Uygun. Tel:+90- 02722167900 Email:[email protected].
©2020 The Author(s). This is an open access article distributed under the terms of the Creative Commons Attribution License (http://creativecommons.
org/licenses/by/4.0/), which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Demirhan Uygun
178 | J Dent Res Dent Clin Dent Prospects , 2020, Volume 14, Issue 2
Demirhan Uygun
the absence of difference between the groups, might higher fracture resistance than the rotation motion
indicate that standardization is achieved in the group, consistent with previous studies.10,11,25,26
cyclic fatigue resistance test. However, previous literature shows that the stress
Previous studies have shown that reciprocal concentrated on the NiTi instruments in the
movement prolongs the files’ usage time compared continuous rotation motion at a certain point
to the rotation movement.11,20 Therefore, in a study decreases by reversing the reciprocal motion,
performed to compare these files with similar and how this difference occurs has not been fully
physical properties, it was predicted that the VDW. revealed. Gambarini et al27 claimed that a full
ROTATE instruments used with rotation motion rotation cycle was completed with more reciprocal
might have lower fracture resistance than Reciproc cycles in the reciprocating movement, and that
Blue instruments used with reciprocal motion. To the reciprocating cycle required more time for one
eliminate the effect of motion kinematics, the VDW. full rotation. Therefore, lower speed and a higher
ROTATE instruments were tested and compared number of reciprocating cycles provide increased
with the motion of the Reciproc Blue, and the cyclic fatigue resistance.
number of groups increased to three. According to the results of this study, the cyclic
Reciproc Blue files are recommended for use fatigue resistance of Reciproc Blue instruments was
in a reciprocation mode where the angles of significantly higher than that of VDW.ROTATE
motion and speed cannot be changed in endo instruments, both in rotation and reciprocation
motors manufactured by the same company. In kinematics. To the best of our knowledge, as there
the reciprocation mode, the motion and speed is no study on VDW.ROTATE in the literature, the
angles are CCW = 150° and CW = 30° and 300 current results cannot be compared with those of
rpm, respectively.21 However, VDW.ROTATE is any other study. The VDW.ROTATE instrument
recommended for CW continuous rotation at 300- consists of a series of heat-treated, blue instruments,
400 rpm.22 Since the direction of cutting edges of such as the Reciproc Blue instrument.
the instruments is designed differently, one cuts Moreover, in the scanning electron microscopy
the dentin in CW while the other cuts the dentin images of the fractured surfaces, it has an S-shaped
in CCW direction. Accordingly, this study used an cross-section similar to Reciproc Blue (Figure 1).
endo motor capable of reciprocal and rotary motion However, there was a statistical difference between
in clockwise and counterclockwise directions, and these two instruments, and the findings of this study
in which angles and speed can be adjusted. could be attributed to differences in instrument
Previous studies on endodontic motors have designs. This must be confirmed by further in vitro
claimed that endo motors do not work under investigations.
the reciprocation angle values given by their
Conclusions
manufacturer. First, Fidler23 claimed that the
kinematic of reciprocation is more complicated Within the limitation of the study, Reciproc Blue
than it seems, as it is described only using angles and instruments exhibited significantly more cyclic
rotational speed, and the actual kinematic values of fatigue than VDW.ROTATE instruments. When
VDW Silver (VDW, Munich, Germany) and ATR using the VDW.ROTATE instruments with the
Tecnika (Tecnika, Pistoia, Italy) endodontic motors reciprocal motion, the resistance to fracture
differ from those declared by their manufacturers.
Irmak and Ozgur24 showed inconsistency between
the reciprocal angle values of the endodontic motor
X-Smart Plus and the values given by the company.
They also showed differences in reciprocal angle
values between new and used endodontic motors. In
the present study, the Genius Eze endodontic motor
was preferred because it can rotate and reciprocate
clockwise and counterclockwise at different angles.
However, to the best of our knowledge, there was
no study examining the accuracy of this motor’s
reciprocal motion values. This is the only limitation
of the present study. Considering the possibility
that the endodontic motor does not work under
the actual values, the Reciproc Blue R25 and VDW.
ROTATE (25.06) instruments were compared in Figure 1. Scanning electron microscopic appearances
the same reciprocating mode. Only the direction of of the Reciproc Blue and VDW.rotate instruments
after cyclic fatigue testing. The fracture surface view
the motion was changed. The data obtained in the of Reciproc Blue (A), VDW.rotate (C), and a high-
study were assumed to be accurate, and statistical magnification view of the Reciproc Blue (B) and VDW.
evaluation was performed. rotate (D) instruments. The crack initiation origins
In this study, reciprocal motion groups exhibited (arrows) are observed in the fracture surface.
J Dent Res Dent Clin Dent Prospects, 2020, Volume 14, Issue 2 | 179
Demirhan Uygun
180 | J Dent Res Dent Clin Dent Prospects , 2020, Volume 14, Issue 2