Panelboards

Selection and
application guide

usa.siemens.com/panelboards
Contents
PAGE
Introduction 2
General Specifications 3-5
Catalog Numbering System 6

1
SECTION A detailed Table of Contents is located
at the beginning of each product section.

P1 Panelboards

2
SECTION

3
SECTION

P2 Panelboards

P3 Panelboards

SECTION

SECTION

5 4 P4 Panelboards

P5 Panelboards

6
SECTION

7
SECTION
C1/C2 Panelboards

Miscellaneous
Introduction

This new generation of products from Siemens offers the high • The highly flexible P2 provides options to fit the most
level of engineering and innovation you’ve come to expect from demanding specifications.
the leader in power distribution technology. The “P Series” line of • Sized more like a lighting panel, the P3 packs the power of a
panelboards offers a stepped approach to power distribution. distribution panel in a space-saving, highly flexible design.
• The P4 is a mid-sized distribution panel that allows both fusible
Additional strength has been added to an already rugged and and circuit breaker branch and main devices.
durable panelboard family. Engineered specifically to provide • The powerful P5 anchors the high end of the series. With
maximum flexibility, the new designs simplify wiring and reduce larger fusible and circuit breaker branch and main devices, the
material requirements making them easier to install and less venerable P5 delivers maximum power and flexibility to larger
costly than competitive products. At the heart of the product distribution systems.
line is the extensive research and technology found among
Siemens circuit protection devices – both fusible switches and Siemens also offers a number of specialty panels, like column
molded case circuit breakers. panels. Don’t see a panel to meet your requirements? Ask your
Siemens representative about our custom capabilities.
The line is anchored by the innovative P1. Featuring the industry’s
most flexible designs, the P1 virtually eliminates common Features Overview
errors, such as feed direction, and main lug versus main breaker. P Series lighting panel features include Fas-Latch trim, which is
Increasing distribution is simplified by the ability to add feed-thru popular among installers; the jacking screw system, that permits
lugs. The Revised P1 design introduced in January 2015 has added adjustments even after wiring has been installed; our exclusive
extended Circuits up to 66 and has available smaller Enclosures split neutral, and more. Many panelboards have the capability of
with no Subfeed option for added flexibility. mixing and matching breakers of different sizes and ratings – or
changing from main lug to main breaker, or adding subfeed
Subsequent steps in the P Series offer increased capacity and breakers without changing the box size. Other models accept
more design options: a wide range of fuse types, including Siemens exclusive
Vacu-Break® technology.
Table G-1 – Key Panelboard Features
RP1 P2 P3 P4 P5
Lighting and Appliance Applications(Pre 2008NEC) • • • • •
Power Panelboard Applications — • • • •
Convertible From Top Feed To Bottom Feed Or Vice Versa • — — — —
Change From Main Lug To Main Breaker Or
• — — — —
Add Subfeed Without Changing Enclosure Size 3
Space-Saving, Horizontally Mounted Main Breaker Up To 250 Amps Up To 250 Amps Up To 250 Amps • •
Short-Circuit Rating Label Giving Performance Level • • • • •
Standard Aluminum Ground Assembly • • • • •
Blank End-Walls Standard 1 • • • • •
Bolted Current-Carrying Parts • • • • •
Split Neutral • • • • •
Connection Accessible From Front • • • • •
Screw-Type Mechanical Lugs • • • • •
Time-Reducing Wing Nuts To Secure Interior Without Tools • • • • •
Main and Branch Devices Connected With
Case-Hardened Hardware • • • • •
Flush Lock, Concealed Door Hinges/Trim Screws • • • — —
Symmetrical Interior Mounting Studs
• • • • •
To Eliminate Upside-Down Mounting of Box
Interior Height Adjustment For Flush Applications • • • • •
Mix and Match Fusible Switch Circuit Breaker Capability — — — • •
Shallow Depth 5.75” 5.75” 7.75” 10.00” 12.75”
Accepts A Wide Range Of Fuse Types — — — • •
Accepts Vacu-Break Fusible Switch — — — • •
Accepts A Wide Range Of Circuit Breakers • • • • •
Accepts ACCESSTM Communications Tie-In 2 — • • • •
Optional Compression Lugs • • • • •

• Standard 2 Panelboards equipped with Siemens Sensitrip® 3 For Revised P1, only when Subfeed Space is selected,
1 KO’s available on P1 and P2 – 5.75” Deep x 20” Wide circuit breakers or Power Meters can be Interior Part Number ends with "T". When "N" is at
boxes and P3 7.75” deep X 24” wide boxes. integrated into Siemens ACCESS™ Electrical end there is no Subfeed Space available.
Monitoring System.

2
General Specifications

Class CTL Panelboards (when applicable) capable of connecting up (3) #10 max. wires. The #6 holes can
Class CTL panelboards incorporate physical features which, in accept up to (2) #12 max. wires. Copper ground assemblies
conjunction with the physical size, configuration, or other means (ECGK, ICGK) are rated for copper wire only and have the same
provided in Class CTL circuit breakers, are designed to prevent wiring capacity as the Al/Cu connectors.
the installation of more over current protective poles than the
number for which the device is designed and rated, per UL 67 Standard neutrals, like standard main lugs, are also rated for
and National Electrical Code (NEC) NFPA70. copper or aluminum wire. The neutral cross bar material follows
the selection bus. Copper neutral lugs are rated for copper cable
Service Entrance Equipment only and available as a price added option.
When a panelboard is used as service entrance equipment, it Lug Data
must be located near the point of entrance of building supply Space Required for Mounting of Double Panels
conductors. In a main lugs only panel, the number of breakers
or switches directly connected to the main bus must be limited Wall Wall

to six. In a panel having a main breaker or main switch, the


number of circuits are not limited except as may be provided
under other panelboard requirements, i.e., lighting and
Shown mounted in wall Shown mounted on surface of wall
appliance branch circuit panelboards. Also, panels must include
a connector for bonding and grounding neutral conductor. Use two or more panelboards with feed-thru or subfeed lugs
when:
Panelboard Code Data (where applicable) 1. Lighting and appliance panelboards are required with
Lighting and appliance branch circuit panelboards were included more than 42 circuits in areas where the zone code has
in editions of the National Electrical Code prior to 2008. The not been accepted.
NEC no longer distinguishes between lighting and appliance 2. More circuit mounting space is required than is provided in
panelboards and power panelboards; therefore, eliminating the the largest box size.
42 circuit branch circuit limitation. Adoption of this code vary
by a state or local jurisdiction. Consult the local code authorities Feed-Thru Lugs Subfeed Lugs or Double Lugs
to determine if this has been adopted in that area. Fig. G-1 Fig. G-2

Integrated Equipment Short Circuit Rating


The term “Integrated Equipment Short Circuit Rating” refers to the
application of series connected circuit breakers in a combination
that allows some breakers to have lower individual interrupting
ratings than the available fault current. This is permitted as long
as the series combination has been tested and certified by UL.

Standards
NEC: 2014 (where accepted)
Feed-thru lugs are mounted at the opposite end of the main bus
NEMA: PB1
from the main lugs or main breaker and are used to connect two
UL: 67, 50 and 50E. Listed by Underwriter’s Laboratories, Inc.,
or more panelboards to the incoming feeder. The feeder cables
under “Panelboards” File #E2269, and #E4016. Meets
are brought into Panelboard 1 and connected to the main lugs
Federal Specification W-P-115c.
or main breaker. Cables interconnecting the two panelboards are
connected to the feed-thru lugs in Panelboard1 and are carried
Wire Connectors
over the main lugs in Panelboard 2. This arrangement could be
Standard wire connectors in Siemens panels are suitable for copper
reversed with the main lugs located at the top and the feed-thru
or aluminum cables rated 60/75 degree. Copper main lugs are a
lugs at the bottom of the panel. Subfeed lugs are mounted
price-added option for most panel types and some Circuit Breakers
directly beside the main incoming lugs and are used to connect
(check with Siemens sales for availability). It should be noted that
two or more panelboards to the incoming feeder. The feeder
most copper lugs will only accept copper cables. Some applications,
cables are brought into Panelboard 1 and connected to the main
100% rated devices in particular, require that the cable and
lugs. Another set of cables that are the same size are connected
connectors be rated 90 degree but are sized to the 75 degree tables.
to the subfeed lugs of Panelboard 1 and are carried over the
main lugs of Panelboard 2.
Standard ground connectors are also suitable for copper or
aluminum wire. Ground connector assemblies (EGK, IGK) have
(7) 1/0 max. and (15) #6 max. connections. The 1/0 holes are Note: P1 panelboards do not have subfeed lugs available. If this
configuration is needed, move to a P2 or P3 panelboard.

3
General Specifications

Bussing Sequence As standard, branch breakers shall be mounted at the top of


Interiors are designed to accommodate top or bottom feed. the panel with “spaces” at the bottom, regardless of the direction
Regardless of which is specified, the uppermost pole is always panel is fed.
on “A” phase; the second pole down is always on “B” phase,
and the third pole down is always on ”C” phase (assuming All breakers have bolted connections except plug-in type. The
3Ø panel). panel design provides bracing up to 200,000A IR UL short
circuit rating. Case-hardened, high performance, thread rolling
screws are used on branch bus.

Circuit Breaker Lighting Circuit Breaker Lighting or Circuit Breaker Distribution


T Panel Type P1 Distribution Panel Types P2/P3 Panel Type P4/P5
Fusible Switch Distribution
Panel Type P4/P5

Table G2 – Panelboard Ratings

Description P1 Revised P2 P3 P4 P5
Max. Voltage 480Y/277V AC Max. 600V AC Max. 600V AC Max. 600V AC Max. 600V AC Max.
600Y/347V AC 8 500V DC Max. 500V DC Max. 500V DC Max. 500V DC Max.
System 1-Phase, 2-wire 1-Phase, 2-wire 1-Phase, 2-wire 1-Phase, 3-wire 1-Phase, 3-wire
1-Phase, 3-wire 1-Phase, 3-wire 1-Phase, 3-wire 3-Phase, 4-wire 3-Phase, 4-wire
3-Phase, 3-wire 3-Phase, 3-wire 3-Phase, 4-wire 3-Phase, 3-wire 3-Phase, 3-wire
3-Phase, 4-wire 3-Phase, 4-wire 3-Phase, 3-wire
Mains
Main Lugs 125A-400A 125A-600A 250A-800A 400A-1200A 800A-1200A
Main Breaker 100A-400A 100A-600A 225A-600A 400A-800A 800A-1200A
Main Switch — — — — 200A-1200A
Circuits 18, 30, 42, 54, 66 18, 30, 42, 54, 66 — — —
78, 90 1
Branch Ratings 15-125A 15-400A 15-400A 15-800A MCCB 15-1200A MCCB
30-200A Fusible 30-1200 Fusible
B
Branch BL, BLH, HBL, BQD, BL, BLH, HBL, BQD, BQD6, BL, BLH, HBL, BQD, BQD6, All 15-600A MCCBs, All 15-1200A MCCBs,
Disconnect BQD6, BLE, BLEH, QJ25, QJH25, QJ2H5, QR25, QJ26, QJH26, QJ2H6, QR26, VL MG at 800A and 30-600A VB switches
Devices BLF2, BLHF2, HBLF2, BLFB, QRH25, HQR25, HQR2H5, ED2, QRH26, HQR26, HQR2H6, 30-200A VB switches and 400-1200A HCP
BLHFB, BAF2, BAFH2, ED4, HED4, ED6, BLE, BLEH, ED2, switches
HBAF2, BGL, BLF2, BLHF2, HBLF2, BLFB, ED4, HED4, ED6, BLHF,
NGB 7, HGB 7, LGB 7 BLHFB, BAF2, BAFH2, HBAF2, BAF2, BAFH2, HBAF2, BGL,
BGL, NGB, HGB, LGB NGB, HGB, LGB, NEB, HEB
Subfeed ED2, ED4, ED6, HED4, HED6, JD6, HJD6, JD6, HJD6, — —
Circuit QJ2, QJH2, QJ2H, QR2, JXD6, HJXD6, JXD6,
Breakers 2 3 QRH2, HQR2, HQR2H, FD6, FD6, HFD6, FD6, HFD6,
HFD6, FXD6, HFXD6 FXD6, HFXD6 FXD6, HFXD6
Enclosure 26, 32, 38, 44, 50, 56 26, 32, 38, 44, 50, 56, 56, 62, 68, 74, 80 60, 75, 90 60, 75, 90
Heights @250A (660, 813, 965, 62, 68, 74 (1422-2032) (1524, 1905, 2286) (1524, 1905, 2286)
Inches ± (mm) 1118, 1270, 1422) (660-1880)
56, 62, 68, 74 @400A
(1422, 1575, 1727, 1880)
Standard Fas-Latch ± 1 Piece Fas-Latch ± 1 Piece Fas-Latch ± 1 Piece Four Piece 4 Four Piece 4
Trims Surface or Flush Surface or Flush Surface or Flush Surface or Flush Surface or Flush

1 Functional pricing is based on circuits shown. 3 JD and FD breakers are mounted vertical. 6 A maximum of (6) QJ/QR breakers may be mounted
However, the panel can be figured with less circuits. Limitations apply. in a P3 panel and are twin mounted.
2 P1 can have max. 1 subfeed breaker when Subfeed 4 Trim ring provided for flush applications. 7 P1 panels with xGB breakers are limited to xGB
Space is available. P2 and P3 can have up to (2) FD 5 A maximum of (4) QJ/QR breakers may be mounted branch devices only. BL and BQD frames may not be
subfeed breakers. in a P2 Panel and are single mounted. mixed in this panel type.
8 Factory assembled P1 has capability of 600Y/347V
AC system when proper breakersare installed.
4
General Specifications

Table G3 – Typical Panelboard Modifications


Lighting and Distribution Panelboards Distribution Panelboards
Description P1 P2 P3 P4 P5
Box
Standard Standard Standard
Type 1 Standard Standard
(20" W) (20" W) (24" W)
Type 1 Enclosure with Hood P • • • •
Type 1 w/Gasket between box and front • • • — —
Type 2 Enclosure - Drip Tight (this is not available) — — — — —
Type 3R/12 • • • • •
Type 4, 4X (size varies by type/material) • • • • •
Wider Box (check w/factory for custom options not shown) • (24”W) • (24”W) • (custom) • (custom) • (custom)
Deeper Box (check w/factory for custom options not shown) — • (7.75”D) • (custom) • (custom) • (custom)
Front
Front with Door Standard Standard Standard • •
4-piece Front — — — Standard Standard
4-piece Front w/Hinged Gutter Covers — — — • •
Hinged-to-Box Front • • • (see Door-in-Door) (see Door-in-Door)
Door-in-Door Front • • • • •
Common Front (custom - multi section applications) • (custom) • (custom) • (custom) — —
Special Locks • (custom) • (custom) • (custom) • (custom) • (custom)
Nameplate (mounting provisions provided as Std - P1/P2/P3)
• • • • •
- Nameplate text is configured in COMPAS with limitations.
Interior
Aluminum Equipment Ground Bar Standard Standard Standard Standard Standard
Copper Equipment Ground Bar • • • • •
Insulated Equipment Ground (CU or AL) • • • • •
Subfeed Lugs — • • • •
Feed-Thru Lugs • • • • •
Split Bus — • • • •
Compression Lugs • • • • •
Copper Lugs • • • • •
200% Neutral • • • 400 - 600A 400 - 600A
Temperature Rated - Aluminum1 Standard Standard Standard Standard Standard
Temperature Rated - Copper 1 • • • • •
750 Ampere / in. - Aluminum — • • • •
1000 Ampere / in. - Copper — • • • •
Tin Std./ Tin Std./
Copper Plating Tin Silver Silver
Silver Opt. Silver Opt.
External
Remote Control Switches • • • •
Mounted
External
Time Clocks • • • •
Mounted
Circuit Breaker Shunt Trips • • • • •
R, J and T Fuse Clips — — — • •
All aluminum bus is tin-plated. • Available as an option. — Not Available

Table G4 – UL Fuse Classes 1


Interrupting
Class Amperes Volts Ratings (kA) l2t, li Circuits
H 1-600 250 and 600V or less AC 10 — Less than 10,000A Available
l•t – RK5 up to 100A,
K5 2 1-600 250 and 600V or less AC 100 Feeder circuits
li – RK5 up to 100A
J 1-600 600V or less 200 l•t – Low, li – Low Feeder circuits (motor load small %)
RK1 1/10 - 600 600V or less and 250V or less 200 l•t – Slightly >J, li – Slightly > J Feeder circuits (motor load small %)
RK5 1/10 - 600 600V or less and 250V or less 200 l•t – > RK-1, li – > RK-1 Motor starting currents a factor
1 - 800,
T 300 and 600V or less AC To 200 l•t – Low, li – Low Non-Motor loads
1 - 1200
L 601 - 1200 600V or less 200 l•t – Low, li – Low Mains, feeder circuits

1 Per UL 67. 2 Fuses do not prohibit the use of Class H type fuse in switch.

5
Catalog Numbering System
Catalog Numbering System
Type of Panel
P1, P2, P3, P4, P5
Voltage and System*
C = 208Y/120 3Ø 4 W Wye AC - All R = 415/240 3Ø 4 W Wye AC - All
E = 480Y/277 3Ø 4 W Wye AC - All S = 440/250 3Ø 4 W Wye AC - All
D = 240 3Ø 3 W Delta AC - All L = 600/347 3Ø 4 W Wye AC - All
F = 480 3Ø 3 W Delta AC - All T = 230 3Ø 3 W Delta AC - All
G = 600 3Ø 3 W Delta AC - P2, P3, P4, P5 W = 380 3Ø 3 W Delta AC - P2, P3, P4, P5
I = 347 3Ø 3 W Delta AC P2, P3, P4, P5 1 = 24V DC 1-Pole Branches Only - P2, P3, P4, P5
B = 240/120 3Ø 4 W Delta BØ High Leg AC - P2, P3, P4, P5 2 = 24V DC 2-Pole Branches Only - P2, P3, P4, P5
Q = 240/120 3Ø 4 W Delta CØ High Leg AC - P2, P3, P4, P5 3 = 48V DC 1-Pole Branches Only - P2, P3, P4, P5
A = 120/240 1Ø 3 W Grounded Neutral AC - All P4 = 48V DC 2-Pole Branches Only - P2, P3, P4, P5
H = 120 1Ø 2 W Grounded Neutral AC - P2, P3, P4, P5 5 = 125V DC 1-Pole Branches Only - P2, P3, P4, P5
J = 240 1Ø 2 W No Neutral AC - All N = 125V DC 2-Pole Branches Only - P2, P3, P4, P5
Y = 125 1Ø 2 W Grounded Neutral AC - P2, P3, P4, P5 O = 125/250V DC 2-Pole Branches Only - P2, P3, P4, P5
Z = 500 2W DC - P2, P3, P4, P5 P = 125/250V DC 2 & 3-Pole Branches - P2, P3, P4, P5
K = 220/127 3Ø 4 W Wye AC - All U = 120V AC 3Ø3W - All
M = 380/220 3Ø 4 W Wye AC - All V = 240V 3Ø3W Grounded B Phase - P2, P3, P4, P5
*For any voltage system not listed, check with sales for availability.

Circuits or Enclosure Height


P1 – 18, 30, 42, 54, 66 P3 – 56, 62, 68, 74, 80
P2 – 18, 30, 42, 54, 66, 78, 90 P4, P5 – 60, 75, 90
Main Lug (ML), Main Breaker
(See Main Breaker Table coding below), Main Switch (MS)

Amperage
100–400A = P1 250 – 800A = P3
100–600A = P2 400 –1200A = P4, P5
Bus Bus Bus 2
Code Material Plating P1 1 P2 P3 P4 P5
A Temp rated Al. Tin-Plated • • • • •
B 750A/sq. in. Al. Tin-Plated • • • • •
C Temp rated Cu. Tin-Plated • n/a n/a n/a n/a
E Temp rated Cu. Silver-Plated n/a optional optional • •
F Temp rated Cu. Tin-Plated n/a • • • •
G 1000A/sq. in. Cu. Tin-Plated n/a • • optional optional
H 1000A/sq. in. Cu. Silver-Plated n/a optional optional • •
• Indicates default for this bus type.
Feed Location T = Top B = Bottom

Mounting
S = Surface
F = Flush. Flush trims extend 1 1/2" beyond the base box dimensions on P1, P2 and P3 and 2" on P4 and P5 panels.
2
Subfeed Space Indicator (for P1 only) T = Subfeed Space Included N = No Subfeed Space

Main Breaker Coding


Breaker Breaker Breaker Breaker Breaker Breaker Breaker Breaker
Code Type Code Type Code Type Code Type Code Type Code Type Code Type Code Type
BL BL H1 HHFD6 SC SCJD6 S2 SHLD6 S5 SHMD6 SD SHND6H M5 HMG N7 NNG
BH BLH H3 HHFXD6 SX SHJD6 SL SLD6 S6 SHMD6H SN SND6 M2 HMX N1 NNX
BR BLR G2 HGB SY SHJD6H QJ QJ2 SM SMD6 AY SND6H M8 HMY N4 NNY
HB HBL G3 LGB SJ SJD6 Q2 QJ2H AX SMD6H J6 HJG M6 LMG QR QR2
BQ BQD NB NGB SH SJD6H QH QJH2 CN CND6 J7 HJX M3 LMX Q4 QRH2
B6 BQD6 CJ CJD6 CL CLD6 C9 CMD6 C6 CND6H J5 HJY M9 LMY Q5 HQR2
CE CED6 6H HHJD6 HH HHLD6 CH CMD6H HN HND6 J9 LJG M4 NMG Q6 HQR2H
E4 ED4 H9 HHJXD6 XH HHLXD6 HM HMD6 HT HNXD6 J3 LJX M1 NMX Q7 QR2-MCS
E6 ED6 H6 HJD6 HL HLD6 HR HMXD6 HX HNXD6H J8 LJY M7 NMY
H4 HED4 H5 HJXD6 HO HLXD6 HS HMXD6H ND ND6 L3 LLK N8 HNG
CF CFD6 H7 HJXD6H HP HLXD6H MD MD6 NX NXD6 J2 NJG N2 HNX
FD FD6 J6 JD6 L6 LD6 MX MXD6 NT NXD6H J1 NJX N5 HNY
FX FXD6 JD JXD2 LX LXD6 MH MXD6H SR SCND6 J4 NJY N9 LNG
HF HFD6 JX JXD6 LH LXD6H SO SCMD6 ST SCND6H L2 HLK N3 LNX
H2 HFXD6 JH JXD6H S1 SCLD6 SQ SCMD6H AD SHND6 L7 NLK N6 LNY
1 Standard bussing in P1, P2 and P3 panels is tin-plated for aluminum and
copper. Standard bus is temperature rated to the maximum amperage in
the panel.
2 Not available for Revised P1 xGB interiors.

6
SECTION 1
P1 Panelboards
Description Page
General Information 1-2 Side Gutter Wiring Space 1-6
Selection and Application 1-2 Branch Breaker Side Gutters 1-6
Application 1-3 – 1-6 Typical Catalog Numbers 1-7
Main Breaker Panel Size Selector 1-3 Main Lugs Only 1-7
Main Breaker Selection 1-3 Main Circuit Breaker 1-7
Main Lugs Size Selector 1-4 Standard Enclosures 1-7
Branch Circuit Breakers 1-4 Standard Modifications 1-8
Subfeed Breakers 1-5 Connector Modifications 1-9
Breaker Mounting Kits 1-5 Compression Lugs 1-9
Lug Kits 1-5 Enclosure Modifications 1-9
Main Breaker Gutter Dimensions 1-6 Remote Switch Modifications 1-9
Main Lug End Gutter Dimensions 1-6 Dimensions 1-10
Type P1 Panelboards

P1 panelboards are pre-engineered to accept the most common Voltage – 480Y/277 Vac max.
modifications without increasing box height. The enclosure size
is determined by the number of circuits as shown in the Main Lug Amperage – 400 amp max.
Table P1-5 or the Main Circuit Breaker Table P1-3. All P1 Revised
main lug or main breaker panelboards have space built-in to Short Circuit Rating – 200 KAIC max. symmetrical or equal
accept either feed-thru lugs equal to the panel rating, one sub- to the lowest rated device installed unless a series rating is
feed circuit breaker up to 250 amperes or a surge suppressor indicated. Panels with subfeed or feed-thru lugs without a
(TVSS) without increasing box height. (When ordered with main device, circuit breaker or fusible unit, are limited to a
sub-feed, space indicated by a “T” at end of nterior number). three-cycle rating. The three-cycle rating for the P1 panel is
limited to 22 KAIC. Note that the main device may be mounted
Note the following features, all found in the innovative P1 remote from the panel.
lighting panelboards:
• Symmetrical Interiors - No top or bottom! To change from Bussing – The P1 panel meets the majority of the markets
top to bottom (or vice-versa), simply invert the interior. The bussing requirements. The standard bussing is temperature
deadfront labeling is always right-side up. rated aluminum. The rating is per the requirements of UL 67–
• First in the Industry Ratings of 125 through 400A main lug and the standard for panelboards. All aluminum bussing is tin-plated.
main breaker. Field convertible from main lug to main breaker Optional bussing for the P1 panel is temperature rated copper.
and vice versa – with no increase in enclosure height. The copper bus option for this panel is tin-plated.
• Field adaptability of feed-thru lugs or subfeed circuit breaker
without increasing enclosure size. Weight – Approximate
• Neutral system is field upgradeable to 200% capacity – Total panelboard weight when filled with a normal quantity of
another industry first. breakers and accessories is about 3 lbs. (1 kg) per inch (54g per
• Five circuit sizes means only three box heights, regardless mm) of box height
of main configuration through 250 amp and an additional
four circuit versions-- and boxes available at 400 amps.
• Suitable for use as service entrance given compliance Table P1-1 – Box Material Gauge
with NEC. Width Height (inches) Gauge Steel
• Bonding provisions are shipped with each panel. 20” (250A) 26, 32, 38, 44, 50, 56 #16
• 240V and 480Y / 277V for versions utilize identical boxes (400A) 56, 62, 68, 74
and fronts.
Table P1-2 – Trim Material Gauge
Enclosure – Standard Type 1 enclosure is 20" wide x 5.75" 20” (250A) 26, 32, 38, 44, 50, 56 #14
deep. Box Height is determined only by the number of (400A) 56, 62, 68, 74
circuits, not by main lug or main circuit breaker. See chart
P1-5 for box height.

Selection and Application


3 Easy Steps for Selecting a Siemens P1 Panelboard
Step 1 Step 2
Determine voltage, system, amperage Create a catalog number by following A unique feature of P1 panels is that they
and interrupting rating of branch the Panelboard Catalog Numbering can accommodate either feed-thru lugs
devices, and modifications if any. System on page 6. The BL branch breakers or one subfeed circuit breaker (up to
were selected from the branch breaker 250A) without any addition to box
Example for standard lighting selection table on page 1-4. height. For our example changing the
panelboard: branch circuits to 39-20/1 and 1-125/3,
1-P1C42ML250ATST we have the following:
Amperage 250A
42-20/1 BL
Voltage 208Y/120V 1-P1C42ML250ATST
System 3Ø4W Step 3 39-20/1 BL
Main Main Lug Select enclosure size by the number 1-125/3 QJ2/QR2
Branches 10K AIR, 42-20/1 of circuits as shown in the panelboard Box size – 44” high
Modifications None dimensional chart on page 1-6.
Feed Location Top The QJ2/QR2 subfeed was selected from
Mounting Surface 1-P1C42ML250ATST the table of subfeed breakers on page 1-
42-20 BL 5. The box height remains the same.
Box size – 44” high

1-2
SECTION 1
Application
Type P1 Panelboards

Table P1-3 – Main Breaker Panel Size Selector


Dimensions in inches (mm)
Unit Space
Max Main Max # Max # Box
Ampere Breaker Connections suitable Poles Poles FT NFT Height Weight in
rating Types for Cu or Al FT 1 NFT A A B Lbs. (kg)
18 – 9 26 (661) 90 (41)
#8-#6 AWG Cu or Al 18 30 9 15 32 (813) 105 (48)
#8-6 AWG Cu or
BL2, BLH2, 30 42 15 21 38 (965) 120 (55)
100 #8-4 AWG Al
HBL2, BQD2 42 54 21 27 44 (1118) 135 (61)
#8-#1 AWG Cu or
#6-#1/0 AWG Al 54 66 27 33 50 (1270) 150 (67)
66 – 33 – 56 (1423) 165 (73)
15-30 amp: #14-#6 Cu or
NGB2, HGB2, #12-#6 Al
18 – 9 26 (661) 95 (43)
LGB2 35-125 amp: #6-1/0 Cu
#4-2/0 Al
125 ED2, ED4 #14-#10 AWG Cu or 18 30 9 15 32 (813) 110 (50)
#12-10 AWG Al 30 42 15 21 38 (965) 125 (57)
42 54 21 27 44 (1118) 140 (64)
ED6, HED4 #3-3/0 Cu or #1-2/0 Al 54 66 27 33 50 (1270) 155 (71)
HED6 #3-3/0 Cu or #1-2/0 Al 66 – 33 – 56 (1423) 170 (78)
QJ2, QJH2, 18 – 9 26 (661) 95 (43)
QJ2H #6 AWG-300 Kcmil (Cu) or
225 18 30 9 15 32 (813) 110 (50)
QR2, QRH2, #4 AWG-300 Kcmil (Al)
HQR2, HQR2H 30 42 15 21 38 (965) 125 (57)
42 54 21 27 44 (1118) 140 (64)
FXD6, FD6, #6 AWG-350 Kcmil (Cu) or
250 54 66 27 33 50 (1270) 155 (71)
HFD6, HFXD6 #4 AWG-350 Kcmil (Al)
66 – 33 – 56 (1423) 170 (78)
– 30 – 15 56 (1423) 172 (78)
JD6, JXD6, 30 42 15 21 62 (1575) 190 (86)
3/0-500 Kcmil (Cu) or
400 HJD6,
4/0-500 Kcmil (Al) 42 54 21 27 68 (1728) 208 (95)
HJXD6
54 66 27 33 74 (1880) 226 (104)
Note: Main breakers use breaker connectors. For sizes, see breaker connector chart. 400 amp main breaker panel has wire bending space for 600 kcmil cables as standard.
Use 750 Kcmil lug if 600 Kcmil cable is to be used.
1 400A 66 circuit only available with non-feed thru versions.
2 BL, BLH, HBL, BQD, and xGB mount in unit space and count in max. # of poles.

T
Table P1-4 – Main Breaker Selection
Max. Ir (kA) at Main
Breaker / Breaker
Ampere rating Types 240 AC 480/277V AC Code Additional Trip Values
BL (STD) 10 – BL 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100
BLH 22 – BH 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100
100
HBL 65 – HB 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100
BQD 65 14 BQ 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100
NGB (STD) 100 25 NB3 50, 60, 70, 80, 90, 100, 110, 125
HGB 100 35 G23 50, 60, 70, 80, 90, 100, 110, 125
125 LGB 100 65 G33 50, 60, 70, 80, 90, 100, 110, 125
ED4 (STD) 65 25 E4 50, 60, 70, 80, 90, 100, 110, 125
HED4 42 42 H4 50, 60, 70, 80, 90, 100, 110, 125
QJ2 (STD) 10 – QJ 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
225 QJH2 22 – QH 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
QJ2H 42 – Q2 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
QR2 10 – QR 100, 110, 125, 150, 175, 200, 225
QRH2 25 – Q4 100, 110, 125, 150, 175, 200, 225
225
HQR2 65 – Q5 100, 110, 125, 150, 175, 200, 225
HQR2H 100 – Q6 100, 110, 125, 150, 175, 200, 225
FXD6 (STD) 65 35 FX 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250
FD6 65 35 FD 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250
250
HFD6 100 65 HF 70, 80, 90, 100, 150, 175, 200, 225, 250
HFXD6 100 65 H2 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250
JXD2 65 – JD 300, 400
JXD6 (STD) 65 35 JX 200, 225, 250, 300, 350, 400
400 JD6 65 35 J6 200, 225, 250, 300, 350, 400
HJD6 100 65 H6 200, 225, 250, 300, 350, 400
HJXD6 100 65 H5 200, 225, 250, 300, 350, 400
        
3 [*%LQWHULRUVDUHQRWDYDLODEOHDVQRQIHHGWKUXZLWKRXWVXEIHHGVSDFH

1-3
Application
Type P1 Panelboards

Table P1-5 – Main Lugs Size Selector

Dimensions in Inches (mm)


Maximum Max # Max #
Ampere Poles Poles FT NFT Box Height Weight in MLO Connectors
Rating NFT NFT A A B” lbs. (kg) Suitable for Cu or Al
18 – 9 26 (661) 90 (41)
18 30 9 15 32 (813) 105 (48)
125 30 42 15 21 38 (965) 120 (55) (1) #6 AWG - 350 kcmil
(or) 42 54 21 27 44 (1118) 135 (61) (CU or AL)
250 54 66 27 33 50 (1270) 150 (68)
66 — 33 — 56 (1422) 165 (75)
— 30 — 15 56 (1422) 120 (55)
30 42 15 21 62 (1575) 135 (61) (2) #3/0-250 kcmil or
400
42 54 21 27 68 (1728) 150 (68) (1) #3/0-600 kcmil
54 66 27 33 74 (1880) 165 (75)

Table P1-6 – Branch Circuit Breakers


Max. Interrupting Rating (kA)
Breaker Number
Type of Poles 120V 120/240V 240V 277V 480/277V Available Trip Values
1 10 — — — — 15, 20, 25, 30, 35, 40, 45, 50, 55, 60, 70
BL 2 — 10 — — — 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100
3 — — 10 — — 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100
BLR 2 — — 10 — — 15, 20, 30, 40, 50, 60, 70, 90, 100
1 10 — — — — 15, 20, 30
BL, HID
2 — 10 — — — 15, 20, 30
1 — 22 — — — 15, 20, 30, 40, 50, 55, 60, 70
BLH 2 — 22 — — — 15, 20, 30, 40, 50, 60, 70, 90, 100
3 — — 22 — — 15, 20, 30, 40, 50, 60, 70, 80, 90, 100
1 — 65 — — — 15, 20, 30, 40, 50
HBL 2 — 65 — — — 15, 20, 30, 40, 50, 60, 70
3 — — 65 — — 15, 20, 30, 40, 50, 60, 70, 80, 90, 100
1 10 — — — — 15, 20, 30
BLF
2 — 10 — — — 15, 20, 30, 40, 50, 60
1 22 — — — — 15, 20, 30
BLHF
2 — 22 — — — 15, 20, 30, 40, 50, 60
2 10 — — — — 15, 20, 30
BG 1
3 — 10 — — — 15, 20, 30
1 10 — — — — 15, 20, 30
BLE
2 — 10 — — — 15, 20, 30, 40, 50, 60
BLEH 1 22 — — — — 20, 30
2 — 22 — — — 15, 20, 30, 40, 50, 60
BAF 1 10 — — — — 15, 20
BAFH 1 22 — — — — 15, 20
1 — 65 — 14 — 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100
BQD 2 — 65 — — 14 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100
3 — — 65 — 14 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100
1 100 — — 25 — 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100, 1253
NGB 2 3 2 — 100 100 — 25 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100, 1253
3 — 100 100 — 25 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100, 1253
1 100 — — 35 — 15, 20, 25, 30, 35, 40, 50, 60 70, 80, 90, 100, 1253
HGB 2 3 2 — 100 100 — 35 15, 20, 25, 30, 35, 40, 50, 60 70, 80, 90, 100, 1253
3 — 100 100 — 35 15, 20, 25, 30, 35, 40, 50, 60 70, 80, 90, 100, 1253
1 100 — — 65 — 15, 20, 25, 30, 35, 40, 50, 60 70, 80, 90, 100, 1253
LGB 2 3 2 — 100 100 — 65 15, 20, 25, 30, 35, 40, 50, 60 70, 80, 90, 100, 1253
3 — 100 100 — 65 15, 20, 25, 30, 35, 40, 50, 60 70, 80, 90, 100, 1253
1 Two-pole breaker is one phase and neutral. Three-pole is two phases and neutral.
2 P1 panel with xGB branch devices will not accept BL or BQD frames in the same panel as branch devices.
3 The New Revised P1 (18 circuit 250A only) is limited to 100A per connection (200A per pair) when installing Branch Breakers across from one another. All other
configurations allow 125A per connection max. (250A per pair max.)
NOTE: BL, HBL and BQD breakers are mounted in common mountings in 3” or (6) pole increments.

1-4
SECTION 1
Application
Type P1 Panelboards

Table P1-7 – Subfeed Breakers


Max. Interrupting Rating (kA)
Breaker Number
Type of Poles 240V 480Y/277V Available Trip Values
QJ2 2, 3 10 — 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
QJH2 2, 3 22 — 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
QJ2H 2, 3 42 — 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
QR2 2, 3 10 — 100, 110, 125, 150, 175, 200, 225
QRH2 2, 3 25 — 100, 110, 125, 150, 175, 200, 225
HQR2 2, 3 65 — 100, 110, 125, 150, 175, 200, 225
HQR2H 2, 3 100 — 100, 110, 125, 150, 175, 200, 225
ED4 2, 3 65 18 15, 20, 25, 30, 35, 40, 45, 50, 55, 60, 70, 80, 90, 100, 110, 125
HED4 2, 3 100 42 15, 20, 25, 30, 35, 40, 45, 50, 55, 60, 70, 80, 90, 100, 110, 125
FXD6 2, 3 65 35 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250
FD6 2, 3 65 35 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250
HFD6 2, 3 100 65 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250
HFXD6 2, 3 100 65 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250

Table P1-8 – Breaker Mounting Kit


Main or Subfeed w/o Breaker Table P1-10 – Copper Neutral Lug Kits – 250A
Original P1 Revised P1 Original P1 Revised P1
Amp Catalog Catalog No. of Catalog Catalog
Rating Breaker Frames Service Number Number Circuits Description Number Number
100A BQD 3 Phase MBKBC3 Use Back-fed 18 CNLK18 Use 30 ckt kit
100A BL, BLH, HBL 1 Phase MBKBL1 Main Label 30 2 or 4 Branch Neutral Strips, CNLK30 CNLK30A
Kit # MBKBFA 3
3 Phase MBKBL3 (includes 42 1 Main Neutral Lug, Hardware CNLK42 CNLK42A
125A NGB, HGB, LGB 1 Phase MBKNB1 "MAIN" label 54, 66 — CNLK54A
and instructions)
3 Phase MBKNB3
ED4, ED6, HED4, HED6 1 Phase MBKED1 MBKED1A
125 Table P1-10A – 2/0 Neutral Lug Kits – 250A and 400A
3 Phase MBKED3 MBKED3A
QJ2, QJH2, QJ2H 1 Phase MBKQJ1 MBKQJ1A Original P1 Revised P1
225
3 Phase MBKQJ3 MBKQJ3A No. of Catalog Catalog
225A 2 QR2, QRH2, HQR2, 1 Phase MBKQR1 MBKQR1A Circuits Description Number Number
HQR2H 3 Phase MBKQR3 MBKQR3A 18 — Use 30 ckt kit
FXD6, FD6, HFD, HFXD6 1 Phase MBKFD1 MBKFD1A 30 2 or 4 Branch Neutral Strips, — LNLK30A
250
3 Phase MBKFD3 MBKFD3A 42 Hardware — LNLK42A
JXD6, JD6, 1 Phase MBKJD1 MBKJD1A 54, 66 — LNLK54A
400 1
HJD6, HJXD6 3 Phase MBKJD3 MBKJD3A
1 400 amp kit is for main—only not allowed for subfeed breaker.
2 Although QR is rated 250A, it is limited to 225A in panelboard.
3 Back-fed occupies branch space.

Table P1-9 – Lug Kits Main or Feed-Thru Table P1-11 – 200% Neutral Lug Kits – 250A
Original Revised P1
Original P1 Revised P1
Amp Catalog Catalog
No. of Catalog Catalog
Rating Material Wire Range Service Number Number
Circuits Description Number Number
Al (1) #6 AWG- 1 Phase MLKA1 MLKA1A 18 2NLK18 Use 30 ckt kit
350 Kcmil (Cu or Al) 3 Phase MLKA3 MLKA3A
30 2 or 4 Branch Neutral Strips, 2NLK30 LNLK30A
Cu (1) #6 AWG- 1 Phase MLKC1 MLKC1A
250 42 1 Main Neutral Lug, Hardware 2NLK42 LNLK42A
350 Kcmil (Cu or Al) 3 Phase MLKC3 MLKC3A
1 Phase 4MLKA1 4MLKA1A 54, 66 — LNLK54A
AL (2) 1/0 - 250 Kcmil
or (1) #2 AWG 600 Kcmil 3 Phase 4MLKA3 4MLKA3A
400
Cu (2) 1/O - 4/0 1 Phase 4MLKC1 4MLKC1A Table P1-12 – 200% Neutral Lug Kits – 400A
or (1) 1/0 600 Kcmil 3 Phase 4MLKC3 4MLKC3A
(1) AL 1/0-750 Kcmil 1 Phase — 4MLKA1B Original P1 Revised P1
(2) AL/CU 250 kcmil No. of Catalog Catalog
400 AL max. Circuits Description Number Number
(max. (1) 600 Kcmil 3 Phase — 4MLKA1B 18 42NLK18 N/A
wire) 30 2 or 4 Branch Neutral Strips, 1 Main 42NLK30 42NLK30A
42 600 kcmil Neutral Lug, Hardware 42NLK42 42NLK42A
NOTES: Original P1 kits will not work with Revised P1 starters if the chart shows
different part numbers for each. 54, 66 — 42NLK54A
Revised P1 kits will not work with Original P1 starters if the chart shows different
part numbers for each.

1-5
Application
Type P1 Panelboards

Table P1-13 – Main Breaker Gutter Dimensions Inches (mm)


Max. Interrupting Rating (kA) Neutral Location
Main Breaker 20” wide box 24” wide box 20” wide box
BL, BLH, HBL, BQD 2 8.500 (216) 3 10.500 (267) 3 10.500 (267)
NGB, HGB, LGB 2 8.000 (203) 3 10.000 (254) 3 10.500 (267)
ED2, ED4, ED6, HED4 6.125 (156) 8.125 (206) 10.500 (267)
QJ2, QJH2, QJ2H 6.500 (165) 8.500 (216) 10.500 (267)
QR2, QRH2, HQR2, HQR2H 6.500 (165) 8.500 (216) 10.500 (267)
FD6, FXD6, HFD6, HFXD6 5.250 (133) 7.250 (184) 10.500 (267)
JD6, JXD6 1 15.000 (381) 15.000 (381) 26.500 (674)
1 JD frame mounted vertically.
2 For Revised P1, use Side Gutter Wiring Specs Table P1-15. These are back-fed main breakers.
3 These dimensions are for Original P1 as a reference only, not for Revised P1.

Table P1-14 – Main Lug End Gutter Dimensions Inches (mm)


Amp End Gutter Neutral Location
Rating 20” wide box 24” wide box 20” wide box 24” wide box
125 9.500 (242) 9.500 (242) 10.500 (267) 10.500 (267)
250 9.500 (242) 9.500 (242) 10.500 (267) 10.500 (267)
400 25.500 (648) 25.500 (648) 26.750 (680) 26.750 (680)
NOTE: Feed-thru lug and neutral wire bending space is 15.000” and 16.250” respectively on 400A panel.

Table P1-15 – Side Gutter Wiring


Space Inches (mm) (Fig P1-1) Fig P1-1
Reference Panel Panel
Letter Width 20” Width 24”
Optional
A2 6.375 (162) 8.375 (213)
B2 5.500 (140) 7.500 (191)
C2 5.000 (127) 7.000 (178)
D1 6.125 (156) 8.125 (206)
E1 6.500 (165) 8.500 (216)
F1 5.250 (133) 7.250 (184)
1 Subfeed mounting limit 1 per panel. Panel Width
2 For all Revised P1 panels using BL/BQD or xGB 20 in. (508 mm)
breakers as mains in back-fed position, use this
chart for wiring space.

Table P1-16 – Miscellaneous Parts and Accessories


Catalog Catalog
Number Description Number Description
BK1 Bonding Kit for 400A max. Original P1 Panels EBF1 NEB/HEB Filler Plate
BK1A Bonding Kit for 400A max. Revised P1 Panels P1SCRWS Package of 42 breaker mounting screws for P1
BK2 Bonding Kit for S1/S2 400 & 600 DFFP1 1” Branch circuit filler plate (suitable for replacing QF3 in P1
BK3 Bonding Kit for S3 Panel thru P5 Panelboards and Switchboards)
IMK1 Interior Adjusting Kit P1CONBPHCU1 Connector Kit – 6 pcs. B-phase Copper
11-1824-01 Directory Card Holder P1CONBPHAL1 Connector Kit – 6 pcs. B-phase Aluminum
12-1110-01 Directory Card P1CONBPHAL1 Connector Kit – 6 pcs. B-phase Aluminum
MCHK Metal Card Holder Kit P1CONACPHCU1 Connector Kit – 6 pcs. A or C-phase Copper
NEMA PB1.13 NEMA Instruction Book 11-506-01 P1CONACPHAL1 Connector Kit – 6 pcs. A or C-phase Aluminum
NBK03 Number Strips 1-42. Stick-on type: Use w/P1 series Panels MBKORFK P1/Revised P1 Filler for 1PH/3PH QR. Horizonal mount only.
NBK04 Number Strips 43-84. Stick-on type: Use w/P1series Panels SEBKRP1V12 FD, QJ, QR Service Entrance Barrier Kit (Revised P1)
NBK05 Number Strips 85-126. Stick-on type: Use w/P1series Panels SEBKRP1V22 ED Service Entrance Barrier Kit (Revised P1)
NBK06 Number Strips 127-168. Stick-on type: Use w/P1series Panels SEBKRP1V32 BQD Service Entrance Barrier Kit (Revised P1 - back-fed)
EGK AL Ground Bus 44 Connections SEBKRP1V42 xGB Service Entrance Barrier Kit (Revised P1) - back-fed
ECGK CU Ground Bus 44 Connections SEBKRP1P2P3V12 JD, LD Service Entrance Barrier Kit (RP1, P1, P2, P3)
IGK Insulated AL Gound Bus 1 Replacement parts.
ICGK Insulated CU Gound Bus 2 Factory installed and Field installable Service Entrance Barrier kits are now available as
EWK1 End Wall Kit with Knockouts (20”W x 5.75” DP) required by UL67 (In COMPAS, you must select Service Entrance Required.)
3 Can be downloaded at no charge from webiste: link
EWK2 End Wall Kit with Knockouts (24”W x 7.75” DP)

1-6
SECTION 1
Typical Catalog Numbers
Type P1 Panelboards

Shown with Standard Mains, Top Fed and Surface Trim Replace fifth and sixth position in panelboard catalog number,
Catalog number is for aluminum main bus. For optional copper with alternate main breaker code. Use price adders from main
main bus change “A” in position 11 to “C”. breaker selection table. Horizontally mounted.
Panels are top feed, surface mounted. For bottom feed, change
“T” in position 12 to “B”. For flush mounting, change “S” in
position 13 to “F”.
Note: Original P1 was produced until mid 2014 and in July the revised P1 was introduced. All interior numbers that end with "T" or "N" are the new Revised interiors."T" at
end of catalog number indicates there is a Subfeed area available. "N" at end of catalog number indicates there is no Subfeed area available.

Table P1-17 – Main Lugs Only


Main Lug Only Original P1– Revised P1– Original P1– Revised P1– Original P1– Revised P1–
Subfeed Space Subfeed Space 1, 3 Subfeed Space Subfeed Space 1, 3 Subfeed Space Subfeed Space 1, 3, 4
Max Panel Max Box
Amp 1-Pole Height 208Y/120V 3-Phase, 208Y/120V 3-Phase, 120/240V 1-Phase, 120/240V 1-Phase, 480Y/277V 3-Phase, 480Y/277V 3-Phase,
Rating Circuits (in) 4-Wire Catalog # 4-Wire Catalog # 3-Wire Catalog # 3-Wire Catalog # 4-Wire Catalog # 4-Wire Catalog #
18 32 P1C18ML125ATS P1C18ML125ATST P1A18ML125ATS P1A18ML125ATST P1E18ML125ATS P1E18ML125ATST
30 38 P1C30ML125ATS P1C30ML125ATST P1A30ML125ATS P1A30ML125ATST P1E30ML125ATS P1E30ML125ATST
125 42 44 P1C42ML125ATS P1C42ML125ATST P1A42ML125ATS P1A42ML125ATST P1E42ML125ATS P1E42ML125ATST
54 50 N/A P1C54ML125ATST N/A P1A54ML125ATST N/A P1E54ML125ATST
66 56 N/A P1C66ML125ATST N/A P1A66ML125ATST N/A P1E66ML125ATST
18 32 P1C18ML250ATS P1C18ML250ATST P1A18ML250ATS P1A18ML250ATST P1E18ML250ATS P1E18ML250ATST
30 38 P1C30ML250ATS P1C30ML250ATST P1A30ML250ATS P1A30ML250ATST P1E30ML250ATS P1E30ML250ATST
250 42 44 P1C42ML250ATS P1C42ML250ATST P1A42ML250ATS P1A42ML250ATST P1E42ML250ATS P1E42ML250ATST
54 50 N/A P1C54ML250ATST N/A P1A54ML250ATST N/A P1E54ML250ATST
66 56 N/A P1C66ML250ATST N/A P1A66ML250ATST N/A P1E66ML250ATST
18 56 P1C18ML400ATS — P1A18ML400ATS — P1E18ML400ATS —
30 62 P1C30ML400ATS P1C30ML400ATST P1A30ML400ATS P1A30ML400ATST P1E30ML400ATS P1E30ML400ATST
400 42 68 P1C42ML400ATS P1C42ML400ATST P1A42ML400ATS P1A42ML400ATST P1E42ML400ATS P1E42ML400ATST
54 74 — P1C54ML400ATST — P1A54ML400ATST — P1E54ML400ATST
66 2 74 2 — P1C66ML400ATSN 2 — P1A66ML400ATSN 2 — P1E66ML400ATS 2

Table P1-18 – Main Circuit Breaker


18 32 P1C18BL100ATS P1C18BL100ATST P1A18BL100ATS P1A18BL100ATST P1E18BD100ATS P1E18BD100ATST
30 38 P1C30BL100ATS P1C30BL100ATST P1A30BL100ATS P1A30BL100ATST P1E30BD100ATS P1E30BD100ATST
100 42 44 P1C42BL100ATS P1C42BL100ATST P1A42BL100ATS P1A42BL100ATST P1E42BD100ATS P1E42BD100ATST
54 50 — P1C54BL100ATST — P1A54BL100ATST — P1E54BD100ATST
66 56 — P1C66BL100ATST — P1A66BL100ATST — P1E66BD100ATST
18 32 P1C18NB125ATS P1C18NB125ATST P1A18NB125ATS P1A18NB125ATST P1E18NB125ATS P1E18NB125ATST
30 38 P1C30NB125ATS P1C30NB125ATST P1A30NB125ATS P1A30NB125ATST P1E30NB125ATS P1E30NB125ATST
125 3 42 44 P1C42NB125ATS P1C42NB125ATST P1A42NB125ATS P1A42NB125ATST P1E42NB125ATS P1E42NB125ATST
54 50 — P1C54NB125ATST — P1A54NB125ATST — P1E54NB125ATST
66 56 — P1C66NB125ATST — P1A66NB125ATST — P1E66NB125ATST
18 32 P1C18QJ225ATS P1C18QJ225ATST P1A18QJ225ATS P1A18QJ225ATST P1E18FX225ATS P1E18FX225ATST
30 38 P1C30QJ225ATS P1C30QJ225ATST P1A30QJ225ATS P1A30QJ225ATST P1E30FX225ATS P1E30FX225ATST
225 42 44 P1C42QJ225ATS P1C42QJ225ATST P1A42QJ225ATS P1A42QJ225ATST P1E42FX225ATS P1E42FX225ATST
54 50 — P1C54QJ225ATST — P1A54QJ225ATST — P1E54FX225ATST
66 56 — P1C66QJ225ATST — P1A66QJ225ATST — P1E66FX225ATST
18 32 P1C18FX250ATS P1C18FX250ATST P1A18FX250ATS P1A18FX250ATST P1E18FX250ATS P1E18FX250ATST
30 38 P1C30FX250ATS P1C30FX250ATST P1A30FX250ATS P1A30FX250ATST P1E30FX250ATS P1E30FX250ATST
250 42 44 P1C42FX250ATS P1C42FX250ATST P1A42FX250ATS P1A42FX250ATST P1E42FX250ATS P1E42FX250ATST
54 50 — P1C54FX250ATST — P1A54FX250ATST — P1E54FX250ATST
66 56 — P1C66FX250ATST — P1A66FX250ATST — P1E66FX250ATST
18 56 P1C18JX400ATS — P1A18JX400ATS — P1E18JX400ATS —
30 62 P1C30JX400ATS P1C30JX400ATST P1A30JX400ATS P1A30JX400ATST P1E30JX400ATS P1E30JX400ATST
400 42 68 P1C42JX400ATS P1C42JX400ATST P1A42JX400ATS P1A42JX400ATST P1E42JX400ATS P1E42JX400ATST
54 74 — P1C54JX400ATST — P1A54JX400ATST — P1E54JX400ATST
66 2 74 2 — P1C66JX400ATSN 3 — P1A66JX400ATSN 2 — P1E66JX400ATSN 2

Table P1-19 – Standard Enclosures


Box Catalog Number
Height Type 1 Standard Trim
(in.) Box Surface Flush Type 3R Type 3R/12
26 B26 S26B F26B NR26 WP26 1 For all products without subfeed space - change
32 B32 S32B F32B NR32 WP32 "T" at end to "N" and reduce box size by 6".
38 B38 S38B F38B NR38 WP38 2 No sub-feed space only for 400A 66 circuit.
44 B44 S44B F44B NR44 WP40 3 BL/BQD/GB Type Mains are only available as Back-Fed. No
50 B50 S50B F50B NR50 WP50 kits are available for use in Main or Sub-feedspace. (GB
56 B56 S56B F56B NR56 WP56 Type includes NGB, HGB and LGB Breakers). These breakers
62 B62 S62B F62B NR62 WP62 take up branch circuit space.
68 B68 S68B F68B NR68 WP68 4 xGB interiors are not available as Non-Feed-Thru,
74 B74 S74B F74B NR74 WP74 without Subfeed Space.

1-7
Standard Modifications
Type P1 Panelboards

Panel Options • NEMA 3R/12 enclosures


Enclosures • NEMA 4 enclosures
• Extra gutter to sides or ends of the can • NEMA 4X enclosures
• 24" wide boxes • Special Keyed Locks (Keys are not supplied)
• Hinged trims
TEY
• Door-in-door trims
TEU1
• Screw to the box trims Cat 60 All fit Fast-Latch Front
ª Piano hinge trims LL803
• Painted boxes LL806
• Custom colors Yale 47 (NYC)
• Increase gauge trims and boxes National C413A
• Stainless steel trims and boxes, Type 1 Beck Lock 7-pin tumbler Special non-Fast-Latch
• Type 1 enclosures (Std 16 Gage / Optional 14 or 12 Gage) Southco 1/4 F astener
Corbin 1001 FAB7

• Panel skirts
• Gaskets between trim and box

Panel Modifications
• Main Bus • Bus mounted TVSS 1
Standard main bus is tin-plated aluminum. For copper main • Service entrance labeling /
bus, add from the table for each panel. Includes copper neutral • Grounding of Panelboards
cross bar. For copper neutral branch lugs, see miscellaneous. Ground Bars except for brazed to box are shipped with
/ /
• Compression lug for MLO 1 the panel interior factory mounted.
• Contactor mains - Mount in 23" enclosure ahead of panel. - Non-Insulated Equipment Ground Bar – Standard /
- Asco 920 through 225 amps 3 - Copper Non-Insulated Ground Bar
- Asco 911 through 150 amps 3 - Al Insulated Equipment Ground Bar
- Siemens LEN through 30 amps 3 - Cu Insulated Equipment Ground Bar
• Branch and main breaker accessories - Ground Bar Brazed to Box (recommended for painted boxes)
- Handle blocks • Shunt Trip on Main or Branch
- Handle locks BL2, BLH 2, HBL2, BQD 2, xGB 2 as branch use 1” unit space for
• Feed-thru lugs 1 shunt trip.
Cannot be used in conjunction with TVSS or subfeed
QJ2, QJ2H, QJH2, QR2, QRH2, HQR2, HQR2H, ED2, ED4, ED6, HED4, HED6,
breakers. Do not add height to the panel. HHED6, FD6, FXD6, HFD6, HFXD6, JXD6, JD6, HJD6, HJXD6
Connector
• Remote control switches – 480V AC max. mounted in a
Amp Rating Type Cu/Al Range
23” enclosure to be cable connected to the panel.
Al/Cu (1)–#6 AWG-
250 • Time Clocks – mounted in a 23” enclosure to be cable
Mechanical 350 kcmil
Cu (1)–#6 AWG- connected to the panel. Sangamo, Tork or Paragon time
Mechanical 350 kcmil clock can be supplied and mounted in panelboard cabinet.
Al/Cu (1)–#6 AWG-
Compression 350 kcmil Description
Al/Cu (1)–#3/0 AWG- Time Clock (1-or 2-Pole, Single or Double Throw Contacts;
400
AWG Mechanical 250 kcmil or 3-Pole Single Throw)
(1)–#3/0 AWG- 277V Maximum with Plain Dial
600 kcmil Options:
Cu (1)–#2-600 kcmil Astronomical Dial
Al/Cu (1) 400-600 An Omitting Device
Compression kcmil Reserve Power or Carryover ±
Note: Specify copper or aluminum cable. Space and Mounting Provisions Only

1 Do not increase panel or enclosure size


• 200% neutral 1 2 Accessories on 1" pole breakers (BL, BQD, xGB, ED) will take 1” unit space.
• Copper lugs, mechanical line and branch neutral 1 3 External to the panel, supplied in a separate enclosure.

1-8
SECTION 1
Connector Modifications
Type P1 Panelboards

Compression Lugs
Table P1-20 – Lugs
//
Amp Breaker Compression Box Height
Style / Rating Type Connectors Addition
125
N/A (1) #4 AWG - 350 kcmil None
250
MLO (1) 250-600 kcmil or
400 N/A (2) #3/0 AWG - 250 kcmil None
(custom option)
125 ED4, ED6, HED4 (1) #12-1/0 AWG Box must go to 24” wide
QJ2, QJH2,
/ / QJ2H, QR2, (1) #6 AWG - 350 kcmil
225 Box must go to 24” wide for all breakers
Main Breaker QRH2, HQR2, HQR2H Cu or AI
/ (1) #6 AWG - 350 kcmil
250 FXD6, HFD6
// // Box must go to 24” wide for all breakers
Cu or AI
Note: Standard compression lugs used for
/ P1 panels are range taking lugs
/ and require a particular crimping tool (tool is Hubbel Versa Crimp VC6)
toNOTE: Standardthe
accommodate compression lugsfactory
range. Consult used for
forP1 panels are 200%
information. rangeneutral
taking not / / require
lugsavailable
and withacompression
particular crimping
lugs. xGBtool (tool iscannot
breakers Hubbel Versa Crimp VC6)
accommodate
to accommodate
compression lugs. the range. Consult factory for information. 200% neutral not available with compression lugs. NGB breakers cannot accommodate
compressions lugs /

Enclosure Modifications
NEMA-4–Water Tight, Dust Tight, Steel NEMA-4X For Type P1
Enclosure (Actual NEMA-4 enclosure is Water Tight, Dust Tight and Corrosion Resistant
larger than standard Type 1 enclosre. See (consult plant to verify actual enclosure size)
chart below for reference tomapproximate Table P1-22
actual size.)
Table P1-21 Enclosure – Stainless Steel Enclosure Fiberglass
Size (inches) (304SS is sandard) Size (inches)
Actual NEMA 4 Catalog
Standard Number H
H W D H
H W
W DD
Enclosure Size
Box Height B4X26
B 26 20 5.75 36 30 8
(in inches) H W D
B4X32 32 20 5.75 36 30 8
32 32 20 8
B4X38 38 20 5.75 48 36 12
38 42 30 8
B4X44 44 20 5.75 48 36 12
44 48 36 8
B4X50 50 20 5.75 60 36 12
56 60 36 10
B4X56 56 20 5.75 60 36 12
Note: Larger NEMA 4 enclosures are not available.
B4X62 62 20 5.75
B4X68 68 20 5.75
B4X74 74 20 5.75
± ± be specified.
Note: 316SS is available as an option – must

±
Remote Switch Modifications
Table P1-23 – Control Power Transformer Table P1-24 – Applications for a Remote Switch
Size VA Relay Switch Type Modification
0,1 50 920 Mounts in 23” relay cabinet as a main only
2 75 LEN 30A mounts in 23” relay cabinet as a main only
3 150
4 250

Table P1-25 – Remote Control


Switch Modification
Description
Auxiliary Contacts (mounted, not wired)
2-Wire Control

1-9
Dimensions
Type P1 Panelboards

Type 1 Box
Box is symmetrical
y

26 in., , 50 in.
[ 660 ] [1270]
, 74 in.
[1880]

Type 3R and
e 3R3R/12 Box
and 3R/12 Box

26 in., , 50 in.
[ 660 ] [1270]
, 74 in.
[1880]

1 Dimensions are interior of the box. Add 5/8” to width for


absolute dimension. Add 1/8” to height for absolute dimension.

Dimensions shown in inches and millimeters [ ].

1-10
SECTION 2
P2 Panelboards
Description Page
General Information 2-2 Typical Catalog Numbers 2-6
Selection and Application 2-2 Main Lugs Only 2-6
Application 2-3 – 2-5 Main Circuit Breakers 2-6
Panel Unit Space To Box Height Requirements 2-3 Standard Modifications 2-7
Main Lug Connectors 2-3 Box Size Additions For Optional Features 2-8
Branch Breaker Side Gutters 2-3 Connector Modifications 2-9 – 2-10
Main Breaker Selection 2-4 Compression Lugs 2-9
Subfeed Breakers 2-4 Enclosure Modification 2-10
Branch Circuit Breakers 2-5 Remote Switch Modifications 2-10
Branch Neutral Connections 2-5 Dimensions 2-11
Kits and Accessories 2-13
P2 Panelboards

Flexibility is the hallmark of the P2 panel. This panel offers a wide Main Lug / Main Breaker
array of factory-assembled options to meet virtually any lighting Enclosure – Standard Type 1 enclosure is 20" wide x 5.75"
panel application. The ability to mix breaker frames within the deep X. Box Height is determined by main device and unit space.
unit space up to 225 amps will also meet certain distribution See charts for box height.
panel requirements in a much smaller package. Bussing options
for the P2 vary from a typical temperature rating of 750 A/Si Voltage – 600 Vac Max.
aluminum, to 1000 A/Si copper. Standard bussing in the P2 250 Vdc Max.
panel is tin-plated. Silver-plated copper is offered as an option.
Integrated time clocks, bus mounted contactors (as mains or Amperage – 600 amp Max.
sub mains), split bus, and subfeed lugs (up to 400 amps) are
just a few of the options available in this unique panel. Short circuit rating – 200 KAIC Max. symmetrical or equal to the
lowest rated device installed unless a series rating is indicated.
Like a lighting panel, P2 is set up around 18, 30, 42, 54, 66, 78, Panels with subfeed or feed-thru lugs without a main device,
and 90 circuit configurations. It will also allow the user to circuit breaker or fusible unit, are limited to a three-cycle rating.
configure the panel to the smallest possible size. The P2 panel The three-cycle rating for the P2 panel is limited to 22 KAIC. Note
starts with 9" of unit space (18 circuits of 1" pole breakers). that the main device may be mounted remote from the panel.
Breakers mounted in unit space can be mixed and matched to
meet customer requirements. All 1" pole breakers (BL, BQD, ED Bussing – The P2 panel has more options to meet market
frames) are mounted in 3" or 6" pole increments. Breaker frames, requirements. The standard bussing is temperature rated
above 125 amps, are mounted in 6" single breaker mountings. aluminum. The rating is per the requirements of UL 67 – the
As an example of a minimum panel, (6) 20 amp 1-pole BL standard for panelboards. All aluminum bussing is tin-plated.
breakers (3" of unit space) and a 3-pole 225 amp QJ breaker Optional bussing for the P2 panel is: 750 A/Si aluminum,
(6" of unit space) equaling 9" of unit space can be configured in temperature rated copper, and 1000 A/Si copper. The copper
a P2 panel without any extra provisions or space required. FD 250 bus option for this panel is tin-plated.
amp and JD 400 amp breakers are mounted as subfeed breakers
outside of unit space. Weight – Approximate
Total panelboard weight when filled with a normal quantity
Another unique feature of the P2 panel is that blank unit space of breakers and accessories is about 3 lbs. (1 kg) per inch
can be added to allow for future expansions or modifications. Any (54g per mm) of box height.
expansions or modifications must be in 3" increments. BL, BQD,
Table P2-1 – Gauge Steel of Boxes
and ED frame breakers have 3" or 6" pole kits, and can be mixed Fronts, Surface and Flush
in unit space by these increments. Breakers of the same frame
Dimensions in inches (mm) Gauge Steel
can cross from one mounting to another if contiguous. QR frame
Width Height Box Front
breakers are mounted in 6" increments for two- and three pole, 20” 26 - 74 #16 #14
single mounted units. Changes in the unit spacelength for BL, (508) (660, 1880)
BQD, or ED frame breakers require an addition deadfront, center
strip kit. Check with sales or the factory for additional unit
space kits.

Selection and Application


Step 1 Step 2
Determine configuration required. Create a catalog number by following the Check with sales or the factory for other
Example: Catalog Numbering System on page 6. options as we will be adding to our
Amperage 250A Note that the number of circuits number capabilities.
Voltage 208Y/120V (4th and 5th position) will be 18 for those
System 3Ø4W panels with 6-18 circuits, 30 for those Based on the above
Main Main Lug panels with 19-30 circuits, 42 for those P2C18ML250ATS
Bus Material ASI panels 31 to 42 circuits and 54 for those (6) BL 20 amp 1-Pole
rated aluminum panels 43 to 54 circuits. The most cost (1) QJ2/QR2 225 amp 3-pole
Interrupt Rating 10 Ka effective 20 amp 1-pole breaker for this
Step 3
Branch Devices (6) 20 amp,1-pole application would be BL. However, a
myriad of other breakers with options Determine the enclosure size. The matrix on
(1) 225 amp, 3-pole page 2-3 shows the enclosure sizes based
Feed Location Top may be used in the P2 panel. The most
cost effective 225 amp breaker for this on the amperage, main device and unit
Mounting Surface space required.
application is the QJ2/QR2.

2-2
SECTION 2
Application
Type P2 Panelboards

Table P2-2 – Panel Unit Space To Box Height Requirements

P2 Panels With Standard Line Lugs. Unit Space (starting with 9" and adding 6" increments) “A” Dimension
“B”
Main Lugs Main Breakers
Dimen-
sion 125A 250A 400A 600A 125A 125A 125A 225A 225 250A 250A 250A 400A 400A 600A 600A
Box Horiz. Horiz. Vert. Horiz. Vert. Horiz. Vert. Vert. Vert. Vert. Vert. Vert.
Height BL,BQD,
xGB, ED CED ED QJ/QR QJ/QR FD FD CFD JD CJD LD CLD
26 9 — — — 9 — — — — — — — — — — —
32 15 9 — — 15 9 9 9 — — — — — -— — —
38 21 15 9 9 21 15 15 15 9 9 — — — — — —
44 27 21 15 15 27 21 21 21 15 15 9 — — — — —
50 33 27 21 21 33 27 27 27 21 21 15 9 9 — — —
56 39 33 27 27 39 33 33 33 27 27 21 15 15 — 9 —
62 45 39 33 33 45 39 39 39 33 33 27 21 21 9 15
68 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45
74 45 45 45 45 45 45 45 45 45 45 39 33 33 21 27 21
Note: When the number of circuits exceeds 54 on a 125 and 250A MLO and 125 and 250A main breaker application, add 6” to the box height.

Table P2-3 – Main Breaker (Fig. P2-1) Table P2-4 – Main Lug Connectors (Fig. P2-2)
Panel Amps Breaker Frames C D Panel Amps Standard Connectors C D
BL 5.75 8.00 125 (1) #14 - 2/0 6.62 8.19
100
BQD 5.125 8.00 250 (1) #6 AWG - 350 Kcmil 12.34 11.22
xGB, HGB, LGB 4.63 8.00 (1) #4 AWG - 600 Kcmil
125 400 14.00 13.09
ED 4.00 8.00 or (2) #6 - 250 Kcmil
225 QJ/QR 5.00 7.00 600 (2) #4 AWG - 500 Kcmil 14.00 11.00
250 FD 5.00 7.00
400 JD 14.00 25.00
600 LD 15.50 23.00

Fig. P2-1 Fig. P2-2 Table P2-5 – Branch Breaker Side


Gutters Inches (mm) (Fig. P2-3)
Reference Panel
Letter Width 20” (508)
A 5.750 (146)
B 5.125 (130)
C 4.000 (102)
D1 5.000 (127)
E 4.625 (117)
1 Single branch mounting construction.

Fig. P2-3

A BL, BLH, HBL BL, BLH, HBL


A
BLF, BLFH BLF, BLFH
B BQD, BQD6 BQD, BQD6 B
C ED, ED4, ED6 ED, ED4, ED6 C
HED4, HHED6 HED4, HHED6
QJ2,QJH2,QJ2H
Box depth = 5.75 in. (146 mm) Box depth = 5.75 in. (146 mm) D QR2, QRH2, HQR2, HQR2H D
Box width – 20 in. (508 mm) Box width – 20 in. (508 mm) (Single Mounted)
for 100-600A for 100-600A E xGB xGB E

Panel Width
20 in. (508 mm)

2-3
Application
Type P2 Panelboards

Table P2-6 – Main Breaker Selection 1


Ampere Breaker Max. Interrupting Rating (kA) Ref.
Rating Type 240V 480V 600V Catalog No. Available Trip Values
BL 10 — — BL 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100 Note: When ED4, ED6,
W
HBL 65 — — HB 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100 HED4, QJ2, QJH2,
BQD 65 14 — BQ 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100 QJ2H, QR2, QRH2,
BLH 22 — — BH 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100 HQR2,HQR2H, FD6,
ED4 65 18 — E4 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100
NGB 100 25 14 NB 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 100 HFD6, or FXD6 frame
100 main breaker, vertically
HGB 100 35 14 G2 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 100
LGB 100 65 14 G3 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 100 mounted, is required,
ED6 100 25 14 E6 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100 price as a main breaker
HED4 100 42 — H4 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100
HHED6 100 65 18 HA 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100 panel and add from
CED6 2 200 200 100 CE 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100 the table for the main
NGB 100 25 14 NB 110, 125 breaker mounting.
HGB 100 35 14 G2 110, 125
LGB 100 65 14 G3 110, 125
ED4 65 18 — E4 125
125
ED6 65 25 18 E6 125
HED4 100 42 — H4 125
HHED6 100 65 18 HA 125
CED6 2 200 200 100 CE 125
QJ2 10 — — QJ 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
QJH2 22 — — QH 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
QJ2H 42 — — Q2 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
QR2 10 — — QR 100, 110, 125, 150, 175, 200, 225
QRH2 25 — — Q4 100, 110, 125, 150, 175, 200, 225
HQR2 65 — — Q5 100, 110, 125, 150, 175, 200, 225
225
HQR2H 100 — — Q6 100, 110, 125, 150, 175, 200, 225
FD6 65 35 18 FD 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
FXD6 65 35 18 FX 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
HFD6 100 65 25 HF 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
HFXD6 100 65 25 H2 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
CFD6 2 200 200 100 CF 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
FD6 65 35 18 FD 250
FXD6 65 35 18 FX 250
250 HFD6 100 65 35 HF 250
HFXD6 65 35 25 H2 250
CFD6 2 200 150 1 00 CF 50
JXD6 2 65 35 25 JX 200, 225, 250, 300, 350, 400
JD6 2 65 35 35 J6 200, 225, 250, 300, 350, 400
HJXD6 2 100 65 35 H6 200, 225, 250, 300, 350, 400
HJD6 2 100 65 35 H5 200, 225, 250, 300, 350, 400
400
SJD6 2 65 35 25 SJ 200, 300, 400
SHJD6 2 100 65 35 S2 200, 300, 400
CJD6 2 200 200 100 CJ 200, 300, 400
SCJD6 2 200 200 100 SC 200, 300, 400
LXD6 2 65 35 25 LX 450, 500, 600
LD6 2 65 35 25 L6 250, 300, 350, 400, 450, 500, 600
HLXD6 2 100 65 35 HL 250, 300, 350, 400, 450, 500, 600
HLD6 2 100 65 35 HO 250, 300, 350, 400, 450, 500, 600
600
SLD6 2 65 35 25 SL 300, 400, 500, 600
SHLD6 2 100 65 35 S6 300, 400, 500, 600
CLD6 2 200 150 100 CL 300, 400, 500, 600
SCLD6 200 150 100 C6 300, 400, 500, 600

Table P2-7 – Subfeed Breakers


1 Interchangeable trip main breakers
Mounting Position Maximum Interrupting are mounted at top of panel only.
When Used As Subfeed Breaker Rating (kA) Symmetrical 2 Vertically mounted
Breaker 3 Twin mounted subfeed breakers
Type Vertical Ampere Ratings For Load 240V AC 480V AC 600V DC
are mounted at bottom of panelboard
FD63, FXD6 Twin/Single 70 - 250 65 35 18 only and adds 24" to the panel height.
4 Subfeed breaker is mounted at
HFD6 3, HFXD6 Twin 70 - 250 100 65 25
bottom of panelboard only. 400 amp
JD6 4, JXD6 Single 200 - 400 65 35 25 subfeed breaker adds 30" to the
HJD6 4, HJXD6 Single 200 - 400 100 65 35 panel height (only for use with MLO).

2-4
SECTION 2
Application
Type P2 Panelboards

Table P2-8 – Branch Circuit Breakers


Max. Bolt-On
Availability Maximum Interrupting Rating (kA)
Amp Breaker
Rating Type Amps 1-Pole 2-Pole 3-Pole 120V AC 120/240V AC 240V AC 277V AC 480V AC 600V AC 250V DC
15–60 P P P 10 — — — — — —
BL 70 P P P — 10 — — — — —
80–100 — P P — — 10 — — — —
15–60 P P P — 22 — — — — —
BLH 70 P P P — 22 — — — — —
80–100 — P P — — 22 — — — —
15–55 P P P — 65 — — — — —
HBL
60–100 — P P — 65 — — — — —
BL, HID 15–30 P P — 10 10 — — — — —
15–60 — P — — — 10 — — — —
BLR (240V)
70–100 — P — — — 10 — — — —
15–30 P P — 10 — — — — — —
BLE (GFCI)
100 40–60 — P — — 10 — — — — —
20–30 P — — 22 — — — — — —
BLEH
15–60 P P — — 22 — — — — —
15–30 P P — 10 — — — — — —
BLF (GFCI)
40–60 P P — — 10 — — — — —
15–30 P P — 22 — — — — — —
BLHF (GFCI)
40–60 P P — — 22 — — — — —
HBLF2 (GFCI) 15–30 P — — 65 — — — — — —
BGL 2 15–30 — P P 10 10 — — — — —
BAF 15–20 P P — 10 — — — — — —
BAFH 15–20 P P — 22 — — — — — —
15–60 P P P — 65 — 14 — — 14
BQD
70–100 P P P — 65 — — 14 — 14
15–60 P P P 100 100 100 25 25 14 14 4
NGB 70–100 P P P 100 100 100 25 25 14 14 4
110–125 — P P 100 100 100 25 25 14 14 4
15–60 P P P 100 100 100 35 35 14 14 4
HGB 70–100 P P P 100 100 100 35 35 14 14 4
110–125 — P P 100 100 100 35 35 14 14 4
15–60 P P P 100 100 100 65 65 14 14 4
LGB 70–100 P P P 100 100 100 65 65 14 14 4
110–125 — P P 100 100 100 65 65 14 14 4
125
15–60 P P P 65 — — 22 — — —
ED4 70–100 P P P — — 65 — 18 — 30
110–125 — P P — — 65 — 18 — —
15–60 — P P — — 65 — 25 18 30
ED6 70–100 — P P — — 65 — 25 18 —
110–125 — P P — — 65 — 25 18 —
15–60 P P P — — 65 — 42 18 30
HED4a 70–100 P P P — — 65 — 42 18 —
110–125 — P P — — 65 — 42 18 —
QJ2 60–225 — P P — — 10 — — — —
QJH2 60–225 — P P — — 22 — — — —
QJ2H 60–225 — P P — — 42 — — — —
225 QR2 100–225 — P P — — 10 — — — —
QRH2 100–225 — P P — — 25 — — — —
HQR2 100–225 — P P — — 65 — — — —
HQR2H 100–225 — P P — — 100 — — — —

Branch Device Limitations Table P2-9 – Branch Neutral Connections


Lighting and appliance branch circuit panelboards were included Wire Range Max. Number of Connections Max. Amps 3
in editions of the National Electrical Code prior to 2008. By #14-#6 48 65
application rule (408.15 in all versions of the NEC prior to 2008), #14-1/0 56 125
lighting and appliance panels are limited to 42 installed circuits. #6 - 350 Kcmil 4 250
Each overcurrent device pole counts as a circuit. (1) #4-600 Kcmil 1 400
or (2) #6-250 Kcmil

11-Pole HED 4 15–30A Rated 65kA 35 through 100A Rated 25kA. NOTE: QJ/QR Breakers are single mounted in unit space and take 6" of unit space.
2 Two pole breaker is one phase and neutral. Three pole is two phase and neutral. Limited to (4) per panel max. xGB, BL, HBL, BLH and BQD breakers are mounted in
3 Based on 75 degree copper. common mountings in 3" or (6) pole increments. ED4, ED6, HED4 and HHED6
4 2-pole only (or) two outer poles of 3-pole breaker. breakers are mounted in common mountings in 3" or (6) pole increments."

2-5
Typical Catalog Numbers
Type P2 Panelboards

Table P2-10 – Main Lugs Only


Maximum Maximum Box Catalog Number Catalog Number Catalog Number
Panel 1-pole Height
Amp Rating Circuits Inches 3Ø4W 208Y/120V 1Ø3W 120/240V 3Ø4W 480Y/277V
18 26 P2C18ML125ATS P2A18ML125ATS P2E18ML125ATS
30 32 P2C30ML125ATS P2A30ML125ATS P2E30ML125ATS
42 38 P2C42ML125ATS P2A42ML125ATS P2E42ML125ATS
125 54 56 P2C54ML125ATS P2A54ML125ATS P2E54ML125ATS
66 62 P2C66ML125ATS P2A66ML125ATS P2E66ML125ATS
78 68 P2C78ML125ATS P2A78ML125ATS P2E78ML125ATS
90 74 P2C90ML125ATS P2A90ML125ATS P2E90ML125ATS
18 32 P2C18ML250ATS P2A18ML250ATS P2E18ML250ATS
30 38 P2C30ML250ATS P2A30ML250ATS P2E30ML250ATS
42 44 P2C42ML250ATS P2A42ML250ATS P2E42ML250ATS
250 54 56 P2C54ML250ATS P2A54ML250ATS P2E54ML250ATS
66 62 P2C66ML250ATS P2A66ML250ATS P2E66ML250ATS
78 68 P2C78ML250ATS P2A78ML250ATS P2E78ML250ATS
90 74 P2C90ML250ATS P2A90ML250ATS P2E90ML250ATS
18 38 P2C18ML400ATS P2A18ML400ATS P2E18ML400ATS
30 44 P2C30ML400ATS P2A30ML400ATS P2E30ML400ATS
42 50 P2C42ML400ATS P2A42ML400ATS P2E42ML400ATS
400 54 56 P2C54ML400ATS P2A54ML400ATS P2E54ML400ATS
66 62 P2C66ML400ATS P2A66ML400ATS P2E66ML400ATS
78 68 P2C78ML400ATS P2A78ML400ATS P2E78ML400ATS
90 74 P2C90ML400ATS P2A90ML400ATS P2E90ML400ATS
18 38 P2C18ML600ATS P2A18ML600ATS P2E18ML600ATS
30 44 P2C30ML600ATS P2A30ML600ATS P2E30ML600ATS
42 50 P2C42ML600ATS P2A42ML600ATS P2E42ML600ATS
600 54 56 P2C54ML600ATS P2A54ML600ATS P2E54ML600ATS
66 62 P2C66ML600ATS P2A66ML600ATS P2E66ML600ATS
78 68 P2C78ML600ATS P2A78ML600ATS P2E78ML600ATS
90 74 P2C90ML600ATS P2A90ML600ATS P2E90ML600ATS

Table P2-11 – Main Circuit Breaker


18 26 P2C18BL100ATS P2A18BL100ATS P2E18BL100ATS
100 30 32 P2C30BL100ATS P2A30BL100ATS P2E30BL100ATS
42 38 P2C42BL100ATS P2A42BL100ATS P2E42BL100ATS
30 32 P2C30NB125ATS P2A30NB125ATS P2E30NB125ATS
42 38 P2C42NB125ATS P2A42NB125ATS P2E42NB125ATS
125 54 56 P2C54NB125ATS P2A54NB125ATS P2E54NB125ATS
66 62 P2C66NB125ATS P2A66NB125ATS P2E66NB125ATS
78 68 P2C78NB125ATS P2A78NB125ATS P2E78NB125ATS
90 74 P2C90NB125ATS P2A90NB125ATS P2E90NB125ATS
18 32 P2C18QR225ATS P2A18QR225ATS P2E18FX225ATS
30 38 P2C30QR225ATS P2A30QR225ATS P2E30FX225ATS
42 44 P2C42QR225ATS P2A42QR225ATS P2E42FX225ATS
2251 54 56 P2C54QR225ATS P2A54QR225ATS P2E54FX225ATS
66 62 P2C66QR225ATS P2A66QR225ATS P2E66FX225ATS
78 68 P2C78QR225ATS P2A78QR225ATS P2E78FX225ATS
90 74 P2C90QR225ATS P2A90QR225ATS P2E90FX225ATS
18 38 P2C18FX250ATS P2A18FX250ATS P2E18FX250ATS
30 44 P2C30FX250ATS P2A30FX250ATS P2E30FX250ATS
250 42 50 P2C42FX250ATS P2A42FX250ATS P2E42FX250ATS
54 62 P2C54FX250ATS P2A54FX250ATS P2E54FX250ATS
66 68 P2C66FX250ATS P2A66FX250ATS P2E66FX250ATS
78 74 P2C78FX250ATS P2A78FX250ATS P2E78FX250ATS
18 50 P2C18JX400ATS P2A18JX400ATS P2E18JX400ATS
30 56 P2C30JX400ATS P2A30JX400ATS P2E30JX400ATS
400 42 62 P2C42JX400ATS P2A42JX400ATS P2E42JX400ATS
54 68 P2C54JX400ATS P2A54JX400ATS P2E54JX400ATS
66 74 P2C66JX400ATS P2A66JX400ATS P2E66JX400ATS
18 56 P2C18LX600ATS P2A18LX600ATS P2E18LX600ATS
600 30 62 P2C30LX600ATS P2A30LX600ATS P2E30LX600ATS
42 68 P2C42LX600ATS P2A42LX600ATS P2E42LX600ATS
54 74 P2C54LX600ATS P2A54LX600ATS P2E54LX600ATS
1 QJ series was available prior to QR.

2-6
SECTION 2
Standard Modifications
Type P2 Panelboards

P2 Panel Options
Enclosures
• Extra gutter to sides or ends of the can • Aluminum trims and boxes, Type 1
• 24" wide boxes • NEMA 3R enclosures
• Hinged trims • NEMA 3R/12 enclosures
• Door-in-door trims • NEMA 4 enclosures
• Screw to the box trims • NEMA 4X enclosures
• Trim mounted devices (Devices mounted and wired • Special keyed locks
to the trim should also have hinged trim specified) • TEY • LL803
• Pilot lights • TEU1 • LL806
• Toggle switches • Cat 60 • Yale
• Push buttons • Gasketing trim to box
• Painted boxes • Meters (Contact application engineering for space
• Custom colors requirements)
• Increase gauge trims and boxes • Panel Skirts
• Stainless steel trims and boxes, Type 1

Panel Modifications
• Main Bus • Grounding of panelboards
Standard main bus is temperature rated tin-plated aluminum. Ground Bars, except brazed-to-box, are shipped with the
Bus options are 750 A/Si aluminum, tin-plated temperature panel interior factory mounted.
rated copper tin-plated standard – silver optional. 1000 A/Si • Non-Insulated Equipment Ground Bar – Standard
copper tin-plated standard – silver optional. Includes copper • Copper Non-Insulated Ground Bar
neutral cross bar. For copper neutral branch lugs, see • Al Insulated Equipment Ground Bar
miscellaneous. • Cu Insulated Equipment Ground Bar
• Split bus adds 6” to unit space • Ground Bar Brazed to Box (recommended for
• Compression lug for MLO painted boxes)
• Compression lugs on Main breaker (may require • Shunt Trip on Main or Branch
extra width or length on enclosure). BL, BLH, HBL, ED2, ED4, HED4, HED6, HHED6 uses 1” unit
• Contactor mains or submain space for shunt trip. All may be used on mains or subfeeds.
• Asco 920 through 225 amps. Adds 12” unit space as main,
15” unit space as submain. QJ2, QJ2H, QJH2, QR2, QRH2, HQR2, HQR2H, ED2, ED4, ED6, HED4,
• Asco 911 through 150 amps. Adds 21” unit space. HED6, HHED6, FXD6, HFD6, JXD6, JD6, HJD6, HJXD6
• Siemens LEN through 30 amps. Adds 12” unit space. • Remote control switches – 480V AC max. mounted in a
Makes box 10" deep. 23” enclosure to be cable connected to the panel.
• Control power transformers (contact engineering for extra • Time Clocks – mounted in a 23” enclosure to be cable
gutter requirements) connected to the panel. Sangamo, Tork or Paragon time
• Branch and main breaker accessories clock can be supplied and mounted in panelboard cabinet.
• Handle blocks
• Handle locks Description
• Aux. Contacts 1 Time Clock (1-or 2-Pole, Single or Double Throw Contacts;
• UVR 1 3-Pole Single Throw)
• Feed-thru lugs 277V Maximum with Plain Dial
• 200% neutral Options –
• Copper lugs, mechanical Astronomical Dial
• Bus mounted TVSS An Omitting Device
• Service entrance labeled Reserve Power or Carryover
Type P2 Panelboards are factory labeled suitable for use as Space and Mounting Provisions Only
service entrance equipment when NEC requirements are met.
A panelboard cannot have more than six main disconnects,
unless it is a lighting and appliance branch panelboard.
Lighting and appliance branch panelboards are limited to
two main disconnects. Factory installed and Field installable
Service Entrance Barrier kits are now available as required by
UL67. (In COMPAS, you must select Service Entrance Required.)

1 Accessories on 1" pole breakers (BL, BQD, ED) will take unit space

2-7
Standard Modifications
Type P2 Panelboards

Table P2-12 – Box Size Additions (In.) For Optional Features on MLO Applications
Main Lugs Main Breakers
125A 250A 400A 600A 125A 125A 125A 225A 225A 225A 250A 250A 400A 400A 600A 600A
Options Horiz. Horiz. Vert. Horiz. Vert. Horiz. Vert. Vert. JD CJD LD CLD
BL, BQD, QJ QJ
ED, xGB CED ED QR QR FD FD CFD
*Min. Box Size 26" 32" 38" 38" 26" 32" 32" 32" 38" 38" 44" 50" 50" 62" 56" 62"
200% Neutral 0 0 6 (all) 6 (all) 0 0 0 N/A 0 N/A 0 0 0 0 0 0
(lug type)
Std. Lugs 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
(100% Neut. PNL)
CU Lugs (100% 6 6 6 0 N/A N/A 0 N/A 0 N/A 0 0 0 0 0 0
Neut. PNL)
Comp Lugs 6 6 6 6 N/A N/A 0 N/A 0 N/A 0 0 0 0 0 0
(100% Neut. PNL)
Feed-thru
Standard Lugs 6 6 12 12 6 6 6 N/A 6 N/A 6 6 12 12 12 12
Feed-thru Cu Lugs 6 6 12 N/A N/A N/A 6 N/A 6 N/A 6 6 12 12 N/A N/A
Feed-thru
Comp Lugs 6 12 12 N/A N/A N/A 6 N/A 6 N/A 12 12 12 12 N/A N/A
Subfeed Standard
Lugs 0 6 6 N/A — — — — — — — — N/A — — —
Split Bus 6 6 6 6 6 6 6 N/A 6 N/A 6 6 6 6 6 6
(1) FD Subfeed N/A 12 12 12 N/A N/A N/A N/A N/A 12 12 12 12 12 12 12
(Horizontal Mtg.)
(2) FD Subfeed N/A 24 24 24 N/A N/A N/A N/A N/A 24 24 24 24 N/A N/A N/A
(Vertical Mtg.)
SPD 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12

Split bus is paired with feed-thru lugs by default. Feed-thru lugs are to feed the section after the split.
NOTE: N/A = OPTION NOT AVAILABLE
*Min. Box Size, corresponding to 9" of Unit Space.

2-8
SECTION 2
Connector Modifications
Type P2 Panelboards

Compression Lugs
Table P2-13 – Lugs
Style Amp Rating Breaker Type Compression Connectors Box Height Addition
125 N/A (1) #6 - 350 kcmil Al/Cu 6
250 N/A (1) #6 - 350 kcmil Al/Cu 6
(1) 400 - 600 kcmil Cu or
400 N/A 6
MLO (2) #6 - 350 kcmil Al/Cu
(2) #6 - 350 kcmil Cu or Cu/Al or
600 N/A 6
400 - 600 kcmil Al/Cu
ED4, ED6, HED4 Box must go to 24”W for CED6 breaker only
100 (1) #14-2/0 AWG Cu or Al
HHED6, CED61 Add 6” to box height for NØ
QJ2, QJH2, QJ2H,
225 QR2, QRH2, HQR2, (1) #6 - 350 kcmil Cu or Al Box must go to 24” wide
HQR2H
Box must go to 24” wide for all breakers
250 FXD6, HFD6, CFD6, (1) #6 - 350 kcmil Cu or Al Requires an additional 6.0” box height
Main Breaker
JD6, JXD6, HJD6,
400 CJD6, SJD6, SHJD6, (2) #1/0 AWG - 500 kcmil Cu or AL 9
SCJD6
LD6, LXD6, HLD6,
600 CJD6, SLD6, SHLD6, (2) #2/0 AWG - 500 kcmil Cu or Al 6
SCLD6

Alternate Lugs
Table P2-14 – Lugs
Style Amp Rating Breaker Type Compression Connectors Box Height Addition
(1) 250 - 350 kcmil or
MLO 400 N/A 6
(2) #3/0 AWG - 250 kcmil Cu or Al
JD6, JXD6, HJD6,
Main Breaker 400 CJD6, SJD6, SHJD6, (1) #3/0 AWG - 750 kcmill Cu or Al 6
SCJD6

2-9
Connector Modifications
Type P2 Panelboards

Enclosure Modifications
Enclosure Modification NEMA 4 for NEMA-4X For Type P2
Type P2 Water Tight and Dust Tight, Water Tight, Dust Tight and Corrosion Resistant
Steel Enclosure (consult plant to verify (consult plant to verify enclosure size)
enclosure size)
Table P2-16
Table P2-15 Enclosure - Stainless Steel Enclosure - Stainless Steel and
and Steel with Epoxy Coating Steel with Epoxy Coating 1
Standard Actual NEMA Box Height
Box Height Enclosure Size Inches H W D H W D
Inches H W D 26 26 36 30 8
32 32 20 8 32 32 36 30 8
38 42 30 8 38 38 48 36 12
44 48 36 8 44 44 48 36 12
56 60 36 10 50 50 20 5.75 60 36 12
56 56 60 36 12
Note: Larger NEMA 4 enclosures are not available.
62 62 — — —
68 68 — — —
74 74 — — —
1 Limited to the sizes shown.

Remote Switch Modifications


Table P2-17 – Control Power Table P2-18 – Applications for a Remote Switch
Transformer
Switch Type Modification
Size VA
ASCO 920 30 to 225A – Add 12” to MLO box height
0,1 50 ASCO 9111 ≤ 225A – Add 21” to the box height. >225A is not available in P2
2 75 60A to 100A adds 6” to the box height with a min. depth of 7.75”
LEN
3 150 200A adds 6” to the box height with a min. depth of 10.00”
4 250
1 >225A is recommended for use in a P4 panel.

.
Table P2-19 – Remote Control
Switch Modification
Description
Auxiliary Contacts (mounted not wired)
Ea. 2-Wire Control

2-10
SECTION 2
Dimensions
Type P2 Panelboards

Type 1 Box
Box is symmetrical

Type 3R and 3R/12 Box

1 Dimensions are interior of the box. Add 5/8” to width for


absolute dimension. Add 1/8” to height for absolute dimension.
2 See table P2-12 to match ratings with height.

Dimensions shown in inches and millimeters [ ].

2-11
Dimensions
Type P2 Panelboards

A B C Standard Box Size


17.94 18.00 16.75 26H 20W 5.75D
23.94 24.00 22.75 32H 20W 5.75D
29.94 30.00 28.75 36H 20W 5.75D
35.94 36.00 34.75 44H 20W 5.75D
41.94 42.00 40.75 50H 20W 5.75D
47.94 48.00 46.75 56H 20W 5.75D
53.94 54.00 52.75 62H 20W 5.75D
59.94 60.00 58.75 68H 20W 5.75D
65.94 66.00 64.75 74H 20W 5.75D

2-12
2 SECTION
Kits and Accessories
Type P2 Panelboards

Table P2-20 – Standard Enclosures


Catalog Number
Box Type 1 Type 3R Type 3R/12
Height Standard Trim
Inches Box Surface Flush
26 B26 S26B F26B NR26 WP26
32 B32 S32B F32B NR32 WP32
38 B38 S38B F38B NR38 WP38
44 B44 S44B F44B NR44 WP44
50 B50 S50B F50B NR50 WP50
56 B56 S56B F56B NR56 WP56
62 B62 S62B F62B NR62 WP62
68 B68 S68B F68B NR68 WP68
74 B74 S74B F74B NR74 WP74

Options For Type 1 Trims


Items must be ordered as manual line item on Spartanburg.
Hinged trim – Replace “B” suffix with “H”
Door-in-door – Replace “B” suffix with “D”
Screw to Box – Replace "B" suffix with "C"
Metal card holder – Replace “B” suffix with “M” on standard trim, add “M” suffix on optional trims
Option For 24” Wide Enclosures with Equal Gutter on Both Sides (Excludes NEMA 3R)
24” wide with equal gutter on both sides - Add “24” as prefix
Table P2-21 – Breaker Kits and Accessories
Kit No. Description Contents
BBKB32 (P2/P3) BL/BQD 6-pole 3” branch breaker kit Kit contains top barrier, (3) A/C connectors, (1) B connectors, hardware
BBKED32 (P2/P3) ED 6-pole 3” branch breaker kit Kit contains breaker support. inter-phase barriers, (3) AC connectors, (1) B connector, hardware
BBKNB32 (P2/P3) xGB 6-pole 3” branch mounting kit Kit contains top barrier, (3) A/C connectors, (1) B connector, hardware
QJ/QR branch breaker kit for 2 and
BBKQ1 (P2) Kit to contain all connectors and cover plates necessary to mount both 2 and -pole breakers
3-pole single mount
P2 branch BKR strap kit for single QR
BBKQR11 1-phase/3-phase
P3 branch BKR strap kit for single QR
BBKQR21
1-phase/3-phase
BL, BQD, ED deadfront kit for
DFK1 Center strips 3”, 6”, 9”, 15”, 21” plus mounting hardware
1” pole breakers
DFFP3 Deadfront filler 3” 3” empty space filler and hardware
DFFP6 Deadfront filler 6” 6” empty space filler and hardware
BNK2 Branch neutral (P2) Three tier lug with mounting hardware to increase neutral capacity
P2BK1 P2 250A max. bonding kit Bonding strap and hardware
P2BK2 P2 400A max. bonding kit Bonding strap and hardware
P2BK3 P2 600A max. bonding kit Bonding strap and hardware
P2 filler for QR. Horizontal or vertical
BBKQRP1FK Kit contains all cover plates necessary to change from QJ to QR both 2 and 3-pole breakers.
mount. 1-phase/3-phase.
P3 filler for QR. Dual mount Kit contains all cover plates necessary to change from QJ to QR both 2 and 3-pole breakers. For
BBKQRP2FK
horizontal. 1-phase/3-phase. 1-phase panel, both breakers must change from QJ to QR, cannot have one of each installed.
BL, BQD Main Service Entrance Barrier
SEBKP2V13 Kit contains barrier, mounting brackets, and hardware
(P2 only)
xGB Main Service Entrance Barrier
SEBKP2V2 3 Kit contains barrier, mounting brackets, and hardware
(P2 only)
FD, QJ, QR Horizontal Main Service
SEBKP2V3 3 Kit contains barrier, mounting brackets, and hardware
Entrance Barrier (P2, P2 with SEM3, P3)
FD, QJ, QR Vertical Main Service
SEBKP2V4 3 Kit contains barrier, mounting brackets, and hardware
Entrance Barrier (P2, P2 with SEM3)
ED Horizontal Main Service Entrance
SEBKP2V5 3 Kit contains barrier, mounting brackets, and hardware
Barrier (P2, P2 with SEM3)
ED Vertical Main Service Entrance
SEBKP2V6 2 3 Kit contains barrier, mounting brackets, and hardware
Barrier (P2, P2 with SEM3)
JD, LD Service Entrance Barrier Kit
SEBKP1P2P3V13 Kit contains barrier, mounting brackets, and hardware
(RP1, P1, P2, P3)
1 Although QR is rated 250A. it is limited to 225A in panelboard.
2 Two kits required for P2 extended circuit panels.
3 Factory installed and Field installable Service Entrance Barrier kits are now available as required by UL67. (In COMPAS, you must select Service Entrance Required.)
2-13
Notes
SECTION 3
P3 Panelboards
Description Page
General Information 3-2 Typical Catalog Numbers 3-6 – 3-7
Selection and Application 3-2 Main Lugs 3-6
Application 3-3 – 3-5 Main Circuit Breakers 3-7
Panel Unit Space to Box Height Requirements 3-3 Standard Modifications 3-8 – 3-9
Main Breaker and Main Lug Wire Bending 3-3 Option Combinations 3-9
Branch Breaker Side Gutters 3-3 Connector Modifications 3-10
Main Lug and Main Breaker Compression Lugs 3-10
Unit Space Dimensions 3-3 Enclosure Modifications 3-10
Main Breaker Selection 3-4 Remote Switch Modifications 3-10
Subfeed Breakers 3-4 Dimensions 3-11
Neutral Connectors 3-4 Kits and Accessories 3-13
Branch Circuit Breakers 3-5
Type P3 Panelboards

Another innovation from Siemens is the P3 panel. It is a smaller, Main Lug / Main Breaker
footprint distribution panel to fit a large number of applications Enclosure – Standard Type 1 enclosure is 24" wide x 7.75"
that require more (or larger) branch devices than the lighting deep. X Box Height is determined by main device and unit space.
panel class offer. This panel offers a wide array of factory- See charts for box height.
assembled options, and has the ability to mix breaker frames
in unit space up to 250 amps. Bussing options for the P3 vary Voltage – 600 Vac Max.
from the standard temperature aluminum to temperature rated 250 Vdc Max.
copper, 750 A/Si aluminum, and 1000A/Si copper designs. All bussing
Amperage – 800 amp Max.
in the P3 panel is tin-plated as a standard. Silver-plated copper is offered
as an option on a copper bus. Integrated time clocks, bus mounted Short Circuit Rating – 200 KAIC Max. symmetrical or equal
contactors, as mains or sub mains, split bus and subfeed lugs (up to to the lowest rated device installed unless a series rating is
400 amp) are just a few of the options of this unique panel. indicated. Panels with subfeed or feed-thru lugs without a
main device, circuit breaker or fusible unit, are limited to a
The P3 panel configurations, defined by the unit space, allow for a
three-cycle rating. The three-cycle rating for the P3 panel is
given amperage, main device, and box height. The P3 panel starts with
limited to 22 KAIC. Note that the main device may be mounted
a 56" high box. Breaker unit space can be mixed and matched to meet
remote from the panel.
customer requirements. All 1" pole breakers (BL, BQD, ED, xGB frames)
are mounted in 3" or 6" pole increments. Breakers frames, above 125 Bussing – The P3 panel has more options to meet market
amps, are mounted in 6" single or twin breaker mountings. As an requirements. The standard bussing is temperature rated
example panel, FD 250 amp and JD 400 amp breakers are mounted aluminum. The rating is per the requirements of UL 67 – the
as subfeed breakers outside of unit space. standard for panelboards. All aluminum bussing is tin-plated.
Optional bussing for the P3 panel is: 750 A/si aluminum,
Like other distribution panels, the P3 panel can have blank space added
temperature rated copper, and 1000 A/si copper. The copper
into the panel to allow for future expansions or modifications. Any
bus option for this panel is tin-plated.
expansions or modifications must be in 3" increments. BL, BQD and
ED frame breakers have 3" or 6-pole kits and can be mixed in unit space Weight – Approximate
by these increments. Breakers of the same frame can cross from one Total panelboard weight when filled with a normal quantity
mounting to another if contiguous. xGB frame breakers cannot be of breakers and accessories is about 5 lbs. (1 kg) per inch
mixed with other frame types. Any expansion or modification must (54g per mm) of box height.
be in 3" increments also. QJ/QR frame breakers are mounted in 6"
Table P3-1 – Gauge Steel of Boxes Fronts, Surface & Flush
increments for two -and three pole single and twin mounted units.
Changes in the unit space length for BL, BQD, xGB, or ED frame breakers Dimensions in inches (mm) Gauge Steel
require an additional deadfront center strip kit. Check with sales or the Width Height Box Front
factory for additional unit space kits. 24” 56 - 80 #16 #14
(610) (1422, 2032)

1 ASI = Amperes per square inch

Selection and Application


1) To specify a particular panelboard, first determine voltage, Select appropriate enclosure height from selection chart on
system, amperage and type main, amperage and type of page 3-3, based on unit space requirements. (Step 2)
branch devices, and modifications, if any. (Step 1)
3) Select panelboard catalog number from appropriate table
2) List branch devices and modifications requiring space based upon voltage, system, amperage and unit space
additions. List unit space requirements of each. requirements. (Step 3)
Note: Some units are twin mounted meaning two breakers
occupy the same unit space.
Step #1 Step #2 Step #3
Amperage 400 6-20A/3 3x3” = 6 poles = 9” Panel - P3C56ML400ATS
Voltage 208Y/120 2-225/3 QJ2/QR2 6” = 6” Box - 24WD56
System 3 Phase, 4 wire 15”
Main Main Lug Trim - P3S56
Bus Standard Aluminum Enclosure is 56” from Table P3-2
Branches 6-20A13, 2-225/3, (24” wide, 56” high, 7.75” deep).
Modifications None
Feed Top
Mounting Surface

3-2
SECTION 3
Application
Type P3 Panelboards

Table P3-2 – Panel Unit Space To Box Height Requirements


P3 Panels With Standard Line Lugs. Unit Space (starting with 9" and adding 6" increments) “A” Dimension
“B” Main Lugs Main Breakers
Dimension 250A 400A 600A 800A 250A 250A 250A 400A 400A 600A 600A
Box Height Horizontal Vertical Vertical Vertical Vertical Vertical Vertical
FD FD CFD JD CJD LD CLD
56 27 21 21 21 21 15 9 9 — 9 —
62 33 27 27 27 27 21 15 15 9 15 9
33 39 33 33 33 33 27 21 21 15 21 15
74 45 39 39 39 39 33 27 27 21 27 21
80 45 45 45 45 45 39 33 33 27 33 27

Table P3-3 – Main Breaker Wire Bending (Fig. P3-1) Table P3-4 – Main Lug Wire Bending (Fig. P3-2)
Breaker Panel Amps Standard Connectors C D
Frame C E F 250 (1) #6 AWG - 350 kcmil 10.75 1 13.50
FD Horiz. 7.25 — 20.13 (2) #3/0 AWG - 250 kcmil
400 16.00 17.88
FD Vert. — 12.25 25.38 or (1) #3/0 600 kcmil
CFD — 13.63 31.38 600 (2) #3/0 AWG - 500 kcmil or 16.00 17.88
JD — 15.63 29.38 800 (2) #3/0 - 600 kcmil 16.00 17.88
CJD — 14.75 35.38 1 This lug is classified as removable.
LD — 14.75 29.38
CLD — 14.00 35.38

Fig. P3-1 Table P3-5 – Branch Breaker Fig. P3-2


Side Gutters Inches (mm) (Fig. P3-3)
Reference Panel
Letter Width 24” (609)
A 7.750 (197)
B 7.125 (181)
C 6.000 (152)
D1 7.000 (178)
E 5.000 (127)
F 6.625 (168)
G 5.750 (144)
1 Single branch mounting constuction.

Fig. P3-3

BL, BLH, HBL BL, BLH, HBL


A A
BLF2, BLHF2, BLF2, BLHF2,
HBLF2, BLFB, HBLF2, BLFB,
BLHFB BLHFB
BQD, BQD6 BQD, BQD6

Box depth = 7.75 in. (197 mm) Box depth = 7.75 in. (197 mm)
Box width = 24 in. (610 mm) Box width = 24 in. (610 mm)
QJ2,QJH2, QJ2,QJH2,
QJ2H,QR2, QJ2H,QR2,
QRH2,HQR2, QRH2,HQR2,
HQR2H HQR2H

Panel Width
24 in. (610 mm)

Table P3-6 – Subfeed Breaker Wire Bending (Fig. P3-1)

Breaker Reference Dimensions


Family C E F
FD Single 7.25 — 8.25
Dual FD — 15.25 8.25
Single JD 8.00 — 29.38

3-3
Application
Type P3 Panelboards

Table P3-7 – Main Breaker Selection 1


Maximum Interrupting Ref.
Ampere Breaker Rating (kA) Catalog Available Configurations 2
Rating Type 240V 480V 600V Number 240V AC 480V AC 600V AC Available Trip Values
FD6 65 35 18 FD STD STD STD 70, 80, 90, 100, 110, 125, 150, 200, 225, 250
FXD6 65 35 18 FX STD STD STD 70, 80, 90, 100, 110, 125, 150, 200, 225, 250
250 HFD6 100 65 25 HF ADD ADD ADD 70, 80, 90, 100, 110, 125, 150, 200, 225, 250
HFXD6 100 65 25 H2 ADD ADD ADD 70, 80, 90, 100, 110, 125, 150, 200, 225, 250
CFD6 1 200 150 100 CF ADD ADD ADD 70, 80, 90, 100, 110, 125, 150, 200, 225, 250
JXD6 1 65 35 25 JX STD STD STD 200, 225, 250, 300, 350, 400
JD6 1 65 35 25 J6 STD STD STD 200, 225, 250, 300, 350, 400
HJXD6 1 100 65 35 H6 ADD ADD ADD 200, 225, 250, 300, 350, 400
HJD6 1 100 65 35 H5 ADD ADD ADD 200, 225, 250, 300, 350, 400
400
SJD6 1 65 35 25 SJ ADD ADD ADD 200, 300, 400
SHJD6 1 100 65 35 S2 ADD ADD ADD 200, 300, 400
CJD6 1 200 200 100 CJ ADD ADD ADD 200, 300, 400
SCJD6 1 200 200 100 SC ADD ADD ADD 200, 300, 400
LXD6 1 65 35 25 LX STD STD STD 450, 500, 600
LD6 1 65 35 25 L6 STD STD STD 250, 300, 350, 400, 450, 500, 600
HLXD6 1 100 65 35 HL ADD ADD ADD 250, 300, 350, 400, 450, 500, 600
HLD6 1 100 65 35 HO ADD ADD ADD 250, 300, 350, 400, 450, 500, 600
600
SLD6 1 65 35 25 SL ADD ADD ADD 300, 400, 500, 600
SHLD6 1 100 65 35 S6 ADD ADD ADD 300, 400, 500, 600
CLD6 1 200 150 100 CL ADD ADD ADD 300, 400, 500, 600
SCLD6 200 150 100 C6 ADD ADD ADD 300, 400, 500, 600
1 Vertically mounted 2 STD – Standard configuration. ADD – Additional cost.

Table P3-8 – Subfeed Breaker Selection and Mounting Reference


Mounting Orientation Maximum Interrupting Rating (ka)
Breaker and Configuration
Type Vertical Horizontal 240V AC 480V AC 600V DC Available Trip Values
Twin — 65 35 18
FD , FXD
— Single 100 65 25 70, 80, 90, 100, 110, 125, 150, 200, 225, 250
HFD, HFX6

JXD, JD6 — Single 65 35 25


HJXD6 200, 225, 250, 300, 350, 400
100 65 35
HJD6

Branch Device Limitations Table P3-9 – Neutral Connectors


Lighting and appliance branch circuit panelboards were (Based on 75ºC copper)
included in editions of the National Electrical Code prior to Max. Number
2008 By application rule (40815 in all versions of the NEC Wire Range of Connections Max. Amps
prior to 2008), lighting and appliance panels are limited to #14 - #1/0 44 125
42 installed circuits. Each over current device pole counts as #4 - 350 kcmil 6 250
a circuit. (1)#4 - 600 kcmil or
1 400
(2)#6 - 250 kcmil

3-4
SECTION 3
Application
Type
B P3 Panelboards

Table P3-10 – Branch Circuit Breakers


Max. Amp Bolt-On Provisions for Maximum Interrupting Rating (kA)
Rating Breaker Type Amps 120V AC 120/240V AC 240V AC 277V AC 480V AC 600V AC 250V DC
15–60 10 — — — — — —
BL 70 — 10 — — — — —
80–100 — — 10 — — — —
15–60 — 22 — — — — —
BLH 70 — 22 — — — — —
80–100 — — 22 — — — —
15–55 — 65 — — — — —
HBL
60–100 — — 65 — — — —
BL, (HID) 15–30 10 — — — — — —
15–60 — — 10 — — — —
BLR (240V)
70–100 — — 10 — — — —
15–30 10 — — — — — —
100 BLE (GFCI)
40–60 — 10 — — — — —
15–30 22 — — — — — —
BLEH (GFCI)
15–60 — 22 — — — — —
15–30 10 — — — — — —
BLF (GFCI)
40–60 — 10 — — — — —
15–30 22 — — — — — —
BLHF (GFCI)
40–60 — 22 — — — — —
HBLF2 (GFCI) 15–30 65 — — — — — —
BGL1 15–30 10 — — — — — —
BAF 15–20 10 — — — — — —
BAFH 15–20 22 — — — — — —
BQD 15–60 — 65 — — 14 — 14
70–100 — — 65 — 14 — 14
15–60 100 100 100 25 25 14 142
NGB 70–100 100 100 100 25 25 14 142
110–125 100 100 100 25 25 14 142
15–60 100 100 100 35 35 14 142
HGB 70–100 100 100 100 35 35 14 142
110–125 100 100 100 35 35 14 142
15–60 100 100 100 65 65 14 142
LGB 70–100 100 100 100 65 65 14 142
110–125 100 100 100 65 65 14 142
15–60 85 85 85 35 35 22 35
NEB 70–100 85 85 85 35 35 22 35
110–125 85 85 85 35 35 22 35
125
15–60 100 100 100 65 65 25 42
HEB 70–100 100 100 100 65 65 25 42
110–125 100 100 100 65 65 25 42
15–60 65 — — 22 — — —
ED4 70–100 — — 65 — 18 — 30
110–125 — — 65 — 18 — —
15–60 — — 65 — 25 18 30
ED6 70–100 — — 65 — 25 18 —
110–125 100 — — — — — —
15–60 100 — — — — — —
HED4 70–100 — — — 65 — — —
110–125 — — — 65 — — —
QJ2 60–225 — — 10 — — — —
QJH2 60–225 — — 22 — — — —
QJ2H 60–225 — — 42 — — — —
225 QR2 100–225 — — 10 — — — —
QRH2 100–225 — — 25 — — — —
HQR2 100–225 — — 65 — — — —
HQR2H 100–225 — — 100 — — — —

Note: QJ/QR Breakers are twin mounted in unit spaceand take 6" of unit space. Limited to (6) per panel max. BL, HBL, BLH and BQD breakers are mounted incommon
mountings in 3" or (6) pole increments. ED2,ED4, ED6, HED4 and HHED6 breakers are mounted incommon mountings in 3" or (6) pole increments.

1 BGL 2-pole is (1) phase and neutral 3-pole is (2) phases and neutral.
2 2-pole only (or) two outer poles of 3-pole breaker.

3-5
Typical Catalog Numbers
Type P3 Panelboards

Table P3-11 – Main Lugs Only – shown with aluminum bus, top fed, and surface trims
208Y/120V 240/120V 120/240V or
250 Vdc Max
Maximum 3 Phase, 4 Wire 3 Phase, 4 Wire 1 Phase, 3 Wire
Panel Amp Rating Unit Space (inches) Catalog Number Catalog Number Catalog Number
27 P3C56ML250ATS P3B56ML250ATS P3A56ML250ATS
33 P3C62ML250ATS P3B62ML250ATS P3A62ML250ATS
250 39 P3C68ML250ATS P3B62ML250ATS P3A62ML250ATS
45 P3C74ML250ATS P3B74ML250ATS P3A74ML250ATS
51 P3C80ML250ATS P3B80ML250ATS P3A80ML250ATS
21 P3C56ML400ATS P3B56ML400ATS P3A56ML400ATS
27 P3C62ML400ATS P3B62ML400ATS P3A62ML400ATS
400 33 P3C68ML400ATS P3B68ML400ATS P3A68ML400ATS
39 P3C74ML400ATS P3B74ML400ATS P3A74ML400ATS
45 P3C80ML400ATS P3B80ML400ATS P3A80ML400ATS
21 P3C56ML600ATS P3B56ML600ATS P3A56ML600ATS
27 P3C62ML600ATS P3B62ML600ATS P3A62ML600ATS
600 33 P3C68ML600ATS P3B68ML600ATS P3A68ML600ATS
39 P3C74ML600ATS P3B74ML600ATS P3A74ML600ATS
45 P3C80ML600ATS P3B80ML600ATS P3A80ML600ATS
21 P3C56ML800ATS P3B56ML800ATS P3A56ML800ATS
27 P3C62ML800ATS P3B62ML800ATS P3A62ML800ATS
800 33 P3C68ML800ATS P3B68ML800ATS P3A68ML800ATS
39 P3C74ML800ATS P3B74ML800ATS P3A74ML800ATS
45 P3C80ML800ATS P3B80ML800ATS P3A80ML800ATS
240V 408Y/277V 480V 1
Maximum 3 Phase, 3 Wire 3 Phase, 4 Wire 3 Phase, 3 Wire
Panel Amp Rating Unit Space (inches) Catalog Number Catalog Number Catalog Number
27 P3D56ML250ATS P3E56ML250ATS P3F56ML250ATS
33 P3D62ML250ATS P3E62ML250ATS P3F62ML250ATS
250 39 P3D68ML250ATS P3E68ML250ATS P3F68ML250ATS
45 P3D74ML250ATS P3E74ML250ATS P3F74ML250ATS
51 P3D80ML250ATS P3E80ML250ATS P3F80ML250ATS
21 P3D56ML400ATS P3E56ML400ATS P3F56ML400ATS
27 P3D62ML400ATS P3E62ML400ATS P3F62ML400ATS
400 33 P3D68ML400ATS P3E68ML400ATS P3F68ML400ATS
39 P3D74ML400ATS P3E74ML400ATS P3F74ML400ATS
45 P3D80ML400ATS P3E80ML400ATS P3F80ML400ATS
21 P3D56ML600ATS P3E56ML600ATS P3F56ML600ATS
27 P3D62ML600ATS P3E62ML600ATS P3F62ML600ATS
600 33 P3D68ML600ATS P3E68ML600ATS P3F68ML600ATS
39 P3D74ML600ATS P3E74ML600ATS P3F74ML600ATS
45 P3D80ML600ATS P3E80ML600ATS P3F80ML600ATS
21 P3D56ML800ATS P3E56ML800ATS P3F56ML800ATS
27 P3D62ML800ATS P3E62ML800ATS P3F62ML800ATS
800 33 P3D68ML800ATS P3E68ML800ATS P3F68ML800ATS
39 P3D74ML800ATS P3E74ML800ATS P3F74ML800ATS
45 P3D80ML800ATS P3E80ML800ATS P3F80ML800ATS
1 For 600V, change “F” in position 3 to “G.” Price only branch breakers with 600V ratings.

3-6
SECTION 3
Typical Catalog Numbers
Type P3 Panelboards

Table P3-12 – Main Circuit Breaker – shown with aluminum bus, top fed and surface trims.
Maximum Unit 208Y/120V 240/120V 120/240V or 250V dc Max
Panel Space 3 Phase, 4 Wire 3 Phase, 4 Wire 1 Phase, 3 Wire
Amp Rating (inches) Catalog Number Catalog Number Catalog Number
21 P3C56FD250ATS P3B56FD250ATS P3A56FD250ATS
27 P3C62FD250ATS P3B62FD250ATS P3A62FD250ATS
250 33 P3C68FD250ATS P3B68FD250ATS P3A68FD250ATS
39 P3C74FD250ATS P3B74FD250ATS P3A74FD250ATS
45 P3C80FD250ATS P3B80FD250ATS P3A80FD250ATS
9 P3C56JD400ATS P3B56JD400ATS P3A56JD400ATS
15 P3C62JD400ATS P3B62JD400ATS P3A62JD400ATS
400 21 P3C68JD400ATS P3B68JD400ATS P3A68JD400ATS
27 P3C74JD400ATS P3B74JD400ATS P3A74JD400ATS
33 P3C80JD400ATS P3B80JD400ATS P3A80JD400ATS
9 P3C56LD600ATS P3B56LD600ATS P3A56LD600ATS
15 P3C62LD600ATS P3B62LD600ATS P3A62LD600ATS
600 21 P3C68LD600ATS P3B68LD600ATS P3A68LD600ATS
27 P3C74LD600ATS P3B74LD600ATS P3A74LD600ATS
33 P3C80LD600ATS P3B80LD600ATS P3A80LD600ATS
Maximum Unit 240V 408Y/277V 480V 1
Panel Space 3 Phase, 3 Wire 3 Phase, 4 Wire 3 Phase, 3 Wire
Amp Rating (inches) Catalog Number Catalog Number Catalog Number

21 P3D56FD250ATS P3E56FD250ATS P3F56FD250ATS


27 P3D62FD250ATS P3E62FD250ATS P3F62FD250ATS
250 33 P3D68FD250ATS P3E62FD250ATS P3F62FD250ATS
39 P3D74FD250ATS P3E74FD250ATS P3F74FD250ATS
45 P3D80FD250ATS P3E80FD250ATS P3F80FD250ATS
9 P3D56JD400ATS P3E56JD400ATS P3F56JD400ATS
15 P3D62JD400ATS P3E62JD400ATS P3F62JD400ATS
400 21 P3D68JD400ATS P3E68JD400ATS P3F68JD400ATS
27 P3D74JD400ATS P3E74JD400ATS P3F74JD400ATS
33 P3D80JD400ATS P3E80JD400ATS P3F80JD400ATS
9 P3D56LD600ATS P3E56LD600ATS P3F56LD600ATS
15 P3D62LD600ATS P3E62LD600ATS P3F62LD600ATS
600 21 P3D68LD600ATS P3E68LD600ATS P3F68LD600ATS
27 P3D74LD600ATS P3E74LD600ATS P3F74LD600ATS
33 P3D80LD600ATS P3E80LD600ATS P3F80LD600ATS
1 For 600V, change “F” in position 3 to “G.” Price only branch breakers with 600V ratings.

3-7
Standard Modifications
Type P3 Panelboards

P3 Panel Options • NEMA 3R/12 enclosures


Enclosures • NEMA 4 enclosures
• Extra gutter to sides or ends of the can • NEMA 4X enclosures
• Hinged trims • Special keyed locks
• Door-in-door trims - TEY
• Screw to the box trims - TEU1
• Trim mounted devices (Devices mounted and wired - Cat 60
to the trim should also have hinged trim specified) - LL803
- Pilot lights - LL806
- Toggle switches - Yale
- Push buttons • Meters (Contact application engineering for space requirements)
• Painted boxes • Panel Skirts
• Custom colors • Gasketing between trim and box (Type 1)
• Increase gauge trims and boxes • Name Plates
• Stainless steel trims and boxes, Type 1
• Aluminum trims and boxes, Type 1
• NEMA 3R enclosures

Panel Modifications • Grounding of Panelboards


• Main Bus Ground Bars except for brazed-to-box are shipped with the
Standard main bus in tin-plated aluminum. For copper main panel interior.
bus, add from the table for each panel. Includes copper neutral - Non-Insulated Equipment Ground Bar – Standard
cross bar. For copper neutral branch lugs, see miscellaneous. - Copper Non-Insulated Ground Bar
• Split bus requires 6” of unit space. - Al Insulated Equipment Ground Bar
• Compression lug for MLO - Cu Insulated Equipment Ground Bar
• Compression lugs on Main breaker (may require extra - Ground Bar Brazed to Box (recommended for painted boxes)
width or length on enclosure). • Shunt Trip 1
• Contactor mains or submain BL, BLH, HBL, BQD, NGB, HGB, LGB, NEB, HEB, ED2, ED4, HED4,
- Asco 920 through 225 amps - Adds 12" unit space as main, ED6, HED6, HHED6, QJ2, QJ2H, QJH2, QR2, QR2H, HQR2,
HQR2H as branch only. BL, BLH, HBL, ED2, ED4, HED4, ED6,
15” unit space as submain
HED6, HHED6 uses 1” unit space for shunt trip. All others may
- Asco 911 through 150 amps - Adds 21" unit space. be used on mains or subfeeds.
- Siemens LEN through 30 amps - Adds 12” unit space. Makes
box 10” deep. FXD6, HFD6, JXD6, JD6, HJD6, HJXD6
• Control power transformers (contact engineering for
extra gutter requirements) • Remote control switches – 480V AC max. mounted in
• Branch and main breaker accessories a 23” enclosure to be cable connected to the panel.
- Handle blocks • Time Clocks – mounted in a 23” enclosure to be cable
- Handle locks connected to the panel. Sangamo, Tork or Paragon
time clock can be supplied and mounted in panelboard
- Aux. Contacts 1
cabinet.
- UVR 1
• Feed-thru lugs Description
Cannot be used in conjunction with TVSS or sub-feed breakers. Time Clock (1-or 2-Pole, Single or Double Throw Contacts;
See Page 3-10 for unit space impact. Wire ranges are the same 3-Pole Single Throw)
as main lug. 277V Maximum with Plain Dial
Options:
• 200% neutral
Astronomical Dial
• Copper lugs, mechanical An Omitting Device
• Bus mounted TVSS Reserve Power or Carryover
• Service Entrance Label Space and Mounting Provisions Only
Type P3 Panelboards are factory labeled suitable for use as
service entrance equipment when NEC requirements are met.
A panelboard cannot have more than six main disconnects, 1 Accessories on 1" pole breakers (BL, BQD, ED) will take unit space.

unless it is a lighting and appliance branch panelboard.


Lighting and appliance branch panelboards are limited to two
main disconnects.

3-8
SECTION 3
Standard Modifications
Type P3 Panelboards

Table P3-13 – Option Combinations

Subfeed Feed-thru FD1 JD1 FD2 200% Min. Box Unit Space
Amps Incoming Lugs Lugs Subfeed Subfeed Subfeeds Neutral Size (in.) (in.)
• — — — • 56 27
Main Lug Only — — • — — • 56 15
— — — • • 56 9
• — — — • 56 21
Main Lugs w/Subfeed Lugs • — • — — • 56 21
250 — — — • • 62 9
— • — — — • 56 21
Main Breaker (Horiz. FD)
— — • — — • 56 9
Main Breaker (Vert. FD) None Std. • — — — • 56 15
• — — — • 56 9
Main Breaker (CFD) None Std.
— • — — • 68 9
• — — — — • 56 21
— • — — — • 56 15
Main Lug Only — — • — — • 56 9
— — — • — • 56 9
— — — — • • 62 9
— — — — • 56 9
• — — — • 62 9
400 2 3 Main Breaker (JD) None Std. — • — — • 68 9
— — • — • 68 9
— — — • • 74 9
— — — — • 62 9
• — — — • 74 9
Main Breaker (CJD) None Std — • — — • 74 9
— — • — • 74 9
— — — • • 80 9
— — — — • 56 21
• — — — • 56 15
Main Lug Only — — • — — • 56 9
— — • — — 56 9
— — — • • 62 9
— — — — • 56 9
• — — — • 62 9
600 2 3 Main Breaker LD — — • — — • 68 9
— — • — — 68 9
— — — • • 74 9
— — — — • 62 9
• — — — • 68 9
Main Breaker CLD — — • — — • 74 9
— — • — — 74 9
— — — • • 80 9
— — — — • 56 21
• — — — • 56 9
800 2 3 Main Lug Only — — • — — • 56 9
— — • — — 56 9
— — — • • 62 9

3-9
Connector Modifications
Type P3 Panelboards

Compression Lugs
Table P3-14 – Lugs
Style Amp Rating Breaker Type Compression Connectors Box Height Addition
250 N/A (1)#6 AWG - 350 Kcmil —
MLO 400 N/A (1) 250 - 500 Kcmil or —
(2)# 1/0 AWG - 250 Kcmil —
600 N/A (2)#3/0 AWG - 500 Kcmil —
800 N/A (2) 400-750 Kcmil Al only —
250 FXD6, HFD6, CFD6 (1)#6 AWG - 350 Kcmil Cu or Al CFD6 requires an additional 6.0” box height
Main 400 JD6, JXD6, HJD6, (2)#1/0 AWG - 500 Kcmil Cu or Al 6
Breaker CJD6, SJD6, SHJD6, SCJD6
600 LD6, LXD6, HLD6, CJD6, (2)#2/0 AWG - 500 Kcmil Cu or Al 6
SLD6, SHLD6, SCLD6

Table P3-15 – Alternate Lugs


Style Amp Rating Breaker Type Compression Connectors Box Height Addition
MLO 400 N/A (1) 250 - 750 Kcmil or 6
(2)#6 AWG - 350 Kcmil Cu or Al
800 N/A (3) 600 Kcmil 6
Main Breaker 400 JD6, JXD6, HJD6, CJD6, (1)#4/0 AWG - 750 Kcmil Cu or Al 6
SJD6, SHJD6, SCJD6

Enclosure Modifications
NEMA-4 For Type P3 NEMA-4X For Type P3
Water Tight, Dust Tight, Steel Enclosure Water Tight, Dust Tight and Corrosion Resistant
(consult plant for actual enclosure size) (consult plant for actual enclosure size)
Table P3-16 Table P3-17
Box Height Enclosure Size Enclosure - Stainless Steel Enclosure - Fiberglass
Inches H W D Box Height and Steel with Epoxy Coating Size (inches)
56 60 36 8 Inches H W D H W D
62 66 36 8 56 60 36 12 60 36 12
68 72 36 8 62 66 36 8 66 36 8
74 78 36 8 68 72 36 8 72 36 8
80 84 36 8 74 78 36 8 78 36 8
80 84 36 8 84 36 8

Remote Switch Modifications


Table P3-18 – Control Power Table P3-19 – Application For Remote Switch
Transformer
Switch Type Modification
Size VA
920 Adds 12” to unit space
0,1 50 911 ≤ 225A Adds 21” unit space
2 75 LEN >30A ≤ 100 Adds 12” to unit space
3 150 100 A ≤ 200 Adds 12” to unit space and 10” Dp. min.
4 250

Table P3-20 – Remote Control


Switch Modification
Description
Auxiliary Contacts (mounted, not wired)
Ea. 2-Wire Control

3-10
SECTION 3
Dimensions
Type P3 Panelboards

Type 1 Box
Box is symmetrical


a"

a"

a"

Type 3R and 3R/12 Box


a"

햲"
a

a"

햲 Dimensions are interior of the box. Add 5/8” to width for


absolute dimension. Add 1/8” to height for absolute dimension.
햳 See table P3-2 to match ratings.

Dimensions shown in inches and millimeters [ ].

3-11
Dimensions
Type P3 Panelboards

Standard
A B C Box Size
47.97 42.00 40.75 56H 24W 7.75D
53.97 48.00 46.75 62H 24W 7.75D
59.97 54.00 52.75 68H 24W 7.75D
65.97 60.00 58.75 74H 24W 7.75D
71.97 66.00 64.75 80H 24W 7.75D

3-12
2
SECTION
Kits and Accessories
Type P3 Panelboards

Table P3-21 – Standard Enclosures


Catalog Number
Box Type 1 Type 3R Type 3R/12
Height Standard Trim
(in.) Box Surface Flush
56 24WD56 P3S56 P3F56 24NRD56 24WPD56
62 24WD62 P3S62 P3F62 24NRD62 24WPD62
68 24WD68 P3S68 P3F68 24NRD68 24WPD68
74 24WD74 P3S74 P3F74 24NRD74 24WPD74
80 24WD80 P3S80 P3F80 24NRD80 24WPD80

Options For Type 1 Trims


Items must be ordered as manual line item on factory
Hinged trim – Add “H” suffix
Door-in-door – Add “D” suffix
Metal card holder – Add “M” suffix

Table P3-22 – Breaker Kits and Accessories


Kit No. Description Contents
BBKB32 (P2/P3) BL/BQD 6-pole 3” branch breaker kit Kit contains top barrier, (3) A/C connectors, (3) B connectors, hardware
BBKNB32 (P2/P3) NGB 6-pole 3” branch mounting kit Kit contains top barrier, (3) A/C connectors, (1) B connector, hardware
BBKEB32 (P3) NEB/HEB 6-pole 3” branch mounting kit Kit contains top barrier, (3) A/C connectors, (1) B connector, hardware
BBKED32 (P2/P3) ED 6-pole 3” branch breaker kit Kit contains breaker support, inter-phase barriers, (3) A/C connectors, (1) B connector, hardware
QJ/QR branch breaker kit for 2 and
BBKQ2 (P3) Kit contains all connectors and cover plates necessary to mount 2 and 3 pole breakers
3-pole single mount
P2 branch BKR strap kit for single QR
BBKQR11 Kit contains all connectors and cover plates necessary to mount both 2 and 3-pole breakers
1-phase/3-phase
BBKQR21 P3 branch BKR strap kit for single QR
Kit contains all connectors and cover plates necessary to mount both 2 and 3-pole breakers
1-phase/3-phase
DFFP3 Deadfront filler 3” 3” empty space filler and hardware
DFFP6 Deadfront filler 6” 6” empty space filler and hardware
P3BK1 P3 bonding kit Bonding strap and hardware
EBF1 NEB/HEB filler plate 1” filler plate
BBKQRP1FK P2 filler for QR. Horizontal or vertical Kit contains all cover plates necessary to change from QJ to QR both 2 and 3-pole breaker
mount. 1-phase/3-phase.
BBKQRP2FK P3 filler for QR. Dual mount horizontal. Kit contains all cover plates necessary to change from QJ to QR both 2 and 3-pole breakers.
1-phase/3-phase. For 1-phase panel, both breakers mush change from QJ to QR, cannot have one of
each installed.
SEBP3V12 Service entrance barrier kit CFD, FD Kit contains barrier, mounting brackets, and hardware
(P3 only)
SEBKP1P2P3V12 JD, LD Service Entrance Barrier Kit Kit contains barrier, mounting brackets, and hardware
(RP1, P1, P2, P3)
1 Although QR is rated 250A. it is limited to 225A in panelboard.
2 Factory installed and Field installable Service Entrance Barrier kits are now available
as required by UL67 (In COMPAS, you must select Service Entrance Required.)

3-13
Notes
SECTION 4
P4 Panelboards
Description Page
General Information 4-2 Branch Breaker Side Gutter 4-7
Selection and Application 4-2 Typical Catalog Numbers 4-8
Applications 4-3 – 4-6 Main Lugs Only 4-8
Main Breaker Selection 4-3 Main Circuit Breakers Only 4-8
Main Switch Connectors 4-3 Modifications and Additions 4-9
Enclosure Selection 4-3 Connector Modifications 4-10
Main Breaker Unit Space Dimensions 4-3
Compression Lugs 4-10
Main Lugs Only Unit Space Dimensions 4-4
Branch Switch Unit Space 4-4 Alternate Lugs 4-10
Branch Circuit Breakers 4-5 – 4-6 Dimensions 4-11
Branch Breaker Unit Space 4-7 Kits and Accessories 4-12 – 4-13
Type P4 Panelboards

The P4 panel is a medium sized footprint distribution panel to Bussing – The P4 panel has more options to meet market
fit a large number of applications that require more or larger requirements. The standard bussing is temperature rated
branch devices and higher amp ratings than the lighting panel aluminum. The rating is per the requirements of UL 67 – the
class offers. Even with the increased capacity, this panel is a standard for panelboards. All aluminum bussing is tin-plated.
space saver with its 32" width and 10" depth. The P4 panel offers Optional bussing for the P4 panel is: 750 A/Si aluminum,
a wide array of factory-assembled options and has the ability to temperature rated copper, and 1000 A/Si copper. The copper
mix breaker frames in unit space up to 800 amps and fusible bus option for this panel is silver-plated.
switches up to 200 amps. Bussing options for the P4 vary from
the standard temperature rated aluminum to temperature rated Weight – Approximate
copper and 750A/Si aluminum and 1000A/Si copper designs. Total panelboard weight when filled with a normal quantity of
All aluminum bussing in the P4 panel is tin-plated as a standard. breakers and accessories is about 8 lbs. (1 kg) per inch (54g per
Silver-plated is offered as the default for copper bus and tin as an mm) of box height.
option. Integrated time clocks, bus mounted contactors as mains
or submains, split bus and subfeed lugs (up to 600 amp) are just Table P4-1 – Main Lugs 1
a few of the options of this flexible panel. Ampere Rating Connectors Suitable for Copper or Aluminum
400 (1) - #3/0 AWG-600 Kcmil
The 3 panel configurations defined by the unit space allowed
(2) - #3/0 AWG-250 Kcmil
for a given amperage, main device and box height. The P4 panel
600 (2) - #3/0 AWG-600 Kcmil
starts with a 60" high box. All of the branch devices are unit 800 (3) - #3/0 AWG-600 Kcmil
space mounted. Breakers and switches can be mixed and 1000 (4) - #3/0 AWG-600 Kcmil
matched to meet customer requirements. 1200 (4) - #3/0 AWG-600 Kcmil

Main Lug / Main Breaker / Main Switch 1 Alternate lugs for 750 kcmil cable are available, but result in significant loss of
branch unit mounting space. Consult Siemens.
Enclosure – Standard Type 1 enclosure is 32" wide x 10" deep. Table P4-2 – Gauge Steel of Boxes
X Box Height is determined by main device and unit space. See Fronts, Surface and Flush
charts for box height.
Dimensions in inches (mm) Gauge Steel
Voltage – 600 Vac Max. Width Height Box Fronts
250 Vdc Max #161 #14 (1 piece trim)
32” 60 - 75 - 90 #14 (4 piece trim)
Amperage – 400-800 amp main breaker or 400-1200 amp (813) (1524, 1905, #12 #12 (1 piece trim, door in door)
2286) #10 #10 (1 piece door trim in)
Main Lug Only #16 #16 (4 piece trim)
Short Circuit Rating – 200 KAIC Max. symmetrical or equal to 1 Box has 16 gauge side panels, 14 gauge backplates and 12 gauge back support.
the lowest rated device installed unless a series rating is indicated.
Panels with subfeed or feed-thru lugs without a main device,
circuit breaker or fusible unit, are limited to a three-cycle rating.
The three-cycle rating for the P4 panel is limited to 42 KAIC. Note
that the main device may be mounted remote from the panel.

Selection and Application


1) To specify a particular panelboard, first determine voltage, Select appropriate enclosure height from selection chart on
system, amperage and type of main, amperage and type page 4-3, based on unit space requirements. (Step 2)
of branch devices, and modifications, if any. (Step 1)
3) Select panelboard catalog number from appropriate table
2) List branch devices and modifications requiring space based upon voltage, system, amperage and unit space
additions. List unit space requirements of each. requirements. (Step 3)
Note: Some units are twin mounted meaning two breakers
occupy the same unit space.
Step #1 Step #2 Step #3
Amperage 400 5-125/3 ED4 3.75” = 11.25” Twin Mounted 1-P4C75JX400ATS
Voltage 208Y/120 2-225/3 QJ2/QR2 5” = 5” Twin Mounted 3-ED4 1-Pole Provision
System 3 Phase, 4 wire 1-250/3 FXD6 5” = 5” 5-125/3
Main Main Breaker 21.25 2-225/3 QJ2/QR2
Branches 5-125/3, 2-225/3, 1-250/3 FXD6
1-250/3 Enclosure is B275 from Selection
12” Space
Modifications None Chart on Page 4-3.
Feed Top (32” wide, 75” high, 10” deep)
Mounting Surface

4-2
SECTION 4
Application
Type P4 Panelboards

Table P4-3 – Main Breaker Selection


Breaker type Maximum IC (KA) Symmetrical Amperes
Main Breaker
Ampere Trip Frame Breaker Unit Space in
rating type type family 240V 480V 600V inches (mm) Continuous Current Rating
JXD6, JD6 Sentron 65 35 22 8.75 (222) 200, 225, 250, 300, 350, 400
Thermal HJXD6, HJD6 Sentron 100 65 35 8.75 (222) 200, 225, 250, 300, 350, 400
Magnetic HHJXD6, HHJD6 Sentron 200 100 50 8.75 (222) 200, 225, 250, 300, 350, 400
CJD6 Sentron 200 150 100 8.75 (222) 200, 225, 250, 300, 350, 400
NJ VL 65 35 25 6.25 (159) 250, 400
400A SJD6 Sentron 65 35 25 8.75 (222) 200, 300, 400
Electronic HJ VL 100 65 25 6.25 (159) 250, 400
(solid state) SHJD6 Sentron 100 65 35 8.75 (222) 200, 300, 400
LJ VL 200 100 25 6.25 (159) 250, 400
SCJD6 Sentron 200 150 100 8.75 (222) 200, 300, 400
LXD6 Sentron 65 35 25 8.75 (222) 450, 500, 600
LD6 Sentron 65 35 25 8.75 (222) 250, 300, 350, 400, 450, 500, 600
Thermal HLXD6, HLD6 Sentron 100 65 35 8.75 (222) 250, 300, 350, 400, 450, 500, 600
Magnetic
HHLXD6, HHLD6 Sentron 200 100 50 8.75 (222) 250, 300, 350, 400, 450, 500, 600
600A CLD6 Sentron 200 150 100 8.75 (222) 250, 300, 350, 400, 450, 500, 600
NL VL 65 35 18 6.25 (159) 400, 600
SLD6 Sentron 65 35 25 8.75 (222) 300, 400, 500, 600
Electronic HL VL 100 65 18 6.25 (159) 400, 600
(solid state) SHLD6 Sentron 100 65 35 8.75 (222) 300, 400, 500, 600
LL VL 200 100 18 6.25 (159) 400, 600
SCLD6 Sentron 200 150 100 8.75 (222) 300, 400, 500, 600
NM VL 65 35 25 8.75 (222) 600, 700, 800
Thermal
Magnetic HM VL 100 65 35 8.75 (222) 600, 700, 800
LM VL 200 100 50 8.75 (222) 600, 700, 800
800A NM VL 65 35 25 8.75 (222) 600, 800
Electronic
(solid state) HM VL 100 65 35 8.75 (222) 600, 800
LM VL 200 100 50 8.75 (222) 600, 800

Table P4-4 – Enclosure Selection 1 Fig. P4-1


Enclosure Dimension Available Circuit Space in Inches (mm)
in Inches (mm) Dimension “C”
Main Lug Main Breaker H
H W D 400-800A 400-800A
60 (1524) 32 (813) 10 (254) 30 (762) 21.25 (540)
75 (1905) 32 (813) 10 (254) 45 (1143) 36.25 (921) 90 90
90 (2286) 32 (813) 10 (254) 60 (1524) 51.25 (1302)

1 Standard trim is four piece without door. Surface or flush one piece trim is available for 32 in. (813 mm) wide
circuit breaker panels.

Table P4-5 – Main Breaker Lug Location Reference (Fig. P4-1)


Ampere Breaker Dimensions in Inches (mm)
Rating Type A B
400 JXD6, JD6, HJXD6, HJD6
10.425 (265)
400 HHJXD6, HHJD6
400 NJ, HJ, LJ 12.500 (318)
400 SJD6, SHJD6 10.425 (265)
400 CJD6, SCJD6 8.250 (210)
LXD6, LD6, HLXD6, HLD6, 13.125 (333)
600 10.425 (265)
HHLXD6, HHLD6
600 NL, HL, LL 11.250 (286)
600 SLD6, SHLD6 10.425 (265)
600 CLD6, SCLD6 8.250 (210)
800 NM, HM, LM, 10.425 (265)

4-3
Application
Type P4 Panelboards

Table P4-6 – Main Lugs Location Reference (Fig. P4-2) Fig. P4-2
Dimensions in inches (mm)
Main Lug Neutral
400A 600A 800A 1000A 1200A 400-600A 800-1200A
Lugs A B C D E F G
Standard 16.500 16.750 15.969 15.969 15.969 13.125 13.125
(419) (425) (406) (406) (406) (333) (333)
Oversize 16.500 21.750 25.969 25.969 25.969 18.125 23.125
(419) (552) (660) (660) (660) (460) (587)
Crimp 19.187 18.250 18.687 18.250 18.250 15.937 15.937
(487) (464) (475) (464) (464) (405) (405)
Standard 16.750 15.969 — — — 13.125 13.125
w/Subfeed (425) (406) (333) (333)
Standard 16.500 16.750 — — — 13.125 13.125
w/Feed-thru (419) (425 ) (333) (333)

Table P4-7 – Available Unit Space – MLO


Dimensions in inches (mm)
Ampere Rating
Lug Type Box Height 400 600 800 1000 1200
60 30 30 30 30 30
Standard
Mechanical 75 45 45 45 45 45
90 60 60 60 60 60
60 30 25 20 20 20
Oversized
Mechanical 75 45 40 35 35 35
90 60 55 50 50 50
60 25 25 25 25 24
Crimp Type 75 40 40 40 40 40
90 55 55 55 55 55
60 30 30 — — —
Std Mechanical
75 45 45 — — —
W/ Sub-feed
90 60 60 — — —
60 20 20 12.5 12.5 12.5
Std. Mechancial
75 35 35 27.5 27.5 27.5
W/ Feed-thru
90 50 50 42.5 42.5 42.5

Table P4-8 – Branch Switch Unit Space


Unit Space
in inches (mm)
Ampere Number Twin Single AC Cables Per Connectors Suitable For
Rating of Poles Mounted Mounted Voltage Connector Copper or Aluminum
30-30 2,3 2.50 (64) — 240 1 #14 - #8 AWG (Cu Only)
30-30 2,3 5.00 (127) — 240 1 #14 - #4 AWG
30-60 2,3 5.00 (127) — 240 1 #14 - #4 AWG
60-60 2,3 5.00 (127) — 240 1 #14 - #4 AWG
60-100 2,3 7.50 (191) — 240 1 #10 - #1/0 AWG
100-100 2,3 7.50 (191) — 240 1 #10 - #1/0 AWG
200-200 3 10.00 (254) — 240 1 #6 AWG - 350 Kcmil
200 2 — 7.50 (191) 240 1 #6 AWG - 350 Kcmil
200 3 — 10.00 (254) 240 2 #6 AWG - 350 Kcmil
30-30 2,3 7.5 (191) — 600 1 #14 - #8 AWG
30-60 2,3 7.5 (191) — 600 1 #14 - #4 AWG
60-60 2,3 7.5 (191) — 600 1 #14 - #4 AWG
60-100 2,3 7.5 (191) — 600 1 #10-#1/0 AWG
100-100 2,3 7.5 (191) — 600 1 #10-#1/0 AWG
200-200 3 10.00 (254) — 600 1 #6 AWG - 250 Kcmil
100 2,3 — 7.50 (191) 600 1 #10-#1/0 AWG
200 2,3 — 10.00 (254) 600 1 #6 AWG - 250 Kcmil

4-4
SECTION 4
Application
Type P4 Panelboards

Table P4-9 – Branch Circuit Breakers


Maximum Bolt-on Maximum IC (KA) Symmetrical Amperes
Ampere Breaker Number Trip Amp Voltage - AC
Rating Type of Poles Rating 120 120/240 240 277 480/ 277 480 600/347 600
1 15-30 10 — — — — — — —
BLF
2 15-60 — 10 — — — — — —
1 15-30 22 — — — — — — —
BLHF
2 15-60 — 22 — — — — — —
1 15-30 10 — — — — — — —
BLE
2 15-60 — 10 — — — — — —
1 15-30 22 — — — — — — —
BLEH
2 15-60 — 22 — — — — — —
BAF, BAFC 1 15-20 10 — — — — — — —
BAFH, BAFHC 1 15-20 22 — — — — — — —
BAF 2 15-20 — 10 — — — — — —
BAFH 2 15-20 — 22 — — — — — —
BGL 2 15-30 10 — — — — — — —
3 15-30 — 10 — — — — — —
BLR 2 15-100 — — 10 — — — — —
100
BL 1 15-70 10 — — — — — — —
2 15-100 — 10 — — — — — —
3 15-100 — — 10 — — — — —
BLH 1 15-70 — 22 — — — — — —
2 15-100 — 22 — — — — — —
3 15-100 — — 22 — — — — —
HBL 1 15-70 — 65 — — — — — —
2 15-100 — 65 — — — — — —
3 15-100 — — 65 — — — — —
BQD 1 15-100 — 65 — 14 — — — —
2 15-100 — 65 — — 14 — — —
3 15-100 — — 65 — 14 — — —
BQD61 1 15-70 65 — — — — — — —
2/3 15-100 — — 65 — — — — 10
BL (HID) 1/2 15-30 — 10 — — — — — —
BLF (GFCI) 1 15-60 — 10 — — — — — —
2 40-60 — 10 — — — — — —
BLE (EQ GFI) 1/2 15-30 — 10 — — — — — —
BLG (SWN) 2 15-30 10 — — — — — — —
3 15-30 — 10 — — — — — —
BLHF (GCFI) 1/2 15-30 — 22 — — — — — —
NGB 1 15-125 100 — — 25 — — — —
2/3 15-125 — 100 100 — 25 — 14 —
HGB 1 15-125 100 — — 35 — — — —
2/3 15-125 — 100 100 — 35 — 14 —
LGB 1 15-125 100 — — 65 — — — —
2/3 15-125 — 100 100 — 65 — 14 —
NEB 1 15-125 100 85 85 35 — — — —
2/3 15-125 — 85 85 — 35 35 22 —
HEB 1 15-125 200 100 100 65 — — — —
2/3 15-125 100 100 — 100 65 25 25 —
125 ED4 1 15-125 65 — — 22 — — — —
2/3 15-125 — 65 65 — 18 18 —
ED6 2 15-125 — — — — 25 25 30 —
3 15-125 — — 65 — 25 25 — 18
HED4 1 15-125 100 — — 652 — — — —
2/3 15-125 — 100 100 — 42 42 — —
HHED6 2/3 15-125 100 — — — 65 65 18 18
CED6 2/3 15-125 200 — — — 200 200 100 100
1 CSA listed only at 600V AC.
2 15-30A trip (shown) 65 KA, 35-100A 25 KA.

4-5
Application
Type P4 Panelboards

Table P4-9 – Branch Circuit Breakers (continued)


Maximum Bolt-on Number Trip Amp Maximum IC (KA) Symmetrical Amperes
Ampere Breaker of Poles Rating Voltage – AC
Breaker Type 120 120/240 240 277 480/277 480 600/347 480
QJ2 2/3 60-225 — — 10 — — — — —
225
QJH2 2/3 60-225 — — 22 — — — — —
QJ2H 2/3 60-225 — — 42 — — — — —
QR2 2/3 100-225 — — 10 — — — — —
QRH2 2/3 100-225 — — 25 — — — — —
HQR2 2/3 100-225 — — 65 — — — — —
HQR2H 2/3 100-225 — — 100 — — — — —
FXD6, FD6 2/3 70-250 — — 65 — 35 35 18 18
HFXD6, HFD6 2/3 70-250 — — 100 — 65 65 25 25
250
HHFXD6, HHFD6 2/3 70-250 — — 200 — 100 100 25 25
CFD 2/3 70-250 — — 200 — 200 200 100 100
JXD6, JD6, SJD6 2/3 200-400 — — 65 — 35 35 25 25
HJXD6, HJD6, SHJD6 2/3 200-400 — — 100 — 65 65 35 35
400
HHJXD6, HHJD6 2/3 200-400 — — 200 — 100 100 50 50
CJD6 2/3 200-400 — — 200 — 150 150 100 100
LXD6 2/3 450-600 — — 65 — 35 35 25 25
LD6 2/3 250-600 — — 65 — 35 35 25 25
SLD6 2/3 300-600 — — 65 — 35 35 25 25
600 HLD6, HLXD6 2/3 250-600 — — 100 — 65 65 35 35
SHLD6 2/3 300-600 — — 100 — 65 65 35 35
HHLD6, HHLXD6 2/3 250-600 — — 200 — 100 100 50 50
CLD6 2/3 450-600 — — 200 — 150 150 100 100
SCLD6 2/3 300-600 — — 200 — 150 150 100 100

Table P4-10 – Branch Circuit Breakers (VL)


Maximum IC (KA) Symmetrical Amperes
Maximum Bolt-on Number Trip
Ampere Breaker of Amp Volts – AC
Rating Type Poles Rating 120 120/240 240 277 480/277 480 600/347 600
ND 3 60 - 150 — 65 65 — 35 35 18 18
150 1 HD 3 60 - 150 — 100 100 — 65 65 20 20
LD 3 60 - 150 — 200 200 — 100 100 25 25
NF 3 100 - 250 — 65 65 — 35 35 18 18
250 1 HF 3 100 - 250 — 100 100 — 65 65 20 20
LF 3 100 - 250 — 200 200 — 100 100 25 25
NJ 3 250 - 400 — 65 65 — 35 35 25 25
400 1 HJ 3 250 - 400 — 100 100 — 65 65 25 25
LJ 3 250 - 400 — 200 200 — 100 100 25 25
NL 3 400 - 600 — 65 65 — 35 35 18 18
600 1 HL 3 400 - 600 — 100 100 — 65 65 18 18
LL 3 400 - 600 — 200 200 — 100 100 18 18
NM 2/3 600 - 800 — 65 65 — 35 35 25 25
800 HM 2/3 600 - 800 — 100 100 — 65 65 35 35
LM 2/3 600 - 800 — 200 200 — 100 100 50 50
1 Only offered with Electronic Trip Units.

4-6
SECTION 4
Application
Type P4 Panelboards

Table P4-11 – Branch Breaker Unit Space Requirements


Mounting Height in inches (mm)
Ampere Number Twin Single AC Cables Per Connectors Suitable for
Rating of Poles Mounted Mounted Voltage Connector Copper or Aluminum
30-30 2, 3 2.50 (64) — 240 1 #14 - #8 AWG (Cu Only)
30-30 2, 3 5.00 (127) — 240 1 #14 - #4 AWG
30-60 2, 3 5.00 (127) — 240 1 #14 - #4 AWG
60-60 2, 3 5.00 (127) — 240 1 #14 - #4 AWG
60-100 2, 3 7.50 (191) — 240 1 #10 - #1/0 AWG
100-100 2, 3 7.50 (191) — 240 1 #10 - #1/0 AWG
200-200 3 10.00 (254) — 240 1 #6 AWG - 350 kcmil
200 2 — 7.50 (191) 240 1 #6 AWG - 350 kcmil
200 3 — 10.00 (254) 240 2 #6 AWG - 350 kcmil
30-30 2, 3 7.5 (191) — 600 1 #14 - #8 AWG
30-60 2, 3 7.5 (191) — 600 1 #14 - #4 AWG
60-60 2, 3 7.5 (191) — 600 1 #14 - #4 AWG
60-100 2, 3 7.5 (191) — 600 1 #10-#1/0 AWG
100-100 2, 3 7.5 (191) — 600 1 #10-#1/0 AWG
200-200 3 10.00 (254) — 600 1 #6 AWG - 250 kcmil
100 2, 3 — 7.50 (191) 600 1 #10-#1/0 AWG
200 2, 3 — 10.00 (254) 600 1 #6 AWG - 250 kcmil

Table P4-12 – Branch Breaker Side Fig. P4-3


Gutter Inches (mm) (Fig. P4-3)
Panel Width 32 in (813) BL, BLH, HBL, BQD, BLE BL, BLH, HBL, BQD, BLE
Reference
Letter Dimensions in inches (mm) A BLEH, BLR, BLF, BLHF, BLEH, BLR, BLF, BLHF, A
A 11.0 (279) BAF, BAHF, BGL, BQD BAF, BAHF, BGL, BQD
B NGB. HGB. LGB NGB, HGB, LGB B
B 10.98 (279)
C 8.62 (219) C NEB, HEB NEB, HEB C
D 7.0 (178) D ED4, ED6, ED4, ED6, D
E 5.75 (146) HED4 HED4
F 5.25 (133)
H CED CED H
G — QJ2, QJH2, QJ2H, QJ2, QJH2, QJ2H,
H 4.62 (177) E QR2, QR2H QR2, QR2H E
I 8.76 (223) HQR2, HQR2H HQR2, HQR2H
J 10.42 (265) FXD6, FD6, HFXD6, FXD6, FD6, HFXD6,
K 10.0 (254) F HFD6, HHFXD6, HHFD6, HFD6, HHFXD6, HHFD6 F
L 8.25 (210) SFD6, SHFD6 SFD6, SHFD6
M 10.0 (254) Q ND, HD, LD ND, HD, LD Q
N 7.0 (178) R NF, HF, LF NF, HF, LF R
O 5.0 (127) I CFD6, SCFD6 I
P 7.50 (191)
JD6, JXD6, SJD6, HJD6, HXJD6, SHJD6, HHJD6,
Q 7.9 (200) J J
HHJXD6, LD6, LXD6, SLD6, HLD6, HXLD6, SHLD6,
R 7.9 (200)
HHLD6, HHLXD6
S 2.5 (318)
L CJD6, SCJD6, CLD6, SCLD6 L
T 11.25 (286)
S NJ, HJ, LJ S
T NL, HL, LL T
K NM, HM, LM K
M VB 30A, VB 60A (5”) VB 30A, VB 60A (5”) M
N VB 30A, VB 60A (5”) VB 30A, VB 60A (5”) N
O VB 100 - 200A VB 100 - 200A O
P VB 100 - 200A Single P

4-7
Application
Type P4 Panelboards

Table P4-13 – Main Lugs Only – shown with aluminum bus, top fed, and surface trims
Max. 208Y/120V 240/120V 120/240V or 240V 480Y/277V 480V 1
Panel Unit 250 Vdc Max
Amp Space 3 Phase, 4 Wire 3 Phase, 4 Wire 1 Phase, 3 Wire 3 Phase, 3 Wire 3 Phase, 4 Wire 3 Phase, 3 Wire
Rating (inches) Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
30 P4C60ML400ATS P4B60ML400ATS P4A60ML400ATS P4D60ML400ATS P4E60ML400ATS P4F60ML400ATS
400 45 P4C75ML400ATS P4B75ML400ATS P4A75ML400ATS P4D75ML400ATS P4E75ML400ATS P4F75ML400ATS
60 P4C90ML400ATS P4B90ML400ATS P4A90ML400ATS P4D90ML400ATS P4E90ML400ATS P4F90ML400ATS
30 P4C60ML600ATS P4B60ML600ATS P4A60ML600ATS P4D60ML600ATS P4E60ML600ATS P4F60ML600ATS
600 45 P4C75ML600ATS P4B75ML600ATS P4A75ML600ATS P4D75ML600ATS P4E75ML600ATS P4F75ML600ATS
60 P4C90ML600ATS P4B90ML600ATS P4A90ML600ATS P4D90ML600ATS P4E90ML600ATS P4F90ML600ATS
30 P4C60ML800ATS P4B60ML800ATS P4A60ML800ATS P4D60ML800ATS P4E60ML800ATS P4F60ML800ATS
800 45 P4C75ML800ATS P4B75ML800ATS P4A75ML800ATS P4D75ML800ATS P4E75ML800ATS P4F75ML800ATS
60 P4C90ML800ATS P4B90ML800ATS P4A90ML800ATS P4D90ML800ATS P4E90ML800ATS P4F90ML800ATS
30 P4C60ML101ATS P4B60ML101ATS P4A60ML101ATS P4D60ML101ATS P4E60ML101ATS P4F60ML101ATS
1000 45 P4C75ML101ATS P4B75ML101ATS P4A75ML101ATS P4D75ML101ATS P4E75ML101ATS P4F75ML101ATS
60 P4C90ML101ATS P4B90ML101ATS P4A90ML101ATS P4D90ML101ATS P4E90ML101ATS P4F90ML101ATS
30 P4C60ML120ATS P4B60ML120ATS P4A60ML120ATS P4D60ML120ATS P4E60ML120ATS P4F60ML120ATS
1200 45 P4C75ML120ATS P4B75ML120ATS P4A75ML120ATS P4D75ML120ATS P4E75ML120ATS P4F75ML120ATS
60 P4C90ML120ATS P4B90ML120ATS P4A90ML120ATS P4D90ML120ATS P4E90ML120ATS P4F90ML120ATS

Table P4-14 – Main Circuit Breakers Only – shown with standard mains, aluminum bus, top fed, and surface trims
Max. 208Y/120V 240/120V 120/240V or 240V 480Y/277V 480V 1
Panel Unit 250 Vdc Max
Amp Space 3 Phase, 4 Wire 3 Phase, 4 Wire 1 Phase, 3 Wire 3 Phase, 3 Wire 3 Phase, 4 Wire 3 Phase, 3 Wire
Rating (inches) Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
21.25 P4C60JX400ATS P4B60JX400ATS P4A60JX400ATS P4D60JX400ATS P4E60JX400ATS P4F60JX400ATS
400 36.25 P4C75JX400ATS P4B75JX400ATS P4A75JX400ATS P4D75JX400ATS P4E75JX400ATS P4F75JX400ATS
51.25 P4C90JX400ATS P4B90JX400ATS P4A90JX400ATS P4D90JX400ATS P4E90JX400ATS P4F90JX400ATS
21.25 P4C60LX600ATS P4B60LX600ATS P4A60LX600ATS P4D60LX600ATS P4E60LX600ATS P4F60LX600ATS
600 36.25 P4C75LX600ATS P4B75LX600ATS P4A75LX600ATS P4D75LX600ATS P4E75LX600ATS P4F75LX600ATS
51.25 P4C90LX600ATS P4B90LX600ATS P4A90LX600ATS P4D90LX600ATS P4E90LX600ATS P4F90LX600ATS
21.25 P4C60M1800ATS P4B60M1800ATS P4A60M1800ATS P4D60M1800ATS P4E60M1800ATS P4F60M1800ATS
800 36.25 P4C75M1800ATS P4B75M1800ATS P4A75M1800ATS P4D75M1800ATS P4E75M1800ATS P4F75M1800ATS
51.25 P4C90M1800ATS P4B90M1800ATS P4A90M1800ATS P4D90M1800ATS P4E90M1800ATS P4F90M1800ATS
1 For 600V, change “F” in position 3 to “G.”

4-8
SECTION 4
Modifications and Additions
P4 Panelboards

Devices Mounted on Gutter Cover Fuse Clip Provisions Main Bus


Includes Device, Mounting – Wired or (Add to 250 Volts or 600 Volts Standard main bus and ground bus are
Unwired Unit Prices Per Switch) tin-plated aluminum. For copper main
bus, neutral bus and ground bus, add
Description Amp Class Class Class from the table for each panel.
One piece front with door Rating J R T
Hinged Gutter Covers 4 pc front 30 — • • Lugs – For Main Lug Only Panels
Toggle Switch — SPST or 3-way 60 — • • Standard main lugs and neutral lugs
15A, 277V maximum 100 — • •
Pilot Light — General Purpose
are tin-plated aluminum, UL listed for
200 — • • use with aluminum/copper cables.
Neon or Incandescent
Pushbutton Copper only lugs are an option.
Spanner Wrenches
Ampere Rating
(for Vacu-Break Switches)
Increased Capacity Neutral 400 - 1200
Ampere Rating Unit Space
Ground Fault on Main Breaker
Phase Neutral ( inches) Description Shunt Trip on Main and Branches 4
400 600 0 Conventional Ground Fault 1
400 800 0 Includes: Description
600 1200 0 Ground Fault Relay, Ground Sensor, BL, BQD, NGB, HGB, LGB (branch only)
800 1200 0 CPT and Shunt Trip QJ2, QJH2, QJ2H, QR2, QRH2, HQR2,
Test and Monitor Panel 2 HQR2H, NEB, HEB, ED4, ED6, HED4,
Ground Fault add to Sensitrip III HHED6, CED6
Subfeed or Feed-Thru Lugs breaker price
(One Set Per Panel)
Subfeed Double Lugs
(Main Lug Panels) Time Clocks 3 100% Rated Main Circuit Breakers
Sangamo, Tork or Paragon time clock
Unit Spaces Ampere Breaker
can be supplied, mounted in panelboard Rating Type
Amp (Additional inches) cabinet. For required increase in enclosure
Rating MLO JXD6H, HJXD6H
dimension, consult local sales office.
400A SCJD6H, SHJD6H
400 0
Description NJY, HJY, LJY
600 0
Time clock (1- or 2-Pole, Single or Double LXD6H, HLXD6H
800 N/A 600A
Throw Contacts; 3-Pole Single Throw) NMY 5, HMY 5, LMY 5
1200 N/A
277V Maximum with Plain Dial All others to 800A
Optional:
Feed-Thru Lugs Astronomical Dial
Ampere Rating Unit Space (inches) An Omitting Device
Reserve Power or Carryover
400 10
Space and Mounting Provisions Only
600 10
800 17.5
Circuit Breaker Accessories
1200 17.5
Handle Blocking Device
Blocks handle in either the
Grounding of Panelboards “ON” or “OFF” position.
Ground Bars (except for brazed-to-box)
are shipped with the panel interior Padlocking Device – Padlocks
factory mounted. in “OFF” position.
• Non-Insulated Equipment Ground
Bar – Standard
• Copper Non-Insulated Ground Bar
• Al Insulated Equipment Ground Bar
• Cu Insulated Equipment Ground Bar
• Ground Bar Brazed to Box

1 Available in 90” high enclosure only. Unit space is 4 Shunt Trip on 100A frame breakers increases
42 1/2” with Test and Monitor Panel; 45” without mounting height to 6.25” for twin mounting.
Test and Monitor Panel. 5 The 600A, 100% rated breaker requires the use of
2 Not available on Sensitrip III. an 800A frame breaker.
3 For required unit space, consult local sales office.

4-9
Connector Modifications
P4 Panelboards

Lug Modifications
Table P4-15 – Compression Lugs
Amp Breaker Compression Box Height
Style Rating Type Connectors Addition
250 N/A (1)#6 AWG - 350 kcmil —
(1) 250 - 500 kcmil or —
400 N/A
MLO (2)# 1/0 AWG - 250 kcmil —
600 N/A (2)#3/0 AWG - 500 kcmil —
800 N/A (2) 400-750 kcmil Cu only —
CFD6 requires an
250 FXD6, HFD6, CFD6 (1)#6 AWG - 350 kcmil Cu or Al
additional 6.0" box height
Main 400 JD6, JXD6, HJD6, CJD6, SJD6, SHJD6, SCJD6 (2)#1/0 AWG - 500 kcmil Cu or Al —
Breaker
LD6, LXD6, HLD6, CJD6,
600 (2)#2/0 AWG - 500 kcmil Cu or Al —
SLD6, SHLD6, SCLD6

Table P4-16 – Alternate Lugs


Amp Breaker
Rating Type Compression Connectors Available Unit Space Reduction
(1)#3/0 AWG - 750 Kcmil or
400 N/A Deduct 0” of Unit Space
(2)#3/0 AWG 250 Kcmil Cu or Al
600 N/A (2)#3/0 AWG - 750 Kcmil Deduct 5” of Unit Space
800 N/A (3)#3/0 AWG - 750 Kcmil Cu or Al Deduct 10” of Unit Space
(4)#3/0 AWG - 600 Kcmil Cu or Al
1200 N/A Deduct 10” of Unit Space
(4)#3/0 AWG - 750 Kcmil Cu or Al

4-10
SECTION 4
Dimensions
Type P4 Panelboards

Type 1 Box
Box is symmetrical

30.0 in.
[ 254 ]

Type 3R and 3R/12 Box

햲 Dimensions are interior of the box. Add 5/8” to width for


absolute dimension. Add 1/8” to height for absolute dimension.

Dimensions shown in inches and millimeters [ ].

4-11
Kits and Accessories
Type P4 Panelboards

Table P4-17 – Connector Strap Kits – w/o Circuit Breaker 1 2


For use with Sentron SPP Shallow Depth or Type P4 Power Panels
Unit Height
Breaker Type Mounting Type Inches (mm) Catalog Number
BL, BQD Twin 3.75 (95) SBL
NGB, HGB, LGB Twin 3.75 (95) SNB
EB Twin 3.75 (95) SEB
ED Twin 3.75 (95) SE6
CED6 Twin 3.75 (95) SCE
DG 3 Twin 5.00 (127) SDG
QJ Twin 5.00 (127) SQJ
QR Twin 5.00 (127) SQR
FG 3 Twin 5.00 (127) SFG
FD6 Twin 5.00 (127) SF6
CFD6 Single 5.00 (127) SCF
JG 3 Single 6.25 (159) SJG
JD Single 8.75 (223) SJ1
SJD Single 8.75 (223) SSJ1
CJD6 Single 8.75 (223) SCJ
SCJD Single 8.75 (223) SSCJ
LG 3 Single 6.25 (159) SLG
LD Single 8.75 (223) SL6
SLD Single 8.75 (223) SSL6
CLD6 Single 8.75 (223) SCL
SCLD Single 8.75 (223) SSCL
MG 3 Single 8.75 (223) MG1
1 Includes cover plate and mounting hardware, less circuit breaker.
2 Also for use with S4/F4 and SPP/FPP (10” Deep).
3 VL family of circuit breakers.

Table P4-18 – Connecting Strap Kits – Fusible Table P4-19


Service Entrance Barriers
For use with Sentron Shallow Depth or Type SPP/FPP/F1/P4 power panels
Unit Height Field installable Barriers to
Ampere Rating Inches (mm) Catalog Number meet UL 67 service entrance
30–30 2.5 (63.5) F602
requirements.
30–60 5.0 (127), 7.5 (191) F657 Breaker Type Catalog Number
30–60 5.0 (127), 7.5 (191) F657
(S)JD, (S)LD, MG MGSEBP4V1
60–60 5.0 (127), 7.5 (191) F657
60–100 5.0 (127), 7.5 (191) F657 CJD, CLD SEBP4V2
100–100 5.0 (127), 7.5 (191) F657 JG, LG SEBP4V3
100 7.5 (191) F657
200 7.5 (191) F657
200 10.0 (254) F671
200–200 10.0 (254) F672

Table P4-20 – Blank Plates


Circuit Breaker and Vacu-Break Table P4-21 – Filler Plates
For use with Sentron SPP and Type P4 power panels For use with Sentron SPP and P4 power panels
Height Breaker Type Filler Plate Catalog Number
Inches Catalog
(mm) Number BL, BLH, HBL,
BQD, NGB, HGB,
1.25 (32) 6FPB01
LGB, ED2, ED4, DFFP11
2.5 (63.5) 6FPB02
ED6, HED4,
3.75 (95) 6FPB03
HHED6,
5.0 (127) 6FPB05
NEB, HEB EBF1
10.0 (254) 6FPB10
1 Suitable to replace QF3 in P1 thru P5 Panelboards
and Switchboards.

4-12
4 SECTION
Kits and Accessories
Type P4 Panelboards

Table P4-22 – Enclosures


Description Catalog number
P4 Type 1 32” W x 10” D x 60” H PB60
P4 Type 1 32” W x 10” D x 75” H PB75
P4 Type 1 32” W x 10” D x 90” H PB90
P4 Type 3R/12 60” H WP260
P4 Type 3R/12 75” H WP275
P4 Type 3R/12 90” H WP290

Table P4-23 – Trims


Description Catalog number
P4 Std (4 piece trim) vented 60” P460V
P4 Std (4 piece trim) vented 75” P475V
P4 Std (4 piece trim) vented 90” P490V
P4 VBS Std (4 piece trim) vented 60” P460V V
P4 VBS Std (4 piece trim) vented 75” P475V V
P4 VBS Std (4 piece trim) vented 90” P490V V
P4 Std (4 piece trim) unvented 60” P460NV
P4 Std (4 piece trim) unvented 75” P475NV
P4 Std (4 piece trim) unvented 90” P490NV
P4 VBS Std (4 piece trim) unvented 60” P460NV V
P4 VBS Std (4 piece trim) unvented 75” P475NV V
P4 VBS Std (4 piece trim) unvented 90” P490NV V
P4 Std (4 piece trim) vented 60” with hinged gutter covers P460VHG
P4 Std (4 piece trim) vented 75” with hinged gutter covers P475VHG
P4 Std (4 piece trim) vented 90” with hinged gutter covers P490VHG
P4 VBS Std (4 piece trim) vented 60” with hinged gutter covers P460V VHG
P4 VBS Std (4 piece trim) vented 75” with hinged gutter covers P475V VHG
P4 VBS Std (4 piece trim) vented 90” with hinged gutter covers P490V VHG
P4 Std (4 piece trim) unvented 60” with hinged gutter covers P460NVHG
P4 Std (4 piece trim) unvented 75” with hinged gutter covers P475NVHG
P4 Std (4 piece trim) unvented 90” with hinged gutter covers P490NVHG
P4 VBS Std (4 piece trim) unvented 60” with hinged gutter covers P460NVVHG
P4 VBS Std (4 piece trim) unvented 75” with hinged gutter covers P475NVVHG
P4 VBS Std (4 piece trim) unvented 90” with hinged gutter covers P490NVVHG
P4 Std (1 PC Door) vented 60” P460VD
P4 Std (1 PC Door) vented 75” P475VD
P4 Std (1 PC Door) vented 90” P490VD
P4 Std (1 PC Door) unvented 60” P460NVD
P4 Std (1 PC Door) unvented 75” P475NVD
P4 Std (1 PC Door) unvented 90” P490NVD
P4 Std (1 PC Door-in-door) vented 60” P460VDD
P4 Std (1 PC Door-in-door) vented 75” P475VDD
P4 Std (1 PC Door-in-door) vented 90” P490VDD
P4 Std (1 PC Door-in-door) unvented 60” P460NVDD
P4 Std (1 PC Door-in-door) unvented 75” P475NVDD
P4 Std (1 PC Door-in-door) unvented 90” P490NVDD

Table P4-24 – Flush mounting kits


Description Catalog number
Flush kit for P4 60” High F60
Flush kit for P4 75” High F75
Flush kit for P4 90” High F90

4-13
Notes
SECTION 5
P5 Panelboards
Description Page Typical Catalog Numbers 5-9
General Information 5-2 Main Lugs Only 5-9
Selection and Application 5-2 Main Circuit Breakers Only 5-9
Application 5-3 – 5-8 Main Fusible Switch 5-9
Main Breaker Selection 5-3 Modifications and Additions 5-10 – 5-12
Enclosure Selection 5-4 Motor Starters 5-11 – 5-12
Main Breaker and Main Switch 5-3 – 5-4 Connector Modifications 5-12
Main Switch Connectors 5-4 Compression Lugs 5-12
Main Lugs Only Unit Space 5-5 Alternate Lugs 5-12
Branch Switch Unit Space 5-5 Dimensions 5-13
Branch Circuit Breakers 5-6 Kits and Accessories 5-14 – 5-15
Branch Breaker Unit Space 5-7
Branch Breaker Side Gutters 5-8
Type P5 Panelboards

The P5 panel is the largest distribution panel in the Siemens The three-cycle rating for the P5 panel is limited to 42 KAIC. Note
panel family. Even so, the P5 panel is still a space saver with that the main device may be mounted remote from the panel.
it’s 38” width and 12.75” depth. With even higher main ratings
to fit the application that require more or larger branch devices. Bussing – The P5 panel has more options to meet market
This panel offers a wide array of factory-assembled options and requirements. The standard bussing is temperature rated
enables users to mix breaker frames in unit space up to 1200 aluminum. The rating is per the requirements of UL 67 – the
amps and fusible switches up to 1200 amps. Bussing options for standard for panelboards. All aluminum bussing is tin-plated.
the P5 vary from the standard temperature rated aluminum to Optional bussing for the P5 panel is: 750 A/Si aluminum,
temperature rated copper and 750 A/Si aluminum and 1000A/Si temperature rated copper, and 1000 A/Si copper. The copper
copper designs. All aluminum bussing in the P5 panel is tin- bus option for this panel is tin-plated.
plated as a standard. All copper bus is silver plated. Integrated Weight – Approximate
time clocks, bus mounted contactors as mains or submains, split Total panelboard weight when filled with a normal quantity of
bus and subfeed lugs (up to 600 amps) are just a few of the breakers and accessories is about 10 lbs. (1 kg) per inch (54g
options of this flexible panel. per mm) of box height.
P5 panel configurations are defined by the unit space allowed Table P5-1 – Main Lugs 1
for a given amperage, main device and box height. The P5 panel
Ampere Connectors Suitable for
starts with a 60” high box. All branch devices are unit space Rating Copper or Aluminum
mounted. Breakers and switches can be mixed and matched to 400 (1) 250 - 500 Kcmil
meet customer requirements. 600 (2) #3/0 - 500 Kcmil
800 (3) #3/0 AWG-500 Kcmil
Main Lug / Main Breaker / Main Switch 1000 (4) #3/0 AWG-500 Kcmil
1200 (4) #3/0 AWB-500 Kcmil
Enclosure – Standard Type 1 enclosure is 38" wide x 12.75"
1 Alternate lugs for 750 Kcmil cable are available, but result in significant loss of
deep. X Box Height is determined by main device and unit
branch unit mounting space. Consult Siemens.
space. See charts for box height.
Table P5-2 – Gauge Steel of Boxes Fronts, Surface and Flush
Voltage – 600 Vac Max.
Dimensions in inches (mm) Gauge Steel
250 Vdc Max. Width Height Box Fronts
Amperage – 400-1200 amp Main breaker, 400-1200 amp MLO 60 - 75 - 90 #16 1 #14 (1 piece trim)
(1524, 1905, 2286) #14 (4 piece trim)
200-1200 amp Main switch. 60 - 75 - 90 #14 #12 (1 piece trim)
38” (1524, 1905, 2286) & door in door
Short Circuit Rating – 200 KAIC Max. symmetrical or equal to (965) #10 (1 piece &
the lowest rated device installed unless a series rating is indicated. door in door)
Panels with subfeed or feed-thru lugs without a main device, 60 - 75 - 90 #14 #16 (4 piece, top
(1524, 1905, 2286) and bottom over)
circuit breaker or fusible unit, are limited to a three-cycle rating. #10 (4 piece, side/
gutter cover)
1 16 gauge side panels, 12 gauge back support, 14 gauge back panels.

Selection and Application


1) To specify a particular panelboard, first determine voltage, Select appropriate enclosure height from selection chart on
system, amperage and type of main, amperage and type of page 5-3 based on unit space requirements. (Step 2)
branch devices, and modifications, if any. (Step 1)
3) Select panelboard catalog number from appropriate table
2) List branch devices and modifications requiring space based upon voltage, system, amperage and unit space
additions. List unit space requirements of each. requirements. (Step 3)

Note: Some units are twin mounted meaning two breakers


occupy the same unit space.
Step #1 Step #2 Step #3
Amperage 1200 5-125/3 xGB 3.75” = 11.25” Twin Mounted 1-P5C75NI120ATS
Voltage 208Y/120 2-225/3 QJ2/QR2 5” = 5” Twin Mounted 5-125/3 xGB
System 3 Phase, 4 wire 1-250/3 FXD6 5” = 5” 3-xGB 1 Pole Provision
Main Main Breaker 21.25 2-225/3 QJ2/QR2
Branches 5-125/3, 2-225/3, 1-250/3 FXD6
Enclosure is B875 from Selection
1-250/3 1-FXD6 Prov. 13.25” Space
Modifications None Chart on Page 5-3.
Feed Top (32” wide, 75” high, 10” deep)
Mounting Surface
5-2
SECTION 5
Application
Type P5 Panelboards
Table P5-3 – Alternate Main Breaker Selection 1
Breaker Alternate Unit Space Maximum Interruption Rating (KAIC)
Frame Trip Breaker Frame Main Breaker Trip Requirements Volts AC
Rating Type Family Type Code 32 Amperage in Inches 240 480 600
JXD6 JX 200, 225, 250, 300, 350, 400 8.75 65,000 35,000 25,000
JD6 J6 200, 225, 250, 300, 350, 400 8.75 65,000 35,000 25,000
Thermal HJXD6 H5 200, 225, 250, 300, 350, 400 8.75 100,000 65,000 35,000
Sentron HJD6 H6 200, 225, 250, 300, 350, 400 8.75 100,000 65,000 35,000
Magnetic HHJXD6 H9 200, 225, 250, 300, 350, 400 8.75 200,000 100,000 50,000
HHJD6 6H 200, 225, 250, 300, 350, 400 8.75 200,000 100,000 50,000
400 CJD6 CJ 200, 225, 250, 300, 350, 400 8.75 200,000 150,000 100,000
NJ J1 250, 400 6.25 65,000 35,000 25,000
VL HJ J7 250, 400 6.25 100,000 65,000 25,000
Electronic LJ J3 250, 400 6.25 200,000 100,000 25,000
(Solid state) SJD6 SJ 200, 300, 400 8.75 65,000 35,000 25,000
Sentron SHJD6 SX 200, 300, 400 8.75 100,000 65,000 35,000
SCJD6 SC 200, 300, 400 8.75 200,000 150,000 100,000
LXD6 LX 450, 500, 600 8.75 65,000 35,000 25,000
LD6 L6 250, 300, 350, 400, 450, 500, 600 8.75 65,000 35,000 25,000
Thermal HLXD6 HO 250, 300, 350, 400, 450, 500, 600 8.75 100,000 65,000 35,000
Sentron HLD6 HL 250, 300, 350, 400, 450, 500, 600 8.75 100,000 65,000 35,000
Magnetic HHLXD6 XH 250, 300, 350, 400, 450, 500, 600 8.75 200,000 100,000 50,000
HHLD6 HH 250, 300, 350, 400, 450, 500, 600 8.75 200,000 100,000 50,000
600 CLD6 CL 250, 300, 350, 400, 450, 500, 600 8.75 200,000 150,000 100,000
NL L7 400, 600 6.25 65,000 35,000 25,000
VL HL L2 400, 600 6.25 100,000 65,000 25,000
Electronic LL SL 400, 600 6.25 200,000 100,000 25,000
(Solid state) SLD6 L6 300, 400, 500, 600 8.75 65,000 35,000 25,000
Sentron SHLD6 S2 300, 400, 500, 600 8.75 100,000 65,000 35,000
SCLD6 SI 300, 400, 500, 600 8.75 200,000 150,000 100,000
NM M1 600, 700, 800 8.75 65,000 35,000 25,000
VL HM M2 600, 700, 800 8.75 100,000 65,000 35,000
LM M3 600, 700, 800 8.75 200,000 100,000 50,000
LMXD6 LM 500, 600, 700, 800 8.75 65,000 50,000 25,000
LMD6 L1 500, 600, 700, 800 8.75 65,000 50,000 25,000
Thermal HLMXD6 HK 500, 600, 700, 800 8.75 100,000 65,000 50,000
Magnetic HLMD6 HJ 500, 600, 700, 800 8.75 100,000 65,000 50,000
Sentron MXD6 MX 500, 600, 700, 800 10.00 65,000 50,000 25,000
MD6 MD 500, 600, 700, 800 10.00 65,000 50,000 25,000
800
HMXD6 HR 500, 600, 700, 800 10.00 100,000 65,000 50,000
HMD6 HM 500, 600, 700, 800 10.00 100,000 65,000 50,000
CMD6 CM 500, 600, 700, 800 10.00 200,000 100,000 65,000
NM M1 600, 800 8.75 65,000 35,000 25,000
VL HM M2 600, 800 8.75 100,000 65,000 35,000
Electronic LM M3 600, 800 8.75 200,000 100,000 50,000
(Solid state) SMD6 SM 600, 700, 800 10.00 65,000 50,000 25,000
Sentron SHMD6 S5 600, 700, 800 10.00 100,000 65,000 50,000
SCMD6 SO 600, 700, 800 10.00 200,000 100,000 65,000
NN N1 800, 900, 1000, 1200 10.00 65,000 35,000 25,000
VL HN N2 800, 900, 1000, 1200 10.00 100,000 65,000 35,000
LN N3 800, 900, 1000, 1200 10.00 200,000 100,000 65,000
Thermal NXD6 NX 900, 1000, 1200 10.00 65,000 50,000 25,000
Magnetic ND6 ND 900, 1000, 1200 10.00 65,000 50,000 25,000
Sentron HNXD6 HT 900, 1000, 1200 10.00 100,000 65,000 50,000
HND6 HN 900, 1000, 1200 10.00 100,000 65,000 50,000
1200 CND6 Cn 900, 1000, 1200 10.00 200,000 100,000 65,000
NN N1 800, 1000, 1200 10.00 65,000 35,000 25,000
VL HN N2 800, 1000, 1200 10.00 100,000 65,000 35,000
Electronic LN N3 800, 1000, 1200 10.00 200,000 100,000 65,000
(Solid state) SND6 SN 800, 1000, 1200 10.00 65,000 50,000 25,000
Sentron SHND6 AD 800, 1000, 1200 10.00 100,000 65,000 50,000
SCND6 SR 800, 1000, 1200 10.00 200,000 100,000 65,000
1 For ground fault, see SpeedFax page 5-10.
2 Replace “MS” in catalog number with code letter.

5-3
Application
Type P5 Panelboards
Fig. P5-1
Table P5-4 – Enclosure Selection 1
Enclosure Dimension Available Unit Space in inches (mm)
in Inches (mm) Dimension “C” in Fig. P5-1
H W D Main Lug only Main Breaker Main Switch
Type 1 Type 3R/12 800 / 1200A 800 / 1200A 800 / 1200A
60 (1524) 38 (965) 12.75 (324) 14.25 (362) 30 (762) 20 (508) 13.75 (349)
75 (1905) 38 (965) 12.75 (324) 14.25 (362) 45 (1143) 35 (889) 28.75 (730)
90 (2286) 38 (965) 12.75 (324) 14.25 (362) 60 (1524) 50 (1270) 43.75 (1111)
1 Standard trim is four piece without door. Surface or flush one piece trim is
available for 32 in. (813 mm) wide circuit breaker panels.

Table P5-5 – Main Breaker Lug Location Reference (Fig. P5-1)


Ampere Breaker Dimensions in inches (mm)
Rating Type A B
400 JXD6, JD6, HJXD6, HJD6, HHJXD6, HHJD6 13.425 (265)
400 NJ, HJ, LJ 15.500 (318)
400 SJD6, SHJD6 13.425 (265)
400 CJD6, SCJD6 11.250 (210)
600 LXD6, LD6, HLXD6, HLD6, HHLXD6, HHLD6 13.425 (265) 13.125 (333)
600 NL, HL, LL 14.250 (286)
600 SLD6, SHLD6 13.425 (265)
600 CLD6, SCLD6 11.250 (210)
800 NM, HM, LM 13.425 (265)
800 MXD6, MD6, HMXD6, HMD6, 13.00 (330)
CMD6, SMD6, SHMD6, SCMD6 10.42 (265)
1200 NN, HN, LN 13.425 (265)
1200 NXD6, ND6, HNXD6, HMD6, 13.00 (330)
CND6, SND6, SHMD6, SCND6 13.00 (330)

Table P5-6 – Main Switch Table P5–7 Main Switch Connectors


Maximum Ampere
Ampere Rating A B Rating Connectors Suitable for Copper or Aluminum

400A/600A VB 9.30 (236) 400 (1) #3/0 – 500KCMIL


800A/1200A HCP 10.30 (262) 13.125 (333) (2) #3/0 – 250KCMIL
200A VB 13.425 (265) 600 (2) #3/0 – 500KCMIL
800 (3) #3/0 – 500KCMIL
1200 (4) #3/0 – 500KCMIL

5-4
SECTION 5
Application
Type P5 Panelboards

Table P5-8 – Main Lugs Only Unit Space (Fig. P5-2) Fig. P5-2
Dimensions in inches (mm)
Main Lug Neutral
400A 600A 800A 1000A 1200A 800A
Lugs A B C D E G
Standard 16.500 (419) 16.750 (425) 15.969 (406) 15.969 (406) 15.969 (406) 13.125 (333)
Oversize 16.500 (419) 21.750 (552) 25.969 (660) 25.969 (660) 25.969 (660) 23.125 (587)
Crimp 19.187 (487) 18.250 (484) 18.687 (475) 18.250 (464) 18.250 (464) 15.937 (405)
Standard with
16.750 (425) 15.969 (406) — — — 13.125 (333)
Subfeed
Standard with — — 13.125 (333)
16.500 (419) 16.750 (425) —
Feed-thru

Table P5-9 – Branch Switch Unit Space


Unit Space
in Inches (mm)
Ampere Number Twin Single AC Cables Per Connectors Suitable For
Rating of Poles Mounted Mounted Voltage Connector Copper or Aluminum
30-30 2, 3 2.50 (64) — 240 1 #14 - #8 AWG (Cu Only)
30-30 2, 3 5.00 (127) — 240 1 #14 - #4 AWG
30-60 2, 3 5.00 (127) — 240 1 #14 - #4 AWG
60-60 2, 3 5.00 (127) — 240 1 #14 - #4 AWG
60-100 2, 3 7.50 (191) — 240 1 #10 - #1/0 AWG
100-100 2 ,3 7.50 (191) — 240 1 #10 - #1/0 AWG
200-200 3 10.00 (254) — 240 1 #6 AWG - 350 Kcmil
200 2 — 7.50 (191) 240 1 #6 AWG - 350 Kcmil
200 3 — 10.00 (254) 240 2 #6 AWG - 350 Kcmil
30-30 2, 3 7.50 (191) — 600 1 #14 - #4 AWG
30-60 2, 3 7.50 (191) — 600 1 #14 - #4 AWG
60-60 2, 3 7.50 (191) — 600 1 #14 - #4 AWG
60-100 2, 3 7.50 (191) — 600 1 #10-#1/0 AWG
100-100 2, 3 7.50 (191) — 600 1 #10-#1/0 AWG
200-200 3 10.00 (254) — 600 1 #6 AWG - 350 Kcmil
100 2, 3 — 7.50 (191) 600 1 #10 - #1/0 AWG
200 2, 3 — 10.00 (254) 600 2 #6 AWG - 350 Kcmil

5-5
Application
Type P5 Panelboards
Table P5-10 – Branch Circuit Breakers
Unit Space
Breaker Requirements Maximum Interruption Rating (KAIC) Volts AC
Frame Trip Breaker Frame Trip in Inches 480Y/ 600Y/
Rating Type Family Type Poles Amperage Single Twin 120 240 277 480 347 600
100 Thermal General BL 1, 2, 3 15-60, 70, 80, 90, 100, 110, 125 — 3.752 3 10,000 10,000 — — — —
Magnetic Appli- BLR 2 15, 20, 30, 40, 50, 60, 70, 80, 90, — 3.752 3 10,000 10,000 — — — —
cation 100
BLH 1, 2, 3 15-60, 70, 80, 90, 100, 110, 125 — 3.752 3 22,000 22,000 — — — —
HBL 1, 2, 3 15-60, 70, 80, 90, 100, 110, 125 — 3.752 3 65,000 65,000 — — — —
BQD 1, 2, 3 15-50, 60, 70, 80, 90, 100 — 3.752 3 65,000 65,000 14,000 — — —
BQD6 1, 2, 3 15-50, 60, 70 — 3.752 3 65,000 65,000 — — 10,000 —
Special BL-HID 1, 2 15, 20, 30 — 3.752 3 10,000 10,000 — — — —
Application BL-BG 2, 3 15, 20, 30 — 3.752 3 10,000 10,000 — — — —
Ground BLE-GFCI 1, 2 15, 20, 30, 40, 50, 60 — 3.752 10,000 10,000 — — — —
Fault BLEH-GFCI 1, 2 15, 20, 30, 40, 50, 60 — 3.752 10,000 10,000 — — — —
Circuit BLF-GFCI 1, 2 15, 20, 30, 40, 50, 60 — 3.752 10,000 10,000 — — — —
Interrupter
BLHF-GFCI 1, 2 15, 20, 30, 40, 50, 60 — 3.752 10,000 10,000 — — — —
Arc BAF-AFCI 1, 2 15, 20 — 3.752 10,000 10,000 — — — —
Fault BAFH-AFCI 1, 2 15, 20 — 3.752 10,000 10,000 — — — —
Circuit BAFC-AFCI 1, 2 15, 20 — 3.752 10,000 10,000 — — — —
Interrupter
BAFCH-AFCI 1, 2 15, 20 — 3.752 10,000 10,000 — — — —
125 Thermal General NGB 1, 2, 3 15-60, 70, 80, 90, 100, 110, 125 — 3.752 3 — 100,000 25,000 — 14,000 —
Magnetic Appli- HGB 1, 2, 3 15-60, 70, 80, 90, 100, 110, 125 — 3.752 3 — 100,000 35,000 — 14,000 —
cation LGB 1, 2, 3 15-60, 70, 80, 90, 100, 110, 125 — 3.752 3 — 100,000 65,000 — 14,000 —
NEB 1, 2, 3 15-60, 70, 80, 90, 100, 110, 125 — 3.752 3 — 85,000 — 35,000 — 22,000
HEB 1, 2, 3 15-60, 70, 80, 90, 100, 110, 125 — 3.752 3 — 100,000 — 65,000 — 25,000
ED4 1, 2, 3 15-50, 60, 70, 80, 90, 100, 110, 125 — 3.752 3 — 65,000 — 18,000 — —
HED44 5 1, 2, 3 15-50, 60, 70, 80, 90, 100, 110, 125 — 3.752 3 — 100,000 — 42,000 — —
CED6 2, 3 15-50, 60, 70, 80, 90, 100, 110, 125 — 3.752 3 — 200,000 — 200,000 — 100,000
150 Electronic VL ND 3 60, 100, 150 — 5.00 — 65,000 — 35,000 — 18,000
(Solid state) HD 3 60, 100, 150 — 5.00 — 100,000 — 65,000 — 20,000
LD 3 60, 100, 150 — 5.00 — 200,000 — 100,000 — 25,000
225 Thermal General QJ2 2, 3 60-110, 125, 150, 175, — 5.00 — 10,000 — — — —
Magnetic Appli- 200, 225
cation QJH2 2, 3 60-110, 125, 150, 175, — 5.00 — 22,000 — — — —
200, 225
QJ2H 2, 3 60-110, 125, 150, 175, — 5.00 — 42,000 — — — —
200, 225
QR2 2, 3 100, 110, 125, 150, 175, 200, 225 — 5.00 — 10,000 — — — —
QRH2 2, 3 100, 110, 125, 150, 175, 200, 225 — 5.00 — 25,000 — — — —
HQR2 2, 3 100, 110, 125, 150, 175, 200, 225 — 5.00 — 65,000 — — — —
HQR2H 2, 3 100, 110, 125, 150, 175, 200, 225 — 5.00 — 100,000 — — — —
250 Thermal Sentron FXD6, FD6 2, 3 70-110, 125, 150, 175, 200, 225, 5.00 5.00 — 65,000 — 35,000 — 22,000
Magnetic 250
HFXD6, 2, 3 70-110, 125, 150, 175, 200, 225, 5.00 5.00 — 100,000 — 65,000 — 25,000
HFD6 250
HHFXD6, 2, 3 70-110, 125, 150, 175, 200, 225, 5.00 5.00 — 200,000 — 100,000 — 25,000
HHFD6 250
CFD6 3 70-110, 125, 150, 175, 200, 225, — 5.00 — 200,000 — 200,000 — 100,000
250
Electronic VL NF 3 100, 150, 250 — 5.00 — 65,000 — 35,000 — 18,000
(Solid state) HF 3 100, 150, 250 — 5.00 — 100,000 — 65,000 — 20,000
LF 3 100, 150, 250 — 5.00 — 200,000 — 100,000 — 25,000

1 Includes housing frame plate with blank cover plate. Provision price includes all 3 Accessories such as shunt trips on three pole breakers require 6.25" of unit space.
necessary mounting hardware, less circuit breaker, and includes housing frame 4 HED4 1-pole 15–30A = 65,000 IR
cover plate with breaker handle opening. 35–100A = 25,000 IR
2 1 to 6 poles may be mounted in 3.75" of unit space. 5 HED4 3-Pole = 42,000 IR.

5-6
SECTION 5
Application
Type P5 Panelboards
Table P5-10 – Branch Circuit Breakers (continued)
Unit Space
Breaker Requirements Maximum Interruption Rating (KAIC) Volts AC
Frame Trip Breaker Frame Trip in Inches 480Y/ 600Y/
Rating Type Family Type Poles Amperage Single Twin 120 240 277 480 347 600
400 Thermal Sentron JXD6, JD6 2, 3 200, 225, 250, 300, 350, 8.75 8.75 — 65,000 — 35,000 — 25,000
Magnetic 400
HJXD6, 2, 3 200, 225, 250, 300, 350, 8.75 8.75 — 100,000 — 65,000 — 35,000
HJD6 400
HHJXD6, 2, 3 200, 225, 250, 300, 350, 8.75 8.75 — 200,000 — 100,000 — 50,000
HHJD6 400
CJD6 3 200, 225, 250, 300, 350, 8.75 — — 200,000 — 150,000 — 100,000
400
Electronic VL NJ 3 250, 400 6.25 6.25 — 65,000 — 35,000 — 25,000
(Solid HJ 3 250, 400 6.25 6.25 — 100,000 — 65,000 — 25,000
state)
LJ 3 250, 400 6.25 6.25 — 200,000 — 100,000 — 25,000
Sentron SJD6 3 200, 300, 400 8.75 — — 65,000 — 35,000 — 25,000
SHJD6 3 200, 300, 400 8.75 — — 100,000 — 65,000 — 35,000
SCJD6 3 200, 300, 400 8.75 — — 200,000 — 150,000 — 100,000

Table P5-11 – Branch Breaker Circuit Breakers (VL)


Maximum Trip Maximum IC (KA) Symmetrical Amperes
Ampere Breaker Number Amp Voltage – AC
Rating Type of Poles Rating 120 120/250 240 277 480/277 480 600/347 600
ND 3 60-150 — 65 65 — 35 35 18 18
150 1 HD 3 60-150 — 100 100 — 65 65 20 20
LD 3 60-150 — 200 200 — 100 100 25 25
NF 3 100-250 — 65 65 — 35 35 18 18
250 1 HF 3 100-250 — 100 100 — 65 65 20 20
LF 3 100-250 — 200 200 — 100 100 25 25
NJ 3 250-400 — 65 65 — 35 35 25 25
400 1 HJ 3 250-400 — 100 100 — 65 65 25 25
LJ 3 250-400 — 200 200 — 100 100 25 25
NL 3 400-600 — 65 65 — 35 35 18 18
600 1 HL 3 400-600 — 100 100 — 65 65 18 18
LL 3 400-600 — 200 200 — 100 100 18 18
NM 2/3 600-800 — 65 65 — 35 35 25 25
800 HM 2/3 600-800 — 100 100 — 65 65 35 35
LM 2/3 600-800 — 200 200 — 100 100 50 50
NN 2/3 800-1200 — 65 65 — 35 35 25 25
1200 HN 2/3 800-1200 — 100 100 — 65 65 35 35
LN 2/3 800-1200 — 200 200 — 100 100 50 50
1 Only available with Electronic Trip Units.

5-7
Application
Type P5 Panelboards

Table P5-12 – Branch Breakers Unit Space Requirements


Mounting Height
Amp Breaker in Inches (mm)
Rating Type Twin Single
1 BL,BLH,HBL,BQD,BLE, BLEH, BLR, BLF, BLHF, BAF, BAFC, BAFH, BAFCH, BGL 3.75 (95) 1
100
BL, BLH, HBL, BQD -With accessories 6.25 (159) —
xGB, NEB, HEB, ED4, ED6, HED4, HHED6, CED6 3.75 (95)1
125
xGB, ED41 2, ED61 2, HED41 2, HHED61 2, CED61 2 (With accessories) 6.25 (159) —
150 ND, HD, LD 5.00 (127) —
225 QJ2, QJH2, QJ2H, QR2, QRH2, HQR2, HQR2H 5.00 (127) —
NF, HF, LF 5.00 (127) —
250 FD6, FXD6, HFD6, HFXD6, HHFD6, HHFXD6 5.00 (127) —
CFD6 — 5.00 (127)
NJ, HJ, LJ 6.25 (159)
400 —
JD6, JXD6, HJD6, HJXD6, HHJD6, HHJXD6, CJD6 8.75 (222)
NL, HL, LL 6.25 (159)
600 —
LD6, LXD6, HLD, HLXD6, HHLD6, HHLXD6, CLD6 8.75 (222)
NM, HM, LM 8.75 (222)
800 —
MXD6, MD6, HMXD6, HMD6, CMD6 10.00 (254)
NN, HN, LN
1200 — 10.00 (254)
NXD6, ND6, HNXD6, HND6, CND6
1 Mounting height shown will accomodate from (1) to (6) poles.
2 Accessories such as shunt trips on three pole breakers requires 6.25" of unit space.

Table P5-13 – Branch Breaker Fig. P5-3


Side Gutter
A BL, BLH, HBL, BQD BL, BLH, HBL, BDQ A
Reference Panel Width – 32 (813)
Letter Dimensions in inches (mm) B NGB, HGB, LGB NGB, HGB, LGB B
A 14.0 (356) C NEB, HEB NEB, HEB C
B 13.98 (355) D
ED4, ED6 ED4, ED6 D
C 11.62 (295) HED4 HED4
E CED6 CED6 E
D 10.0 (254)
QJ2, QJH2, QJ2H, QJ2, QJH2, QJ2H,
E 7.61 (193)
F QR2, QRH2, QR2, QRH2, F
F 8.75 (222)
HQR2, HQR2H HQR2, HQR2H
G 8.25 (210) FD6, FXD6, FD6, FXD6
H 10.90 (276) G G
HFD6, HHFD6 HFD6, HHFD6
I 10.90 (276) H ND, HD, LD ND, HD, LD H
J 11.76 (299) I NF, HF, LF NF, HF, LF I
K 7.92 (201) J CFD J
L 8.0 (203) JD6, JXD6, JD6, JXD6,
M 13.42 (341) K HJD6, HHJD6 HJD6, HHJD6 K
N 12.0 (305) L NJ, HJ, LJ NJ, HJ, LJ L
O 15.50 (393) SJD6, SHJD6, LD6, LXD6,
P 14.25 (362) M HLD6, HHLD6, SLD6, SHLD6 M
Q 13.42 (341) CJD6, SCJD6, CLD6, SCLD6
N N
R 13.42 (341) NJ, HJ, LJ
O O
S 10.0 (254)
P NL, HL, LL P
T 8.0 (203)
U 10.50 (267) Q NM, HM, LM Q
V 10.50 (267) R NN, HN, LN R
W 9.30 (236) S VB 30 A VB 30 A S
X 10.30 (262) T VB 30 - 60A VB 30 - 60 A T
Y 9.30 (236) U VB 60 -100A VB 60 - 100A U
Z 10.30 (262) V VB 200A VB 200A V
W VB 100A Single W
X VB 200A Single X
Y VBVB 5 Single
400 – 600A Single Y

Z HCP 400 – 1200A Single Z

5-8
SECTION 5
Typical Catalog Numbers
Type P5 Panelboards

Table P5-14 – Main Lugs Only – shown with aluminum bus, top fed, and surface trims
Max. 208Y/120V 240/120V 120/240V or 240 480Y/277V 480V 1
Panel Unit 250 Vdc Max
Amp Space 3 Phase, 4 Wire 3 Phase, 4 Wire 1 Phase, 3 Wire 3 Phase, 3 Wire 3 Phase, 4 Wire 1 Phase, 3 Wire
Rating (inches) Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
30 P5C60ML800ATS P5B60ML800ATS P5A60ML800ATS P5D60ML800ATS P5E60ML800ATS P5F60ML800ATS
800 45 P5C75ML800ATS P5B75ML800ATS P5A75ML800ATS P5D75ML800ATS P5E75ML800ATS P5F75ML800ATS
60 P5C90ML800ATS P5B90ML800ATS P5A90ML800ATS P5D90ML800ATS P5E90ML800ATS P5F90ML800ATS
30 P5C60ML101ATS P5B60ML101ATS P5A60ML101ATS P5D60ML101ATS P5E60ML101ATS P5F60ML101ATS
1000 45 P5C75ML101ATS P5B75ML101ATS P5A75ML101ATS P5D75ML101ATS P5E75ML101ATS P5F75ML101ATS
60 P5C90ML101ATS P5B90ML101ATS P5A90ML101ATS P5D90ML101ATS P5E90ML101ATS P5F90ML101ATS
30 P5C60ML120ATS P5B60ML120ATS P5A60ML120ATS P5D60ML120ATS P5E60ML120ATS P5F60ML120ATS
1200 45 P5C75ML120ATS P5B75ML120ATS P5A75ML120ATS P5D75ML120ATS P5E75ML120ATS P5F75ML120ATS
60 P5C90ML120ATS P5B90ML120ATS P5A90ML120ATS P5D90ML120ATS P5E90ML120ATS P5F90ML120ATS

Table P5-15 – Main Circuit Breakers – shown with aluminum bus, top fed, and surface trims
Max. 208Y/120V 240/120V 120/240V or 240 480Y/277V 480V 1
Panel Unit 250 Vdc Max
Amp Space 3 Phase, 4 Wire 3 Phase, 4 Wire 1 Phase, 3 Wire 3 Phase, 3 Wire 3 Phase, 4 Wire 1 Phase, 3 Wire
Rating (inches) Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
21.25 P5C60M1800ATS P5B60M1800ATS P5A60M1800ATS P5D60M1800ATS P5E60M1800ATS P5F60M1800ATS
800 2 36.25 P5C75M1800ATS P5B75M1800ATS P5A75M1800ATS P5D75M1800ATS P5E75M1800ATS P5F75M1800ATS
51.25 P5C90M1800ATS P5B90M1800ATS P5A90M1800ATS P5D90M1800ATS P5E90M1800ATS P5F90M1800ATS
20 P5C60N1120ATS P5B60N1120ATS P5A60N1120ATS P5D60N1120ATS P5E60N1120ATS P5F60N1120ATS
1200 35 P5C75N1120ATS P5B75N1120ATS P5A75N1120ATS P5D75N1120ATS P5E75N1120ATS P5F75N1120ATS
50 P5C90N1120ATS P5B90N1120ATS P5A90N1120ATS P5D90N1120ATS P5E90N1120ATS P5F90N1120ATS

Table P5-16 – Main Fusible Switch (fuses not included)


Max. 208Y/120V 240/120V 120/240V 240V 480Y/277V 480V 1
Panel Unit
Amp Space 3 Phase, 4 Wire 3 Phase, 4 Wire 1 Phase, 3 Wire 3 Phase, 3 Wire 3 Phase, 4 Wire 3 Phase, 3 Wire
Rating (inches) Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
20 P5C75MS400ATS P5B75MS400ATS P5A75MS400ATS P5D75MS400ATS P5E75MS400ATS P5F75MS400ATS
400 40 P5C90MS400ATS P5B90MS400ATS P5A90MS400ATS P5D90MS400ATS P5E90MS400ATS P5F90MS400ATS
25 P5C75MS600ATS P5B75MS600ATS P5A75MS600ATS P5D75MS600ATS P5E75MS600ATS P5F75MS600ATS
600
40 P5C90MS600ATS P5B90MS600ATS P5A90MS600ATS P5D90MS600ATS P5E90MS600ATS P5F90MS600ATS
28.75 P5C75MS800ATS P5B75MS800ATS P5A75MS800ATS P5D75MS800ATS P5E75MS800ATS P5F75MS800ATS
800 3 43.75 P5C90MS800ATS P5B90MS800ATS P5A90MS800ATS P5D90MS800ATS P5E90MS800ATS P5F90MS800ATS
28.75 P5C75MS120ATS P5B75MS120ATS P5A75MS120ATS P5D75MS120ATS P5E75MS120ATS P5F75MS120ATS
1200 3 43.75 P5C90MS120ATS P5B90MS120ATS P5A90MS120ATS P5D90MS120ATS P5E90MS120ATS P5F90MS120ATS
1 For 600V, change “F” in position 3 to “G.”
2 Alternate main breaker requires an additional 1.25” unit space.
3 800 and 1200 ampere switches have "L" class fuse provisions (Type HCD).

5-9
Modification and Additions
Type P5 Panelboards

Devices Mounted on Gutter Cover Ground Fault on Main Breaker Main Bus
Includes Device, Mounting – Wired Standard main bus and ground bus are
Amp
or Unwired Description Rating tin-plated aluminum. For copper main
bus, neutral bus and ground bus, add
Description Conventional Ground
from the table for each panel.
One piece front with door Fault 2 Includes:
(Depth increases to 14.25”) Ground Fault Relay, Ground
Sensor, CPT and Shunt Trip 800-1200 Lugs – For Main Lug Only Panels
Hinged Gutter Covers 4 pc front Standard main lugs and neutral lugs
Toggle Switch — SPST or 3-way Test and Monitor Panel 3
are tin-plated aluminum, UL listed for
15A, 277V maximum Ground Fault add to
Sensitrip III breaker price 800-1200 use with aluminum/copper cables.
Pilot Light — General Purpose (takes 5” of unit space) Copper only lugs are an option.
Neon or Incandescent
Pushbutton •Indicates available Ampere Rating
400 - 1200
Time Clocks 4
Feed-Thru Lugs Sangamo, Tork or Paragon time clock
Ampere Rating Unit Space (inches) can be supplied, mounted in panel- Shunt Trip on Main and Branches 5
400 10
board cabinet. For required increase Description
600 10
in enclosure dimension, consult local
BL, BQD, xGB, HGB, LGB, NEB, HEB
800 17.5
sales office. (branch only)
1200 17.5 QJ2, QJH2, QJ2H, QR2, QRH2, HQR2,
Description
HQR2H, ED2, ED4, HED4, HHED6, CED6
Time clock (1- or 2-Pole, Single or Double (branch only)
Grounding of Panelboards Throw Contacts; 3-Pole Single Throw)
All others through 1200A
Ground Bars except for brazed to box 277V Maximum with Plain Dial
are shipped with the panel interior Options:
factory mounted. Astronomical Dial 100% Rated Main Circuit Breakers
• Non-Insulated Equipment Ground An Omitting Device
Ampere
Bar – Standard Reserve Power or Carryover Rating Breaker Type
• Copper Non-Insulated Ground Bar Space and Mounting Provisions Only JXD6H, HJXD6H
• Al Insulated Equipment Ground Bar 400
NJY, HJY, LJY
• Cu Insulated Equipment Ground Bar 600 LXD6H, HLXD6H
• Ground Bar Brazed to Box Circuit Breaker Accessories 600 6 NMY, HMY, LMY
Handle Blocking Device MXD6H, HMXD6U, SMD6,
800 7
Fuse Clip Provisions Blocks handle in either the SHMD6, SND6, SHND6,
“ON” or “OFF” position. NXD6H, HNXD6H
(Add to 250 Volts or 600 Volts
NNY, HNY, LNY
Unit Prices Per Switch) 1200
Padlocking Device – Padlocks NXD6H, HNXDH
Amp Class Class Class in “OFF” position.
Rating J R T
30 • • N/A
60 • • N/A
100 • • •
200 1 • • •
400 • • •
600 • • •

1 For use on main lug, main breaker or main switch panels without subfeed breakers.
2 Available in 90” high enclosure only. Unit space is 42 1/2” with Test and Monitor Panel; 45” without Test Monitor Panel.
3 Not available on Sensitrip III.
4 For required unit space, consult local sales office.
5 Shunt Trip on 100A frame breakers increases mounting height to 6.25” for twin mounting.
6 The 600A, 100% rated braaker application requires the use of an 800A frame breaker.
7 The 800A, 100% rated breaker application requires the use of a 1200A frame breaker.

5-10
SECTION 5
Modification and Additions
Type P5 Panelboards

Motor Starters disconnect devices in either one of Standard Motor Starters Equipped
ETI instantaneous-trip circuit breakers two circumstances: 1. by using a branch With:
are recommended for use in combination thermal magnetic (ETI) circuit breaker to • 3rd overload relay
motor starters to provide selective short feed a remote starter that controls a • Mechanical interlock between circuit
circuit protection for the motor branch motor which is in sight of and within breaker (or switch) and motor starter
circuit. The adjustable instantaneous-trip fifty feet of the panelboard. 2. by using door
feature provides a trip setting slightly a branch instantaneous trip only (ETI) • Reset button
above the peak motor inrush current. circuit breaker in conjunction with a • Class 1, Type A wiring
With this setting, there is no delay motor starter mounted in the same
opening the circuit when the fault occurs. enclosure which is in sight of and within Optional Motor Control Accessories
Since these circuit breakers have no time fifty feet of the controlled motor. • Pushbuttons: Start/Stop or Open/Close,
delay trip element, they must be used in Reverse/Forward/Stop or High/Low/Stop
conjunction with, and immediately ahead Whether a remote starter is used, or • Selector Switch: Hand/Off/Auto or
of, the motor-running over-current the breaker and starter are mounted On/Off
protective device. in the same enclosure, a padlocking
• Pilot Light: Red or Amber
device must be specified so a padlock
Check the voltage and interrupting rating can be installed in the “OFF” position. • Auxiliary interlock (normally open or
of the circuit breaker to ensure they are P2 panelboards incorporate motor normally closed-unwired)
adequate for the electrical system. UL disconnect devices much in the same • Control transformer, 60Hz, fused LV,
recognized ETI breakers must be used. way as P5 panelboards, except a fusible Sizes 1 thru 4
Vacu-Break switch unit is utilized rather • Class 1, Type B wiring
Full voltage, non-reversing NEMA Size than an ETI circuit breaker. In addition,
1 through Size 4 motor starters are padlocking devices are standard on all
available as additions to P5 panelboards. Vacu-Break switches eliminating the
P5 panelboards can accommodate motor need to order them as an accessory.

Table P5-17 – ETI circuit Breakers (Instantaneous Trip Only) Table P5-18 – Full Voltage
For Branch-Circuit Use with AC Full Voltage Motor Starters Non-Reversing Starters Class A20
Maximum 3Ø Ratings Mounting Height in Inches (mm) NEMA Unit Space
Amp Breaker Min. Section Starter Size Mtg. Ht. In. (mm)
Rating Type 220 (208)V 240V 480V 1 2 Twin Single Width Inches (mm) Left Right
3 — — 1 5 (127) — 32 (813) 0 — 5 (127) 3
5 0.5 0.5 2 5 (127) — 32 (813) 0 0 5 (127) 3
10 ED 1 2 2 3 5 (127) — 32 (813) 1 — 5 (127) 3
25 5 5 10 5 (127) — 32 (813) 1 0 5 (127) 3
50 15 15 30 5 (127) — 32 (813) 1 1 5 (127) 3
100 30 30 60 5 (127) — 32 (813) 2 — 10 (254)
150 FD6 2 40 40 75 5 (127) — 32 (813) 2 0 10 (254)
225 FD6, 50 50 100 5 (127) — 32 (813) 2 1 10 (254)
CFD6 2 2 10 (254)
3 — 15 (381)
1 100,000 kA at 480V with E-frame and CFD6 frame breakers.
3 0 15 (381)
2 65,000 kA at 480V with F-frame breakers.
3 Increase to 7.50 inches when pilot light or control transformer is required. 3 1 15 (381)
3 2 15 (381)
3 3 15 (381)
4 — 15 (381)

Table P5-19 – Maximum 3 Phase


Horsepower Rating
NEMA
Starter Voltage AC
Size 220 (208)V 240V 480V
0 3 3 5
1 7.5 7.5 10
2 10 15 25
3 25 30 50
4 40 50 100

5-11
Modification and Additions
Type P5 Panelboards

Table P5-20 – Vacu-Break Fusible Switches


For Branch Circuit Use with AC Combination Full Voltage Starters 1
Horsepower Ratings Mounting Height in Inches (mm)
240V AC 480V AC 240V AC 480V AC Min. Section
Amp With With Dual- With NEC With Dual- Width
Rating NEC Fuse Element Fuse Fuse Element Fuse Twin Single Twin Single Inches (mm)
2.50 2
30-30 3 7.5 — — — — — 32 (813)
(64)
5.00 7.50
30-30 3 7.5 5 10 — — 32 (813)
(127) (191)
5.00 7.50
30-60 3-7.5 7.5-15 5-15 25 — — 32 (813)
(127) (191)
5.00 7.50
60-60 7.5 15 15 25 — — 32 (813)
(127) (191)
7.50 7.50
60-100 7.5-15 15-30 15-25 25-50 — — 32 (813)
(191) (191)
7.50 7.50
100-100 15 30 25 50 — — 32 (813)
(191) (191)
7.50
100 — — 25 50 — — — 32 (813)
(191)
10.00 10.00
200 25 50 50 100 — — 32 (813)
(254) (254)
10.00 10.00
200-200 — 50 — 100 — — 32 (813)
(254) (254)
15.00 15.00
400 50 100 100 — — — 38 (965)
(381) (381)
15.00 15.00
600 75 100 — — — — 38 (965)
(381) (381)

1 100,000 kA at 480V with Class J or Class RK5 fuses.


2 The 2.50 inch (64mm) high unit is suitable for NEC Class H and K5 fuses only. Class R rejection type fuse holders are not available.

Connector Modifications
Compression Lugs
Table P5-21 – Compression Lugs

Style Amp Rating Breaker Type Compression Connectors Available Unit Space Reduction
800 N/A All compression lugs Deduct 10.0” Unit Space
MLO 1000 N/A All compression lugs Deduct 10.0” Unit Space
1200 N/A All compression lugs Deduct 10.0” Unit Space
800 MD6, HMD6, CMD6,
SMD6, SHMD6, (3)#2/0 AWG - 500 Kcmil CU or Al 0
Main Breaker SCMD6
1200 ND6, HND6, CND6,
SND6, SHND6. (4)#250 - 500 Kcmil Cu or Al 0
SCND6

Table P5-22 – Alternate Lugs

Style Amp Rating Breaker Type Compression Connectors Available Unit Space Reduction
800 N/A (3)#3/0 AWG - 750 Kcmil Cu or Al Deduct 5.0” Unit Space
MLO 1000 N/A (4)#3/0 AWG - 750 Kcmil Cu or Al Deduct 7.5” Unit Space
1200 N/A (4)#3/0 AWG - 750 Kcmil CU or Al Deduct 7.5” Unit Space

5-12
SECTION 5
Dimensions
Type P5 Panelboards

Type 1 Box
Box is symmetrical

Type 3R and 3R/12 Box

햲 Dimensions are interior of the box. Add 5/8” to width for


absolute dimension. Add 1/8” to height for absolute dimension.

Dimensions shown in inches and millimeters [ ].

5-13
Kits and Accessories
Type P5 Panelboards

Table P5-23 – Branch Breaker Connecting Strap Kits 1 2 Table P5-24 – Blank Plates – Circuit
For use with P5, Sentron Deep or Type S5 Power Panels Breaker and Vacu-Break 4
Max Unit
Amp Breaker Breaker Catalog Height For use with Sentron SPP and Type P5 power panels
Rating Family Type Number (inches) Mounting Height
100 General BL, BQD SBLBD 3.75 Twin Inches Catalog
125 General NGB, HGB, LGB SNBD 3.75 Twin (mm) Number
General EB SEBD 3.75 Twin 1.25 (32) 6FPB01
General ED SE6D 3.75 Twin 2.5 (63.5) 6FPB02
General CED SCED 3.75 Twin 3.75 (95) 6FPB03
150 VL DG SDGD 5.00 Twin 5.0 (127) 6FPB05
225 General QJ SQJD 5.00 Twin 10.0 (254) 6FPB10
General QR SQRD 5.00 Twin
250 Sentron FD SF6D 5.00 Twin
VL FG SFGD 5.00 Twin Table P5-25 – Filler Plates
Sentron CFD SCFD 5.00 Single
400 Sentron JD SJ1D 8.75 Single For use with Sentron SPP and P5 power panels
Sentron JD SJ2D 8.75 Twin Breaker Type Filler Plate
Sentron SJD SSJ1D 8.75 Single Catalog Number
VL JG SJG1D 6.25 Single BL, BLH, HBL, BQD,
VL JG SJG2D 6.25 Twin NGB, HGB, LGB, ED2, DFFP15
Sentron CJD SCJD 8.75 Single ED4, ED6, HED4, HHED6
Sentron SJD SSCJD 8.75 Single NEB, HEB EBF1
600 Sentron LD SL6D 8.75 Single Note: When a front filler plate is not completely filled
Sentron SLD SSL6D 8.75 Single with breakers, the openings in the unused space must be
VL LG SLGD 6.25 Single closed with filler plates selected from this table.
Sentron CLD SCLD 8.75 Single
Sentron SCLD SSCLD 8.75 Single
g Table P5-26 – Cover Plates
800 VL MG MG1D 8.75 Single For use with P5, Sentron SPP and
Sentron LMD SLM1D 8.75 Single Type S6 power panels
Sentron MD SMND 10.00 Single Breaker Type Catalog Number
Sentron SMD SSMND 10.00 Single QR SQRC 6
1200 VL NG NG1D 10.00 Single
Sentron ND SMND 10.00 Single
Sentron SND SSMND 10.00 Single
fAlthough QR is rated 250A, it is limited to 225A in panelboard.

Table P5-27 – Connecting Strap Kits – Fusible 2 Table P5-28 – Service Entrance Barriers
For use with Sentron FPP Deep or Type F2/P5 power panels Field installable Barriers to meet UL 67
service entrance requirements
Unit
Ampere Height Catalog
Rating Inches (mm) Number Breaker Type Catalog Number
30–30 2.5 (63.5) F602D (S)JD, (S)LD, MG SEBP4V1
30–30 5.0 (127), 7.5 (191) F657D CJD, CLD SEBP4V2
30–60 5.0 (127), 7.5 (191) F657D JG, LG SEBP4V3
60–60 5.0 (127), 7.5 (191) F657D (S)MD, (S)ND without shield SEBP5V1
60–100 5.0 (127), 7.5 (191) F657D (S)MD, (S)ND without shield SEBP5V2
100–100 5.0 (127), 7.5 (191) F657D Vacu-Break Switches SEBP5V3
100 7.5 (191) F657D HCP Switches SEBP5V4
200 7.5 (191) F657D
200 10.0 (254) F671D
200–200 10.0 (254) F672D
400–600 15.0 (381) F6150D
800–1200 2 16.25 (413) F6162D
1 Includes cover plate and mounting hardware, less circuit breaker.
2 Also fits Types FCI, FCII, SB1, SB2 and SB3 switchboards.
3 800-1200 amp units are HCP switch.
4 Normal stock item.
5 Suitable to replace QF3 in P1 thru P5 panelboards and switchboards.
6 To replace QJ with a QR only a new cover is needed up to 225A.

5-14
5 SECTION
Kits and Accessories
Type P5 Panelboards

Table P5-29 – Enclosures


Description Catalog number
P5 Type 1 38” W x 12.75” D x 60” H PB860
P5 Type 1 38”” W x 12.75” D x 75” H PB875
P5 Type 1 38”” W x 12.75” D x 90” H PB890
P5 Type 1 38” W x 14.75” D x 60” H PBD860 1
P5 Type 1 38”” W x 14.75” D x 75” H PBD875 1
P5 Type 1 38”” W x 14.75” D x 90” H PBD890 1
P5 Type 3R/12 60” H WP860
P5 Type 3R/12 75” H WP875
P5 Type 3R/12 90” H WP890
1 Required with door over breaker handles.

Table P5-30 – Trims


Description Catalog number
P5 Std (4 piece trim) vented 60” P560V
P5 Std (4 piece trim) vented 75” P575V
P5 Std (4 piece trim) vented 90” P590V
P5 Std (4 piece trim) unvented 60” P560NV 1
P5 Std (4 piece trim) unvented 75” P575NV 1
P5 Std (4 piece trim) unvented 90” P575NV 1
P5 Std (4 piece trim) vented 60” with hinged gutter covers P560VHG
P5 Std (4 piece trim) vented 75” with hinged gutter covers P575VHG
P5 Std (4 piece trim) vented 90” with hinged gutter covers P590VHG
P5 Std (4 piece trim) unvented 60” with hinged gutter covers P560NVHG
P5 Std (4 piece trim) unvented 75” with hinged gutter covers P575NVHG
P5 Std (4 piece trim) unvented 90” with hinged gutter covers P590NVHG
P5 Std (1 PC Door) vented 60” P560VD 2
P5 Std (1 PC Door) vented 75” P575VD 2
P5 Std (1 PC Door) vented 90” P590VD 2
P5 Std (1 PC Door) unvented 60” P560NVD 2
P5 Std (1 PC Door) unvented 75” P575NVD 2
P5 Std (1 PC Door) unvented 90” P590NVD 2
P5 Std (1 PC Door-in-door) vented 60” P560VDD 2
P5 Std (1 PC Door-in-door) vented 75” P575VDD 2
P5 Std (1 PC Door-in-door) vented 90” P590VDD 2
P5 Std (1 PC Door-in-door) unvented 60” P560VDD 2
P5 Std (1 PC Door-in-door) unvented 75” P575VDD 2
P5 Std (1 PC Door-in-door) unvented 90” P590VDD 2
1 Unvented trims require amps per square inch bussing.
2 Requires 14.5” deep box.

Table P5-31 – Flush mounting kits


Description Catalog number
Flush kit to P5 60” High F860
Flush kit to P5 75” High F875
Flush kit to P5 90” High F890

5-15
Notes
SECTION 6
C1/ C2 Panelboards
Description Page
General Specifications 6-2 Subfeed Breakers C1 6-4
Box Sizing 6-2 Alternate Main Breaker Selection C2 6-5
Gauge Steel Boxes 6-2 Branch Circuit Breaker C2 6-5
Fronts 6-2 Subfeed Breakers C2 6-5
Main Breaker Connectors 6-2 Modification and Additions 6-6
Main Lug Connectors 6-2 Box Modifications 6-6
Selection 6-3 – 6-5 Interior Modifications 6-6
Main Lugs Only C1 and C2 6-3 Column Extension 6-6
Main Circuit Breaker C1 and C2 6-3 Pull Boxes 6-6
Alternate Main Breaker Selection C1 6-3
Branch Breaker Selection C1 6-4
General Specifications
C1 and C2 Panelboards

Type C1 Table C1/C2-1 – Box Sizing


240 Volts AC Maximum Certain Modifications such as subfeed breakers and feed-thru
250 Ampere Mains lugs require additional unit space. Use this table to determine
250 Ampere Maximum Branch proper enclosure size.
UL Short Circuit Rating – 200,000 IR Maximum
Branch Breaker Symmetrical Interrupting Rating Panel Height Dimensions in inches (mm)
Based on Underwriters’ Test Procedure Config- No. of Inches Width Depth
uration Circuits (mm) C1 C2 C1 C2
Type C2 18 48 (1219)
480Y/277 Volts AC Maximum Main Lug 30 73 (1854)
250 Ampere Mains 42 85 (2159)
250 Ampere Maximum Branch Main Lug with
18 73 (1854)
UL Short Circuit Rating – 100,000 IR Maximum Feed-Thru Lugs 30 86 (2184)
Meets NEC wire bending requirement, section 312-6 42 85 (2159)
Main Lug with 18 73 (1854)
Panelboards Subfeed Breaker 30 85 (2159) 7.62 8.50 5.75 5.75
Listed by Underwriter’s Laboratories, Inc., under “Panelboards” Main Breaker 18 48 (1219) (194) (216) (146) (146)
File #E2269 30 73 (1854)
Meets Federal Specification W-C375B/Gen. 42 85 (2159)
Main Breaker 18 73 (1854)
Service with Feed-Thru 30 85 (2159)
Description: 240 Volts Maximum. 1-Phase, 3-wire or 3-Phase, Lugs 42 85 (2159)
4-Wire. Main Breaker 18 73 (1854)
with Subfeed 30 85 (2159)
Breaker
Panelboards Fronts and Doors
Standard panelboards are furnished with trim with a flush door
lock. All are factory assembled for ease of installation. Fronts are Table C1/C2-2 – Gauge Steel Boxes
fabricated from code gauge steel and finished ANSI-61.
Type Width Height Gauge Steel
Main Breakers C1 C1 7 ⁵⁄₈” 1 48, 73, 85 #14
BL, BLH and HBL frame breakers are mounted horizontally. All C2 8 ¹⁄₂” 1 48, 73, 85 #14
other frames are mounted vertically.
Table C1/C2-3 – Fronts
Main Breakers C2
BQD frame breakers are mounted horizontally. All other frames Type Width Height Gauge Steel
are mounted vertically. C1 7 ⁵⁄₈” 1 48, 73, 85 #14
C2 8 ¹⁄₂” 1 48, 73, 85 #14
Weight — Approximate
1 Feed thru lugs and subfeed breakers not available for this height.
Total panelboard weight when filled with a normal quantity of
breakers and accessories is about 3 lbs. (1 kg) per inch (54g per
Table C1/C2-4 – Main Breaker Connectors
mm) of box height.
Ampere Rating Connector Suitable for Cu or Al
100 (1) #14-1/0 AWG
125 (1) #4-1/0 AWG
225 (1) #6 AWG-300 kcmil
250 (1) #4 AWG-350 kcmil Al
(1) #6 AWG-350 kcmil Cu

Table C1/C2-5 – Main Lug Connectors

Ampere Rating Connector Suitable for Cu or Al


125 (1) #6 AWG-350 kcmil
250 (1) #6 AWG-350 kcmil

6-2
SECTION 6
Selection
C1 and C2 Panelboards

Table C1/C2-6 – Main Lugs Only C1 Table C1/C2-7 – Main Lugs Only C2

Max. Max.
Panel Max. Box 208Y/120V 120/240V Panel Max. Box 480Y/277V
Amp 1-Pole Height 3, Phase 4 Wire 1 Phase, 3 Wire Amp 1-Pole Height 3 Phase, 4 Wire
Rating Circuits Inches Catalog Number Catalog Number Rating Circuits Inches Catalog Number
18 48 C1C18ML125CTS C1A18ML125CTS 18 48 C2E18ML125CTS
125 30 73 C1C30ML125CTS C1A30ML125CTS 125 30 73 C2E30ML125CTS
42 85 C1C42ML125CTS C1A42ML125CTS 42 85 C2E42ML125CTS
18 48 C1C18ML250CTS C1A18ML250CTS 18 48 C2E18ML250CTS
250 30 73 C1C30ML250CTS C1A30ML250CTS 250 30 73 C2E30ML250CTS
42 85 C1C42ML250CTS C1A42ML250CTS 42 85 C2E42ML250CTS

Table C1/C2-8 – Main Circuit Breaker C1 1 2 Table C1/C2-9 – Main Circuit Breaker C2 1 2
18 48 C1C18BL100CTS C1A18BL100CTS 18 48 C2E18BD100CTS
100 30 73 C1C30BL100CTS C1A30BL100CTS 100 30 73 C2E30BD100CTS
42 85 C1C42BL100CTS C1A42BL100CTS 42 85 C2E42BD100CTS
18 48 C1C18E4125CTS C1A18E4125CTS 18 48 C2E18E4125CTS
125 30 73 C1C30E4125CTS C1A30E4125CTS 125 30 73 C2E30E4125CTS
42 85 C1C42E4125CTS C1A42E4125CTS 42 85 C2E42E4125CTS
18 48 C1C18QR225CTS C1A18QR225CTS 18 48 C2E18FX225CTS
225 30 73 C1C30QR225CTS C1C30QR225CTS/ 225 30 73 C2E30FX225CTS
42 85 C1C42QR225CTS C1A42QR225CTS/ 42 85 C2E42FX225CTS
18 48 C1C18FX250CTS C1A18FX250CTS 18 48 C2E18FX250CTS
250 30 73 C1C30FX250CTS C1A30FX250CTS 250 30 73 C2E30FX250CTS
42 85 C1C42FX250CTS C1A42FX250CTS 42 85 C2E42FX250CTS

Table C1/C2-10– Alternate Main Breaker Selection C1 1 2

Amp Breaker Maximum Interrupting Catalog


Rating Type Rating (KA) Number Available Trip Values
BL 10 BL
100 BLH 22 LH 50, 60, 70, 80, 90, 100
HBL 65 HL
ED4 65 E4
125 50, 60, 70, 80, 90, 100, 110, 125
HED4 100 H4
QJ2 10 QJ
QJH2 22 QH 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
225 QJ2H 42 Q2
QR2 10 QR 100, 110, 125, 150, 175, 200, 225
FXD6 65 FX
70, 80, 90, 100, 110, 125, 150, 175, 200, 225
HFD6 2 100 HF
FXD6 65 FX
250 250
HFD6 2 100 HF
1 BL, BLH, HBL and BQD are horizontally mounted. All others vertically mounted.
2 Interchangeable trip breakers such as FD6 and HFD6 cannot be back fed. Must be top feed only.

6-3
Selection
C1 and C2 Panelboards

Table C1/C2-11 – Branch Breaker Selection C1

Available Maximum Interrupting


Breaker Ampere Rating (kA)
Type Rating 120V 120/240V 240V
15, 20, 30, 40, 50, 60 — 10 —
BL (120V) 70 — 10 —
70, 80, 90, 100 — 10 —
BL (HID) 15, 20, 30 — — —
15, 20, 30 10 — —
BLF (GFCI)
40, 50, 60 10 — —
BLE (EQGFI) 15, 20, 30 10 — —
BGL (SWN) 15, 20, 30 10 — —
15, 20, 30, 40, 50, 60 — — 10
BLR (240V)
70, 80, 90, 100 — — 10
15, 20, 30, 40, 50, 60 — 22 —
BLH (120V) 70 — 22 —
70, 80, 90, 100 — 22 —
15, 20, 30 — 22 —
BLHF (GFCI)
40, 50, 60 — 22 —
15, 20, 30, 40, 50 — 65 65
HBL
60, 70, 80, 90, 100 — 65 65

Table C1/C2-12 – Subfeed Breakers - Limit One Per Panel – C11 (Not available for 42 circuit panels)
15, 20, 30, 40, 50, 60, 70, 80, 90, 100 — — 65
ED4
110, 125 — — 65
15, 20, 30, 40, 50, 60, 70, 80, 90, 100 — — 65
HED4
110, 125 — — 100
QJ2 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225 — — 10
QJH2 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225 — — 22
QJ2H 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225 — — 42
QR2 100, 110, 125, 150, 175, 200, 225 — — 10
FXD6 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 — — 65
HFD62 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 — — 100
1 BL, BLH, HBL, and BQD are horizontally mounted. All others are vertically mounted.
2 Interchangeable trip breakers such as FD6 and HFD6 cannot be back fed. Must be top feed only.

6-4
SECTION 6
Selection
C1 and C2 Panelboards

Table C1/C2-13 – Alternate Main Breaker Selection 1 2 3 C2

Ampere Breaker Catalog


Rating Type IR Number Available Trip Values
BQD 14 BD 50, 60, 70, 80, 90, 100
ED4 18 E4 50, 60, 70, 80, 90, 100
100 ED6 25 E6 50, 60, 70, 80, 90, 100
HED4 42 H4 50, 60, 70, 80, 90, 100
HHED6 65 H6 50, 60, 70, 80, 90, 100
ED4 18 E4 110, 125
ED6 25 E6 110, 125
125
HED4 42 H4 110, 125
HHED6 65 H6 110, 125
FXD6 35 FX 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
225
HFD6 65 HF 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
FXD6 35 FX 250
250
HFD6 65 HF 250
1 No increase in box height. Space is already built into C1 panel. 3 Interchangeable trip breakers such as FD6 and HFD6 cannot be back fed. Must be
2 BL, BLH, HBL and BQD are horizontally mounted. All others vertically mounted. top feed only.

Table C1/C2-14 – Branch Circuit Breakers C2


Maximum Interrupting Rating (kA)
Breaker Type Available Ampere Rating 277V 480/277V 480V
15, 20, 30, 40, 50, 60 14 14 —
BQD
70, 80, 90, 100 14 14 —

Table C1/C2-15 – Subfeed Breakers - Limit One Per Panel 1 2 C2 (Not available for 42 circuit panels)
15, 20, 30, 40, 50, 60, 70, 80, 90, 100 — 18 18
ED4
110, 125 — 18 18
ED6 15, 20, 30, 40, 50, 60, 70, 80, 90, 100 — — 25
110, 125 — — 25
HED4 15, 20, 30, 40, 50, 60, 70, 80, 90, 100 — — 42
110, 125 — — 42
FXD6 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 — — 35
HFD6 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 — — 65
1 No increase in box height. Space is already built into C1 panel.
2 BL, BLH, HBL and BQD are horizontally mounted. All others vertically mounted.

6-5
Modification and Additions
C1 and C2 Panelboards

Type C1/C2 Column Extension Pull Boxes


When required, special constructions Available in various standard lengths, Two styles of pull boxes are available,
or additions to standard panelboards extensions are 5 ¹⁄₄ inches deep and top and front mounted. When the panel
may be specified for factory-assembled 7 inches wide. and its extensions are mounted in a
column panelboards. structural WF beam, a front mounted
pull box is required. When the panels
Table C1/C2-16 – Box Modifications Table C1/C2-18 – Column Extension are surface mounted, a top mounted
Description Height Catalog Number pull box may be used. Provisions are
Gasketed (inches) made so that the neutral bar may be
Metal Card Holder 14 LXX-14 mounted in the pull box when required.
Welded Metal Card Holder 20 LXX-20 (Front mounted pull box dimensions
Nameplate 26 LXX-26 are 14” H x 20” W.)
Al Ground Bar 32 LXX-32
Cu Ground Bar 38 LXX-38 Table C1/C2-19 – Pull Boxes
Insulated Al Ground Bar 41 LXX-41 Description Catalog Number
Insulated Cu Ground Bar 44 LXX-44
Top Mount LXXP-T
53 LXX-53
Front Mount 1 LXX50-F
56 LXX-56
1 Includes 50” extension.
Table C1/C2-17 – Interior Modifications 62 LXX-62
65 LXX-65
Description 68 LXX-68
Feed-Thru Lugs 74 LXX-74
Cu Neutral Lugs 80 LXX-80
Cu Main Lugs 125A 86 LXX-86
Cu Main Lugs 250A

Fig. C1/C2-1

6-6
SECTION 7
Miscellaneous
Description Page
Telephone Cabinets 7-2 Strap Kits 7-4
Conduit Enclosing Shield (Panel Skirts) 7-2 Connecting Strap Kits 7-4
Breaker Mechanical Lugs 7-2 Blank Plates – Vacu-Break 7-4
Compression Lugs 7-2 Molded Case Switches 7-4
Optional Mechanical Lugs 7-3
Aluminum Body Lugs for Copper or
Aluminum Wire 7-3
Miscellaneous Replacement Parts 7-4
Miscellaneous

Telephone Cabinets and vault handle supplied with double Backboard


Conform to requirements of Underwriter’s doors; two spring catches supplied on 0.75 in. (19mm) plywood backboard
Laboratories, Inc., for all cabinets and boxes doors more than 48 in. (1219 mm) high. supplied when specified.
bearing their label. Surface enclosures,
box and front constructed of code gauge Table Misc.– 1
steel. Entire cabinet finished with light
gray, ANSI-61. Flush enclosures, box con- Box Width – In. (mm) Door
structed of code-gauge galvanized steel, 0 (0)–20 (508) Single Depth
front only finished with light gray, ANSI-61. 21 (533)–24 (610) Single 0.75 in. Surface Mounting
25 (635)–36 (914) Single (19 mm)
Boxes 25 (635)–36 (914) Double
0.75 in.
(19 mm)
Standard construction has blank ends,
37 (940)–38 (965) Double
without knockouts.
49 (1245)–60 (1524) Double
Trim Depth
Front Overlap
All available with 0.75 in. (19 mm) backboard.
Concealed hinges standard on fronts. Depth 12 in. (305 mm) or less. Height 72 in. (1829
Flush Mounting
Double doors supplied when door width mm) or less. Specify Mounting – Surface or Flush.
exceeds 24 in. (610 mm). 3-point catch Box width minus 5 in. (127 mm) equals door width.

Conduit Enclosing Shield Panel Skirts Standard Length


(Panel Skirts)
3 Sides Open Back 4 Sides Screw Front
Sheet metal to cover conduits above
or below a standard panelboard box.

8, 9, 10, 11, 12, 14, 17, 18, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33, 34, 35, 36, 37, 38, 39, 40, 41, 42, 43, 44

Table Misc. 2 – Compression Lugs Table Misc. 3 – Breaker Mechanical Lugs

For Circuit Ampere Lugs Lug Wire For Use Amp Cables
Breaker Types Rating Poles Per Kit Size With Type(s) Rating Per Lug Lug Wire Range
Lugs (contains indicated number of lugs and necessary hardware per kit) Load Side
ED2, ED4, ED6, 15-125 1,2,3 1 #2/0 BQ, BQH, 15-20 1 #14-#10 AWG Cu
HED4, HHED6, CED4 BQHF, BQE 1 #12-#10 AWG Al
QJ2, QJH2, QJ2H, QR2, 125-225 2, 3 1 350 kcmil BQF, 25-35 1 #8-#6 AWG Cu
QR2H, HQR2, HQR2H BL, BLH 1 #8-#6 AWG Al
F(X)D6-A, HF(X)D6, 125-250 2, 3 1 350 Kcmil HBL, HBQ 40-50 1 #8-#6 AWG Cu
HHF(X)D6, CFD6 1 #8-#4 AWG Al
JXD2-A, J(X)D6-A, Switching 55-70 1 #8-#4 AWG Cu
HJ(X)D6-A, HHJXD6-A, Neutrals 1 #8-#2 AWG Al
CJD6, SJD6-A, 200-600 2, 3 1 500 Kcmil 80-100 1 #4-#1/0 AWG Cu
SHJD6-A, SCJD6, L(X)D6-A, BG 1 #2-#1/0 AWG Al
HL(X)D6-A, CLD6, SLD6-A, BLG 110-125 1 #2-#1/0 AWG Cu
SHLD6-A, SCLD6 1 #1/0-#2/0 AWG Al
Kits (contains lug and hardware for complete line of load end of 2 or 3 pole breaker) 15-40 1 #14-#6 AWG Cu
M(X)D6, HM(X)D6, CMD6, 500-800 2 6 500 Kcmil BQD #12-#6 AWG Al
SMD6, SHMD6, SCMD6 3 9 500 Kcmil BQD6 45-100 1 #8-1 AWG Cu
N(X)D6, HN(X)D6, CND6, 900-1200 2 8 500 Kcmil #6-#1/0 AWG Al
SND6, SHND6, SCND6 3 12 500 Kcmil

7-2
SECTION 7
Miscellaneous

Table Misc. 4 – Aluminum Body Lugs for Copper or Aluminum Wire


Circuit
For Use Breaker Cables
With Type Amp Rating Per Lug Lug Wire Range
QJ2, QJH2, QJ2H 60-225 1 #6 AWG-300 kcmil (Cu)
QR2, QRH2, HQR2, HQR2H #4 AWG-300 Kcmil (Al)
All 2&3 pole 15-25 1 #14-#10 AWG (Cu)
ED2, ED4, ED6, #12-#10 AWG (Al)
ED6ETI 30-100 1 #10-#1/0AWG (Cu or Al)
HED4, 110-125 1 #3-3/0 (Cu)
HHED6 1 #1-2/0 (Al)
CED6, All 1 Pole, 30-60 1 #10-4 (Cu or Al)
ED, HED 70-100 1 #4-#1/0 (Cu or Al)
FXD6-A, FD6-A, HFD6, 70-250 1 #6 AWG-350 Kcmil (Cu)
CFD6, HHFD6 #4 AWG-350 Kcmil (Al)
SJD6(A), SHJD6(A), 65-200 1-2 #4 AWG-310 Kcmil (Cu or Al)
SCJD6
JXD2(A), JXD6(A),
JD6(A), SJD6(A),
HJD6(A), HHJXD6(A), 200-400 1-2 3/0-500 Kcmil (Cu)
HHJD6, SHJD6(A), 4/0-500 Kcmil (Al)
CJD6, SCJD6
LXD6(A), LD6(A),
SLD6(A), HLD6(A),
HHLXD6, HHLD6, 250-600 1-2 3/0-500 Kcmil (Cu)
SHLD6(A), CLD6, SCLD6 4/0-500 Kcmil (Al)
LMD6, 1 LMXD6, 1
HLMD6,1 HLMXD6, 1 500-600 1-2 250-500 Kcmil (Cu or Al)
MD6, MXD6, SMD6,
HMD6, HMXD6, SHMD6, 700-800 1-3 1/0-500 Kcmil (Cu or Al)
CMD6, SCMD6 500-750 Kcmil (Cu or Al)
ND6, NXD6, SND6,
HND6, HNXD6, SHND6, 800-1200 1-4 250-500 Kcmil (Cu or Al)
CND6, SCND6
1 Use TA2K500 or TA3K500 only.

Table Misc. 5 – Optional Mechanical Lugs

For Use Circuit Breaker Cables Lug Quantity per


With Type Ampere Rating Per Lug Material Lug Wire Range Catalog Number
QJ2, QJH2,QJ2H, QR2,
QRH2, HQR2, HQR2H 60-225 1 Cu #6 AWG-250 Kcmil (Cu) 1
ED, HED, 2&3 pole 2-3 pole 30-125 1 Cu #10-#1/0 (Cu)
HFD6, HHFD6 70-250 1 Cu #6 AWG-350 Kcmil (Cu) 1
CFD6, F(X)D6-A
J(X)D2(A), J(X)D6(A), 1 3/0-600 Kcmil (Cu) 1
HJD6(A), HHJD6, 1,2 Cu 3/0-500 Kcmil (Cu) 1
SHJD6(A), L(X)D6(A),
HHLD6, SCD6, 250-600 1 Al 500-750 Kcmil (Al) 1
HLD6(A), SHLD6(A),
CJD6, CLD6, SCJD6, 1 500-600 Kcmil (Cu) 1
SCLD6
SMD6, M(X)D6, 500-600 1-2 Cu #1 AWG-500 Kcmil (Cu) 1
HM(X)D6, HMD6, 1-3 Cu #1 AWG-350 Kcmil (Cu) 1
CMD6, SCMD6, SND6, 700-800 1-2 Al 500-750 Kcmil (Cu) 2
N(X)D6, HN(X)D6, 1-2 Al 500-750 Kcmil (Al) 3
SHND6, CND6, SCND6 800-1200 1-3 Al 500-750 Kcmil(Cu) 2
500-750 kcmil (Al) 3

7-3
Miscellaneous

Table Misc. 6 – Miscellaneous Replacement Accessories


Catalog For
Number Description Panel Type
EGK Al Ground Assembly 44 Connections P1, P2, P3
BK1 Bonding Kit for P1 250A Max. as noted
BK3 Bonding Kit for S3 Panel
BK4 Bonding Kit for SE & P5 400 as noted
IMK Interior Adjusting Kit P1, P2, P3
11-1824-01 Directory Card Holder P1, P2, P3
12-1110-01 Directory Card P1, P2, P3
ANSI/NEMA General Instructions for Proper All
PB 1.1-2013 2 Installation, Operation, and Maintenance
of Panelboards Rated 600 Volts or
Less (O&M Manual)
NBK3 Number Strips 1-42 P1, P2, P3
NBK4 Number Strips 43-84 P1, P2, P3
NBK5 Number Strips 85-126 P1, P2, P3
NBK6 Number Strips 127-168 P1, P2, P3
ECGK Cu Ground Bus 44 Connections P1, P2, P3
IGK Insulated Al Ground Bus P1, P2, P3
ICGK Insulated Cu Ground Bus P1, P2, P3
EWK2 End Wall Kit with Knockouts P1
(24" W x 7.75" DP)
DFFP1 Filler Plate (Suitable for replacing P1, P2, P3,
QF3 in P1 thru P5 Panelboards P4, P5
and Switchboards)
1 All 1” QP, BL, BQD and ED Frame Provisions.
2 PDF can be downloaded for free and printed at this location:
http://www.nema.org/standards/pages/Panelboards.aspx

Connecting Strap Kits - Obsolete Circuit Breakers FC20, FCI and FCII switchboards – includes copper straps, cover
For use with Series 5 or 6 CDP circuit breaker panelboards plates and necessary hardware.

Table Misc. 7 Table Misc. 8 – Blank Plates – Vacu-Break


For use with VB-23, VB-30, VB-32 and Uni-Power Switchboards
Breaker Strap Kit Height
Frame 1 Catalog Number (in.) 12 in. Units - 23 in. 17 in. Units - 30 in. and
KM, HN 6KM1 10 Unit Wide Enclosure Only 32 in. Wide Enclosures
CN 6CN1 10 Height Catalog Catalog
Inches Number Number
KMB, HNB 6KMB1 10
SKM 6SKM1 10 2 1/2 VB2F025 VB7F025
KP, HK 6KP1 10 5 VB2F050 VB7F050
KPB, HKB 6KPB1 10 7 1/2 VB2F075 VB7F075
SKP, SHK 6SKP1 10 10 VB2F100 VB7F100

Table Misc. 9 – Connecting Strap Kits — Vacu-Break Table Misc. 10 – Molded Case
For use with VB-23 and VB-32 Type Panelboards. Switches (Non-Automatic
Circuit Interrupters)
For Use With
Panel Catalog Ampere Unit Height Ampere Breaker
Type Number Rating (in.) Rating Frame
VB-23 V2AX25 30-30 2 1/2 100 ED2, ED4, ED6
V2BX50 30-30 and 60-60 5 225 QJ2, QR2
V7AX25 30-30 2 1/2 250 FXD6
V7BX50 30-30 and 60-60 5 400 JXD2, JXD6
VB-32 V7EX75 100-100 7 1/2 600 LXD6
100 7 1/2 800 MD6
200 7 1/2 (2-Pole) 1200 ND6
V7FX100 200 10 (3-Pole)

7-4
Published by
Siemens Industry, Inc. 2016.

Siemens Industry, Inc.


5400 Triangle Parkway
Norcross, GA 30092

For more information, please contact


our Customer Support Center.
Phone: 1-800-241-4453
E-mail: [email protected]

usa.siemens.com/panelboards

Order No.PBCS-20301-1116

Printed in U.S.A.
© 2016 Siemens Industry, Inc.

Subject to changes and errors.


The information given in this document only contains general
descriptions and/or performance features which may not always
specifically reflect those described, or which may undergo modification
in the course of further development of the products. The requested
performance features are binding only when they are expressly agreed
upon in the concluded contract.

You might also like