SIE Selection and Application Guide Panelboards
SIE Selection and Application Guide Panelboards
Selection and
application guide
usa.siemens.com/panelboards
Contents
PAGE
Introduction 2
General Specifications 3-5
Catalog Numbering System 6
1
SECTION A detailed Table of Contents is located
at the beginning of each product section.
P1 Panelboards
2
SECTION
3
SECTION
P2 Panelboards
P3 Panelboards
SECTION
SECTION
5 4 P4 Panelboards
P5 Panelboards
6
SECTION
7
SECTION
C1/C2 Panelboards
Miscellaneous
Introduction
This new generation of products from Siemens offers the high • The highly flexible P2 provides options to fit the most
level of engineering and innovation you’ve come to expect from demanding specifications.
the leader in power distribution technology. The “P Series” line of • Sized more like a lighting panel, the P3 packs the power of a
panelboards offers a stepped approach to power distribution. distribution panel in a space-saving, highly flexible design.
• The P4 is a mid-sized distribution panel that allows both fusible
Additional strength has been added to an already rugged and and circuit breaker branch and main devices.
durable panelboard family. Engineered specifically to provide • The powerful P5 anchors the high end of the series. With
maximum flexibility, the new designs simplify wiring and reduce larger fusible and circuit breaker branch and main devices, the
material requirements making them easier to install and less venerable P5 delivers maximum power and flexibility to larger
costly than competitive products. At the heart of the product distribution systems.
line is the extensive research and technology found among
Siemens circuit protection devices – both fusible switches and Siemens also offers a number of specialty panels, like column
molded case circuit breakers. panels. Don’t see a panel to meet your requirements? Ask your
Siemens representative about our custom capabilities.
The line is anchored by the innovative P1. Featuring the industry’s
most flexible designs, the P1 virtually eliminates common Features Overview
errors, such as feed direction, and main lug versus main breaker. P Series lighting panel features include Fas-Latch trim, which is
Increasing distribution is simplified by the ability to add feed-thru popular among installers; the jacking screw system, that permits
lugs. The Revised P1 design introduced in January 2015 has added adjustments even after wiring has been installed; our exclusive
extended Circuits up to 66 and has available smaller Enclosures split neutral, and more. Many panelboards have the capability of
with no Subfeed option for added flexibility. mixing and matching breakers of different sizes and ratings – or
changing from main lug to main breaker, or adding subfeed
Subsequent steps in the P Series offer increased capacity and breakers without changing the box size. Other models accept
more design options: a wide range of fuse types, including Siemens exclusive
Vacu-Break® technology.
Table G-1 – Key Panelboard Features
RP1 P2 P3 P4 P5
Lighting and Appliance Applications(Pre 2008NEC) • • • • •
Power Panelboard Applications — • • • •
Convertible From Top Feed To Bottom Feed Or Vice Versa • — — — —
Change From Main Lug To Main Breaker Or
• — — — —
Add Subfeed Without Changing Enclosure Size 3
Space-Saving, Horizontally Mounted Main Breaker Up To 250 Amps Up To 250 Amps Up To 250 Amps • •
Short-Circuit Rating Label Giving Performance Level • • • • •
Standard Aluminum Ground Assembly • • • • •
Blank End-Walls Standard 1 • • • • •
Bolted Current-Carrying Parts • • • • •
Split Neutral • • • • •
Connection Accessible From Front • • • • •
Screw-Type Mechanical Lugs • • • • •
Time-Reducing Wing Nuts To Secure Interior Without Tools • • • • •
Main and Branch Devices Connected With
Case-Hardened Hardware • • • • •
Flush Lock, Concealed Door Hinges/Trim Screws • • • — —
Symmetrical Interior Mounting Studs
• • • • •
To Eliminate Upside-Down Mounting of Box
Interior Height Adjustment For Flush Applications • • • • •
Mix and Match Fusible Switch Circuit Breaker Capability — — — • •
Shallow Depth 5.75” 5.75” 7.75” 10.00” 12.75”
Accepts A Wide Range Of Fuse Types — — — • •
Accepts Vacu-Break Fusible Switch — — — • •
Accepts A Wide Range Of Circuit Breakers • • • • •
Accepts ACCESSTM Communications Tie-In 2 — • • • •
Optional Compression Lugs • • • • •
• Standard 2 Panelboards equipped with Siemens Sensitrip® 3 For Revised P1, only when Subfeed Space is selected,
1 KO’s available on P1 and P2 – 5.75” Deep x 20” Wide circuit breakers or Power Meters can be Interior Part Number ends with "T". When "N" is at
boxes and P3 7.75” deep X 24” wide boxes. integrated into Siemens ACCESS™ Electrical end there is no Subfeed Space available.
Monitoring System.
2
General Specifications
Class CTL Panelboards (when applicable) capable of connecting up (3) #10 max. wires. The #6 holes can
Class CTL panelboards incorporate physical features which, in accept up to (2) #12 max. wires. Copper ground assemblies
conjunction with the physical size, configuration, or other means (ECGK, ICGK) are rated for copper wire only and have the same
provided in Class CTL circuit breakers, are designed to prevent wiring capacity as the Al/Cu connectors.
the installation of more over current protective poles than the
number for which the device is designed and rated, per UL 67 Standard neutrals, like standard main lugs, are also rated for
and National Electrical Code (NEC) NFPA70. copper or aluminum wire. The neutral cross bar material follows
the selection bus. Copper neutral lugs are rated for copper cable
Service Entrance Equipment only and available as a price added option.
When a panelboard is used as service entrance equipment, it Lug Data
must be located near the point of entrance of building supply Space Required for Mounting of Double Panels
conductors. In a main lugs only panel, the number of breakers
or switches directly connected to the main bus must be limited Wall Wall
Standards
NEC: 2014 (where accepted)
Feed-thru lugs are mounted at the opposite end of the main bus
NEMA: PB1
from the main lugs or main breaker and are used to connect two
UL: 67, 50 and 50E. Listed by Underwriter’s Laboratories, Inc.,
or more panelboards to the incoming feeder. The feeder cables
under “Panelboards” File #E2269, and #E4016. Meets
are brought into Panelboard 1 and connected to the main lugs
Federal Specification W-P-115c.
or main breaker. Cables interconnecting the two panelboards are
connected to the feed-thru lugs in Panelboard1 and are carried
Wire Connectors
over the main lugs in Panelboard 2. This arrangement could be
Standard wire connectors in Siemens panels are suitable for copper
reversed with the main lugs located at the top and the feed-thru
or aluminum cables rated 60/75 degree. Copper main lugs are a
lugs at the bottom of the panel. Subfeed lugs are mounted
price-added option for most panel types and some Circuit Breakers
directly beside the main incoming lugs and are used to connect
(check with Siemens sales for availability). It should be noted that
two or more panelboards to the incoming feeder. The feeder
most copper lugs will only accept copper cables. Some applications,
cables are brought into Panelboard 1 and connected to the main
100% rated devices in particular, require that the cable and
lugs. Another set of cables that are the same size are connected
connectors be rated 90 degree but are sized to the 75 degree tables.
to the subfeed lugs of Panelboard 1 and are carried over the
main lugs of Panelboard 2.
Standard ground connectors are also suitable for copper or
aluminum wire. Ground connector assemblies (EGK, IGK) have
(7) 1/0 max. and (15) #6 max. connections. The 1/0 holes are Note: P1 panelboards do not have subfeed lugs available. If this
configuration is needed, move to a P2 or P3 panelboard.
3
General Specifications
Description P1 Revised P2 P3 P4 P5
Max. Voltage 480Y/277V AC Max. 600V AC Max. 600V AC Max. 600V AC Max. 600V AC Max.
600Y/347V AC 8 500V DC Max. 500V DC Max. 500V DC Max. 500V DC Max.
System 1-Phase, 2-wire 1-Phase, 2-wire 1-Phase, 2-wire 1-Phase, 3-wire 1-Phase, 3-wire
1-Phase, 3-wire 1-Phase, 3-wire 1-Phase, 3-wire 3-Phase, 4-wire 3-Phase, 4-wire
3-Phase, 3-wire 3-Phase, 3-wire 3-Phase, 4-wire 3-Phase, 3-wire 3-Phase, 3-wire
3-Phase, 4-wire 3-Phase, 4-wire 3-Phase, 3-wire
Mains
Main Lugs 125A-400A 125A-600A 250A-800A 400A-1200A 800A-1200A
Main Breaker 100A-400A 100A-600A 225A-600A 400A-800A 800A-1200A
Main Switch — — — — 200A-1200A
Circuits 18, 30, 42, 54, 66 18, 30, 42, 54, 66 — — —
78, 90 1
Branch Ratings 15-125A 15-400A 15-400A 15-800A MCCB 15-1200A MCCB
30-200A Fusible 30-1200 Fusible
B
Branch BL, BLH, HBL, BQD, BL, BLH, HBL, BQD, BQD6, BL, BLH, HBL, BQD, BQD6, All 15-600A MCCBs, All 15-1200A MCCBs,
Disconnect BQD6, BLE, BLEH, QJ25, QJH25, QJ2H5, QR25, QJ26, QJH26, QJ2H6, QR26, VL MG at 800A and 30-600A VB switches
Devices BLF2, BLHF2, HBLF2, BLFB, QRH25, HQR25, HQR2H5, ED2, QRH26, HQR26, HQR2H6, 30-200A VB switches and 400-1200A HCP
BLHFB, BAF2, BAFH2, ED4, HED4, ED6, BLE, BLEH, ED2, switches
HBAF2, BGL, BLF2, BLHF2, HBLF2, BLFB, ED4, HED4, ED6, BLHF,
NGB 7, HGB 7, LGB 7 BLHFB, BAF2, BAFH2, HBAF2, BAF2, BAFH2, HBAF2, BGL,
BGL, NGB, HGB, LGB NGB, HGB, LGB, NEB, HEB
Subfeed ED2, ED4, ED6, HED4, HED6, JD6, HJD6, JD6, HJD6, — —
Circuit QJ2, QJH2, QJ2H, QR2, JXD6, HJXD6, JXD6,
Breakers 2 3 QRH2, HQR2, HQR2H, FD6, FD6, HFD6, FD6, HFD6,
HFD6, FXD6, HFXD6 FXD6, HFXD6 FXD6, HFXD6
Enclosure 26, 32, 38, 44, 50, 56 26, 32, 38, 44, 50, 56, 56, 62, 68, 74, 80 60, 75, 90 60, 75, 90
Heights @250A (660, 813, 965, 62, 68, 74 (1422-2032) (1524, 1905, 2286) (1524, 1905, 2286)
Inches ± (mm) 1118, 1270, 1422) (660-1880)
56, 62, 68, 74 @400A
(1422, 1575, 1727, 1880)
Standard Fas-Latch ± 1 Piece Fas-Latch ± 1 Piece Fas-Latch ± 1 Piece Four Piece 4 Four Piece 4
Trims Surface or Flush Surface or Flush Surface or Flush Surface or Flush Surface or Flush
1 Functional pricing is based on circuits shown. 3 JD and FD breakers are mounted vertical. 6 A maximum of (6) QJ/QR breakers may be mounted
However, the panel can be figured with less circuits. Limitations apply. in a P3 panel and are twin mounted.
2 P1 can have max. 1 subfeed breaker when Subfeed 4 Trim ring provided for flush applications. 7 P1 panels with xGB breakers are limited to xGB
Space is available. P2 and P3 can have up to (2) FD 5 A maximum of (4) QJ/QR breakers may be mounted branch devices only. BL and BQD frames may not be
subfeed breakers. in a P2 Panel and are single mounted. mixed in this panel type.
8 Factory assembled P1 has capability of 600Y/347V
AC system when proper breakersare installed.
4
General Specifications
1 Per UL 67. 2 Fuses do not prohibit the use of Class H type fuse in switch.
5
Catalog Numbering System
Catalog Numbering System
Type of Panel
P1, P2, P3, P4, P5
Voltage and System*
C = 208Y/120 3Ø 4 W Wye AC - All R = 415/240 3Ø 4 W Wye AC - All
E = 480Y/277 3Ø 4 W Wye AC - All S = 440/250 3Ø 4 W Wye AC - All
D = 240 3Ø 3 W Delta AC - All L = 600/347 3Ø 4 W Wye AC - All
F = 480 3Ø 3 W Delta AC - All T = 230 3Ø 3 W Delta AC - All
G = 600 3Ø 3 W Delta AC - P2, P3, P4, P5 W = 380 3Ø 3 W Delta AC - P2, P3, P4, P5
I = 347 3Ø 3 W Delta AC P2, P3, P4, P5 1 = 24V DC 1-Pole Branches Only - P2, P3, P4, P5
B = 240/120 3Ø 4 W Delta BØ High Leg AC - P2, P3, P4, P5 2 = 24V DC 2-Pole Branches Only - P2, P3, P4, P5
Q = 240/120 3Ø 4 W Delta CØ High Leg AC - P2, P3, P4, P5 3 = 48V DC 1-Pole Branches Only - P2, P3, P4, P5
A = 120/240 1Ø 3 W Grounded Neutral AC - All P4 = 48V DC 2-Pole Branches Only - P2, P3, P4, P5
H = 120 1Ø 2 W Grounded Neutral AC - P2, P3, P4, P5 5 = 125V DC 1-Pole Branches Only - P2, P3, P4, P5
J = 240 1Ø 2 W No Neutral AC - All N = 125V DC 2-Pole Branches Only - P2, P3, P4, P5
Y = 125 1Ø 2 W Grounded Neutral AC - P2, P3, P4, P5 O = 125/250V DC 2-Pole Branches Only - P2, P3, P4, P5
Z = 500 2W DC - P2, P3, P4, P5 P = 125/250V DC 2 & 3-Pole Branches - P2, P3, P4, P5
K = 220/127 3Ø 4 W Wye AC - All U = 120V AC 3Ø3W - All
M = 380/220 3Ø 4 W Wye AC - All V = 240V 3Ø3W Grounded B Phase - P2, P3, P4, P5
*For any voltage system not listed, check with sales for availability.
Amperage
100–400A = P1 250 – 800A = P3
100–600A = P2 400 –1200A = P4, P5
Bus Bus Bus 2
Code Material Plating P1 1 P2 P3 P4 P5
A Temp rated Al. Tin-Plated • • • • •
B 750A/sq. in. Al. Tin-Plated • • • • •
C Temp rated Cu. Tin-Plated • n/a n/a n/a n/a
E Temp rated Cu. Silver-Plated n/a optional optional • •
F Temp rated Cu. Tin-Plated n/a • • • •
G 1000A/sq. in. Cu. Tin-Plated n/a • • optional optional
H 1000A/sq. in. Cu. Silver-Plated n/a optional optional • •
• Indicates default for this bus type.
Feed Location T = Top B = Bottom
Mounting
S = Surface
F = Flush. Flush trims extend 1 1/2" beyond the base box dimensions on P1, P2 and P3 and 2" on P4 and P5 panels.
2
Subfeed Space Indicator (for P1 only) T = Subfeed Space Included N = No Subfeed Space
6
SECTION 1
P1 Panelboards
Description Page
General Information 1-2 Side Gutter Wiring Space 1-6
Selection and Application 1-2 Branch Breaker Side Gutters 1-6
Application 1-3 – 1-6 Typical Catalog Numbers 1-7
Main Breaker Panel Size Selector 1-3 Main Lugs Only 1-7
Main Breaker Selection 1-3 Main Circuit Breaker 1-7
Main Lugs Size Selector 1-4 Standard Enclosures 1-7
Branch Circuit Breakers 1-4 Standard Modifications 1-8
Subfeed Breakers 1-5 Connector Modifications 1-9
Breaker Mounting Kits 1-5 Compression Lugs 1-9
Lug Kits 1-5 Enclosure Modifications 1-9
Main Breaker Gutter Dimensions 1-6 Remote Switch Modifications 1-9
Main Lug End Gutter Dimensions 1-6 Dimensions 1-10
Type P1 Panelboards
P1 panelboards are pre-engineered to accept the most common Voltage – 480Y/277 Vac max.
modifications without increasing box height. The enclosure size
is determined by the number of circuits as shown in the Main Lug Amperage – 400 amp max.
Table P1-5 or the Main Circuit Breaker Table P1-3. All P1 Revised
main lug or main breaker panelboards have space built-in to Short Circuit Rating – 200 KAIC max. symmetrical or equal
accept either feed-thru lugs equal to the panel rating, one sub- to the lowest rated device installed unless a series rating is
feed circuit breaker up to 250 amperes or a surge suppressor indicated. Panels with subfeed or feed-thru lugs without a
(TVSS) without increasing box height. (When ordered with main device, circuit breaker or fusible unit, are limited to a
sub-feed, space indicated by a “T” at end of nterior number). three-cycle rating. The three-cycle rating for the P1 panel is
limited to 22 KAIC. Note that the main device may be mounted
Note the following features, all found in the innovative P1 remote from the panel.
lighting panelboards:
• Symmetrical Interiors - No top or bottom! To change from Bussing – The P1 panel meets the majority of the markets
top to bottom (or vice-versa), simply invert the interior. The bussing requirements. The standard bussing is temperature
deadfront labeling is always right-side up. rated aluminum. The rating is per the requirements of UL 67–
• First in the Industry Ratings of 125 through 400A main lug and the standard for panelboards. All aluminum bussing is tin-plated.
main breaker. Field convertible from main lug to main breaker Optional bussing for the P1 panel is temperature rated copper.
and vice versa – with no increase in enclosure height. The copper bus option for this panel is tin-plated.
• Field adaptability of feed-thru lugs or subfeed circuit breaker
without increasing enclosure size. Weight – Approximate
• Neutral system is field upgradeable to 200% capacity – Total panelboard weight when filled with a normal quantity of
another industry first. breakers and accessories is about 3 lbs. (1 kg) per inch (54g per
• Five circuit sizes means only three box heights, regardless mm) of box height
of main configuration through 250 amp and an additional
four circuit versions-- and boxes available at 400 amps.
• Suitable for use as service entrance given compliance Table P1-1 – Box Material Gauge
with NEC. Width Height (inches) Gauge Steel
• Bonding provisions are shipped with each panel. 20” (250A) 26, 32, 38, 44, 50, 56 #16
• 240V and 480Y / 277V for versions utilize identical boxes (400A) 56, 62, 68, 74
and fronts.
Table P1-2 – Trim Material Gauge
Enclosure – Standard Type 1 enclosure is 20" wide x 5.75" 20” (250A) 26, 32, 38, 44, 50, 56 #14
deep. Box Height is determined only by the number of (400A) 56, 62, 68, 74
circuits, not by main lug or main circuit breaker. See chart
P1-5 for box height.
1-2
SECTION 1
Application
Type P1 Panelboards
T
Table P1-4 – Main Breaker Selection
Max. Ir (kA) at Main
Breaker / Breaker
Ampere rating Types 240 AC 480/277V AC Code Additional Trip Values
BL (STD) 10 – BL 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100
BLH 22 – BH 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100
100
HBL 65 – HB 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100
BQD 65 14 BQ 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100
NGB (STD) 100 25 NB3 50, 60, 70, 80, 90, 100, 110, 125
HGB 100 35 G23 50, 60, 70, 80, 90, 100, 110, 125
125 LGB 100 65 G33 50, 60, 70, 80, 90, 100, 110, 125
ED4 (STD) 65 25 E4 50, 60, 70, 80, 90, 100, 110, 125
HED4 42 42 H4 50, 60, 70, 80, 90, 100, 110, 125
QJ2 (STD) 10 – QJ 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
225 QJH2 22 – QH 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
QJ2H 42 – Q2 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
QR2 10 – QR 100, 110, 125, 150, 175, 200, 225
QRH2 25 – Q4 100, 110, 125, 150, 175, 200, 225
225
HQR2 65 – Q5 100, 110, 125, 150, 175, 200, 225
HQR2H 100 – Q6 100, 110, 125, 150, 175, 200, 225
FXD6 (STD) 65 35 FX 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250
FD6 65 35 FD 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250
250
HFD6 100 65 HF 70, 80, 90, 100, 150, 175, 200, 225, 250
HFXD6 100 65 H2 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250
JXD2 65 – JD 300, 400
JXD6 (STD) 65 35 JX 200, 225, 250, 300, 350, 400
400 JD6 65 35 J6 200, 225, 250, 300, 350, 400
HJD6 100 65 H6 200, 225, 250, 300, 350, 400
HJXD6 100 65 H5 200, 225, 250, 300, 350, 400
3 [*%LQWHULRUVDUHQRWDYDLODEOHDVQRQIHHGWKUXZLWKRXWVXEIHHGVSDFH
1-3
Application
Type P1 Panelboards
1-4
SECTION 1
Application
Type P1 Panelboards
Table P1-9 – Lug Kits Main or Feed-Thru Table P1-11 – 200% Neutral Lug Kits – 250A
Original Revised P1
Original P1 Revised P1
Amp Catalog Catalog
No. of Catalog Catalog
Rating Material Wire Range Service Number Number
Circuits Description Number Number
Al (1) #6 AWG- 1 Phase MLKA1 MLKA1A 18 2NLK18 Use 30 ckt kit
350 Kcmil (Cu or Al) 3 Phase MLKA3 MLKA3A
30 2 or 4 Branch Neutral Strips, 2NLK30 LNLK30A
Cu (1) #6 AWG- 1 Phase MLKC1 MLKC1A
250 42 1 Main Neutral Lug, Hardware 2NLK42 LNLK42A
350 Kcmil (Cu or Al) 3 Phase MLKC3 MLKC3A
1 Phase 4MLKA1 4MLKA1A 54, 66 — LNLK54A
AL (2) 1/0 - 250 Kcmil
or (1) #2 AWG 600 Kcmil 3 Phase 4MLKA3 4MLKA3A
400
Cu (2) 1/O - 4/0 1 Phase 4MLKC1 4MLKC1A Table P1-12 – 200% Neutral Lug Kits – 400A
or (1) 1/0 600 Kcmil 3 Phase 4MLKC3 4MLKC3A
(1) AL 1/0-750 Kcmil 1 Phase — 4MLKA1B Original P1 Revised P1
(2) AL/CU 250 kcmil No. of Catalog Catalog
400 AL max. Circuits Description Number Number
(max. (1) 600 Kcmil 3 Phase — 4MLKA1B 18 42NLK18 N/A
wire) 30 2 or 4 Branch Neutral Strips, 1 Main 42NLK30 42NLK30A
42 600 kcmil Neutral Lug, Hardware 42NLK42 42NLK42A
NOTES: Original P1 kits will not work with Revised P1 starters if the chart shows
different part numbers for each. 54, 66 — 42NLK54A
Revised P1 kits will not work with Original P1 starters if the chart shows different
part numbers for each.
1-5
Application
Type P1 Panelboards
1-6
SECTION 1
Typical Catalog Numbers
Type P1 Panelboards
Shown with Standard Mains, Top Fed and Surface Trim Replace fifth and sixth position in panelboard catalog number,
Catalog number is for aluminum main bus. For optional copper with alternate main breaker code. Use price adders from main
main bus change “A” in position 11 to “C”. breaker selection table. Horizontally mounted.
Panels are top feed, surface mounted. For bottom feed, change
“T” in position 12 to “B”. For flush mounting, change “S” in
position 13 to “F”.
Note: Original P1 was produced until mid 2014 and in July the revised P1 was introduced. All interior numbers that end with "T" or "N" are the new Revised interiors."T" at
end of catalog number indicates there is a Subfeed area available. "N" at end of catalog number indicates there is no Subfeed area available.
1-7
Standard Modifications
Type P1 Panelboards
• Panel skirts
• Gaskets between trim and box
Panel Modifications
• Main Bus • Bus mounted TVSS 1
Standard main bus is tin-plated aluminum. For copper main • Service entrance labeling /
bus, add from the table for each panel. Includes copper neutral • Grounding of Panelboards
cross bar. For copper neutral branch lugs, see miscellaneous. Ground Bars except for brazed to box are shipped with
/ /
• Compression lug for MLO 1 the panel interior factory mounted.
• Contactor mains - Mount in 23" enclosure ahead of panel. - Non-Insulated Equipment Ground Bar – Standard /
- Asco 920 through 225 amps 3 - Copper Non-Insulated Ground Bar
- Asco 911 through 150 amps 3 - Al Insulated Equipment Ground Bar
- Siemens LEN through 30 amps 3 - Cu Insulated Equipment Ground Bar
• Branch and main breaker accessories - Ground Bar Brazed to Box (recommended for painted boxes)
- Handle blocks • Shunt Trip on Main or Branch
- Handle locks BL2, BLH 2, HBL2, BQD 2, xGB 2 as branch use 1” unit space for
• Feed-thru lugs 1 shunt trip.
Cannot be used in conjunction with TVSS or subfeed
QJ2, QJ2H, QJH2, QR2, QRH2, HQR2, HQR2H, ED2, ED4, ED6, HED4, HED6,
breakers. Do not add height to the panel. HHED6, FD6, FXD6, HFD6, HFXD6, JXD6, JD6, HJD6, HJXD6
Connector
• Remote control switches – 480V AC max. mounted in a
Amp Rating Type Cu/Al Range
23” enclosure to be cable connected to the panel.
Al/Cu (1)–#6 AWG-
250 • Time Clocks – mounted in a 23” enclosure to be cable
Mechanical 350 kcmil
Cu (1)–#6 AWG- connected to the panel. Sangamo, Tork or Paragon time
Mechanical 350 kcmil clock can be supplied and mounted in panelboard cabinet.
Al/Cu (1)–#6 AWG-
Compression 350 kcmil Description
Al/Cu (1)–#3/0 AWG- Time Clock (1-or 2-Pole, Single or Double Throw Contacts;
400
AWG Mechanical 250 kcmil or 3-Pole Single Throw)
(1)–#3/0 AWG- 277V Maximum with Plain Dial
600 kcmil Options:
Cu (1)–#2-600 kcmil Astronomical Dial
Al/Cu (1) 400-600 An Omitting Device
Compression kcmil Reserve Power or Carryover ±
Note: Specify copper or aluminum cable. Space and Mounting Provisions Only
1-8
SECTION 1
Connector Modifications
Type P1 Panelboards
Compression Lugs
Table P1-20 – Lugs
//
Amp Breaker Compression Box Height
Style / Rating Type Connectors Addition
125
N/A (1) #4 AWG - 350 kcmil None
250
MLO (1) 250-600 kcmil or
400 N/A (2) #3/0 AWG - 250 kcmil None
(custom option)
125 ED4, ED6, HED4 (1) #12-1/0 AWG Box must go to 24” wide
QJ2, QJH2,
/ / QJ2H, QR2, (1) #6 AWG - 350 kcmil
225 Box must go to 24” wide for all breakers
Main Breaker QRH2, HQR2, HQR2H Cu or AI
/ (1) #6 AWG - 350 kcmil
250 FXD6, HFD6
// // Box must go to 24” wide for all breakers
Cu or AI
Note: Standard compression lugs used for
/ P1 panels are range taking lugs
/ and require a particular crimping tool (tool is Hubbel Versa Crimp VC6)
toNOTE: Standardthe
accommodate compression lugsfactory
range. Consult used for
forP1 panels are 200%
information. rangeneutral
taking not / / require
lugsavailable
and withacompression
particular crimping
lugs. xGBtool (tool iscannot
breakers Hubbel Versa Crimp VC6)
accommodate
to accommodate
compression lugs. the range. Consult factory for information. 200% neutral not available with compression lugs. NGB breakers cannot accommodate
compressions lugs /
Enclosure Modifications
NEMA-4–Water Tight, Dust Tight, Steel NEMA-4X For Type P1
Enclosure (Actual NEMA-4 enclosure is Water Tight, Dust Tight and Corrosion Resistant
larger than standard Type 1 enclosre. See (consult plant to verify actual enclosure size)
chart below for reference tomapproximate Table P1-22
actual size.)
Table P1-21 Enclosure – Stainless Steel Enclosure Fiberglass
Size (inches) (304SS is sandard) Size (inches)
Actual NEMA 4 Catalog
Standard Number H
H W D H
H W
W DD
Enclosure Size
Box Height B4X26
B 26 20 5.75 36 30 8
(in inches) H W D
B4X32 32 20 5.75 36 30 8
32 32 20 8
B4X38 38 20 5.75 48 36 12
38 42 30 8
B4X44 44 20 5.75 48 36 12
44 48 36 8
B4X50 50 20 5.75 60 36 12
56 60 36 10
B4X56 56 20 5.75 60 36 12
Note: Larger NEMA 4 enclosures are not available.
B4X62 62 20 5.75
B4X68 68 20 5.75
B4X74 74 20 5.75
± ± be specified.
Note: 316SS is available as an option – must
±
Remote Switch Modifications
Table P1-23 – Control Power Transformer Table P1-24 – Applications for a Remote Switch
Size VA Relay Switch Type Modification
0,1 50 920 Mounts in 23” relay cabinet as a main only
2 75 LEN 30A mounts in 23” relay cabinet as a main only
3 150
4 250
1-9
Dimensions
Type P1 Panelboards
Type 1 Box
Box is symmetrical
y
26 in., , 50 in.
[ 660 ] [1270]
, 74 in.
[1880]
Type 3R and
e 3R3R/12 Box
and 3R/12 Box
26 in., , 50 in.
[ 660 ] [1270]
, 74 in.
[1880]
1-10
SECTION 2
P2 Panelboards
Description Page
General Information 2-2 Typical Catalog Numbers 2-6
Selection and Application 2-2 Main Lugs Only 2-6
Application 2-3 – 2-5 Main Circuit Breakers 2-6
Panel Unit Space To Box Height Requirements 2-3 Standard Modifications 2-7
Main Lug Connectors 2-3 Box Size Additions For Optional Features 2-8
Branch Breaker Side Gutters 2-3 Connector Modifications 2-9 – 2-10
Main Breaker Selection 2-4 Compression Lugs 2-9
Subfeed Breakers 2-4 Enclosure Modification 2-10
Branch Circuit Breakers 2-5 Remote Switch Modifications 2-10
Branch Neutral Connections 2-5 Dimensions 2-11
Kits and Accessories 2-13
P2 Panelboards
Flexibility is the hallmark of the P2 panel. This panel offers a wide Main Lug / Main Breaker
array of factory-assembled options to meet virtually any lighting Enclosure – Standard Type 1 enclosure is 20" wide x 5.75"
panel application. The ability to mix breaker frames within the deep X. Box Height is determined by main device and unit space.
unit space up to 225 amps will also meet certain distribution See charts for box height.
panel requirements in a much smaller package. Bussing options
for the P2 vary from a typical temperature rating of 750 A/Si Voltage – 600 Vac Max.
aluminum, to 1000 A/Si copper. Standard bussing in the P2 250 Vdc Max.
panel is tin-plated. Silver-plated copper is offered as an option.
Integrated time clocks, bus mounted contactors (as mains or Amperage – 600 amp Max.
sub mains), split bus, and subfeed lugs (up to 400 amps) are
just a few of the options available in this unique panel. Short circuit rating – 200 KAIC Max. symmetrical or equal to the
lowest rated device installed unless a series rating is indicated.
Like a lighting panel, P2 is set up around 18, 30, 42, 54, 66, 78, Panels with subfeed or feed-thru lugs without a main device,
and 90 circuit configurations. It will also allow the user to circuit breaker or fusible unit, are limited to a three-cycle rating.
configure the panel to the smallest possible size. The P2 panel The three-cycle rating for the P2 panel is limited to 22 KAIC. Note
starts with 9" of unit space (18 circuits of 1" pole breakers). that the main device may be mounted remote from the panel.
Breakers mounted in unit space can be mixed and matched to
meet customer requirements. All 1" pole breakers (BL, BQD, ED Bussing – The P2 panel has more options to meet market
frames) are mounted in 3" or 6" pole increments. Breaker frames, requirements. The standard bussing is temperature rated
above 125 amps, are mounted in 6" single breaker mountings. aluminum. The rating is per the requirements of UL 67 – the
As an example of a minimum panel, (6) 20 amp 1-pole BL standard for panelboards. All aluminum bussing is tin-plated.
breakers (3" of unit space) and a 3-pole 225 amp QJ breaker Optional bussing for the P2 panel is: 750 A/Si aluminum,
(6" of unit space) equaling 9" of unit space can be configured in temperature rated copper, and 1000 A/Si copper. The copper
a P2 panel without any extra provisions or space required. FD 250 bus option for this panel is tin-plated.
amp and JD 400 amp breakers are mounted as subfeed breakers
outside of unit space. Weight – Approximate
Total panelboard weight when filled with a normal quantity
Another unique feature of the P2 panel is that blank unit space of breakers and accessories is about 3 lbs. (1 kg) per inch
can be added to allow for future expansions or modifications. Any (54g per mm) of box height.
expansions or modifications must be in 3" increments. BL, BQD,
Table P2-1 – Gauge Steel of Boxes
and ED frame breakers have 3" or 6" pole kits, and can be mixed Fronts, Surface and Flush
in unit space by these increments. Breakers of the same frame
Dimensions in inches (mm) Gauge Steel
can cross from one mounting to another if contiguous. QR frame
Width Height Box Front
breakers are mounted in 6" increments for two- and three pole, 20” 26 - 74 #16 #14
single mounted units. Changes in the unit spacelength for BL, (508) (660, 1880)
BQD, or ED frame breakers require an addition deadfront, center
strip kit. Check with sales or the factory for additional unit
space kits.
2-2
SECTION 2
Application
Type P2 Panelboards
P2 Panels With Standard Line Lugs. Unit Space (starting with 9" and adding 6" increments) “A” Dimension
“B”
Main Lugs Main Breakers
Dimen-
sion 125A 250A 400A 600A 125A 125A 125A 225A 225 250A 250A 250A 400A 400A 600A 600A
Box Horiz. Horiz. Vert. Horiz. Vert. Horiz. Vert. Vert. Vert. Vert. Vert. Vert.
Height BL,BQD,
xGB, ED CED ED QJ/QR QJ/QR FD FD CFD JD CJD LD CLD
26 9 — — — 9 — — — — — — — — — — —
32 15 9 — — 15 9 9 9 — — — — — -— — —
38 21 15 9 9 21 15 15 15 9 9 — — — — — —
44 27 21 15 15 27 21 21 21 15 15 9 — — — — —
50 33 27 21 21 33 27 27 27 21 21 15 9 9 — — —
56 39 33 27 27 39 33 33 33 27 27 21 15 15 — 9 —
62 45 39 33 33 45 39 39 39 33 33 27 21 21 9 15
68 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45
74 45 45 45 45 45 45 45 45 45 45 39 33 33 21 27 21
Note: When the number of circuits exceeds 54 on a 125 and 250A MLO and 125 and 250A main breaker application, add 6” to the box height.
Table P2-3 – Main Breaker (Fig. P2-1) Table P2-4 – Main Lug Connectors (Fig. P2-2)
Panel Amps Breaker Frames C D Panel Amps Standard Connectors C D
BL 5.75 8.00 125 (1) #14 - 2/0 6.62 8.19
100
BQD 5.125 8.00 250 (1) #6 AWG - 350 Kcmil 12.34 11.22
xGB, HGB, LGB 4.63 8.00 (1) #4 AWG - 600 Kcmil
125 400 14.00 13.09
ED 4.00 8.00 or (2) #6 - 250 Kcmil
225 QJ/QR 5.00 7.00 600 (2) #4 AWG - 500 Kcmil 14.00 11.00
250 FD 5.00 7.00
400 JD 14.00 25.00
600 LD 15.50 23.00
Fig. P2-3
Panel Width
20 in. (508 mm)
2-3
Application
Type P2 Panelboards
2-4
SECTION 2
Application
Type P2 Panelboards
11-Pole HED 4 15–30A Rated 65kA 35 through 100A Rated 25kA. NOTE: QJ/QR Breakers are single mounted in unit space and take 6" of unit space.
2 Two pole breaker is one phase and neutral. Three pole is two phase and neutral. Limited to (4) per panel max. xGB, BL, HBL, BLH and BQD breakers are mounted in
3 Based on 75 degree copper. common mountings in 3" or (6) pole increments. ED4, ED6, HED4 and HHED6
4 2-pole only (or) two outer poles of 3-pole breaker. breakers are mounted in common mountings in 3" or (6) pole increments."
2-5
Typical Catalog Numbers
Type P2 Panelboards
2-6
SECTION 2
Standard Modifications
Type P2 Panelboards
P2 Panel Options
Enclosures
• Extra gutter to sides or ends of the can • Aluminum trims and boxes, Type 1
• 24" wide boxes • NEMA 3R enclosures
• Hinged trims • NEMA 3R/12 enclosures
• Door-in-door trims • NEMA 4 enclosures
• Screw to the box trims • NEMA 4X enclosures
• Trim mounted devices (Devices mounted and wired • Special keyed locks
to the trim should also have hinged trim specified) • TEY • LL803
• Pilot lights • TEU1 • LL806
• Toggle switches • Cat 60 • Yale
• Push buttons • Gasketing trim to box
• Painted boxes • Meters (Contact application engineering for space
• Custom colors requirements)
• Increase gauge trims and boxes • Panel Skirts
• Stainless steel trims and boxes, Type 1
Panel Modifications
• Main Bus • Grounding of panelboards
Standard main bus is temperature rated tin-plated aluminum. Ground Bars, except brazed-to-box, are shipped with the
Bus options are 750 A/Si aluminum, tin-plated temperature panel interior factory mounted.
rated copper tin-plated standard – silver optional. 1000 A/Si • Non-Insulated Equipment Ground Bar – Standard
copper tin-plated standard – silver optional. Includes copper • Copper Non-Insulated Ground Bar
neutral cross bar. For copper neutral branch lugs, see • Al Insulated Equipment Ground Bar
miscellaneous. • Cu Insulated Equipment Ground Bar
• Split bus adds 6” to unit space • Ground Bar Brazed to Box (recommended for
• Compression lug for MLO painted boxes)
• Compression lugs on Main breaker (may require • Shunt Trip on Main or Branch
extra width or length on enclosure). BL, BLH, HBL, ED2, ED4, HED4, HED6, HHED6 uses 1” unit
• Contactor mains or submain space for shunt trip. All may be used on mains or subfeeds.
• Asco 920 through 225 amps. Adds 12” unit space as main,
15” unit space as submain. QJ2, QJ2H, QJH2, QR2, QRH2, HQR2, HQR2H, ED2, ED4, ED6, HED4,
• Asco 911 through 150 amps. Adds 21” unit space. HED6, HHED6, FXD6, HFD6, JXD6, JD6, HJD6, HJXD6
• Siemens LEN through 30 amps. Adds 12” unit space. • Remote control switches – 480V AC max. mounted in a
Makes box 10" deep. 23” enclosure to be cable connected to the panel.
• Control power transformers (contact engineering for extra • Time Clocks – mounted in a 23” enclosure to be cable
gutter requirements) connected to the panel. Sangamo, Tork or Paragon time
• Branch and main breaker accessories clock can be supplied and mounted in panelboard cabinet.
• Handle blocks
• Handle locks Description
• Aux. Contacts 1 Time Clock (1-or 2-Pole, Single or Double Throw Contacts;
• UVR 1 3-Pole Single Throw)
• Feed-thru lugs 277V Maximum with Plain Dial
• 200% neutral Options –
• Copper lugs, mechanical Astronomical Dial
• Bus mounted TVSS An Omitting Device
• Service entrance labeled Reserve Power or Carryover
Type P2 Panelboards are factory labeled suitable for use as Space and Mounting Provisions Only
service entrance equipment when NEC requirements are met.
A panelboard cannot have more than six main disconnects,
unless it is a lighting and appliance branch panelboard.
Lighting and appliance branch panelboards are limited to
two main disconnects. Factory installed and Field installable
Service Entrance Barrier kits are now available as required by
UL67. (In COMPAS, you must select Service Entrance Required.)
1 Accessories on 1" pole breakers (BL, BQD, ED) will take unit space
2-7
Standard Modifications
Type P2 Panelboards
Table P2-12 – Box Size Additions (In.) For Optional Features on MLO Applications
Main Lugs Main Breakers
125A 250A 400A 600A 125A 125A 125A 225A 225A 225A 250A 250A 400A 400A 600A 600A
Options Horiz. Horiz. Vert. Horiz. Vert. Horiz. Vert. Vert. JD CJD LD CLD
BL, BQD, QJ QJ
ED, xGB CED ED QR QR FD FD CFD
*Min. Box Size 26" 32" 38" 38" 26" 32" 32" 32" 38" 38" 44" 50" 50" 62" 56" 62"
200% Neutral 0 0 6 (all) 6 (all) 0 0 0 N/A 0 N/A 0 0 0 0 0 0
(lug type)
Std. Lugs 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
(100% Neut. PNL)
CU Lugs (100% 6 6 6 0 N/A N/A 0 N/A 0 N/A 0 0 0 0 0 0
Neut. PNL)
Comp Lugs 6 6 6 6 N/A N/A 0 N/A 0 N/A 0 0 0 0 0 0
(100% Neut. PNL)
Feed-thru
Standard Lugs 6 6 12 12 6 6 6 N/A 6 N/A 6 6 12 12 12 12
Feed-thru Cu Lugs 6 6 12 N/A N/A N/A 6 N/A 6 N/A 6 6 12 12 N/A N/A
Feed-thru
Comp Lugs 6 12 12 N/A N/A N/A 6 N/A 6 N/A 12 12 12 12 N/A N/A
Subfeed Standard
Lugs 0 6 6 N/A — — — — — — — — N/A — — —
Split Bus 6 6 6 6 6 6 6 N/A 6 N/A 6 6 6 6 6 6
(1) FD Subfeed N/A 12 12 12 N/A N/A N/A N/A N/A 12 12 12 12 12 12 12
(Horizontal Mtg.)
(2) FD Subfeed N/A 24 24 24 N/A N/A N/A N/A N/A 24 24 24 24 N/A N/A N/A
(Vertical Mtg.)
SPD 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12
Split bus is paired with feed-thru lugs by default. Feed-thru lugs are to feed the section after the split.
NOTE: N/A = OPTION NOT AVAILABLE
*Min. Box Size, corresponding to 9" of Unit Space.
2-8
SECTION 2
Connector Modifications
Type P2 Panelboards
Compression Lugs
Table P2-13 – Lugs
Style Amp Rating Breaker Type Compression Connectors Box Height Addition
125 N/A (1) #6 - 350 kcmil Al/Cu 6
250 N/A (1) #6 - 350 kcmil Al/Cu 6
(1) 400 - 600 kcmil Cu or
400 N/A 6
MLO (2) #6 - 350 kcmil Al/Cu
(2) #6 - 350 kcmil Cu or Cu/Al or
600 N/A 6
400 - 600 kcmil Al/Cu
ED4, ED6, HED4 Box must go to 24”W for CED6 breaker only
100 (1) #14-2/0 AWG Cu or Al
HHED6, CED61 Add 6” to box height for NØ
QJ2, QJH2, QJ2H,
225 QR2, QRH2, HQR2, (1) #6 - 350 kcmil Cu or Al Box must go to 24” wide
HQR2H
Box must go to 24” wide for all breakers
250 FXD6, HFD6, CFD6, (1) #6 - 350 kcmil Cu or Al Requires an additional 6.0” box height
Main Breaker
JD6, JXD6, HJD6,
400 CJD6, SJD6, SHJD6, (2) #1/0 AWG - 500 kcmil Cu or AL 9
SCJD6
LD6, LXD6, HLD6,
600 CJD6, SLD6, SHLD6, (2) #2/0 AWG - 500 kcmil Cu or Al 6
SCLD6
Alternate Lugs
Table P2-14 – Lugs
Style Amp Rating Breaker Type Compression Connectors Box Height Addition
(1) 250 - 350 kcmil or
MLO 400 N/A 6
(2) #3/0 AWG - 250 kcmil Cu or Al
JD6, JXD6, HJD6,
Main Breaker 400 CJD6, SJD6, SHJD6, (1) #3/0 AWG - 750 kcmill Cu or Al 6
SCJD6
2-9
Connector Modifications
Type P2 Panelboards
Enclosure Modifications
Enclosure Modification NEMA 4 for NEMA-4X For Type P2
Type P2 Water Tight and Dust Tight, Water Tight, Dust Tight and Corrosion Resistant
Steel Enclosure (consult plant to verify (consult plant to verify enclosure size)
enclosure size)
Table P2-16
Table P2-15 Enclosure - Stainless Steel Enclosure - Stainless Steel and
and Steel with Epoxy Coating Steel with Epoxy Coating 1
Standard Actual NEMA Box Height
Box Height Enclosure Size Inches H W D H W D
Inches H W D 26 26 36 30 8
32 32 20 8 32 32 36 30 8
38 42 30 8 38 38 48 36 12
44 48 36 8 44 44 48 36 12
56 60 36 10 50 50 20 5.75 60 36 12
56 56 60 36 12
Note: Larger NEMA 4 enclosures are not available.
62 62 — — —
68 68 — — —
74 74 — — —
1 Limited to the sizes shown.
.
Table P2-19 – Remote Control
Switch Modification
Description
Auxiliary Contacts (mounted not wired)
Ea. 2-Wire Control
2-10
SECTION 2
Dimensions
Type P2 Panelboards
Type 1 Box
Box is symmetrical
2-11
Dimensions
Type P2 Panelboards
2-12
2 SECTION
Kits and Accessories
Type P2 Panelboards
Another innovation from Siemens is the P3 panel. It is a smaller, Main Lug / Main Breaker
footprint distribution panel to fit a large number of applications Enclosure – Standard Type 1 enclosure is 24" wide x 7.75"
that require more (or larger) branch devices than the lighting deep. X Box Height is determined by main device and unit space.
panel class offer. This panel offers a wide array of factory- See charts for box height.
assembled options, and has the ability to mix breaker frames
in unit space up to 250 amps. Bussing options for the P3 vary Voltage – 600 Vac Max.
from the standard temperature aluminum to temperature rated 250 Vdc Max.
copper, 750 A/Si aluminum, and 1000A/Si copper designs. All bussing
Amperage – 800 amp Max.
in the P3 panel is tin-plated as a standard. Silver-plated copper is offered
as an option on a copper bus. Integrated time clocks, bus mounted Short Circuit Rating – 200 KAIC Max. symmetrical or equal
contactors, as mains or sub mains, split bus and subfeed lugs (up to to the lowest rated device installed unless a series rating is
400 amp) are just a few of the options of this unique panel. indicated. Panels with subfeed or feed-thru lugs without a
main device, circuit breaker or fusible unit, are limited to a
The P3 panel configurations, defined by the unit space, allow for a
three-cycle rating. The three-cycle rating for the P3 panel is
given amperage, main device, and box height. The P3 panel starts with
limited to 22 KAIC. Note that the main device may be mounted
a 56" high box. Breaker unit space can be mixed and matched to meet
remote from the panel.
customer requirements. All 1" pole breakers (BL, BQD, ED, xGB frames)
are mounted in 3" or 6" pole increments. Breakers frames, above 125 Bussing – The P3 panel has more options to meet market
amps, are mounted in 6" single or twin breaker mountings. As an requirements. The standard bussing is temperature rated
example panel, FD 250 amp and JD 400 amp breakers are mounted aluminum. The rating is per the requirements of UL 67 – the
as subfeed breakers outside of unit space. standard for panelboards. All aluminum bussing is tin-plated.
Optional bussing for the P3 panel is: 750 A/si aluminum,
Like other distribution panels, the P3 panel can have blank space added
temperature rated copper, and 1000 A/si copper. The copper
into the panel to allow for future expansions or modifications. Any
bus option for this panel is tin-plated.
expansions or modifications must be in 3" increments. BL, BQD and
ED frame breakers have 3" or 6-pole kits and can be mixed in unit space Weight – Approximate
by these increments. Breakers of the same frame can cross from one Total panelboard weight when filled with a normal quantity
mounting to another if contiguous. xGB frame breakers cannot be of breakers and accessories is about 5 lbs. (1 kg) per inch
mixed with other frame types. Any expansion or modification must (54g per mm) of box height.
be in 3" increments also. QJ/QR frame breakers are mounted in 6"
Table P3-1 – Gauge Steel of Boxes Fronts, Surface & Flush
increments for two -and three pole single and twin mounted units.
Changes in the unit space length for BL, BQD, xGB, or ED frame breakers Dimensions in inches (mm) Gauge Steel
require an additional deadfront center strip kit. Check with sales or the Width Height Box Front
factory for additional unit space kits. 24” 56 - 80 #16 #14
(610) (1422, 2032)
3-2
SECTION 3
Application
Type P3 Panelboards
Table P3-3 – Main Breaker Wire Bending (Fig. P3-1) Table P3-4 – Main Lug Wire Bending (Fig. P3-2)
Breaker Panel Amps Standard Connectors C D
Frame C E F 250 (1) #6 AWG - 350 kcmil 10.75 1 13.50
FD Horiz. 7.25 — 20.13 (2) #3/0 AWG - 250 kcmil
400 16.00 17.88
FD Vert. — 12.25 25.38 or (1) #3/0 600 kcmil
CFD — 13.63 31.38 600 (2) #3/0 AWG - 500 kcmil or 16.00 17.88
JD — 15.63 29.38 800 (2) #3/0 - 600 kcmil 16.00 17.88
CJD — 14.75 35.38 1 This lug is classified as removable.
LD — 14.75 29.38
CLD — 14.00 35.38
Fig. P3-3
Box depth = 7.75 in. (197 mm) Box depth = 7.75 in. (197 mm)
Box width = 24 in. (610 mm) Box width = 24 in. (610 mm)
QJ2,QJH2, QJ2,QJH2,
QJ2H,QR2, QJ2H,QR2,
QRH2,HQR2, QRH2,HQR2,
HQR2H HQR2H
Panel Width
24 in. (610 mm)
3-3
Application
Type P3 Panelboards
3-4
SECTION 3
Application
Type
B P3 Panelboards
Note: QJ/QR Breakers are twin mounted in unit spaceand take 6" of unit space. Limited to (6) per panel max. BL, HBL, BLH and BQD breakers are mounted incommon
mountings in 3" or (6) pole increments. ED2,ED4, ED6, HED4 and HHED6 breakers are mounted incommon mountings in 3" or (6) pole increments.
1 BGL 2-pole is (1) phase and neutral 3-pole is (2) phases and neutral.
2 2-pole only (or) two outer poles of 3-pole breaker.
3-5
Typical Catalog Numbers
Type P3 Panelboards
Table P3-11 – Main Lugs Only – shown with aluminum bus, top fed, and surface trims
208Y/120V 240/120V 120/240V or
250 Vdc Max
Maximum 3 Phase, 4 Wire 3 Phase, 4 Wire 1 Phase, 3 Wire
Panel Amp Rating Unit Space (inches) Catalog Number Catalog Number Catalog Number
27 P3C56ML250ATS P3B56ML250ATS P3A56ML250ATS
33 P3C62ML250ATS P3B62ML250ATS P3A62ML250ATS
250 39 P3C68ML250ATS P3B62ML250ATS P3A62ML250ATS
45 P3C74ML250ATS P3B74ML250ATS P3A74ML250ATS
51 P3C80ML250ATS P3B80ML250ATS P3A80ML250ATS
21 P3C56ML400ATS P3B56ML400ATS P3A56ML400ATS
27 P3C62ML400ATS P3B62ML400ATS P3A62ML400ATS
400 33 P3C68ML400ATS P3B68ML400ATS P3A68ML400ATS
39 P3C74ML400ATS P3B74ML400ATS P3A74ML400ATS
45 P3C80ML400ATS P3B80ML400ATS P3A80ML400ATS
21 P3C56ML600ATS P3B56ML600ATS P3A56ML600ATS
27 P3C62ML600ATS P3B62ML600ATS P3A62ML600ATS
600 33 P3C68ML600ATS P3B68ML600ATS P3A68ML600ATS
39 P3C74ML600ATS P3B74ML600ATS P3A74ML600ATS
45 P3C80ML600ATS P3B80ML600ATS P3A80ML600ATS
21 P3C56ML800ATS P3B56ML800ATS P3A56ML800ATS
27 P3C62ML800ATS P3B62ML800ATS P3A62ML800ATS
800 33 P3C68ML800ATS P3B68ML800ATS P3A68ML800ATS
39 P3C74ML800ATS P3B74ML800ATS P3A74ML800ATS
45 P3C80ML800ATS P3B80ML800ATS P3A80ML800ATS
240V 408Y/277V 480V 1
Maximum 3 Phase, 3 Wire 3 Phase, 4 Wire 3 Phase, 3 Wire
Panel Amp Rating Unit Space (inches) Catalog Number Catalog Number Catalog Number
27 P3D56ML250ATS P3E56ML250ATS P3F56ML250ATS
33 P3D62ML250ATS P3E62ML250ATS P3F62ML250ATS
250 39 P3D68ML250ATS P3E68ML250ATS P3F68ML250ATS
45 P3D74ML250ATS P3E74ML250ATS P3F74ML250ATS
51 P3D80ML250ATS P3E80ML250ATS P3F80ML250ATS
21 P3D56ML400ATS P3E56ML400ATS P3F56ML400ATS
27 P3D62ML400ATS P3E62ML400ATS P3F62ML400ATS
400 33 P3D68ML400ATS P3E68ML400ATS P3F68ML400ATS
39 P3D74ML400ATS P3E74ML400ATS P3F74ML400ATS
45 P3D80ML400ATS P3E80ML400ATS P3F80ML400ATS
21 P3D56ML600ATS P3E56ML600ATS P3F56ML600ATS
27 P3D62ML600ATS P3E62ML600ATS P3F62ML600ATS
600 33 P3D68ML600ATS P3E68ML600ATS P3F68ML600ATS
39 P3D74ML600ATS P3E74ML600ATS P3F74ML600ATS
45 P3D80ML600ATS P3E80ML600ATS P3F80ML600ATS
21 P3D56ML800ATS P3E56ML800ATS P3F56ML800ATS
27 P3D62ML800ATS P3E62ML800ATS P3F62ML800ATS
800 33 P3D68ML800ATS P3E68ML800ATS P3F68ML800ATS
39 P3D74ML800ATS P3E74ML800ATS P3F74ML800ATS
45 P3D80ML800ATS P3E80ML800ATS P3F80ML800ATS
1 For 600V, change “F” in position 3 to “G.” Price only branch breakers with 600V ratings.
3-6
SECTION 3
Typical Catalog Numbers
Type P3 Panelboards
Table P3-12 – Main Circuit Breaker – shown with aluminum bus, top fed and surface trims.
Maximum Unit 208Y/120V 240/120V 120/240V or 250V dc Max
Panel Space 3 Phase, 4 Wire 3 Phase, 4 Wire 1 Phase, 3 Wire
Amp Rating (inches) Catalog Number Catalog Number Catalog Number
21 P3C56FD250ATS P3B56FD250ATS P3A56FD250ATS
27 P3C62FD250ATS P3B62FD250ATS P3A62FD250ATS
250 33 P3C68FD250ATS P3B68FD250ATS P3A68FD250ATS
39 P3C74FD250ATS P3B74FD250ATS P3A74FD250ATS
45 P3C80FD250ATS P3B80FD250ATS P3A80FD250ATS
9 P3C56JD400ATS P3B56JD400ATS P3A56JD400ATS
15 P3C62JD400ATS P3B62JD400ATS P3A62JD400ATS
400 21 P3C68JD400ATS P3B68JD400ATS P3A68JD400ATS
27 P3C74JD400ATS P3B74JD400ATS P3A74JD400ATS
33 P3C80JD400ATS P3B80JD400ATS P3A80JD400ATS
9 P3C56LD600ATS P3B56LD600ATS P3A56LD600ATS
15 P3C62LD600ATS P3B62LD600ATS P3A62LD600ATS
600 21 P3C68LD600ATS P3B68LD600ATS P3A68LD600ATS
27 P3C74LD600ATS P3B74LD600ATS P3A74LD600ATS
33 P3C80LD600ATS P3B80LD600ATS P3A80LD600ATS
Maximum Unit 240V 408Y/277V 480V 1
Panel Space 3 Phase, 3 Wire 3 Phase, 4 Wire 3 Phase, 3 Wire
Amp Rating (inches) Catalog Number Catalog Number Catalog Number
3-7
Standard Modifications
Type P3 Panelboards
3-8
SECTION 3
Standard Modifications
Type P3 Panelboards
Subfeed Feed-thru FD1 JD1 FD2 200% Min. Box Unit Space
Amps Incoming Lugs Lugs Subfeed Subfeed Subfeeds Neutral Size (in.) (in.)
• — — — • 56 27
Main Lug Only — — • — — • 56 15
— — — • • 56 9
• — — — • 56 21
Main Lugs w/Subfeed Lugs • — • — — • 56 21
250 — — — • • 62 9
— • — — — • 56 21
Main Breaker (Horiz. FD)
— — • — — • 56 9
Main Breaker (Vert. FD) None Std. • — — — • 56 15
• — — — • 56 9
Main Breaker (CFD) None Std.
— • — — • 68 9
• — — — — • 56 21
— • — — — • 56 15
Main Lug Only — — • — — • 56 9
— — — • — • 56 9
— — — — • • 62 9
— — — — • 56 9
• — — — • 62 9
400 2 3 Main Breaker (JD) None Std. — • — — • 68 9
— — • — • 68 9
— — — • • 74 9
— — — — • 62 9
• — — — • 74 9
Main Breaker (CJD) None Std — • — — • 74 9
— — • — • 74 9
— — — • • 80 9
— — — — • 56 21
• — — — • 56 15
Main Lug Only — — • — — • 56 9
— — • — — 56 9
— — — • • 62 9
— — — — • 56 9
• — — — • 62 9
600 2 3 Main Breaker LD — — • — — • 68 9
— — • — — 68 9
— — — • • 74 9
— — — — • 62 9
• — — — • 68 9
Main Breaker CLD — — • — — • 74 9
— — • — — 74 9
— — — • • 80 9
— — — — • 56 21
• — — — • 56 9
800 2 3 Main Lug Only — — • — — • 56 9
— — • — — 56 9
— — — • • 62 9
3-9
Connector Modifications
Type P3 Panelboards
Compression Lugs
Table P3-14 – Lugs
Style Amp Rating Breaker Type Compression Connectors Box Height Addition
250 N/A (1)#6 AWG - 350 Kcmil —
MLO 400 N/A (1) 250 - 500 Kcmil or —
(2)# 1/0 AWG - 250 Kcmil —
600 N/A (2)#3/0 AWG - 500 Kcmil —
800 N/A (2) 400-750 Kcmil Al only —
250 FXD6, HFD6, CFD6 (1)#6 AWG - 350 Kcmil Cu or Al CFD6 requires an additional 6.0” box height
Main 400 JD6, JXD6, HJD6, (2)#1/0 AWG - 500 Kcmil Cu or Al 6
Breaker CJD6, SJD6, SHJD6, SCJD6
600 LD6, LXD6, HLD6, CJD6, (2)#2/0 AWG - 500 Kcmil Cu or Al 6
SLD6, SHLD6, SCLD6
Enclosure Modifications
NEMA-4 For Type P3 NEMA-4X For Type P3
Water Tight, Dust Tight, Steel Enclosure Water Tight, Dust Tight and Corrosion Resistant
(consult plant for actual enclosure size) (consult plant for actual enclosure size)
Table P3-16 Table P3-17
Box Height Enclosure Size Enclosure - Stainless Steel Enclosure - Fiberglass
Inches H W D Box Height and Steel with Epoxy Coating Size (inches)
56 60 36 8 Inches H W D H W D
62 66 36 8 56 60 36 12 60 36 12
68 72 36 8 62 66 36 8 66 36 8
74 78 36 8 68 72 36 8 72 36 8
80 84 36 8 74 78 36 8 78 36 8
80 84 36 8 84 36 8
3-10
SECTION 3
Dimensions
Type P3 Panelboards
Type 1 Box
Box is symmetrical
햲
a"
a"
햲
a"
햲
햲
a"
햳
햲"
a
a"
햲
3-11
Dimensions
Type P3 Panelboards
Standard
A B C Box Size
47.97 42.00 40.75 56H 24W 7.75D
53.97 48.00 46.75 62H 24W 7.75D
59.97 54.00 52.75 68H 24W 7.75D
65.97 60.00 58.75 74H 24W 7.75D
71.97 66.00 64.75 80H 24W 7.75D
3-12
2
SECTION
Kits and Accessories
Type P3 Panelboards
3-13
Notes
SECTION 4
P4 Panelboards
Description Page
General Information 4-2 Branch Breaker Side Gutter 4-7
Selection and Application 4-2 Typical Catalog Numbers 4-8
Applications 4-3 – 4-6 Main Lugs Only 4-8
Main Breaker Selection 4-3 Main Circuit Breakers Only 4-8
Main Switch Connectors 4-3 Modifications and Additions 4-9
Enclosure Selection 4-3 Connector Modifications 4-10
Main Breaker Unit Space Dimensions 4-3
Compression Lugs 4-10
Main Lugs Only Unit Space Dimensions 4-4
Branch Switch Unit Space 4-4 Alternate Lugs 4-10
Branch Circuit Breakers 4-5 – 4-6 Dimensions 4-11
Branch Breaker Unit Space 4-7 Kits and Accessories 4-12 – 4-13
Type P4 Panelboards
The P4 panel is a medium sized footprint distribution panel to Bussing – The P4 panel has more options to meet market
fit a large number of applications that require more or larger requirements. The standard bussing is temperature rated
branch devices and higher amp ratings than the lighting panel aluminum. The rating is per the requirements of UL 67 – the
class offers. Even with the increased capacity, this panel is a standard for panelboards. All aluminum bussing is tin-plated.
space saver with its 32" width and 10" depth. The P4 panel offers Optional bussing for the P4 panel is: 750 A/Si aluminum,
a wide array of factory-assembled options and has the ability to temperature rated copper, and 1000 A/Si copper. The copper
mix breaker frames in unit space up to 800 amps and fusible bus option for this panel is silver-plated.
switches up to 200 amps. Bussing options for the P4 vary from
the standard temperature rated aluminum to temperature rated Weight – Approximate
copper and 750A/Si aluminum and 1000A/Si copper designs. Total panelboard weight when filled with a normal quantity of
All aluminum bussing in the P4 panel is tin-plated as a standard. breakers and accessories is about 8 lbs. (1 kg) per inch (54g per
Silver-plated is offered as the default for copper bus and tin as an mm) of box height.
option. Integrated time clocks, bus mounted contactors as mains
or submains, split bus and subfeed lugs (up to 600 amp) are just Table P4-1 – Main Lugs 1
a few of the options of this flexible panel. Ampere Rating Connectors Suitable for Copper or Aluminum
400 (1) - #3/0 AWG-600 Kcmil
The 3 panel configurations defined by the unit space allowed
(2) - #3/0 AWG-250 Kcmil
for a given amperage, main device and box height. The P4 panel
600 (2) - #3/0 AWG-600 Kcmil
starts with a 60" high box. All of the branch devices are unit 800 (3) - #3/0 AWG-600 Kcmil
space mounted. Breakers and switches can be mixed and 1000 (4) - #3/0 AWG-600 Kcmil
matched to meet customer requirements. 1200 (4) - #3/0 AWG-600 Kcmil
Main Lug / Main Breaker / Main Switch 1 Alternate lugs for 750 kcmil cable are available, but result in significant loss of
branch unit mounting space. Consult Siemens.
Enclosure – Standard Type 1 enclosure is 32" wide x 10" deep. Table P4-2 – Gauge Steel of Boxes
X Box Height is determined by main device and unit space. See Fronts, Surface and Flush
charts for box height.
Dimensions in inches (mm) Gauge Steel
Voltage – 600 Vac Max. Width Height Box Fronts
250 Vdc Max #161 #14 (1 piece trim)
32” 60 - 75 - 90 #14 (4 piece trim)
Amperage – 400-800 amp main breaker or 400-1200 amp (813) (1524, 1905, #12 #12 (1 piece trim, door in door)
2286) #10 #10 (1 piece door trim in)
Main Lug Only #16 #16 (4 piece trim)
Short Circuit Rating – 200 KAIC Max. symmetrical or equal to 1 Box has 16 gauge side panels, 14 gauge backplates and 12 gauge back support.
the lowest rated device installed unless a series rating is indicated.
Panels with subfeed or feed-thru lugs without a main device,
circuit breaker or fusible unit, are limited to a three-cycle rating.
The three-cycle rating for the P4 panel is limited to 42 KAIC. Note
that the main device may be mounted remote from the panel.
4-2
SECTION 4
Application
Type P4 Panelboards
1 Standard trim is four piece without door. Surface or flush one piece trim is available for 32 in. (813 mm) wide
circuit breaker panels.
4-3
Application
Type P4 Panelboards
Table P4-6 – Main Lugs Location Reference (Fig. P4-2) Fig. P4-2
Dimensions in inches (mm)
Main Lug Neutral
400A 600A 800A 1000A 1200A 400-600A 800-1200A
Lugs A B C D E F G
Standard 16.500 16.750 15.969 15.969 15.969 13.125 13.125
(419) (425) (406) (406) (406) (333) (333)
Oversize 16.500 21.750 25.969 25.969 25.969 18.125 23.125
(419) (552) (660) (660) (660) (460) (587)
Crimp 19.187 18.250 18.687 18.250 18.250 15.937 15.937
(487) (464) (475) (464) (464) (405) (405)
Standard 16.750 15.969 — — — 13.125 13.125
w/Subfeed (425) (406) (333) (333)
Standard 16.500 16.750 — — — 13.125 13.125
w/Feed-thru (419) (425 ) (333) (333)
4-4
SECTION 4
Application
Type P4 Panelboards
4-5
Application
Type P4 Panelboards
4-6
SECTION 4
Application
Type P4 Panelboards
4-7
Application
Type P4 Panelboards
Table P4-13 – Main Lugs Only – shown with aluminum bus, top fed, and surface trims
Max. 208Y/120V 240/120V 120/240V or 240V 480Y/277V 480V 1
Panel Unit 250 Vdc Max
Amp Space 3 Phase, 4 Wire 3 Phase, 4 Wire 1 Phase, 3 Wire 3 Phase, 3 Wire 3 Phase, 4 Wire 3 Phase, 3 Wire
Rating (inches) Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
30 P4C60ML400ATS P4B60ML400ATS P4A60ML400ATS P4D60ML400ATS P4E60ML400ATS P4F60ML400ATS
400 45 P4C75ML400ATS P4B75ML400ATS P4A75ML400ATS P4D75ML400ATS P4E75ML400ATS P4F75ML400ATS
60 P4C90ML400ATS P4B90ML400ATS P4A90ML400ATS P4D90ML400ATS P4E90ML400ATS P4F90ML400ATS
30 P4C60ML600ATS P4B60ML600ATS P4A60ML600ATS P4D60ML600ATS P4E60ML600ATS P4F60ML600ATS
600 45 P4C75ML600ATS P4B75ML600ATS P4A75ML600ATS P4D75ML600ATS P4E75ML600ATS P4F75ML600ATS
60 P4C90ML600ATS P4B90ML600ATS P4A90ML600ATS P4D90ML600ATS P4E90ML600ATS P4F90ML600ATS
30 P4C60ML800ATS P4B60ML800ATS P4A60ML800ATS P4D60ML800ATS P4E60ML800ATS P4F60ML800ATS
800 45 P4C75ML800ATS P4B75ML800ATS P4A75ML800ATS P4D75ML800ATS P4E75ML800ATS P4F75ML800ATS
60 P4C90ML800ATS P4B90ML800ATS P4A90ML800ATS P4D90ML800ATS P4E90ML800ATS P4F90ML800ATS
30 P4C60ML101ATS P4B60ML101ATS P4A60ML101ATS P4D60ML101ATS P4E60ML101ATS P4F60ML101ATS
1000 45 P4C75ML101ATS P4B75ML101ATS P4A75ML101ATS P4D75ML101ATS P4E75ML101ATS P4F75ML101ATS
60 P4C90ML101ATS P4B90ML101ATS P4A90ML101ATS P4D90ML101ATS P4E90ML101ATS P4F90ML101ATS
30 P4C60ML120ATS P4B60ML120ATS P4A60ML120ATS P4D60ML120ATS P4E60ML120ATS P4F60ML120ATS
1200 45 P4C75ML120ATS P4B75ML120ATS P4A75ML120ATS P4D75ML120ATS P4E75ML120ATS P4F75ML120ATS
60 P4C90ML120ATS P4B90ML120ATS P4A90ML120ATS P4D90ML120ATS P4E90ML120ATS P4F90ML120ATS
Table P4-14 – Main Circuit Breakers Only – shown with standard mains, aluminum bus, top fed, and surface trims
Max. 208Y/120V 240/120V 120/240V or 240V 480Y/277V 480V 1
Panel Unit 250 Vdc Max
Amp Space 3 Phase, 4 Wire 3 Phase, 4 Wire 1 Phase, 3 Wire 3 Phase, 3 Wire 3 Phase, 4 Wire 3 Phase, 3 Wire
Rating (inches) Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
21.25 P4C60JX400ATS P4B60JX400ATS P4A60JX400ATS P4D60JX400ATS P4E60JX400ATS P4F60JX400ATS
400 36.25 P4C75JX400ATS P4B75JX400ATS P4A75JX400ATS P4D75JX400ATS P4E75JX400ATS P4F75JX400ATS
51.25 P4C90JX400ATS P4B90JX400ATS P4A90JX400ATS P4D90JX400ATS P4E90JX400ATS P4F90JX400ATS
21.25 P4C60LX600ATS P4B60LX600ATS P4A60LX600ATS P4D60LX600ATS P4E60LX600ATS P4F60LX600ATS
600 36.25 P4C75LX600ATS P4B75LX600ATS P4A75LX600ATS P4D75LX600ATS P4E75LX600ATS P4F75LX600ATS
51.25 P4C90LX600ATS P4B90LX600ATS P4A90LX600ATS P4D90LX600ATS P4E90LX600ATS P4F90LX600ATS
21.25 P4C60M1800ATS P4B60M1800ATS P4A60M1800ATS P4D60M1800ATS P4E60M1800ATS P4F60M1800ATS
800 36.25 P4C75M1800ATS P4B75M1800ATS P4A75M1800ATS P4D75M1800ATS P4E75M1800ATS P4F75M1800ATS
51.25 P4C90M1800ATS P4B90M1800ATS P4A90M1800ATS P4D90M1800ATS P4E90M1800ATS P4F90M1800ATS
1 For 600V, change “F” in position 3 to “G.”
4-8
SECTION 4
Modifications and Additions
P4 Panelboards
1 Available in 90” high enclosure only. Unit space is 4 Shunt Trip on 100A frame breakers increases
42 1/2” with Test and Monitor Panel; 45” without mounting height to 6.25” for twin mounting.
Test and Monitor Panel. 5 The 600A, 100% rated breaker requires the use of
2 Not available on Sensitrip III. an 800A frame breaker.
3 For required unit space, consult local sales office.
4-9
Connector Modifications
P4 Panelboards
Lug Modifications
Table P4-15 – Compression Lugs
Amp Breaker Compression Box Height
Style Rating Type Connectors Addition
250 N/A (1)#6 AWG - 350 kcmil —
(1) 250 - 500 kcmil or —
400 N/A
MLO (2)# 1/0 AWG - 250 kcmil —
600 N/A (2)#3/0 AWG - 500 kcmil —
800 N/A (2) 400-750 kcmil Cu only —
CFD6 requires an
250 FXD6, HFD6, CFD6 (1)#6 AWG - 350 kcmil Cu or Al
additional 6.0" box height
Main 400 JD6, JXD6, HJD6, CJD6, SJD6, SHJD6, SCJD6 (2)#1/0 AWG - 500 kcmil Cu or Al —
Breaker
LD6, LXD6, HLD6, CJD6,
600 (2)#2/0 AWG - 500 kcmil Cu or Al —
SLD6, SHLD6, SCLD6
4-10
SECTION 4
Dimensions
Type P4 Panelboards
Type 1 Box
Box is symmetrical
30.0 in.
[ 254 ]
4-11
Kits and Accessories
Type P4 Panelboards
4-12
4 SECTION
Kits and Accessories
Type P4 Panelboards
4-13
Notes
SECTION 5
P5 Panelboards
Description Page Typical Catalog Numbers 5-9
General Information 5-2 Main Lugs Only 5-9
Selection and Application 5-2 Main Circuit Breakers Only 5-9
Application 5-3 – 5-8 Main Fusible Switch 5-9
Main Breaker Selection 5-3 Modifications and Additions 5-10 – 5-12
Enclosure Selection 5-4 Motor Starters 5-11 – 5-12
Main Breaker and Main Switch 5-3 – 5-4 Connector Modifications 5-12
Main Switch Connectors 5-4 Compression Lugs 5-12
Main Lugs Only Unit Space 5-5 Alternate Lugs 5-12
Branch Switch Unit Space 5-5 Dimensions 5-13
Branch Circuit Breakers 5-6 Kits and Accessories 5-14 – 5-15
Branch Breaker Unit Space 5-7
Branch Breaker Side Gutters 5-8
Type P5 Panelboards
The P5 panel is the largest distribution panel in the Siemens The three-cycle rating for the P5 panel is limited to 42 KAIC. Note
panel family. Even so, the P5 panel is still a space saver with that the main device may be mounted remote from the panel.
it’s 38” width and 12.75” depth. With even higher main ratings
to fit the application that require more or larger branch devices. Bussing – The P5 panel has more options to meet market
This panel offers a wide array of factory-assembled options and requirements. The standard bussing is temperature rated
enables users to mix breaker frames in unit space up to 1200 aluminum. The rating is per the requirements of UL 67 – the
amps and fusible switches up to 1200 amps. Bussing options for standard for panelboards. All aluminum bussing is tin-plated.
the P5 vary from the standard temperature rated aluminum to Optional bussing for the P5 panel is: 750 A/Si aluminum,
temperature rated copper and 750 A/Si aluminum and 1000A/Si temperature rated copper, and 1000 A/Si copper. The copper
copper designs. All aluminum bussing in the P5 panel is tin- bus option for this panel is tin-plated.
plated as a standard. All copper bus is silver plated. Integrated Weight – Approximate
time clocks, bus mounted contactors as mains or submains, split Total panelboard weight when filled with a normal quantity of
bus and subfeed lugs (up to 600 amps) are just a few of the breakers and accessories is about 10 lbs. (1 kg) per inch (54g
options of this flexible panel. per mm) of box height.
P5 panel configurations are defined by the unit space allowed Table P5-1 – Main Lugs 1
for a given amperage, main device and box height. The P5 panel
Ampere Connectors Suitable for
starts with a 60” high box. All branch devices are unit space Rating Copper or Aluminum
mounted. Breakers and switches can be mixed and matched to 400 (1) 250 - 500 Kcmil
meet customer requirements. 600 (2) #3/0 - 500 Kcmil
800 (3) #3/0 AWG-500 Kcmil
Main Lug / Main Breaker / Main Switch 1000 (4) #3/0 AWG-500 Kcmil
1200 (4) #3/0 AWB-500 Kcmil
Enclosure – Standard Type 1 enclosure is 38" wide x 12.75"
1 Alternate lugs for 750 Kcmil cable are available, but result in significant loss of
deep. X Box Height is determined by main device and unit
branch unit mounting space. Consult Siemens.
space. See charts for box height.
Table P5-2 – Gauge Steel of Boxes Fronts, Surface and Flush
Voltage – 600 Vac Max.
Dimensions in inches (mm) Gauge Steel
250 Vdc Max. Width Height Box Fronts
Amperage – 400-1200 amp Main breaker, 400-1200 amp MLO 60 - 75 - 90 #16 1 #14 (1 piece trim)
(1524, 1905, 2286) #14 (4 piece trim)
200-1200 amp Main switch. 60 - 75 - 90 #14 #12 (1 piece trim)
38” (1524, 1905, 2286) & door in door
Short Circuit Rating – 200 KAIC Max. symmetrical or equal to (965) #10 (1 piece &
the lowest rated device installed unless a series rating is indicated. door in door)
Panels with subfeed or feed-thru lugs without a main device, 60 - 75 - 90 #14 #16 (4 piece, top
(1524, 1905, 2286) and bottom over)
circuit breaker or fusible unit, are limited to a three-cycle rating. #10 (4 piece, side/
gutter cover)
1 16 gauge side panels, 12 gauge back support, 14 gauge back panels.
5-3
Application
Type P5 Panelboards
Fig. P5-1
Table P5-4 – Enclosure Selection 1
Enclosure Dimension Available Unit Space in inches (mm)
in Inches (mm) Dimension “C” in Fig. P5-1
H W D Main Lug only Main Breaker Main Switch
Type 1 Type 3R/12 800 / 1200A 800 / 1200A 800 / 1200A
60 (1524) 38 (965) 12.75 (324) 14.25 (362) 30 (762) 20 (508) 13.75 (349)
75 (1905) 38 (965) 12.75 (324) 14.25 (362) 45 (1143) 35 (889) 28.75 (730)
90 (2286) 38 (965) 12.75 (324) 14.25 (362) 60 (1524) 50 (1270) 43.75 (1111)
1 Standard trim is four piece without door. Surface or flush one piece trim is
available for 32 in. (813 mm) wide circuit breaker panels.
5-4
SECTION 5
Application
Type P5 Panelboards
Table P5-8 – Main Lugs Only Unit Space (Fig. P5-2) Fig. P5-2
Dimensions in inches (mm)
Main Lug Neutral
400A 600A 800A 1000A 1200A 800A
Lugs A B C D E G
Standard 16.500 (419) 16.750 (425) 15.969 (406) 15.969 (406) 15.969 (406) 13.125 (333)
Oversize 16.500 (419) 21.750 (552) 25.969 (660) 25.969 (660) 25.969 (660) 23.125 (587)
Crimp 19.187 (487) 18.250 (484) 18.687 (475) 18.250 (464) 18.250 (464) 15.937 (405)
Standard with
16.750 (425) 15.969 (406) — — — 13.125 (333)
Subfeed
Standard with — — 13.125 (333)
16.500 (419) 16.750 (425) —
Feed-thru
5-5
Application
Type P5 Panelboards
Table P5-10 – Branch Circuit Breakers
Unit Space
Breaker Requirements Maximum Interruption Rating (KAIC) Volts AC
Frame Trip Breaker Frame Trip in Inches 480Y/ 600Y/
Rating Type Family Type Poles Amperage Single Twin 120 240 277 480 347 600
100 Thermal General BL 1, 2, 3 15-60, 70, 80, 90, 100, 110, 125 — 3.752 3 10,000 10,000 — — — —
Magnetic Appli- BLR 2 15, 20, 30, 40, 50, 60, 70, 80, 90, — 3.752 3 10,000 10,000 — — — —
cation 100
BLH 1, 2, 3 15-60, 70, 80, 90, 100, 110, 125 — 3.752 3 22,000 22,000 — — — —
HBL 1, 2, 3 15-60, 70, 80, 90, 100, 110, 125 — 3.752 3 65,000 65,000 — — — —
BQD 1, 2, 3 15-50, 60, 70, 80, 90, 100 — 3.752 3 65,000 65,000 14,000 — — —
BQD6 1, 2, 3 15-50, 60, 70 — 3.752 3 65,000 65,000 — — 10,000 —
Special BL-HID 1, 2 15, 20, 30 — 3.752 3 10,000 10,000 — — — —
Application BL-BG 2, 3 15, 20, 30 — 3.752 3 10,000 10,000 — — — —
Ground BLE-GFCI 1, 2 15, 20, 30, 40, 50, 60 — 3.752 10,000 10,000 — — — —
Fault BLEH-GFCI 1, 2 15, 20, 30, 40, 50, 60 — 3.752 10,000 10,000 — — — —
Circuit BLF-GFCI 1, 2 15, 20, 30, 40, 50, 60 — 3.752 10,000 10,000 — — — —
Interrupter
BLHF-GFCI 1, 2 15, 20, 30, 40, 50, 60 — 3.752 10,000 10,000 — — — —
Arc BAF-AFCI 1, 2 15, 20 — 3.752 10,000 10,000 — — — —
Fault BAFH-AFCI 1, 2 15, 20 — 3.752 10,000 10,000 — — — —
Circuit BAFC-AFCI 1, 2 15, 20 — 3.752 10,000 10,000 — — — —
Interrupter
BAFCH-AFCI 1, 2 15, 20 — 3.752 10,000 10,000 — — — —
125 Thermal General NGB 1, 2, 3 15-60, 70, 80, 90, 100, 110, 125 — 3.752 3 — 100,000 25,000 — 14,000 —
Magnetic Appli- HGB 1, 2, 3 15-60, 70, 80, 90, 100, 110, 125 — 3.752 3 — 100,000 35,000 — 14,000 —
cation LGB 1, 2, 3 15-60, 70, 80, 90, 100, 110, 125 — 3.752 3 — 100,000 65,000 — 14,000 —
NEB 1, 2, 3 15-60, 70, 80, 90, 100, 110, 125 — 3.752 3 — 85,000 — 35,000 — 22,000
HEB 1, 2, 3 15-60, 70, 80, 90, 100, 110, 125 — 3.752 3 — 100,000 — 65,000 — 25,000
ED4 1, 2, 3 15-50, 60, 70, 80, 90, 100, 110, 125 — 3.752 3 — 65,000 — 18,000 — —
HED44 5 1, 2, 3 15-50, 60, 70, 80, 90, 100, 110, 125 — 3.752 3 — 100,000 — 42,000 — —
CED6 2, 3 15-50, 60, 70, 80, 90, 100, 110, 125 — 3.752 3 — 200,000 — 200,000 — 100,000
150 Electronic VL ND 3 60, 100, 150 — 5.00 — 65,000 — 35,000 — 18,000
(Solid state) HD 3 60, 100, 150 — 5.00 — 100,000 — 65,000 — 20,000
LD 3 60, 100, 150 — 5.00 — 200,000 — 100,000 — 25,000
225 Thermal General QJ2 2, 3 60-110, 125, 150, 175, — 5.00 — 10,000 — — — —
Magnetic Appli- 200, 225
cation QJH2 2, 3 60-110, 125, 150, 175, — 5.00 — 22,000 — — — —
200, 225
QJ2H 2, 3 60-110, 125, 150, 175, — 5.00 — 42,000 — — — —
200, 225
QR2 2, 3 100, 110, 125, 150, 175, 200, 225 — 5.00 — 10,000 — — — —
QRH2 2, 3 100, 110, 125, 150, 175, 200, 225 — 5.00 — 25,000 — — — —
HQR2 2, 3 100, 110, 125, 150, 175, 200, 225 — 5.00 — 65,000 — — — —
HQR2H 2, 3 100, 110, 125, 150, 175, 200, 225 — 5.00 — 100,000 — — — —
250 Thermal Sentron FXD6, FD6 2, 3 70-110, 125, 150, 175, 200, 225, 5.00 5.00 — 65,000 — 35,000 — 22,000
Magnetic 250
HFXD6, 2, 3 70-110, 125, 150, 175, 200, 225, 5.00 5.00 — 100,000 — 65,000 — 25,000
HFD6 250
HHFXD6, 2, 3 70-110, 125, 150, 175, 200, 225, 5.00 5.00 — 200,000 — 100,000 — 25,000
HHFD6 250
CFD6 3 70-110, 125, 150, 175, 200, 225, — 5.00 — 200,000 — 200,000 — 100,000
250
Electronic VL NF 3 100, 150, 250 — 5.00 — 65,000 — 35,000 — 18,000
(Solid state) HF 3 100, 150, 250 — 5.00 — 100,000 — 65,000 — 20,000
LF 3 100, 150, 250 — 5.00 — 200,000 — 100,000 — 25,000
1 Includes housing frame plate with blank cover plate. Provision price includes all 3 Accessories such as shunt trips on three pole breakers require 6.25" of unit space.
necessary mounting hardware, less circuit breaker, and includes housing frame 4 HED4 1-pole 15–30A = 65,000 IR
cover plate with breaker handle opening. 35–100A = 25,000 IR
2 1 to 6 poles may be mounted in 3.75" of unit space. 5 HED4 3-Pole = 42,000 IR.
5-6
SECTION 5
Application
Type P5 Panelboards
Table P5-10 – Branch Circuit Breakers (continued)
Unit Space
Breaker Requirements Maximum Interruption Rating (KAIC) Volts AC
Frame Trip Breaker Frame Trip in Inches 480Y/ 600Y/
Rating Type Family Type Poles Amperage Single Twin 120 240 277 480 347 600
400 Thermal Sentron JXD6, JD6 2, 3 200, 225, 250, 300, 350, 8.75 8.75 — 65,000 — 35,000 — 25,000
Magnetic 400
HJXD6, 2, 3 200, 225, 250, 300, 350, 8.75 8.75 — 100,000 — 65,000 — 35,000
HJD6 400
HHJXD6, 2, 3 200, 225, 250, 300, 350, 8.75 8.75 — 200,000 — 100,000 — 50,000
HHJD6 400
CJD6 3 200, 225, 250, 300, 350, 8.75 — — 200,000 — 150,000 — 100,000
400
Electronic VL NJ 3 250, 400 6.25 6.25 — 65,000 — 35,000 — 25,000
(Solid HJ 3 250, 400 6.25 6.25 — 100,000 — 65,000 — 25,000
state)
LJ 3 250, 400 6.25 6.25 — 200,000 — 100,000 — 25,000
Sentron SJD6 3 200, 300, 400 8.75 — — 65,000 — 35,000 — 25,000
SHJD6 3 200, 300, 400 8.75 — — 100,000 — 65,000 — 35,000
SCJD6 3 200, 300, 400 8.75 — — 200,000 — 150,000 — 100,000
5-7
Application
Type P5 Panelboards
5-8
SECTION 5
Typical Catalog Numbers
Type P5 Panelboards
Table P5-14 – Main Lugs Only – shown with aluminum bus, top fed, and surface trims
Max. 208Y/120V 240/120V 120/240V or 240 480Y/277V 480V 1
Panel Unit 250 Vdc Max
Amp Space 3 Phase, 4 Wire 3 Phase, 4 Wire 1 Phase, 3 Wire 3 Phase, 3 Wire 3 Phase, 4 Wire 1 Phase, 3 Wire
Rating (inches) Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
30 P5C60ML800ATS P5B60ML800ATS P5A60ML800ATS P5D60ML800ATS P5E60ML800ATS P5F60ML800ATS
800 45 P5C75ML800ATS P5B75ML800ATS P5A75ML800ATS P5D75ML800ATS P5E75ML800ATS P5F75ML800ATS
60 P5C90ML800ATS P5B90ML800ATS P5A90ML800ATS P5D90ML800ATS P5E90ML800ATS P5F90ML800ATS
30 P5C60ML101ATS P5B60ML101ATS P5A60ML101ATS P5D60ML101ATS P5E60ML101ATS P5F60ML101ATS
1000 45 P5C75ML101ATS P5B75ML101ATS P5A75ML101ATS P5D75ML101ATS P5E75ML101ATS P5F75ML101ATS
60 P5C90ML101ATS P5B90ML101ATS P5A90ML101ATS P5D90ML101ATS P5E90ML101ATS P5F90ML101ATS
30 P5C60ML120ATS P5B60ML120ATS P5A60ML120ATS P5D60ML120ATS P5E60ML120ATS P5F60ML120ATS
1200 45 P5C75ML120ATS P5B75ML120ATS P5A75ML120ATS P5D75ML120ATS P5E75ML120ATS P5F75ML120ATS
60 P5C90ML120ATS P5B90ML120ATS P5A90ML120ATS P5D90ML120ATS P5E90ML120ATS P5F90ML120ATS
Table P5-15 – Main Circuit Breakers – shown with aluminum bus, top fed, and surface trims
Max. 208Y/120V 240/120V 120/240V or 240 480Y/277V 480V 1
Panel Unit 250 Vdc Max
Amp Space 3 Phase, 4 Wire 3 Phase, 4 Wire 1 Phase, 3 Wire 3 Phase, 3 Wire 3 Phase, 4 Wire 1 Phase, 3 Wire
Rating (inches) Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
21.25 P5C60M1800ATS P5B60M1800ATS P5A60M1800ATS P5D60M1800ATS P5E60M1800ATS P5F60M1800ATS
800 2 36.25 P5C75M1800ATS P5B75M1800ATS P5A75M1800ATS P5D75M1800ATS P5E75M1800ATS P5F75M1800ATS
51.25 P5C90M1800ATS P5B90M1800ATS P5A90M1800ATS P5D90M1800ATS P5E90M1800ATS P5F90M1800ATS
20 P5C60N1120ATS P5B60N1120ATS P5A60N1120ATS P5D60N1120ATS P5E60N1120ATS P5F60N1120ATS
1200 35 P5C75N1120ATS P5B75N1120ATS P5A75N1120ATS P5D75N1120ATS P5E75N1120ATS P5F75N1120ATS
50 P5C90N1120ATS P5B90N1120ATS P5A90N1120ATS P5D90N1120ATS P5E90N1120ATS P5F90N1120ATS
5-9
Modification and Additions
Type P5 Panelboards
Devices Mounted on Gutter Cover Ground Fault on Main Breaker Main Bus
Includes Device, Mounting – Wired Standard main bus and ground bus are
Amp
or Unwired Description Rating tin-plated aluminum. For copper main
bus, neutral bus and ground bus, add
Description Conventional Ground
from the table for each panel.
One piece front with door Fault 2 Includes:
(Depth increases to 14.25”) Ground Fault Relay, Ground
Sensor, CPT and Shunt Trip 800-1200 Lugs – For Main Lug Only Panels
Hinged Gutter Covers 4 pc front Standard main lugs and neutral lugs
Toggle Switch — SPST or 3-way Test and Monitor Panel 3
are tin-plated aluminum, UL listed for
15A, 277V maximum Ground Fault add to
Sensitrip III breaker price 800-1200 use with aluminum/copper cables.
Pilot Light — General Purpose (takes 5” of unit space) Copper only lugs are an option.
Neon or Incandescent
Pushbutton •Indicates available Ampere Rating
400 - 1200
Time Clocks 4
Feed-Thru Lugs Sangamo, Tork or Paragon time clock
Ampere Rating Unit Space (inches) can be supplied, mounted in panel- Shunt Trip on Main and Branches 5
400 10
board cabinet. For required increase Description
600 10
in enclosure dimension, consult local
BL, BQD, xGB, HGB, LGB, NEB, HEB
800 17.5
sales office. (branch only)
1200 17.5 QJ2, QJH2, QJ2H, QR2, QRH2, HQR2,
Description
HQR2H, ED2, ED4, HED4, HHED6, CED6
Time clock (1- or 2-Pole, Single or Double (branch only)
Grounding of Panelboards Throw Contacts; 3-Pole Single Throw)
All others through 1200A
Ground Bars except for brazed to box 277V Maximum with Plain Dial
are shipped with the panel interior Options:
factory mounted. Astronomical Dial 100% Rated Main Circuit Breakers
• Non-Insulated Equipment Ground An Omitting Device
Ampere
Bar – Standard Reserve Power or Carryover Rating Breaker Type
• Copper Non-Insulated Ground Bar Space and Mounting Provisions Only JXD6H, HJXD6H
• Al Insulated Equipment Ground Bar 400
NJY, HJY, LJY
• Cu Insulated Equipment Ground Bar 600 LXD6H, HLXD6H
• Ground Bar Brazed to Box Circuit Breaker Accessories 600 6 NMY, HMY, LMY
Handle Blocking Device MXD6H, HMXD6U, SMD6,
800 7
Fuse Clip Provisions Blocks handle in either the SHMD6, SND6, SHND6,
“ON” or “OFF” position. NXD6H, HNXD6H
(Add to 250 Volts or 600 Volts
NNY, HNY, LNY
Unit Prices Per Switch) 1200
Padlocking Device – Padlocks NXD6H, HNXDH
Amp Class Class Class in “OFF” position.
Rating J R T
30 • • N/A
60 • • N/A
100 • • •
200 1 • • •
400 • • •
600 • • •
1 For use on main lug, main breaker or main switch panels without subfeed breakers.
2 Available in 90” high enclosure only. Unit space is 42 1/2” with Test and Monitor Panel; 45” without Test Monitor Panel.
3 Not available on Sensitrip III.
4 For required unit space, consult local sales office.
5 Shunt Trip on 100A frame breakers increases mounting height to 6.25” for twin mounting.
6 The 600A, 100% rated braaker application requires the use of an 800A frame breaker.
7 The 800A, 100% rated breaker application requires the use of a 1200A frame breaker.
5-10
SECTION 5
Modification and Additions
Type P5 Panelboards
Motor Starters disconnect devices in either one of Standard Motor Starters Equipped
ETI instantaneous-trip circuit breakers two circumstances: 1. by using a branch With:
are recommended for use in combination thermal magnetic (ETI) circuit breaker to • 3rd overload relay
motor starters to provide selective short feed a remote starter that controls a • Mechanical interlock between circuit
circuit protection for the motor branch motor which is in sight of and within breaker (or switch) and motor starter
circuit. The adjustable instantaneous-trip fifty feet of the panelboard. 2. by using door
feature provides a trip setting slightly a branch instantaneous trip only (ETI) • Reset button
above the peak motor inrush current. circuit breaker in conjunction with a • Class 1, Type A wiring
With this setting, there is no delay motor starter mounted in the same
opening the circuit when the fault occurs. enclosure which is in sight of and within Optional Motor Control Accessories
Since these circuit breakers have no time fifty feet of the controlled motor. • Pushbuttons: Start/Stop or Open/Close,
delay trip element, they must be used in Reverse/Forward/Stop or High/Low/Stop
conjunction with, and immediately ahead Whether a remote starter is used, or • Selector Switch: Hand/Off/Auto or
of, the motor-running over-current the breaker and starter are mounted On/Off
protective device. in the same enclosure, a padlocking
• Pilot Light: Red or Amber
device must be specified so a padlock
Check the voltage and interrupting rating can be installed in the “OFF” position. • Auxiliary interlock (normally open or
of the circuit breaker to ensure they are P2 panelboards incorporate motor normally closed-unwired)
adequate for the electrical system. UL disconnect devices much in the same • Control transformer, 60Hz, fused LV,
recognized ETI breakers must be used. way as P5 panelboards, except a fusible Sizes 1 thru 4
Vacu-Break switch unit is utilized rather • Class 1, Type B wiring
Full voltage, non-reversing NEMA Size than an ETI circuit breaker. In addition,
1 through Size 4 motor starters are padlocking devices are standard on all
available as additions to P5 panelboards. Vacu-Break switches eliminating the
P5 panelboards can accommodate motor need to order them as an accessory.
Table P5-17 – ETI circuit Breakers (Instantaneous Trip Only) Table P5-18 – Full Voltage
For Branch-Circuit Use with AC Full Voltage Motor Starters Non-Reversing Starters Class A20
Maximum 3Ø Ratings Mounting Height in Inches (mm) NEMA Unit Space
Amp Breaker Min. Section Starter Size Mtg. Ht. In. (mm)
Rating Type 220 (208)V 240V 480V 1 2 Twin Single Width Inches (mm) Left Right
3 — — 1 5 (127) — 32 (813) 0 — 5 (127) 3
5 0.5 0.5 2 5 (127) — 32 (813) 0 0 5 (127) 3
10 ED 1 2 2 3 5 (127) — 32 (813) 1 — 5 (127) 3
25 5 5 10 5 (127) — 32 (813) 1 0 5 (127) 3
50 15 15 30 5 (127) — 32 (813) 1 1 5 (127) 3
100 30 30 60 5 (127) — 32 (813) 2 — 10 (254)
150 FD6 2 40 40 75 5 (127) — 32 (813) 2 0 10 (254)
225 FD6, 50 50 100 5 (127) — 32 (813) 2 1 10 (254)
CFD6 2 2 10 (254)
3 — 15 (381)
1 100,000 kA at 480V with E-frame and CFD6 frame breakers.
3 0 15 (381)
2 65,000 kA at 480V with F-frame breakers.
3 Increase to 7.50 inches when pilot light or control transformer is required. 3 1 15 (381)
3 2 15 (381)
3 3 15 (381)
4 — 15 (381)
5-11
Modification and Additions
Type P5 Panelboards
Connector Modifications
Compression Lugs
Table P5-21 – Compression Lugs
Style Amp Rating Breaker Type Compression Connectors Available Unit Space Reduction
800 N/A All compression lugs Deduct 10.0” Unit Space
MLO 1000 N/A All compression lugs Deduct 10.0” Unit Space
1200 N/A All compression lugs Deduct 10.0” Unit Space
800 MD6, HMD6, CMD6,
SMD6, SHMD6, (3)#2/0 AWG - 500 Kcmil CU or Al 0
Main Breaker SCMD6
1200 ND6, HND6, CND6,
SND6, SHND6. (4)#250 - 500 Kcmil Cu or Al 0
SCND6
Style Amp Rating Breaker Type Compression Connectors Available Unit Space Reduction
800 N/A (3)#3/0 AWG - 750 Kcmil Cu or Al Deduct 5.0” Unit Space
MLO 1000 N/A (4)#3/0 AWG - 750 Kcmil Cu or Al Deduct 7.5” Unit Space
1200 N/A (4)#3/0 AWG - 750 Kcmil CU or Al Deduct 7.5” Unit Space
5-12
SECTION 5
Dimensions
Type P5 Panelboards
Type 1 Box
Box is symmetrical
5-13
Kits and Accessories
Type P5 Panelboards
Table P5-23 – Branch Breaker Connecting Strap Kits 1 2 Table P5-24 – Blank Plates – Circuit
For use with P5, Sentron Deep or Type S5 Power Panels Breaker and Vacu-Break 4
Max Unit
Amp Breaker Breaker Catalog Height For use with Sentron SPP and Type P5 power panels
Rating Family Type Number (inches) Mounting Height
100 General BL, BQD SBLBD 3.75 Twin Inches Catalog
125 General NGB, HGB, LGB SNBD 3.75 Twin (mm) Number
General EB SEBD 3.75 Twin 1.25 (32) 6FPB01
General ED SE6D 3.75 Twin 2.5 (63.5) 6FPB02
General CED SCED 3.75 Twin 3.75 (95) 6FPB03
150 VL DG SDGD 5.00 Twin 5.0 (127) 6FPB05
225 General QJ SQJD 5.00 Twin 10.0 (254) 6FPB10
General QR SQRD 5.00 Twin
250 Sentron FD SF6D 5.00 Twin
VL FG SFGD 5.00 Twin Table P5-25 – Filler Plates
Sentron CFD SCFD 5.00 Single
400 Sentron JD SJ1D 8.75 Single For use with Sentron SPP and P5 power panels
Sentron JD SJ2D 8.75 Twin Breaker Type Filler Plate
Sentron SJD SSJ1D 8.75 Single Catalog Number
VL JG SJG1D 6.25 Single BL, BLH, HBL, BQD,
VL JG SJG2D 6.25 Twin NGB, HGB, LGB, ED2, DFFP15
Sentron CJD SCJD 8.75 Single ED4, ED6, HED4, HHED6
Sentron SJD SSCJD 8.75 Single NEB, HEB EBF1
600 Sentron LD SL6D 8.75 Single Note: When a front filler plate is not completely filled
Sentron SLD SSL6D 8.75 Single with breakers, the openings in the unused space must be
VL LG SLGD 6.25 Single closed with filler plates selected from this table.
Sentron CLD SCLD 8.75 Single
Sentron SCLD SSCLD 8.75 Single
g Table P5-26 – Cover Plates
800 VL MG MG1D 8.75 Single For use with P5, Sentron SPP and
Sentron LMD SLM1D 8.75 Single Type S6 power panels
Sentron MD SMND 10.00 Single Breaker Type Catalog Number
Sentron SMD SSMND 10.00 Single QR SQRC 6
1200 VL NG NG1D 10.00 Single
Sentron ND SMND 10.00 Single
Sentron SND SSMND 10.00 Single
fAlthough QR is rated 250A, it is limited to 225A in panelboard.
Table P5-27 – Connecting Strap Kits – Fusible 2 Table P5-28 – Service Entrance Barriers
For use with Sentron FPP Deep or Type F2/P5 power panels Field installable Barriers to meet UL 67
service entrance requirements
Unit
Ampere Height Catalog
Rating Inches (mm) Number Breaker Type Catalog Number
30–30 2.5 (63.5) F602D (S)JD, (S)LD, MG SEBP4V1
30–30 5.0 (127), 7.5 (191) F657D CJD, CLD SEBP4V2
30–60 5.0 (127), 7.5 (191) F657D JG, LG SEBP4V3
60–60 5.0 (127), 7.5 (191) F657D (S)MD, (S)ND without shield SEBP5V1
60–100 5.0 (127), 7.5 (191) F657D (S)MD, (S)ND without shield SEBP5V2
100–100 5.0 (127), 7.5 (191) F657D Vacu-Break Switches SEBP5V3
100 7.5 (191) F657D HCP Switches SEBP5V4
200 7.5 (191) F657D
200 10.0 (254) F671D
200–200 10.0 (254) F672D
400–600 15.0 (381) F6150D
800–1200 2 16.25 (413) F6162D
1 Includes cover plate and mounting hardware, less circuit breaker.
2 Also fits Types FCI, FCII, SB1, SB2 and SB3 switchboards.
3 800-1200 amp units are HCP switch.
4 Normal stock item.
5 Suitable to replace QF3 in P1 thru P5 panelboards and switchboards.
6 To replace QJ with a QR only a new cover is needed up to 225A.
5-14
5 SECTION
Kits and Accessories
Type P5 Panelboards
5-15
Notes
SECTION 6
C1/ C2 Panelboards
Description Page
General Specifications 6-2 Subfeed Breakers C1 6-4
Box Sizing 6-2 Alternate Main Breaker Selection C2 6-5
Gauge Steel Boxes 6-2 Branch Circuit Breaker C2 6-5
Fronts 6-2 Subfeed Breakers C2 6-5
Main Breaker Connectors 6-2 Modification and Additions 6-6
Main Lug Connectors 6-2 Box Modifications 6-6
Selection 6-3 – 6-5 Interior Modifications 6-6
Main Lugs Only C1 and C2 6-3 Column Extension 6-6
Main Circuit Breaker C1 and C2 6-3 Pull Boxes 6-6
Alternate Main Breaker Selection C1 6-3
Branch Breaker Selection C1 6-4
General Specifications
C1 and C2 Panelboards
6-2
SECTION 6
Selection
C1 and C2 Panelboards
Table C1/C2-6 – Main Lugs Only C1 Table C1/C2-7 – Main Lugs Only C2
Max. Max.
Panel Max. Box 208Y/120V 120/240V Panel Max. Box 480Y/277V
Amp 1-Pole Height 3, Phase 4 Wire 1 Phase, 3 Wire Amp 1-Pole Height 3 Phase, 4 Wire
Rating Circuits Inches Catalog Number Catalog Number Rating Circuits Inches Catalog Number
18 48 C1C18ML125CTS C1A18ML125CTS 18 48 C2E18ML125CTS
125 30 73 C1C30ML125CTS C1A30ML125CTS 125 30 73 C2E30ML125CTS
42 85 C1C42ML125CTS C1A42ML125CTS 42 85 C2E42ML125CTS
18 48 C1C18ML250CTS C1A18ML250CTS 18 48 C2E18ML250CTS
250 30 73 C1C30ML250CTS C1A30ML250CTS 250 30 73 C2E30ML250CTS
42 85 C1C42ML250CTS C1A42ML250CTS 42 85 C2E42ML250CTS
Table C1/C2-8 – Main Circuit Breaker C1 1 2 Table C1/C2-9 – Main Circuit Breaker C2 1 2
18 48 C1C18BL100CTS C1A18BL100CTS 18 48 C2E18BD100CTS
100 30 73 C1C30BL100CTS C1A30BL100CTS 100 30 73 C2E30BD100CTS
42 85 C1C42BL100CTS C1A42BL100CTS 42 85 C2E42BD100CTS
18 48 C1C18E4125CTS C1A18E4125CTS 18 48 C2E18E4125CTS
125 30 73 C1C30E4125CTS C1A30E4125CTS 125 30 73 C2E30E4125CTS
42 85 C1C42E4125CTS C1A42E4125CTS 42 85 C2E42E4125CTS
18 48 C1C18QR225CTS C1A18QR225CTS 18 48 C2E18FX225CTS
225 30 73 C1C30QR225CTS C1C30QR225CTS/ 225 30 73 C2E30FX225CTS
42 85 C1C42QR225CTS C1A42QR225CTS/ 42 85 C2E42FX225CTS
18 48 C1C18FX250CTS C1A18FX250CTS 18 48 C2E18FX250CTS
250 30 73 C1C30FX250CTS C1A30FX250CTS 250 30 73 C2E30FX250CTS
42 85 C1C42FX250CTS C1A42FX250CTS 42 85 C2E42FX250CTS
6-3
Selection
C1 and C2 Panelboards
Table C1/C2-12 – Subfeed Breakers - Limit One Per Panel – C11 (Not available for 42 circuit panels)
15, 20, 30, 40, 50, 60, 70, 80, 90, 100 — — 65
ED4
110, 125 — — 65
15, 20, 30, 40, 50, 60, 70, 80, 90, 100 — — 65
HED4
110, 125 — — 100
QJ2 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225 — — 10
QJH2 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225 — — 22
QJ2H 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225 — — 42
QR2 100, 110, 125, 150, 175, 200, 225 — — 10
FXD6 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 — — 65
HFD62 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 — — 100
1 BL, BLH, HBL, and BQD are horizontally mounted. All others are vertically mounted.
2 Interchangeable trip breakers such as FD6 and HFD6 cannot be back fed. Must be top feed only.
6-4
SECTION 6
Selection
C1 and C2 Panelboards
Table C1/C2-15 – Subfeed Breakers - Limit One Per Panel 1 2 C2 (Not available for 42 circuit panels)
15, 20, 30, 40, 50, 60, 70, 80, 90, 100 — 18 18
ED4
110, 125 — 18 18
ED6 15, 20, 30, 40, 50, 60, 70, 80, 90, 100 — — 25
110, 125 — — 25
HED4 15, 20, 30, 40, 50, 60, 70, 80, 90, 100 — — 42
110, 125 — — 42
FXD6 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 — — 35
HFD6 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 — — 65
1 No increase in box height. Space is already built into C1 panel.
2 BL, BLH, HBL and BQD are horizontally mounted. All others vertically mounted.
6-5
Modification and Additions
C1 and C2 Panelboards
Fig. C1/C2-1
6-6
SECTION 7
Miscellaneous
Description Page
Telephone Cabinets 7-2 Strap Kits 7-4
Conduit Enclosing Shield (Panel Skirts) 7-2 Connecting Strap Kits 7-4
Breaker Mechanical Lugs 7-2 Blank Plates – Vacu-Break 7-4
Compression Lugs 7-2 Molded Case Switches 7-4
Optional Mechanical Lugs 7-3
Aluminum Body Lugs for Copper or
Aluminum Wire 7-3
Miscellaneous Replacement Parts 7-4
Miscellaneous
8, 9, 10, 11, 12, 14, 17, 18, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33, 34, 35, 36, 37, 38, 39, 40, 41, 42, 43, 44
For Circuit Ampere Lugs Lug Wire For Use Amp Cables
Breaker Types Rating Poles Per Kit Size With Type(s) Rating Per Lug Lug Wire Range
Lugs (contains indicated number of lugs and necessary hardware per kit) Load Side
ED2, ED4, ED6, 15-125 1,2,3 1 #2/0 BQ, BQH, 15-20 1 #14-#10 AWG Cu
HED4, HHED6, CED4 BQHF, BQE 1 #12-#10 AWG Al
QJ2, QJH2, QJ2H, QR2, 125-225 2, 3 1 350 kcmil BQF, 25-35 1 #8-#6 AWG Cu
QR2H, HQR2, HQR2H BL, BLH 1 #8-#6 AWG Al
F(X)D6-A, HF(X)D6, 125-250 2, 3 1 350 Kcmil HBL, HBQ 40-50 1 #8-#6 AWG Cu
HHF(X)D6, CFD6 1 #8-#4 AWG Al
JXD2-A, J(X)D6-A, Switching 55-70 1 #8-#4 AWG Cu
HJ(X)D6-A, HHJXD6-A, Neutrals 1 #8-#2 AWG Al
CJD6, SJD6-A, 200-600 2, 3 1 500 Kcmil 80-100 1 #4-#1/0 AWG Cu
SHJD6-A, SCJD6, L(X)D6-A, BG 1 #2-#1/0 AWG Al
HL(X)D6-A, CLD6, SLD6-A, BLG 110-125 1 #2-#1/0 AWG Cu
SHLD6-A, SCLD6 1 #1/0-#2/0 AWG Al
Kits (contains lug and hardware for complete line of load end of 2 or 3 pole breaker) 15-40 1 #14-#6 AWG Cu
M(X)D6, HM(X)D6, CMD6, 500-800 2 6 500 Kcmil BQD #12-#6 AWG Al
SMD6, SHMD6, SCMD6 3 9 500 Kcmil BQD6 45-100 1 #8-1 AWG Cu
N(X)D6, HN(X)D6, CND6, 900-1200 2 8 500 Kcmil #6-#1/0 AWG Al
SND6, SHND6, SCND6 3 12 500 Kcmil
7-2
SECTION 7
Miscellaneous
7-3
Miscellaneous
Connecting Strap Kits - Obsolete Circuit Breakers FC20, FCI and FCII switchboards – includes copper straps, cover
For use with Series 5 or 6 CDP circuit breaker panelboards plates and necessary hardware.
Table Misc. 9 – Connecting Strap Kits — Vacu-Break Table Misc. 10 – Molded Case
For use with VB-23 and VB-32 Type Panelboards. Switches (Non-Automatic
Circuit Interrupters)
For Use With
Panel Catalog Ampere Unit Height Ampere Breaker
Type Number Rating (in.) Rating Frame
VB-23 V2AX25 30-30 2 1/2 100 ED2, ED4, ED6
V2BX50 30-30 and 60-60 5 225 QJ2, QR2
V7AX25 30-30 2 1/2 250 FXD6
V7BX50 30-30 and 60-60 5 400 JXD2, JXD6
VB-32 V7EX75 100-100 7 1/2 600 LXD6
100 7 1/2 800 MD6
200 7 1/2 (2-Pole) 1200 ND6
V7FX100 200 10 (3-Pole)
7-4
Published by
Siemens Industry, Inc. 2016.
usa.siemens.com/panelboards
Order No.PBCS-20301-1116
Printed in U.S.A.
© 2016 Siemens Industry, Inc.