Beipackinformation 1 15 Notice D'utilisation 27: Operating Instructions

The document provides instructions for analog signal isolators in the WAVEANALOGUE PRO series. It describes the models, contains general safety warnings, and explains the application and configuration of the devices. The configuration section outlines how to open the unit, set the DIP switches to select the input type and range, and calibrate the minimum input value and measuring span using front potentiometers.

Uploaded by

Mohammad Hossein
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
158 views13 pages

Beipackinformation 1 15 Notice D'utilisation 27: Operating Instructions

The document provides instructions for analog signal isolators in the WAVEANALOGUE PRO series. It describes the models, contains general safety warnings, and explains the application and configuration of the devices. The configuration section outlines how to open the unit, set the DIP switches to select the input type and range, and calibrate the minimum input value and measuring span using front potentiometers.

Uploaded by

Mohammad Hossein
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 13

Beipackinformation 1

Operating Instructions 15
Notice d’utilisation 27

Analogsignaltrenner
WAVEANALOG PRO RTD
aus der WAVESERIES

RT Nr. 406042

Downloaded from www.Manualslib.com manuals search engine


Analogue Signal Isolators
WAVESERIES
WAVEANALOGUE PRO RTD

MODEL Order Number


Screw terminal connection
WAS5 PRO RTD 8560700000
Tension clamp connection
WAZ5 PRO RTD 8560710000

Please read these instructions before using the product


and retain for future information.
15

Downloaded from www.Manualslib.com manuals search engine


1. General instructions
Warning! The analogue signal isolators of the WAVEANALOGUE PRO series
may only be installed by qualified personnel. Be sure not to
connect the unit to power supply before appropriate installation.
Do not select ranges during operation, because live parts are
exposed during this process. Only use a screwdriver which is
properly insulated against the voltage applied to the input when
fine adjusting the potentiometers on the front.
Be sure to observe the national regulations for installation and
selection of cables.
Appropriate safety measures against electrostatic discharge
(ESD) should be taken during assembly and adjustment work on
the WAVEANALOGUE PRO.

2. Application
Analouge singnal isolators are used for galvanic isolation and conversion of
temperature, resistance and potentiometer signals. Input and output
signals are factory set according to type or can be calibrated/switched via
DIP switches. It is not necessary to adjust the measurement range.
A +/- 5% variation can be achieved in the respective range by connecting
potentiometers for zero and span. The transmitted measurement signal is
linear to the measured temperature.

16

Downloaded from www.Manualslib.com manuals search engine


3. Configuration

3.1 Equipment
A screwdriver with a width of 2.5 mm is required to adjust the unit and to
connect the wires to the terminals.
2

3.2 Opening the unit


Disconnect the plugs. Disengage the top part of
the housing by carefully pressing the latches on 1 1
both sides (1). Pull out the top part of the hous-
ing and the electronics section until they lock (2).

3.3 Settings
Set input and output ranges, minimum input values
and measuring span via the DIP switches SW1 and
SW2 according to the following tables.
When activating variable setting SW 1/8 of the span
SW2
or offset, it is possible to make additional adjust- SW1

ments via front potentiometers span and offset,


accessible below cover (3)

Caution! Only use a screwdriver which is 3


properly insulated against the voltage
applied to the input when fine adjusting Zero
the potentiometers on the front. Span

17

Downloaded from www.Manualslib.com manuals search engine


Selecting the inputs

SW1
Input 1 2 3
PT100 2-wire 1 1 1
PT100 3-wire 0 1 1
PT100 4-wire 1 0 1
R 2-wire 0 0 1
NI100 2-wire 1 1 0
NI100 3-wire 0 1 0
NI100 4-wire 1 0 0
Potentiometer 0 0 0

Selecting the minimum input value

SW1
 min Rmin Potimin 4 5 6 7
0º C 0Ω 0% 1 1 1 1
–10º C 10 Ω 10% 1 1 1 0
–20º C 20 Ω 20% 1 1 0 1
–25º C 25 Ω 25% 1 1 0 0
–30º C 30 Ω 30% 1 0 1 1
–40º C 40 Ω 40% 1 0 1 0
–50º C 50 Ω 50% 1 0 0 1
–60º C 60 Ω 60% 1 0 0 0
–70º C 70 Ω 70% 0 1 1 1
–80º C 80 Ω 80% 0 1 1 0
–90º C 90 Ω 0 1 0 1
18

Downloaded from www.Manualslib.com manuals search engine


SW1
 min Rmin Potimin 4 5 6 7
–100º C 100 Ω 0 1 0 0
–150 °C 150 Ω 0 0 1 1
–200 °C 200 Ω 0 0 1 0
Special range 0 0 0 0

Activating the manual fine adjustment

SW1
manual calibration 8
off 0
on 1

1 = on
0 = off

19

Downloaded from www.Manualslib.com manuals search engine


Selecting the measuring range
SW2
T R Poti 1 2 3 4 5
40K 20 Ω 20% 1 1 1 1 1
50K 25 Ω 25% 1 1 1 1 0
60K 30 Ω 30% 1 1 1 0 1
70K 35 Ω 35% 1 1 1 0 0
80K 40 Ω 40% 1 1 0 1 1
90K 45 Ω 45% 1 1 0 1 0
100K 50 Ω 50% 1 1 0 0 1
110K 55 Ω 55% 1 1 0 0 0
120K 60 Ω 60% 1 0 1 1 1
125K 62,5 Ω 62,5% 1 0 1 1 0
130K 65 Ω 65% 1 0 1 0 1
140K 70 Ω 70% 1 0 1 0 0
150K 75 Ω 75% 1 0 0 1 1
160K 80 Ω 80% 1 0 0 1 0
170K 85 Ω 85% 1 0 0 0 1
180K 90 Ω 90% 1 0 0 0 0
190K 95 Ω 95% 0 1 1 1 1
200K 100 Ω 100% 0 1 1 1 0
250K 125 Ω – 0 1 1 0 1
300K 150 Ω – 0 1 1 0 0
350K 175 Ω – 0 1 0 1 1
400K 200 Ω – 0 1 0 1 0
450K 225 Ω – 0 1 0 0 1
500K 250 Ω – 0 1 0 0 0
550K 275 Ω – 0 0 1 1 1
20

Downloaded from www.Manualslib.com manuals search engine


SW2
T R Poti 1 2 3 4 5
550K 275 Ω – 0 0 1 1 1
600K 300 Ω – 0 0 1 1 0
650 K 325 Ω – 0 0 1 0 1
700K 350 Ω – 0 0 1 0 0
750K 375 Ω – 0 0 0 1 1
800K 400 Ω – 0 0 0 1 0
850K 425 Ω – 0 0 0 0 1
900K 450 Ω – 0 0 0 0 0

Selecting the output

SW2
Output 6 7
0…10 V 1 0
0…20 mA 0 0
4…20 mA 0 1

1 = on
0 = off

21

Downloaded from www.Manualslib.com manuals search engine


Selecting the step response time

SW2
Step response 8
slow 1
fast 0

1 = on
0 = off

3.4 Terminal assignment of the sensors


Terminal assignment for 2-, 3-, 4-wires and potentiometers.

4-wires 3-wires 2-wires Potentiometer


Sensor +

Sensor - Sensor - Sensor -

22

Downloaded from www.Manualslib.com manuals search engine


4. Mounting
The analogue signal isolators are mounted on standard TS 35 rails.

5. Electrical connection
Terminal assignments 10 11 12
Klemmenbelegung
1 Input RTD + 7 8 9
2 1 Ein–gang +
Input Sensor > 5 mA
3 2 –Eingang +
Input RTD £ 500 mV / £ 5 mA We i dm ü l le r

V. 0
WAS5 PRO RTD

11
3 Ein+gang + > 500 mV

10

12
4 Input Sensor

9
7

0V

nc
24V
4 Eingang -

V
0...10V
5 not assigned

0/4...20mA

cc
6 not assigned

I
5 Ausgang
mA +

V/I
7 Output 0/4…20

cc
PS

8 6 Ausgang
Output 0…10 V -

06
9 7 Versorgungsspannung
Output GND

Sense

2 Sense
1 RTD

3 RTD

8560700000
10 8 Versorgungsspannung
Power supply + 24 Vdc (cross connected)

nc

nc
4

6
11 Power supply 0 V (cross connected)
12 not assigned

J
2
Anschlußquerschnitt
Wire cross-section max. 2.5 mm2 max. 2,5 mm
1 2 3
2
Mehrleiteranschluß
Multi-wire conncection max. 1 mm
2 max. 1 mm
4 5 6
(zwei same
(two wires with Leitercross-section)
gleichen Querschnitts)

Warning! For applications with high isolation voltages, take measures to


prevent accidental contact and make sure that there is
sufficient distance or insulation between adjacent devices!

5.1 Power supply


18…30 Vdc/approx. 1 W
Voltage supply via cross-connections
(see Cat. No. point 7)

23

Downloaded from www.Manualslib.com manuals search engine


6. Dimensions

92,4

38
111,4
73,4
Cross-connections
for power supply

GND 24 Vdc

90
17,5

mm

24

Downloaded from www.Manualslib.com manuals search engine


7. Accessories (cross-connection)
Designation Cat. No.
ZQV 2,5 N/2 yellow 169380
ZQV 2,5 N/2 red 171790
ZQV 2,5 N/2 blue 171799
ZQV 2,5 N/2 black 171808

Connection markers
Designation Cat. No.
WS 10/5 Multicard for plotter marking 163501
WS 10/5 Neutral 106086

8. Notes on CE marking
The WAS5/WAZ5 RTD analog signal isolators are marked CE in accordan-
ce with the EU directives 89/336/EEC "Electromagnetic Compatibility" and
73/23/EEC (low-voltage directive) detailing the Harmonized European
Standards (EN).
The declarations of conformity are held, according the above mentioned
EU directive, article 10, for the authorizing body by:

Weidmüller Interface GmbH & Co.


Postfach 30 30
D-32720 Detmold
Tel. (05231) 14-0
Fax (05231) 14-2083

25

Downloaded from www.Manualslib.com manuals search engine


Weidmüller Interface GmbH & Co.
Postfach 30 30
D-32720 Detmold
Tel. (0 52 31) 14-0
Fax (0 52 31) 14-20 83

26

Downloaded from www.Manualslib.com manuals search engine

You might also like