Product datasheet
Specifications
MGE Galaxy 5500 100kVA 400V
Integrated Parallel UPS, Start-up
5x8
G55TUPSM100HINS
Discontinued on: 22 November 2021
To be end-of-service on: 30 September 2031
Discontinued - Service only
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Overview
Presentation A versatile 3-phase UPS for facility, industrial and data center applications. Configurable system with a
comprehensive range of accessories to meet your application demands.
Lead time Usually Ships within 2 Weeks
Main
Main Input Voltage 400 V 3 phases
Other Input Voltage 380 V
415 V
Main Output Voltage 400 V 3 phases
Other Output Voltage 380 V
400 V
415 V
Rated power in W 90000 W
Rated power in VA 100000 VA
Output connector type Hard wire 4-wire (3P + N) 1
Battery type External battery system
Provided equipment Installation guide
Network management card
Start-up service
User manual
General
Bypass voltage tolerance +/- 10 % settable from +/- 4/6/8 and 10 %
Max bypass input current 144 A
Number of power module free 0
slots
Number of power module filled 0
slots
Redundant No
Physical
Height 190 cm
Width 71.2 cm
Depth 85.5 cm
Jun 1, 2022 1
Net weight 520 kg
Mounting preference No preference
USB compatible No
Input
Network frequency 45...65 Hz
Input voltage limits 323...437 V 380 V
340...460 V 400 V
353...477 V 415 V
Maximum input current 190 A
Switching current capacity 315 A
Max short time withstand 30 kA
current
Input harmonic distortion Less than 3 % for full load
Input protection type GL fuse
Load power factor 0.9
Input Power Factor at Full Load 1
Output
Maximum configurable power in 90000 W
W
Harmonic distortion Less than 2 %
Output frequency 50/60 Hz +/- 3 Hz user adjustable +/- 0.1 Hz sync to mains
50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
Crest factor 3:1
Wave type Sine wave
Output voltage tolerance +/- 1% static and +/- 5% at 100% load step
Output harmonic distortion < 1% linear load and < 2.5% non-linear load
Output overload operation 10 minutes at 125% and 60 seconds at 150%
Required output current 144 A
protection
Neutral output current 217 A
Bypass type Built-in maintenance bypass
Built-in static bypass
Optional external bypass
Efficiency 93.6 % (full load)
92.3 % (half load)
Maximum output current 480 A
Maximum configurable power in 100000 VA
VA
Conformance
Product certifications CE
TÜV
Standards EN/IEC 62040-1
EN/IEC 62040-2
EN/IEC 62040-3
IEC 62040-1-2
IEC 62040-2
2
Jun 1, 2022
Environmental
Ambient air temperature for 0…40 °C
operation
Relative humidity 0…95 %
Operating altitude 0...3333 ft
Ambient air temperature for -20…45 °C
storage
Storage Relative Humidity 0…95 %
Storage altitude 0.00…3048.00 m
Acoustic level 61 dBA
Heat dissipation 23549 Btu/h
IP degree of protection IP20
Batteries & Runtime
Number of battery filled slots 0
Number of battery free slots 0
Additional information Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
Battery power in VAH 0 VAh runtime
Extended runtime 0
Communications & Management
Free slots 2
Preinstalled device Network management card 2 with environmental monitoring, out of band access and Modbus
Control panel Multifunction LCD status and control console
Emergency power off Yes
Packing Units
Package 1 Weight 540 kg
Package 1 Height 203 cm
Package 1 width 98 cm
Package 1 Length 96 cm
Number of Units in Package 2 1
Offer Sustainability
EU RoHS Directive Will be compliant – Date to be confirmed
Contractual warranty
Warranty 1 year on-site repair or replace with factory authorized Start-Up, 1 year (parts only)