Vacon OPTC3 C5 Profibus Option Board User Manual DPD00892B UK
Vacon OPTC3 C5 Profibus Option Board User Manual DPD00892B UK
ac drives
optc3/c5
profibus dp option board
user manual
INDEX
Document code: DPD00892B
Date: 12.11.2015
1. GENERAL ....................................................................................................................... 2
6. COMMISSIONING .......................................................................................................... 24
6.1 Fieldbus board parameters ........................................................................................................ 24
6.2 Start-up test ................................................................................................................................. 26
7. PROFIBUS-VACON NX INTERFACE ............................................................................... 27
7.1 General ......................................................................................................................................... 27
7.2 Operation mode............................................................................................................................ 27
7.3 PPO types ..................................................................................................................................... 28
7.4 Process data................................................................................................................................. 29
7.4.1 Control word ........................................................................................................................ 30
7.4.2 Status word .......................................................................................................................... 31
7.4.3 State machine ...................................................................................................................... 32
7.4.4 Reference 1 .......................................................................................................................... 33
7.4.5 Actual value 1....................................................................................................................... 33
7.4.6 PD1…PD8 ............................................................................................................................. 33
7.5 Parameter data ............................................................................................................................ 35
7.5.1 Parameter field.................................................................................................................... 36
7.6 Example messages ...................................................................................................................... 38
8. FAULT TRACKING......................................................................................................... 40
1. GENERAL
The Vacon NX AC drives can be connected to the Profibus DP using a fieldbus board. The drive can
then be controlled, monitored and programmed from the Host system.
The Profibus fieldbus board is installed in slot E on the control board of the AC drive.
Internal components and circuit boards are at high potential when the AC drive is
connected to the power source. This voltage is extremely dangerous and may
cause death or severe injury if you come into contact with it.
WARNING!
NOTE! You can download the English and French product manuals with applicable safety, warn-
ing and caution information from
http://drives.danfoss.com/knowledge-center/technical-documentation/.
REMARQUE Vous pouvez télécharger les versions anglaise et française des manuels du produit
contenant l’emsemble des information de sécurité, avertissements et mises en garde applica-
bles sur le site http://drives.danfoss.com/knowledge-center/technical-documentation/.
The maximum cable length depends on the transmission speed and cable type (see Table 2-3). The
specified cable length can be increased using the repeaters. The use of more than 3 repeaters in se-
ries is not recommended.
NOTE!
3. PROFIBUS DP
3.1 Introduction
Profibus is a vendor-independent, open fieldbus standard for a wide range of applications in manu-
facturing, process and building automation. Vendor independence and openness are guaranteed by
the Profibus standard EN 50 170. With Profibus, devices of different manufacturers can communicate
without special interface adjustments. Profibus can be used for both high-speed time critical data
transmission and extensive complex communication tasks. The Profibus family consists of three
compatible versions.
Profibus DP
Optimized for high speed and inexpensive hookup, this Profibus version is designed especially for
communication between automation control systems and distributed I/O at the device level. Profibus-
DP can be used to replace parallel signal transmission with 24 V or 0 to 20 mA.
Profibus PA
Profibus PA is designed especially for process automation. It permits sensors and actuators to be
connected on one common bus line even in intrinsically-safe areas. Profibus PA permits data com-
munication and power over the bus using a 2-wire technology according to the international standard
IEC 1158-2.
Profibus FMS
Profibus FMS is the general-purpose solution for communication tasks at the cell level. Powerful
FMS services open up a wide range of applications and provide great flexibility. Profibus FMS can also
be used for extensive and complex communication tasks.
Profibus specifies the technical and functional characteristics of a serial fieldbus system with which
decentralized digital controllers can be networked together from the field level to the cell level. Pro-
fibus distinguishes between master devices and slave devices.
Master devices determine the data communication on the bus. A master can send messages without
an external request when it holds the bus access rights (the token). Masters are also called 'active
stations' in the Profibus protocol.
Slave devices are peripheral devices. Typical slave devices include input/output devices, valves,
drives and measuring transmitters. They do not have bus access rights and they can only
acknowledge received messages or send messages to the master when requested to do so. Slaves
are also called 'passive stations'.
3.2 Profiles
The Profibus DP protocol defines how user data are to be transmitted between the stations over the
bus. User data are not evaluated by the Profibus DP transmission protocol. The meaning is specified
in the profiles. In addition, the profiles specify how Profibus DP is to be used in the application area.
The following Profibus DP profile is used in VACON NX Profibus Fieldbus board.
NOTE! The OPT-C3/C5 option board has two hardware versions. These two hardware versions have
different layout, grounding settings, firmware packages and they use different tools for firmware up-
dating. The OPT-C3/C5 hardware version number can be read from the bottom side on the bottom left
of the option board PCB (see Figure 4-1).
11685_uk
Figure 4-1Hardware version text position
Correct firmware must be used for different hardware, incorrect firmware cannot be loaded into un-
supported hardware. See Table 4-1 for firmware support on different hardware.
NOTE! FW0232 is designed to be compatible with the 10502 firmware. Only difference is that Vacon
Loader must be used for firmware update.
Vacon Loader is supported in the NX products which use firmware mentioned in Table 4-2. Older NX
firmware versions support only the NCLoad tool, and therefore updating of the PC01294 OPT-C3/C5
firmware is not possible unless the NX firmware is updated.
1
2
3
4
5
NOTE! Normally, the option board has already been installed in slot E of the control board. It is not
necessary to detach the whole board for the grounding of the bus cable shield. Just detach the termi-
nal block.
4.1.1.1 Grounding the bus cable shield directly to the AC drive frame
Jumper X1
11689_00
Figure 4-4. PC01294 grounding jumpers
Figure 4-5.
3 Leave no more than 1 cm of the red and green data cable outside the terminal block and
strip the data cables at about 0.5 cm to fit in the terminals. See pictures below.
NOTE! Do this for both bus cables.
Figure 4-6.
Figure 4-7.
4 We recommend you to use an Abico connector to fit the grounding cable into the grounding
terminal (#1).
Insert the red and green data cables of both Profibus cables into terminals #3 (red) and #4
(green).
RG
Figure 4-8.
5 Place the Profibus board into slot E of the control board (see board installation on page 22)
and fix both the Profibus cables on the frame with the clamp.
Figure 4-9.
4.1.1.2 Grounding the bus cable shield directly to the AC drive frame using an RC-filter
We recommend you to do the grounding in this manner when the distance between the devices ex-
ceeds 50 meters (55 yds.). When the distance between the devices is long, disturbances (e.g. voltage
spikes) are more likely to appear. In this grounding method, the disturbances are filtered out. Even if
the ground planes of A, B and C are different (which is very typical e.g. in construction) there is no
current between them because the points do not have a ground connection.
NOTE:
If a potential difference occurs between the grounding points, equalization current can flow through a
shield connected at both ends. In this case, install an additional potential equalization line and set this
jumper X1 in ON position.
A B C
Profibus cable Profibus cable Profibus cable
Jumper X1
11689_00
Figure 4-12. PC01294 grounding jumpers
2 Carry out the grounding in the same way as advised in Chapter 4.1.1.1.
1. Strip about 5 cm of the Profibus cable in the same way as shown in Figure 4-5 but cut off the grey
cable shield.
Remember to do this for both bus cables (except for the last device).
2. Leave no more than 1 cm of the red and green data cable outside the terminal block and strip the
data cables at about 0.5 cm to fit in the terminals. See Figure 4-6 and Figure 4-7.
NOTE! Do this for both bus cabels.
3. Insert the red and green data cables of both Profibus cables into terminals #3 (red) and #4
(green). See Figure 4-8.
4. Strip the Profibus cable at such a distance from the terminal that you can fix it to the frame with
the grounding clamp. See Figure 4-14.
5. Ground the cable shield at both ends and on all loads by 360° connection.
9 8 7 6
9 8 7 6
Phoenix SUBCON-PLUS-PROFIB/AX/SC 27 44 38 0
Siemens Profibus connector 6GK1 500-0EA02
15 mm
Max.
length of
the D-
connector
60 mm
Push the
clamp
while
tightening
the screw
Figure 4-18. Attach the D-connector and tighten the grounding plate
NOTE! Termination works properly when the drive has power (active termination) connected.
Bus termination ON
X6
Bus termination OFF
11690_00
Figure 4-19. PC00257 termination resistor jumper X6
Bus termination ON
11691_00
Figure 4-20 PC01294 termination resistor jumper X13
Green
Yellow
Red
X6
X1
11692_00
Figure 4-21. LED indications on the PC00257 Profibus board
PS BS FS
11693_00
Figure 4-22 LED indications on the PC01294 Profibus board
A Vacon NX AC drive
D Install Profibus DP option board in slot E on the control board of the AC drive. Make
sure that the grounding plate (see below) fits tightly in the clamp.
1
2
3 X6
4
5
X1
E Make a sufficiently wide opening for your cable by cutting the grid as wide as nec-
essary.
F Close the cover of the control unit and the cable cover.
6. COMMISSIONING
First, read the chapter 8, Commissioning and additional instructions in Vacon NXS/P User Manual.
Profibus parameters
To commission the Profibus board, enter the level G7.5.1.# from the Parameters group (G7.5.1). Give
desired values to all Profibus parameters (see Figure 6-1 and Table 6-1).
The parameters of every device must be set before connecting to the bus. Especially the parameters
“SLAVE ADDRESS” and “PPO TYPE” must be the same as in the master configuration.
Profibus status
To see the present status of the Profibus fieldbus, enter the Profibus status page from Monitor menu
(G7.5.2). See Figure 6-2 and Table 6-2 below.
READY READY
I/Oterm I/Oter m
Profibus status
0 Waiting parameter from Master
1 Waiting configuration from Master
2 Communication established
Table 6-2. Profibus status indications
AC drive application
Choose Fieldbus (Bus/Comm) as the active control place (see Vacon NXS/P User Manual, Chapter
7.6).
Master software
1. Set Control Word value to 0hex.
5. The Actual value is 5000 and the AC drive output frequency is 25.00 Hz
7. PROFIBUS-VACON NX INTERFACE
Features of the Profibus-Vacon NX interface:
Direct control of Vacon NX ( e.g. Run, Stop, Direction, Speed reference, Fault reset)
Full access to all Vacon NX parameters
Monitor Vacon NX status (e.g. Output frequency, Output current, Fault code)
7.1 General
Data transfer between Profibus DP master and slave takes place via the input/output data field. The
Master writes to Slave’s output data and the Slave answers by sending the contents of its input data to
the Master. The contents of the input/output data is defined in the device profile. The device profile for
AC drives is PROFIDRIVE.
The Vacon NX AC drive can be controlled by Profibus DP Master using the PPO-types defined in
Profidrive (see Chapter 7.3). When fieldbus has been selected as the AC drive’s active control place,
the AC drive’s operation can be controlled from the Profibus DP Master. Whether or not the active
control place is fieldbus, the AC drive can be monitored and its parameters set by the Profibus DP
Master.
PROFIDRIVE
Data transfer follows the document Profibus Profile for variable speed drives, PROFIDRIVE.
BYPASS
The information of the Process Data field is transferred to the application interface without han-
dling
Parameter setting takes place according to the Profidrive definition
ECHO
The OUTPUT data written by the Master is echoed back to the Master in the INPUT field
The data is not shown in the AC drive but the echoing is carried out on the option board
This mode can be used when the function of the bus connection is tested
PPO 1
PPO 2
PPO 3
PPO 4
PPO 5
Descriptions:
Byte
ID Parameter type and number
IND Parameter subindex
VALUE Parameter value
CW Control Word
SW Status Word
REF Reference Value 1
ACT Actual Value 1
PD Process Data
The use of process data depends on the application. In a typical situation the device is started and
stopped via the ControlWord (CW) written by the Master and the Rotating speed is set with Reference
(REF). Via PD1…PD8 the device can be given other reference values (e.g. Torque reference).
With the help of the StatusWord (SW) read by the Master, the status of the device can be seen. Actual
Value (ACT) and PD1…PD8 show the other actual values. See Figure 7-2.
ControlWord
Reference 1
PROFIBUS MASTER
ProcessData 1
…
APPLICATION
ProcessData 8
StatusWord
Actual Value 1
ProcessData 1
ProcessData 8
The Control command for the state machine (see Figure 7-3.) The state machine describes the
device status and the possible control sequence of the AC drive.
The control word is composed of 16 bits that have the following meanings:
Bit Description
Value = 0 Value = 1
0 STOP 1 (by ramp) ON 1
1 STOP 2 (by coast) ON 2
2 STOP 3 (by ramp) ON 3
3 RUN DISABLE ENABLE
4 No Action START
5 No Action START
6 No Action START
7 No Action FAULT RESET (0 -> 1)
8 No Action No Action
9 No Action No Action
10 Disable Profibus control Enable Profibus control
11 Fieldbus DIN1=OFF Fieldbus DIN1=ON
12 Fieldbus DIN2=OFF Fieldbus DIN2=ON
13 Fieldbus DIN3=OFF Fieldbus DIN3=ON
14 Fieldbus DIN4=OFF Fieldbus DIN4=ON
15 Fieldbus DIN5=OFF Fieldbus DIN5=ON
Table 7-1. Control word bit descriptions
With the help of the control word, start and stop commands can be given to the device. Also a fault
can be acknowledged.
As shown above, there are several stop modes. It depends on the operating situation, which mode is
selected.
NOTE! In Vacon NX AC drive STOP1 and STOP3 are identical. Also STOP2 and RUN DISABLE are iden-
tical.
Commands STOP1 and STOP3 can be used only with either one of the motor control modes (P2.6.1)
Frequency control or Speed control selected and the fieldbus selected as the control place.
Information about the status of the device and messages is indicated in the Status word.
The Status word is composed of 16 bits that have the following meanings:
Bit Description
Value = 0 Value = 1
0 Not Ready (initial) READY 1 **
1 Not Ready READY 2 **
2 DISABLE ENABLE **
3 NO FAULT FAULT ACTIVE *
4 STOP 2 NO STOP 2 **
5 STOP 3 NO STOP 3 **
6 START ENABLE START DISABLE **
7 No Warning Warning *
8 Reference Actual value Reference = Actual value *
9 Fieldbus control OFF Fieldbus control ON *
10 Not used Not used
11 Not used Not used
12 FC stopped Running *
13 FC not ready FC ready *
14 Not used Not used
15 Not used Not used
Table 7-3. Status word bit descriptions
Power ON
Fault
Reset fault
STOP by ramp Set CW Bit0=0, Bit10=1
CW Bit7=0
xxxx x1xx xxxx xxx0
READY 2; SW Bit1=0
CW Bit7=1
STATE: STOP
READY 1; SW Bit0=0
DISABLE; SW Bit6=0 STOP 2; CW Bit1=0
STATE: STOP
READY 2; SW Bit1=1
STOP by ramp
Set CW Bit3=1 STOP 3; SW Bit5=0
xxxx x1xx xxxx 1111
STATE: STOP
ENABLE; SW Bit2=1
STATE: RUN
RUNNING
Figure 7-3.
7.4.4 Reference 1
CW REF PD1 PD2 PD3 PD4 PD5 PD6 PD7 PD8
This is the actual value from the AC drive. Used normally as Speed reference, with the value between
–10000...10000. In the application, the value is scaled in percentage of frequency area between set
minimum and maximum frequency.
7.4.6 PD1…PD8
ProcessData Master -> Slave
The Master can write a maximum of 8 additional setting values to the device with the help of the Pro-
cess Data. How these setting values are used is totally dependent on the application in use.
The master can read the AC drive’s actual values using the process data variables.
Depending on the used application, the contents are either standard or can be selected with a param-
eter.
Profibus DP m a ster
VACO N N X
1 Output Frequency
2 Motor Speed
.
.
.
Selector Parameter
or fixed variable
N XB1
Figure 7-4. Control of Process data (see APPENDIX)
ID IND VALUE
ID
Read/Write from Drive
IND
PROFIBUS MASTER
VALUE
APPLICATION
ID
Answer from Drive
IND
VALUE
The parameter addresses are determined in the application. Every parameter and actual value has
been given an ID number in the application. The ID numbering of the parameter as well as the param-
eter ranges and steps can be found in the application manual in question. The parameter value must
be given without decimals. The ID numbers of each parameter/actual value are found in the applica-
tion manual. The ID numbers are grouped as follows:
ID IND VALUE
ID byte1 ID byte2
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Request/Response SM Parameter Number (= Vacon ID number)
type
SM: Spontaneous bit (not used)
Request/Response types
Request Function Response Function
0 No request 0 No response
1 Read parameter value (word) 1 Parameter value ready (word)
2 Write parameter value (word) 7 Request rejected (+fault code)
Index
ID IND VALUE
Not in use
Data Value
ID IND VALUE
In writing mode the data to be written is placed in the field “Data word 2”.
In reading mode the answer is in the field ”Data word 2”.
“Data word 1” is normally zero.
8. FAULT TRACKING
The table below presents the faults related to the Profibus option board. For more information, see
also Vacon NXS/P User Manual, Chapter 10.
The Profibus option board status LEDs have been described in more detail in Chapter 4.4.
54 Slot fault Defective option board or slot Check the board and slot.
Contact the nearest Vacon distributor.
You can define with parameters how the AC drive reacts to certain faults:
9. TYPE FILES
9.1 GSD-file (“Profibus Support Disk” files: vac29500.GSD, vac29500.GSE)
#Profibus_DP Sync_Mode_supp = 1
GSD_Revision = 1 Auto_Baud_supp = 1
Vendor_Name = "Vaasa Control" Set_Slave_Add_supp = 0
Model_Name = "Vacon NX" Min_Slave_Intervall = 20
Revision = "1.0" Modular_Station = 1
Ident_Number = 0x9500 Max_Module = 5
Protocol_Ident = 0 Max_Input_Len = 28
Station_Type = 0 Max_Output_Len = 28
FMS_supp = 0 Max_Data_Len = 56
Hardware_Release = "HW1.0" Modul_Offset = 0
Software_Release = "SW1.0" Slave_Family = 1
9.6_supp = 1 Fail_Safe = 1
19.2_supp = 1 Max_Diag_Data_Len = 6
93.75_supp = 1 Module = "VACON PPO 1" 0xF3, 0xF1
187.5_supp = 1 EndModule;
500_supp = 1 Module = "VACON PPO 2" 0xF3, 0xF5
1.5M_supp = 1 EndModule;
3M_supp = 1 Module = "VACON PPO 3" 0xF1
6M_supp = 1 EndModule;
12M_supp = 1 Module = "VACON PPO 4" 0xF5
MaxTsdr_9.6 = 60 EndModule;
MaxTsdr_19.2 = 60 Module = "VACON PPO 5" 0xF3, 0xF9
MaxTsdr_93.75 = 60 EndModule;
MaxTsdr_187.5 = 60
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150 Module = "___________special____________" 0x00
MaxTsdr_3M = 250 EndModule
MaxTsdr_6M = 450 Module = "PPO 2" 0xF3, 0xF1, 0xF1, 0xF1
MaxTsdr_12M = 800 EndModule
Redundancy = 0 Module = "PPO 4" 0xF1, 0xF1, 0xF1
Repeater_Ctrl_Sig = 0 EndModule
24V_Pins = 0 Module = "PPO 5" 0xF3, 0xF1, 0xF1, 0xF1, 0xF1,
Implementation_Type = "SPC3" 0xF1
EndModule
Freeze_Mode_supp = 1
10. APPENDIX
The fieldbus master can read the AC drive’s actual values using process data variables.
Basic, Standard, Local/Remote, Multi-Step, PID control and Pump and fan control applications use
process data as follows:
The Multipurpose application has a selector parameter for every Process Data. The monitoring values
and drive parameters can be selected using the ID number (see NX All in One Application Manual, Ta-
bles for monitoring values and parameters). Default selections are as in the table above.
Document ID:
Vacon Ltd
Member of the Danfoss Group
Runsorintie 7 Rev. B
65380 Vaasa
Finland Sales code: DOC-OPTC3/C5+DLUK