Certificate

No.: V 484.01/15

Product tested Safety valve - Final element, Certificate Mokveld Valves B.V.
complete with spring return holder Nijverheidsstraat 67
actuator 2802 AJ Gouda
The Netherlands

Type designation RZD-X-SAV with M-series actuator

Codes and standards IEC 61508 Parts 1-7:2010 (in IEC 61511 Parts 1-3:2004 (in
extracts) extracts)

Intended application The safety function of the RZD-X-SAV is to perform a shut-off (Fail Close-
FC) or to blowdown (Fail Open-FO) of the process within a process time of
maximum 2 seconds.
The valve actuator combination has a confirmed systematic capability SC 3
and is suitable to be applied in SIL 3 applications.
Based on the proven in use failure data it can be applied in accordance with
Route 2H.
The Hardware Fault Tolerance must be selected according to the specific
application and must comply with the requirements of the relevant
10/222 12. 12 E A4 ® TÜV, TUEV and TUV are registered trademarks. Utilisation and application requires prior approval.

standards.

Tel.: +49 221 806-1790, Fax: +49 221 806-1539, E-Mail: [email protected]
TÜV Rheinland Industrie Service GmbH, Am Grauen Stein, 51105 Köln / Germany
Specific requirements The instructions of the associated Installation, Operation and Safety
Manual must be considered.

Summary of test results see back side of this certificate.

Valid until 2020-06-01

The issue of this certificate is based upon an examination, whose results are documented in Report No. V 484.01/15
dated 2015-06-01.
This certificate is valid only for products which are identical with the product tested. It becomes invalid at any change of
the codes and standards forming the basis of testing for the intended application.

Köln, 2015-06-01
Certification Body for FS-Products Dipl.-Ing. Stephan Häb

www.fs-products.com

Powered by TCPDF (www.tcpdf.org)


Certificate No. V 484.01/15
Manufacturer Mokveld Valves B.V.
Series RZD-X-SAV including M-Series actuator

The safety function of the RZD-X-SAV is to perform a shut-off (Fail Close-FC) or to blowdown (Failure
Open-FO) of the process within a process time of maximum 2 seconds.

Device specific values


Proof Test Coverage PTC % 95
Hardware Fault Tolerance HFT [-] 0
Diagnostic Coverage DC % 0
Maintenance Coverage MTC % 100
Safe Failure Fraction SFF % 91
Type of sub-system IEC 61508-2,
[-] Type A
7.4.4.1.2

Derived values for 1oo1 architecture


Low demand mode of operation
Process duty clean unclean
1)
Failure mode FS TSO FS TSO
Operational Years y 19462 19462 16862 16862
Undetected Dangerous Failure Rate λDU 1/h 1,17E-08 1,29E-07 1,35E-08 1,56E-07
FIT 12 129 14 156
MTBF (Dangerous Failures) MTBFDU h 8,52E+07 7,75E+06 7,39E+07 6,42E+06
y 9731 885 8431 733
Detected Dangerous Failure Rate λDD h 0 0 0 0
FIT 0 0 0 0
2)
Safe Failure Rate λS 1/h 1,58E-06 1,58E-06 1,58E-06 1,58E-06
FIT 1577 1577 1577 1577
Assumed Test Interval Ti y 1 1 1 1
(1-
Confidence Level % 95 95 95 95
alpha)
Undetected Dangerous Failure Rate
λDU 1/h 1,51E-08 1,31E-07 1,74E-08 1,58E-07
(1-α= 95 %)
Assumed Test Interval Ti y 1 1 1 1
Probability of Dangerous Failure on Failure/
PFDavg 6,61E-05 5,75E-04 7,63E-05 6,93E-04
Demand (1- α = 95 %) Demand

3)
High or continuous demand mode of operation
Probability of Dangerous Failure per Failure/
PFH 1,51E-08 1,31E-07 1,74E-08 1,58E-07
Hour (1- α = 95 %) Hour
1) FS = Full Stroke; TSO = Tight Shut Off
2) No field data available; SFF has been used to estimate Safe Failure Rate
3) max. nop = 10 / y

Useful lifetime under specified operating conditions


An initial useful lifetime of more than 6 years (+ 3 years storage) can only be favored under the
responsibility of the operator, considering the specific external conditions (e.g. process fluid quality,
ambient conditions etc.) and the actual in-situ experience. Furthermore the manufacturer’s safety
manual should be respected.

Remarks
The validity of this report is bound to the proven employment of a safety related quality management
system by the manufacturer.