Standard Features: Engine PERKINS, 4006TAG3 Alternator LEROY SOMER, LSA491L9A
Standard Features: Engine PERKINS, 4006TAG3 Alternator LEROY SOMER, LSA491L9A
STANDARD FEATURES
Radiator 50°C [122°F]°C max T° air inlet with coolant cap
Mechanically welded chassis with antivibration suspension
Control panel conmpliant with European standard
Power circuit breaker
Oil drain tap + diesel pipe
Batteries with cables and batterie mounting
Userguide
POWER DEFINITION
PRP : Prime Power is available for an unlimited number of annual operating hours in variable load applications, in accordance with ISO 8528-1. A 10%
overload capability is available for a period of 1 hour within 12-hour period of operation, in accordance with ISO 3046-1 –
ESP : The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO 8528-1. Overload is
not allowed.
TERM OF USE
Standard reference conditions 40 °C Air Intlet Temp, 500 m A.S.L. 60 % relative humidity. All engine performance data based on the above mentioned
maximum continuous ratings.
Noise level
Dimensions (mm) Tank
Type Weight
LxWxH (l)
dB(A)@1m dB(A)@7m
Soundproofed Version
8150 kg Net
M427-P 83.1 73 6400x2170x3333 9310 kg 930
Gross
TELYS Specifications:
Option Panel Frequency meter, Ammeter, Voltmeter
Alarms and faults:
Oil pressure, water temperature, No start-up, Overspeed, Min/max
alternator, Min/max battery voltage, Low fuel level, Emergency stop
Engine parameters:
Hours counter, Oil pressure, Water temperature,Engine speed, Battery
voltage, Fuel level
KERYS
Option Panel
Specifications:
Frequency meter, Ammeter, Voltmeter
Alarms and faults:
Oil pressure, water temperature, No start-up, Overspeed, Min/max
alternator, Min/max battery voltage, Low fuel level, Emergency stop
Engine parameters:
Hours counter, Oil pressure, Water temperature, Engine speed,
Battery voltage, Fuel level
Additional specifications:
Website, Troubleshooting, Assistance and Maintenance, Plotting
and logging, Load impact, 8 configurations available,
Compliance with international standards...