Page 1 / 4
Technical Schedule For Transformers Design nr.: 8126201 - Rev.0
1 Standards 14-SAMSS-531 10th July-2018,26-SAMSS-59,IEEE C.57.12.00
2 Tag Numbers U63-001-XFR(T)-501 & 502
3 Rated Power
at cooling type ONAN with radiators 50.0 MVA
at cooling type ONAF fans 66.667 MVA
4 Manufacturers type TOFL 66667 / 73
5 Insulation class of windings A (105 ˚C)
6 Rated frequency / phases 60 Hz / 3 phases
7 Ambient temperatures 30 ° C / Design ambient temperature
-5 ° C / minimum ambient temperature
Temperature rise of top oil / average winding / hottest spot of
8 65 / 65 / 80 K
winding
9 a) mounting outdoors
b) duty / purpose continuous / step down
c) altitude of operation max. 1000 m above sea level
10 Vector group symbol Dyn1
Petromin oil /Gulf chemical oil, according
Uninhibited as per
11 Insulation liquid to cl.4 of 26-SAMSS-059,27th May 2014
attached oil data sheet
(IEC 60296 Class1)
12 Number of winding Two
13 Rated voltage and power
at HV 69.0 kV 66.667 MVA
at LV 13.80 kV 66.667 MVA
at Tertiary NA kV MVA
Neutral grounding
14 at HV not applicable
at LV Through NGR, (NGR Not in SPTC Scope)
IEEE Std. C57.131-
16 Type of regulation at HV side on load acc. to IEEE Vacutap 2012
Tappings at HV side 16x0.625% -16x0.625%
full power on each tapping
Details of Tap Changer MR: VM III 500K-123/C-18 35 3WR
Tap changer compartment pressure rise relay Yes
16 Category of voltage variation Constant Flux Voltage Variation
17 Parallel operation No
18 Maximum Flux density ≤ 1.75 T
19 Maximum Current density
- HV Winding ≤ 4.5 A/mm2
- LV Winding ≤ 4.5 A/mm2
Page 2 / 4
20 Type of Insulation
- HV Winding Uniform
- LV Winding Uniform
-Winding material Copper
-Core material CRGO
21 Insulation levels Highest
Power Lightning Switching
voltage for
Frequency Impulse Impulse
equipement
HV Bushing 140 350 -
LV Bushing 34 110 -
HV line 69 kV 73.0 140 350 -
LV Line 13.8 kV 17.0 34 110 -
LV neutral 13.8 kV 17.0 34 110 -
22 Losses Tolerances
Guaranteed no load losses at 100 % Un; 100% fn 40.0 kW 0 %
Guaranteed load losses at 50.0 MVA, 85°C
between windings: HV - LV
tap position N 145.0 kW 0 %
Total losses tap position N 185.00 kW 0 %
Auxiliary Losses 8.0 kW
23 Efficiency At 0.9 PF At 1 PF
At 25% load 99.58 99.62
At 50% Load 99.67 99.71
At 75% load 99.64 99.69
At 100% load 99.59 99.64
24 Winding Termination Type Location
HIGH Voltage Oil to Air outdoor composite bushing Top cover
Low Voltage Air filled Cable Bus Tank Side
Low Voltage Neutral Air filled Cable Box Tank Side
25 Current Transformers
HIGH Voltage windings/Bushings
Low Voltage Windings/Bushings CTs as per the CT Specification drawing 8126162
Winding Neutral End/Bushings
26 Guaranteed short circuit impedance between windings
HV - LV at 50.0 MVA, 85°C Tolerances
tap position N 8.5 % ±7.5 % as per IEEE
27 Short circuit impedance between windings
HV - LV at 66.667 MVA, 85°C
tap position N 11.3 % ±7.5 % as per IEEE
28 Guaranteed no load current at 100 % Un; 100% fn 0.50 % Tolerance: 30 % As per IEC
Page 3 / 4
29 Guaranteed noise level
Noise pressure level at 100%Un at ONAN 75 dB(A) @ 0.3 Meters
As per NEMA TR-1, and IEEE Std ONAF 77 dB(A) @ 2.0 Meters
C57.12.90-2010, Fig 30, Page 66. dB(A)
30 Dimensions and masses (approx.)
Length 7,175 mm ±5%
Width 5,480 mm ±5%
Height 5,582 mm ±5%
Oil mass 19,300 kg
Total mass 81,000 kg
31 a) Bushings on HV Silicon rubber insulator Composite bushing
LV porcelain type with porcelain housing
LV N porcelain type with porcelain housing
b) Creepage distance HV 40 mm/kV
LV / LVN 25 mm/kV
c) Cable boxes on HV not provided
LV / LVN air filled
Tert. N.A.
32 Voltage supply for auxiliary equipment
Marshalling Box, Fans 480 VAC, 3-Phase, 60Hz, 3-Wire
Marshalling Box Lighting/Heater/Socket 230 VAC, 1-Phase, 60Hz
RTCC Lighting/Heater/Socket -
AVR -
MDU Control circuit 125 Vdc
MDU Lighting/Heater/Socket 230 VAC, 1-Phase, 60Hz
33 Signalling equipment
a) Magnetic oil level indicator
- on Trafo side provided
- on OLTC side provided
b) Buchholz relay with contacts for trafo provided
c) Protection relay for OLTC ANSI Code#63, Function: Buchholz Relay per OLTC
d) Top oil thermometer with contacts provided
e) Winding temperature indicator with provided on both LV & HV
thermal image current transformer
f) Current transformers for signal Provided as per document No. 8126162
g) Marshalling box on transformer yes
Protection class NEMA 4X
h) Surge arresters Not in SPTC scope (Only a provison is provided)
i) Dehydrating breather silicagel type
j) Motor Drive Unit (MDU) Provided
34 Cooling : on tank
- radiators 8 no.s , detachable type
- fans 6 no.s, 456V 1.8A , 895 W each
- pumps not applicable
Page 4 / 4
35 Oil preservation :
- conservator with atmoseal
- designed for vacuum 100 % below atmospheric pressure
36 Tank and cover :
- designed for vacuum 100 % below atmospheric pressure
- designed for overpressure 0.05 MPa over normal operational pressure
- type of cover bolted
- tank walls thickness 10mm
- tank base thickness 20mm
- cover thickness 20 mm
- jacking bosses provided
- towing lugs provided
- lifting lugs provided
- base type skid
- rating plate provided
- earthing pad provided
37 Valves :
- filter valves NW 50 (1 top + 1 bottom) provided
- drain valve on tank provided
- closing valve between Buchholz and conservator provided
- closing valve for RS 2001 (protection relay provided
for OLTC) and conservator
- butterfly valves between radiators and tank provided
- thermometer pocket DIN 42554 provided
38 Painting: As per painting specification doc no. 8126056
- tank NC5-I M
- radiators NC5-I M
- colour RAL 7035 (Light grey)
39 Miscellaneous & Accessories
-Oil Temeperature Indicator provided
-Winding Temeperature Indicator provided
-Combustible Gas Detector (Buchholz relay) provided
-Padlockable Drain Valve provided
Rev. Description Prepared Checked Approved Date
0 First Issue Mahdi Ayyoub Ayyoub 25/Feb/21