The DPT100 is a range of compact, configurable single-input transducers that offer accurate true-RMS measurements for utilities and industrial applications. It has best-in-class response times of 100-220ms, long-range configurable inputs and outputs, and load-independent accuracy on its two isolated analog outputs. The DPT100 is compact at 45x75x105mm and has diagnostic LEDs.

Uploaded by

Teguh Waluyo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
160 views4 pages

DPT100 - Single Function Transducer - Cewe

The DPT100 is a range of compact, configurable single-input transducers that offer accurate true-RMS measurements for utilities and industrial applications. It has best-in-class response times of 100-220ms, long-range configurable inputs and outputs, and load-independent accuracy on its two isolated analog outputs. The DPT100 is compact at 45x75x105mm and has diagnostic LEDs.

Uploaded by

Teguh Waluyo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

DPT100: single phase

single-function transducers Accurate


class 0.2, 0.5 & 1
USB
programming
Response time
~100-220 ms
Compact size

Compact, long range site configurable transducers Teguh Waluyo


08212 4272 464
Cewe - Secure

DPT100 is a range of compact, configurable single measurand


transducers designed to meet the demanding needs of supply
utilities and industrial applications. It offers accurate true-RMS
measurements for high efficiency and quick response time. It is
equipped with two load-independent, galvanically-isolated
analogue outputs that can be configured for desired input
range and output curves.
Ÿ Best in class response time
Ÿ Long range, site-configurable inputs and outputs
Ÿ Load-independent accuracy on all outputs
Ÿ Diagnostic LEDs
Ÿ Compact footprint

System Measurement functions Output type Output range no. of Accuracy class
(Measurands) outputs

AC Voltage, current, Option for 0-20 mA, 4-20 mA, 0-10 mA, 0-5 mA* 2 0.2, 0.5, 1.0
frequency, active power mA or V 0-2 mA*, 0-1 mA*, 0-5 V, 0-10 V

DC Voltage, current Option for 0-20 mA, 4-20 mA, 0-10 mA, 0-5 mA* 2 0.2, 0.5, 1.0
mA or V 0-2mA*, 0-1 mA*, 0-5 V#, 0-10 V#

*available in accuracy class 1.0


#Available with DC Voltage function only
DPT100: single phase
Output cuves

Curve A Curve B
Linear Linear with live zero

Output Output

Input Input

Curve F Curve F
Compressed upper region Compressed lower region

Output Output

Input Input

Mechanical dimensions
105 mm
75 mm

45 mm Top view Isometric view


Front view
Technical specifications
Variants

AC/DC voltage
Nominal input (Un) 57.7 to 415 V
Measuring range 0 to 130 % Un (up to 500 V)
Measurement frequency 50/60 Hz (±5%)
Burden ≤0.2 VA
Maximum overload voltage 1.3 x Un continuously (500 V max.)
2 x Un for 1 s, with up to 10 repetitions at 10 s intervals
Scale factor 0.8 to 1.3 Un
For self-powered variant (AC/DC Voltage)
Measurement range 80 to 276 V AC/DC
Measurement range 0 to 110% Un
Burden ≤6VA, 3W with one output at 750 Ω
≤7VA, 3.5W with two outputs at 750 Ω each

AC current
Nominal input (In) 1 A to 5 A
Measuring current range 0 to 150% In
Scale factor 0.6 to 1.5 of In
Burden ≤0.2 VA
Maximum overload current 2 x In continuously
20 x In for 1 s, with up to 10 repetitions at 100 s intervals

DC current
Measurement input range -20-0-(+20) mA directly, or -300-0-(+300) mV through shunt

Frequency
Nominal input voltage (Un) 57.7 to 415 V
Measurement range 45 Hz to 55 Hz or 55 Hz to 65 Hz
Accuracy ±0.2%

Active Power
Nominal input voltage (Un) 57.7 to 415 V
Input voltage range 0 to 130 % Un (up to 500 V)
Nominal input current (In) 1 A to 5 A
Input current range 0 to 150% In
Measurement frequency 50/60 Hz (±5%)
Scale factor 0.5 to 1.5 of Un x In (at unity power factor)

High auxiliary
Nominal voltage range 80-276 V AC/DC (±10%)
Frequency 50/60 Hz
Maximum burden ≤6VA, 3W with one output at 750 Ω
≤7VA, 3.5W with two outputs at 750 Ω each

Low auxiliary
Nominal voltage range 24-80 V DC (±10%)
Maximum burden ≤3 W with one output, ≤4 W with two outputs
Self-powered (only for voltage transducers)
Nominal voltage range 80-276 V AC/DC
Maximum burden ≤6VA, 3W with one output at 750 Ω
≤7VA, 3.5W with two outputs at 750 Ω each
DPT100: single phase
Technical specifications
Analogue outputs
Type mA or V
Maximum load resistance ≤750 Ω for 20 mA, ≥2 kΩ for 10 (for each output)
Response time 5 cycles measurement (≤100-220 ms)
Ripple <0.4 % peak to peak
Temperature range
Operating range -5 °C to +55 °C
Functional range -25 °C to +70 °C
Usage group 1
Mechanical
Dimension (W x H x D) 45 x 75 x 105 mm
Weight 0.4 kg (approx.)
Material Fire-retardant polycarbonate (PC-FR), UL94 V-0
Mounting DIN (EN 50022)
Connector type Screw terminals
Conductor size for terminals ≤4 mm2
Environmental
Protection class II (double insulation) EN 61010-1
Pollution degree 2
Installation category CAT III for < 300V AC and CAT II for < 600V AC
Protection degree Protection housing: IP 40, terminals: IP 20
Compliance
Standards IEC 60688, IEC 61010-1, IEC 61010-2-30,
IEC 61326-1, DIN 50022
Communication ports
Micro USB For on-site configuration
can be configured without auxiliary power
Configuration software tool ConfigView
For on-site configuration of measurement inputs, measurands, output curve and
online parameter reading. It can be freely downloaded from
www.cewesecure.se

Ordering key
DPT XXX-1YY X X X - 1 Y Y
Example
Specifications are subject to change without prior notice

DPT 611-126
where high auxiliary (6), Output Accuracy
mA output (1), accuracy class 0.2, 1: mA# 1: Cl 1.0 Function
function (6) 2: V 2: Cl 0.2 1: Voltage AC/DC
Aux supply HW Configuration 5: Cl 0.5 2: Current DC#
6: High 1 : Default** 7: Accuracy 3: Frequency
7: Low 2 : DC Current as per 5: Current AC
*Self powered is voltage transducer only.
8: Self Powered* configuration 6: Active Power
** Default means AC/DC voltage, AC current
#Current DC available only in
HW configuration: DC Current, output: mA