DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE
(Requirements for Electrical Installations – BS 7671 IEE Wiring Regulations)
DETAILS OF THE CLEINT ADDRESS OF THE INSTALLATION
Client and Installation
address address
Postcode: Postcode:
DETAILS OF THE INSTALLATION The installation is:
Extent of the New
installation
work covered An
by this addition
certificate
An
alteration
DESIGN, CONSTRUCTION, INSEPCTION AND TESTING
The extent of liability of the signatory/signatories is limited to the work described above as the
I/we, being the person/s responsible for the design, construction, inspection and testing of the subject of this certificate. For the DESIGN, CONSTRUCTION, INSPECTION & TESTING of the
electrical installation (as indicated by my/our signature/s below, particulars of which are described installation.
above, having exercised reasonable skill and care when carrying out the design, construction,
Name
inspection and testing hereby Certify that the design, construction, inspection and testing work for Signature Date
(Capitals)
which I/we have been responsible is, to the best of my/our knowledge and belief, in accordance with
BS 7671: 2008 amended to N/A (date) except for the departures, if any, detailed as follows:
The results of the inspection and testing reviewed by
Details of departures from BS 7671:2008, as amended (Regulations 120.3.120.4)
Name
Signature (Capitals Date
PARTICULARS OF THE CONTRACTOR NEXT INSPECTION * Enter interval in terms of years, months, or weeks, as appropriate.
Trading I RECOMMEND that this installation is further inspected and tested after an interval of not more than *
title
Address COMMENTS ON EXISTING INSTALLATION Additional information and report notes
Telephone No Postcode SCHEDULE OF ADDITIONAL RECORDS See attached schedule
Registration No: Branch No:
(Essential information) (if applicable)
Report reference: DOMESTIC ELECTRICAL INSTALLATION - GREEN.odt This form is based on the model shown in Appendix 6 of BS 7671 Report pages including inspection and test schedules 1 of 6
Tick boxes and enter details, as appropriate
SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS Nature of Supply Parameters
NOTES: (1) by enquiry (2) by enquiry or by measurement
◊ System ◊ Number and Type of ◊ Characteristics of Primary supply Overcurrent
(3) where more than one supply, the
Type(s) Live Conductors Protective Device(s)
higher or highest values
TN-S 1-phase 1-phase Nominal Nominal BS(EN)
V Hz
(2 wire) (3 wire) Voltage U (1) frequency f (1)
TN-C-S Type
2-phase 3-phase External earth fault loop
U (1) V Ω
TT (3 wire) (4 wire) impedance Ze (3/4) Rated A Short-circuit kA
current capacity
other Prospective fault Prospective fault
Single-phase kA 3- phase kA
current (2/3) current (2/3)
PARTICULARS OF INSTALLATION AT THE ORIGIN Tick boxes and enter details, as appropriate Measured Ze Ω Main Switch or circuit-Breaker
Maximum kVA/ Type Voltage
Means of earthing Details of installation Earth Electrode (where applicable) V
demand : (load) Amps BS(EN) rating
Distributor's Type: No of Rated
facility (eg rod(s), tape, etc)
Location: Number of smoke alarms
poles Current A
Installation earth Electrode Method of Protective measures Supply RCD
Ω
electrode resistance, RA: measurement: for fault protection conductor operating
mA
material: current I∆n
Earthing conductor Main protective bonding conductors and bonding of extraneous conductive parts ()
Conductor Conductor Conductor Water Oil Supply RCD
material: material: csa: service service conductor operating
2
csa: mm time ms
Conductor Continuity Location: Gas Structural Other
2 (at I∆n)
csa: mm check (√) (where not obvious) service steel service
SCHEDULE OF ITEMS TESTED Note: All boxes must be completed
External earth loop impedance, Ze Polarity Protection by separation of circuits
Installation earth electrode resistance, Ra Earth fault loop impedance Zs Other (*Please note below)
Continuity of protective conductors Verification of phase sequence * Further notes for items tested, if applicable
Continuity of ring final circuit conductors Operation of residual current device(s)
Insulation resistance between live conductors Functional testing of assemblies
Insulation resistance between live conductors and earth Verification of voltage drop
Report reference: DOMESTIC ELECTRICAL INSTALLATION - GREEN.odt This form is based on the model shown in Appendix 6 of BS 7671 Report pages including inspection and test schedules 2 of 6
SCHEDULE OF ITEMS INSPECTED Note: All boxes must be completed
Protective measures against electric shock Additional protection
Cables and conductors
Basic and fault protection
Extra low voltage Selection of of conductors for current carrying
Double or reinforced insulation SELV Presence of residual current devices(s)
capacity and voltage drop
Double or reinforced insulation Presence of supplementary bonding conductors Erection methods
Basic protection
Prevention of mutual detrimental influences Routing of cables in prescribed zones
Cables incorporating earthed armour, sheath or run
Proximity of non-electrical services
Insulation of live parts Barriers and enclosures in an earthed wiring system, or otherwise protected
and other influences
against nails, screws and the like
Fault protection Additional protection by 30mA RCD (where required
Segregation of band I and band II circuits or
in premises not under the supervision of skilled or
band II insulation used
instructed persons)
Automatic disconnected of supply Segregation of safety circuits Connection of conductors
Presence of fire barriers, suitable seals and
Presence of earthing conductors Identification
protection against thermal effects
Presence of diagrams, instructions, circuit
Presence of circuit protection conductors General
charts and similar information
Presence and correct location of
Presence of main protective bonding conductors Presence of danger notices
appropriate devices for isolation and switching
Choice and setting of protective devices (for fault protect and/or Presence of other warning notices, Adequacy of access to switchgear and
overcurrent) including presence of mixed wiring colours other equipment
Labelling of protective devices, switches Particular protective measures for
Electrical separation special installations and locations
and terminals
Connection of single pole devices for protection
For one item of current -using equipment Identification of conductors or switching in line conductors only
Correct connection of accessories and equipment
To indicate that an inspection or test has been carried out and the result Selection of equipment and protective
√ is satisfactory N/V To indicate that details could not be verified measures appropriate to external influences
To indicate that an inspection or test has been carried out and the result To indicate the inspection or test is not Selection of appropriate functional
X was unsatisfactory N/A applicable switching devices
Report reference: DOMESTIC ELECTRICAL INSTALLATION - GREEN.odt This form is based on the model shown in Appendix 6 of BS 7671 Report pages including inspection and test schedules 3 of 6
TEST INSTRUMENTS USED
Earth fault loop impedance Insulation resistance
Continuity RCD
Other Other
NOTES FOR RECIPIENT
THIS CERTIFICATE IS A VALUABLE DOCUMENT AND SHOULD BE RETAINED FOR FUTURE REFERENCE
This safety certificate has been issued to confirm that the electrical installation work to which it relates has been designed, constructed and inspected and tested in accordance with British Standard 7671
(The IEE Wiring regulations).
You should have received an original Certificate and the contractor should have retained a duplicate Certificate. If you were the person ordering the work, but not the owner of the installation, you
should pass this Certificate, or a full copy of it including the schedules immediately to the user.
The original certificate should be retained in a safe place and be shown to any person inspecting or undertaking further work on the electrical installation in the future. If you later vacate the property,
this Certificate will demonstrate to the new owner that the electrical installation complied with the requirements of British Standard 7671 at the time the Certificate was issued was issued. The
Construction (Design and Management) Regulations require that for a project covered by those Regulations, a copy of this Certificate, together with schedules is included in the health and safety
documentations.
For safety reasons, the electrical installation will need to be inspected at appropriate intervals by a competent person. The maximum time interval recommended before the next inspection is stated
in the Certificate under “Next Inspection.”
This Certificate is intended to be issued only for a new electrical installation or for new work associated with an alteration or addition to a existing installation. It should not have been issued for the
inspection of an existing electrical installation. A “Periodic Inspection Report” should be issued for such a periodic inspection.
The Certificate is only valid if a Schedule of Inspection of Test Results is appended.
Report reference: DOMESTIC ELECTRICAL INSTALLATION - GREEN.odt This form is based on the model shown in Appendix 6 of BS 7671 Report pages including inspection and test schedules 4 of 6
DISTRIBUTION BOARD DETAILS
DB Zs at this Ipf at this Main switch type Supply
Rating: Amps mm2 Earth: mm2
ref.: board (Ω): board (KA): BSEN reference: conductors:
Supply protective
Distribution Supplied No. Of
device type: Rating: Amps
board location: from: phases:
BSEN reference:
CIRCUIT DETAILS TEST RESULTS
Max.Disconnection time permitted (s)
Circuit
conductors
Overcurrent devices RCD Circuit impedances Ω Insulation resistance RCD
All circuits
Maximum Measured Zs Ω
Number of points served
Maximum permitted Zs Ω
Short circuit capacity (KA)
Ring final circuits (At least
Reference method
Circuit Reference
only (Measured end one column
Phase /Neutral M Ω
Type of wiring
Neutral /Earth M Ω
Phase /Phase M Ω
Phase /Earth M Ω
to end) to be
At 5 x IΔn ms
Polarity
Type BS EN
completed)
Live (mm2)
cpc (mm2)
Rating (A)
At IΔn ms
IΔn mA
Circuit designation
r1 rn r2 R1 + R2 R2
Report reference: DOMESTIC ELECTRICAL INSTALLATION - GREEN.odt Report pages including inspection and test schedules 5 of 6
CODES FOR TYPES OF WIRING
A B C D E F G H O (other please state)
PVC/PVC PVC CABLES PVC CABLES IN PVC CABLES IN PVC CABLES IN PVC/SWA XLPE/SWA MINERAL-
CABLES IN METALLIC NON-METALIC METALIC NON-METALIC CABLES CABLES INSULATED
CONDUIT CONDUIT TRUNKING TRUNKING CABLES
Report reference: DOMESTIC ELECTRICAL INSTALLATION - GREEN.odt Report pages including inspection and test schedules 6 of 6