Guaranteed Technical Particulars: (200amps

This document contains the manufacturer's guaranteed technical specifications for 200A and 100A MCCBs and enclosures. It includes 20 items describing specifications such as the manufacturer name and address, model number, operating voltage, insulation rating, breaking capacity, dimensions and standards compliance. The manufacturer is required to fill in their guaranteed data against NESCO's requirement for each item described.

Uploaded by

Azad Rahman
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
65 views

Guaranteed Technical Particulars: (200amps

This document contains the manufacturer's guaranteed technical specifications for 200A and 100A MCCBs and enclosures. It includes 20 items describing specifications such as the manufacturer name and address, model number, operating voltage, insulation rating, breaking capacity, dimensions and standards compliance. The manufacturer is required to fill in their guaranteed data against NESCO's requirement for each item described.

Uploaded by

Azad Rahman
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Guaranteed Technical Particulars

OF

[200Amps MCCB]
8.1 MANUFACTURER’s GURANTEED TECHNICAL DATA SCHEDULE
FOR 415V, 3-PHASE, 200 AMPS MCCB & ENCLOSURE

(To be filled up by the Manufacturer in Manufacturer's Letterhead Pad with appropriated data )

SL. DESCRIPTION NESCO'S MANUFACTURER'S


NO. REQUIREMENT GUARANTEED
DATA
A. THREE PHASE 200A LV MCCB

01. Manufacturer's name & address To be mentioned

02. Manufacturers model no. To be mentioned

03. Operating voltage 415 V AC


04. Max. system voltage 457 V AC
05. Rated continuous current 200 Amps.
D6. Number of poles 3 (three)
Rated insulation voltage i.e. maximum system voltage (Ui) ≥ 800 Volts AC
07.

08. Rated Impulse withstands voltage i.e. Uimp ≥ 8.DkV


09. Frame size 250 Amps.

Rated service Short circuit Breaking capacity


10. 18 KA
i.e. Ics
from ≤40% to ≥ 100% of rated
11. Thermal element setting
continuous current.

12. Magnetic element setting from ≤400% to ≥1000% of rated


continuous current

13. Operating mechanism As cl 7.1.5 of spec.

14. Construction As cl 7.1.5 of spec.

15. Nominal dimension (Height xWidth xDepth) mm x mm x mm


t6. Indication for ON-TRIP-OFF position To be provided
17. Original Printed catalogue To be furnished

18. Dimensional drawing To be furnished

19.
Weight , Kg To be furnished

20. IEC Standards for Design, manufacture, testing and latest edition of IEC 60947-1 and
performance. IEC 60947-2
or equivalent international
standards.

Seal & Signature Seal & Signature


of the Manufacturer of the Bidder
8.2 MANUFACTURER’s GURANTEED TECHNICAL DATA SCHEDULE
FOR 415V, 3-PHASE, 200 AMPS MCCB & ENCLOSURE

(To be filled up by the Manufacturer in Manufacturer's Leterhead Pad with appropriated data)

DESCRIPTION NESCO’S MANUFACTURER'S


NO. REQUIREMENT GUARANTEED DATA

B. MCCB PANEL/ENCLOSURE
01. Manufactuer's Name & Address To be mentioned
02. Manufactuer’s Model no. To be mentioned
03. Construction As cl 7.1.5 of spec.
04. Overall dimension (Height x Width x 500 mm x 300 mm x 200mm
Depth)
05. Thickness (minimum) 2mm
06. Material of the box Galvanized steel sheet of min 2
mm thick.
07. Necessary fixing channels with Shall be provided
adjustable hole including nuts, bolts

Latest revision of ASTM A90/


08. Standard of galvanization BS EN ISO 1461:2009
standard.
09. Dimensional drawing To be furnished

Seal & Signature Seal & Signatue of


oT the Manufacturer the Bidder
8.3 MANUFACTURER’s GURANTEED TECHNICAL DATA SCHEDULE
FOR 415V, 3-PHASE, 100 AMPS MCCB & ENCLOSURE

(To be filled up by the Manufacturer in Manufacturer's Letterhead Pad with appropriated data )

SL. DESCRIPTION NESCO'S MANUFACTURER'S


NO. REQUIREMENT GUARANTEED
DATA
A. THREE PHASE 100A LV MCCB

01. Manufacturer's name & address To be mentioned

02. Manufacturers model no. To be mentioned

03. Operating voltage 415 V AC


04. Max. system voltage 457 V AC
05. Rated continuous current 100 Amps.
D6. Number of poles 3 (three)
Rated insulation voltage i.e. maximum system voltage (Ui) ≥ 800 Volts AC
07.

08. Rated Impulse withstands voltage i.e. Uimp ≥ 8.0 kV


09. Frame size 100 Amps.

Rated service Short circuit Breaking capacity


10. 18 KA
i.e. Ics
from ≤40% to ≥ 100% of rated
11. Thermal element setting
continuous current.

12. Magnetic element setting from ≤400% to ≥1000% of rated


continuous current

13. Operating mechanism As cl 7.5 2.80 of spec.

14. Construction As cl. 7.5 2.10 of spec.

15. Nominal dimension (Height xWidth xDepth) mm x mm x mm


t6. Indication for ON-TRIP-OFF position To be provided
17. Original Printed catalogue To be furnished

18. Dimensional drawing To be furnished

19.
Weight , Kg To be furnished

20. IEC Standards for Design, manufacture, testing and latest edition of IEC 60947-1 and
performance. IEC 60947-2
or equivalent international
standards.

Seal & Signature Seal & Signature


of the Manufacturer of the Bidder
8.4 MANUFACTURER’s GURANTEED TECHNICAL DATA SCHEDULE
FOR 415V, 3-PHASE, 100 AMPS MCCB & ENCLOSURE

(To be filled up by the Manufacturer in Manufacturer's Leterhead Pad with appropriated data)

DESCRIPTION NESCO’S MANUFACTURER'S


NO. REQUIREMENT GUARANTEED DATA

B. MCCB PANEL/ENCLOSURE
01. Manufactuer's Name & Address To be mentioned
02. Manufactuer’s Model no. To be mentioned
03. Construction To be mentioned
04. Overall dimension (Height x Width x To be mentioned
Depth)
05. Thickness (minimum) 2 mm
06. Material of the box Galvanized steel sheet of min 2
mm thick.
07. Necessary fixing channels with Shall be provided
adjustable hole including nuts, bolts

Latest revision of ASTM A90/


08. Standard of galvanization BS EN ISO 1461:2009
standard.
09. Dimensional drawing To be furnished

Seal & Signature Seal & Signatue of


oT the Manufacturer the Bid

You might also like