IRI-Pro-V2: C&S Electric Limited
IRI-Pro-V2: C&S Electric Limited
(2) Design
2.1 Front Panel
The front panel of the protective device IRI-PRO comprises the following operational and indication
elements:
● 1 LCD - Liquid Crystal Display (16 x 2)
● Five keypads- for parameter setting
● 8 LEDs for annunciation
2.2 LEDs
On the front panel there are 8 LEDs. Their functions are indicated by the appropriate inscriptions. On fault
I>, I>>, Ie> & Ie>> LEDs with appropriate phase lamps L1/ L2 / L3 give the fault indication. Flashing of the
green LED marked ON gives the indication of healthiness of relay in terms of watchdog.
02
(3) Fault Recording
IRI-PRO records secondary current for last 5 Fault with real time stamp. It saves following information with
CT current in non-volatile memory in following sequence.
(5) Housing
The IRI-PRO is supplied in an individual housing for flush-mounting for installation in a DIN standard of
73x 135 mm.
[A] [B]
Terminal No. Description Terminal No. Description
A1 L1 Current Transformer Phase B1 Relay-1 NO
A2 L1 Current Transformer Neutral B2 Relay-1 COMM
A3 L2 Current Transformer Phase B3 Relay-2 NO
A4 L2 Current Transformer Neutral B4 Relay-2 COMM
A5 L3 Current Transformer Phase B5 Relay-3 NO
A6 L3 Current Transformer Neutral B6 Relay-3 COMM
A7 Earth CT1 B7 Aux Supply Line (non polar)
A8 Earth CT2 B8 Aux Supply Line (non polar)
B9 Earth
03
(7) Trip Test
This feature allows the user to check contact operation. TRIP test can be used while commissioning the
relay to see the operation of contacts of IRI-PRO. It is selectable from front LCD menu and becomes active
only when currents are below all pickup levels and trip levels. Selecting trip test, gives the momentary
operation of all three available contacts in IRI-PRO one by one with LED flashing indications.
04
(10) Technical Data
(10.1) Measuring Input
Rated Data Rated current IN 1A & 5A
Rated frequency FN 50 Hz
Power consumption in At IN = 1A 0.2 VA
current circuit At IN = 5A 0.1 VA
Thermal withstand capability for 1 Sec 100 x IN
in current circuit for 10 Sec 20 x IN
continuously 4 x IN
Dropout Ratio >96%
Returning Time 30ms
Minimum Operating Time 30ms
05
(11) Setting Procedure
06
(12) Dimensional Details
Front View
All dimensions in mm (Gen. Tol: + 1.0mm)
Installation Depth : 111 mm
76.00
144.00
76.00
144.00 68.00
134.00
147.00
07
IRI-PRO-V2
PROTECTION
EO : 1 E/F with High set
3O-EO : 3 O/C+1E/F without High set
3I-EI : 3 O/C+1E/F with High set
I1 : 1 O/C + High set
Notes
The m
for g a te rial in
th
perfo e n e r a l is catalogu
rman
mode ce da i n f o r m a e is
l ta an tion
attem selection. d
pt has Althou proper
Issue Date : 23.09.11, Rev. No : 03, Rev. Date : 21.02.19
that been gh ev
t m
c a t a l h e in f o r m ade to ens ery
o ure
reserv g u e i s c a t io n in
e th
desig s the righ o r r e c t . C is
n, ma t to ch &
conta terial
o ange S
withou in e d in t h r specifica the
t prior is c a tion
inform t
ation. a lo g u e
08