The document summarizes the features of the IRI-PRO-V2 microprocessor-based protective relay. It has overcurrent, short circuit, and earth fault protection functions. It digitally filters current measurements and provides selectable inverse time characteristics. The relay records the last five faults with time stamps and has three output contacts for tripping and annunciation. It is housed in a DIN rail mountable case and has settings and connections configured through the front panel display and terminal blocks.

Uploaded by

Vishal Shah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
55 views8 pages

IRI-Pro-V2: C&S Electric Limited

The document summarizes the features of the IRI-PRO-V2 microprocessor-based protective relay. It has overcurrent, short circuit, and earth fault protection functions. It digitally filters current measurements and provides selectable inverse time characteristics. The relay records the last five faults with time stamps and has three output contacts for tripping and annunciation. It is housed in a DIN rail mountable case and has settings and connections configured through the front panel display and terminal blocks.

Uploaded by

Vishal Shah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

IRI-Pro-V2

Over Current, Short Circuit & Earth Fault Relay

C&S Electric Limited


IRI-PRO-V2-(EO/3OEO/3IEI/I1)-(1/5)-(1/5)
(1) Characteristics & Features

● Micro-controller based Numeric Relay.


● Digital filtering of the measured values to suppress the high frequency harmonics and transient DC
components during short circuit.
● Selectable protective functions between: definite time over-current relay and inverse time over-current
relay.
● Selectable inverse time characteristics according to BS142 and IEC 255-4:
- Normal inverse 3.0
- Normal inverse 1.3
- Normal inverse 0.6
- Very inverse
● Extremely inverse
● Two stage over-current time protection for phase current / earth fault current
● Separately selectable characteristic for Earth fault and phase fault
● Continuous self-supervision of software and hardware
● Wide operating ranges of the supply voltage [AC/DC] 24V-260V AC, 24V-360V DC
● Last five faults recording with real time stamping (Date-time stamp)
● Relay assignment configurable from HMI
● Relay reset configurable from HMI
● Primary current display with CT Ratio

(2) Design
2.1 Front Panel
The front panel of the protective device IRI-PRO comprises the following operational and indication
elements:
● 1 LCD - Liquid Crystal Display (16 x 2)
● Five keypads- for parameter setting
● 8 LEDs for annunciation

2.2 LEDs
On the front panel there are 8 LEDs. Their functions are indicated by the appropriate inscriptions. On fault
I>, I>>, Ie> & Ie>> LEDs with appropriate phase lamps L1/ L2 / L3 give the fault indication. Flashing of the
green LED marked ON gives the indication of healthiness of relay in terms of watchdog.

2.3 Output Contacts


Relay 3 is fixed for CB tripping, common for all type of faults. Relay 1 and Relay 2 are user configurable for
annunciations like OL / SC / E / EH /Self supervision. Reset function of all output contacts is individually
programmable [Auto Reset / Manual Reset] from HMI. RESET DELAY is available with all output contacts
but get disable in Manual Reset mode.

2.4 Power Supply


It has a universal auxiliary supply. The voltage range is 24V to 260V AC and 24V to 360VDC.Power supply
connections are not polarized.

02
(3) Fault Recording
IRI-PRO records secondary current for last 5 Fault with real time stamp. It saves following information with
CT current in non-volatile memory in following sequence.

Type of fault : SC/OL/E/EH


Faulty phase / Earth : L1/L2/L3/E (Secondary)
Value at Fault : L1, L2, L3, Ie Amps (True RMS recording guaranteed only if trip time >= 40msec)

(4) Reset Delay


This parameter [RST-D] introduces a delay in opening of relay contacts, when the current goes below
the dropout value for overload and short circuit & earth faults. This parameter will not work when manual
reset mode is selected.

(5) Housing
The IRI-PRO is supplied in an individual housing for flush-mounting for installation in a DIN standard of
73x 135 mm.

(6) Terminal Description


There are two terminal blocks A & B. Block A is for current connection, while Block B is for Auxiliary & trip
contact connection as per below table.

[A] [B]
Terminal No. Description Terminal No. Description
A1 L1 Current Transformer Phase B1 Relay-1 NO
A2 L1 Current Transformer Neutral B2 Relay-1 COMM
A3 L2 Current Transformer Phase B3 Relay-2 NO
A4 L2 Current Transformer Neutral B4 Relay-2 COMM
A5 L3 Current Transformer Phase B5 Relay-3 NO
A6 L3 Current Transformer Neutral B6 Relay-3 COMM
A7 Earth CT1 B7 Aux Supply Line (non polar)
A8 Earth CT2 B8 Aux Supply Line (non polar)
B9 Earth

03
(7) Trip Test
This feature allows the user to check contact operation. TRIP test can be used while commissioning the
relay to see the operation of contacts of IRI-PRO. It is selectable from front LCD menu and becomes active
only when currents are below all pickup levels and trip levels. Selecting trip test, gives the momentary
operation of all three available contacts in IRI-PRO one by one with LED flashing indications.

(8) Contact Details

Number of Relays 3 (Relay 1, 2, 3)


Type of contact (Relay 1, 2, 3) (SPST-NO, Type-A)
Assignment of contact Relay-3 common for trip on I> and I>>, Ie> and Ie>>
Relay-1 & 2 are configurable for O/L, S/C, E, EH, self
supervision
Max. breaking capacity 1250VA / 150W resistive
500VA / 90W inductive
Max. breaking voltage 400V AC / 125V DC
Max. continuous current 8A
Max. making current (16ms) 50A

(9) Connection Diagram

04
(10) Technical Data
(10.1) Measuring Input
Rated Data Rated current IN 1A & 5A
Rated frequency FN 50 Hz
Power consumption in At IN = 1A 0.2 VA
current circuit At IN = 5A 0.1 VA
Thermal withstand capability for 1 Sec 100 x IN
in current circuit for 10 Sec 20 x IN
continuously 4 x IN
Dropout Ratio >96%
Returning Time 30ms
Minimum Operating Time 30ms

(10.2) Setting Ranges & Steps


Parameter Display Setting Range Step
l> l> 0.20-2.5xIN 0.05xIN
t> 0.1-150s 0.01s
ti> 0.01-1.500 0.005
l>> I>> 0.5-25xIN 0.5xIN
t>> 0.03-20s 0.01s
Ie> Ie> 0.05-2.5xIN 0.05xIN
te> 0.03-150s 0.01s
tie 0.01-1.500 0.005
Ie>> Ie>> 0.5-15xIN 0.05xIN
tie>> 0.02-20s 0.01s
Reset Delay RST-D 0-20s 0.1s
CT Ratio CT Ratio 1-2500 1
Trip Time Tolerances +5% +20mSec for VINV, NINV3.0/1.3 +3%, +20ms for DEFT
(which ever is higher)
+7.5% or +30mSec (which ever is higher) for EINV, NINV0.6
Accuracy as per IEC255-3 in band of (I/Is>2 to I/Is<20) and Is>0.1 IN
Pickup Tolerances +5% from set value

Normal Inverse 3.0 0.14


t= ti[s] I = Injected current
(I/Is)0.02 -1 Is = Pickup set level
Normal Inverse 1.3 0.061 ti = TMS for inverse characteristics
t= ti[s] t = Definite delay in DEFT
(I/Is)0.02 -1

Normal Inverse 0.6 0.028


t= ti[s]
(I/Is)0.02 -1 !
Very Inverse 13.5 !!! CAUTION !!!
t= ti[s] O/L, S/C, E and EH protection
(I/Is) -1
are available with DISABLE in
Extremely Inverse 80 HMI
t= ti[s]
(I/Is)2 -1

05
(11) Setting Procedure

06
(12) Dimensional Details

Panel cut out dimension

Front View
All dimensions in mm (Gen. Tol: + 1.0mm)
Installation Depth : 111 mm
76.00

Width x Height = 139 x 70 mm

144.00

Bottom View Side View

76.00

144.00 68.00
134.00
147.00

07
IRI-PRO-V2

(13) Order Form X X X


IRI-PRO-V2

PROTECTION
EO : 1 E/F with High set
3O-EO : 3 O/C+1E/F without High set
3I-EI : 3 O/C+1E/F with High set
I1 : 1 O/C + High set

RATED CURRENT - PHASE (O/C element) In


1 : Rated 1 Amp
5 : Rated 5 Amp

RATED CURRENT - EARTH


1 : Rated 1 Amp
5 : Rated 5 Amp

Notes
The m
for g a te rial in
th
perfo e n e r a l is catalogu
rman
mode ce da i n f o r m a e is
l ta an tion
attem selection. d
pt has Althou proper
Issue Date : 23.09.11, Rev. No : 03, Rev. Date : 21.02.19
that been gh ev
t m
c a t a l h e in f o r m ade to ens ery
o ure
reserv g u e i s c a t io n in
e th
desig s the righ o r r e c t . C is
n, ma t to ch &
conta terial
o ange S
withou in e d in t h r specifica the
t prior is c a tion
inform t
ation. a lo g u e

C&S Electric Ltd.


(Protection & Measurement Devices)
C-60, Wing-A, Phase-II, Noida -201 305
District Gautam Budh Nagar (U.P) INDIA
Phone : +91 120-38748 00 / 01, Fax: +91 120-3874802 Technical Question or After-sales Service
Customer Center Quick Response
E-mail: [email protected] Service, Excellent Technical Support 1800 572 2012

08

You might also like