HGP Series Generator Type: Molded Case Circuit Breakers

This document provides information on HGP series molded case circuit breakers, including common ratings, model names and frames, short circuit breaking capacity, rated short circuit making capacity, endurance, rated current, and trip device information. Key specifications listed include rated insulation voltage of 1000V, rated operational voltage of 690V, rated impulse withstand voltage of 8kV, and pollution degree of 3. Models range from 50 to 160 frames with 3 or 4 poles and short circuit breaking capacities ranging from 6 to 150kA depending on voltage.

Uploaded by

LOI HO
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
330 views8 pages

HGP Series Generator Type: Molded Case Circuit Breakers

This document provides information on HGP series molded case circuit breakers, including common ratings, model names and frames, short circuit breaking capacity, rated short circuit making capacity, endurance, rated current, and trip device information. Key specifications listed include rated insulation voltage of 1000V, rated operational voltage of 690V, rated impulse withstand voltage of 8kV, and pollution degree of 3. Models range from 50 to 160 frames with 3 or 4 poles and short circuit breaking capacities ranging from 6 to 150kA depending on voltage.

Uploaded by

LOI HO
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

HGP Series Generator Type

Molded Case Circuit Breakers


Model Selection Table

Common Ratings
Rated Insulation Voltage, Ui 1,000 V Suitablilty for Isolation Yes
Rated Operational Voltage, Ue 690 V Utilization Category A
Rated Impulse Withstand Voltage, Uimp 8 kV Pollution Degree 3
Protection Function Overload, Instantaneous, Short-Circuit Protection Reference Standard IEC 60947-2

Model Name HGP50D HGP125D HGP160D HGP100


Frame (AF) 50 125 160 100
Number of Poles (P) 3, 4 1) 3, 4 1) 3, 4 1) 3, 4 1)
Short-Circuit Breaking Category Code F*2) S H X F*2) S H X F*2) S H X F*2) S H X
Rated
Ultimate AC 660/690 V 6 8 8 10 6 8 8 10 6 8 8 10 6 8 8 10
Short-Circuit AC 480/500 V 25 50 65 100 25 50 65 100 25 50 65 100 25 50 65 100
Breaking AC 440/460 V 36 65 85 150 36 65 85 150 36 65 85 150 36 65 85 150
Capacity AC 380/415 V 50 85 100 150 50 85 100 150 50 85 100 150 50 85 100 150
[Icu] AC 220/240 V 65 100 130 200 65 100 130 200 65 100 130 200 65 100 130 200
(kA rms)
DC 250 V 3) 36 65 85 100 36 65 85 100 36 65 85 100 36 65 85 100
Service Breaking Capacity [Ics = % Icu] 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
AC 660/690 V 9 14 14 17 9 14 14 17 9 14 14 17 9 14 14 17
Rated Short- AC 480/500 V 53 105 143 220 53 105 143 220 53 105 143 220 53 105 143 220
Circuit Making
AC 440/460 V 76 143 187 330 76 143 187 330 76 143 187 330 76 143 187 330
Capacity [Icm]
(kA peak) AC 380/415 V 105 187 220 330 105 187 220 330 105 187 220 330 105 187 220 330
AC 220/240 V 143 220 286 440 143 220 286 440 143 220 286 440 143 220 286 440
Endurance [times] Mechanical 25,000 25,000 25,000 25,000
(Durability) In @ 440V 10,000 10,000 10,000 10,000
● ● ● ●
16, 20, 25, 32, 40, 50,
Rated Current, at 40 °C (A) 16, 20, 25, 32, 40, 50 100, 125, 160 40, 50, 63, 80, 100
Thermal 63, 75, 80, 100, 125
Magnetic Long Time [LTD] (0.8-0.9-1.0)×In (0.8-0.9-1.0)×In (0.8-0.9-1.0)×In (0.7-0.8-0.9-1.0)×In
16~32A : 400A, 40~50A 16~32A : 400A, 40~50A
Instantaneous [INST] 10×In 10×In
: 10×In : 10×In
- - - ●
Rated Current, at 40 °C (A) - - - 40, 100
0.4-0.45-0.5-0.56-0.63-
Ir(A) N, D, A, E - - -
0.7-0.8-0.9-1×In
Long Time N - - - 16 @ 6Ir
[LT] D, A, E - - - 0.5–1–2–4–6–8-16@6×Ir
Tr(s)
10-15-20-25-30-35-40-
GD, GE - - -
45-50-60 @1.2×Ir
Trip
Isd(A) N, D, A, E, GD, GE - - - 1.5–2–3–4–5–6–7–8-10×In
Device Short Time
N - - - 0.1
[STD] Tsd(s)
D, A, E, GD, GE - - - 0.1-0.2-0.3-0.4
Electronic N - - - 1,500
Ii(A) D, A, E, 1.5–2–4–6–8–10–11-
Instantaneous - - -
GD, GE 12-13-14-15×In
[INST]
Break N, D, A, E,
- - - 0.05
time(s) GD, GE
N - - - NA
Ground Ig(A) OFF-0.2-0.3-0.4-0.5-0.6-
Fault D, A, E - - -
0.7-0.8-1×In
Protection
[GFT] N - - - NA
Tg(ms)
D, A, E - - - 0.1-0.2-0.3-0.4
N Pole Protection
(A) N, D, A, E - - - OFF-0.5–1-1.6 4)×In
(L, S)
Terminal Screw,
Front Connection Terminal Screw Terminal Screw Terminal Screw
Terminal Bus Bar
Connection/ Horizontal/Vertical Horizontal/Vertical Horizontal/Vertical Horizontal/Vertical
Rear Connection
Installation Installation Cable Cable Cable Cable
and Switchgear  Switchgear  Switchgear  Switchgear 
Plug-in
Dimensions (Line & Load, Line Only) (Line & Load, Line Only) (Line & Load, Line Only) (Line & Load, Line Only)
a (3/4P) 90/120 90/120 90/120 105/140
Dimension
b 140 140 140 165
(mm)
c 86 86 86 86.5

※ 1) 4 Pole Arrangement:Basic specification of R-S-T-N 3) DC is only applicable to thermal magnetic


2) Only applicable to oversea products/ship products 4) Only applicable if Ir < 0.63 ("1" is applicable if Ir ≥ 0.63)
Accessory
Internal Auxiliary switch (AUX), Alarm switch (ALT), Shunt trip (SHT), Undervoltage trip (UVT)
Rotary handle - Front Contact Type (TFG)/Extension Type (TFH), Motor operator (MOT), Mechanical interlock (MIF), 
External Locking device (PLD), Cage terminal block (CTB), Insulation terminal cover (TCF), Insulation barrier (TQQ)
※ Plug-in TDM is only for 3 pole and can be selected by LINE/LODE(P3), LINE Only(F3).Terminal extensions (TBB) excludes HGP50D, 125D and 160D types.

HGP160 HGP250 HGP400 HGP630 HGP800


160 250 400 630 800
3, 4 1) 3, 4 1) 3, 4 1) 3, 4 1) 3, 4 1)
F*2) S H X F*2) S H X F*2) S H X F*2) S H X F*2) S H X
6 8 8 10 6 8 8 10 10 10 20 35 10 10 20 35 10 10 20 35
25 50 65 100 25 50 65 100 25 50 70 100 25 50 70 100 25 50 70 100
36 65 85 150 36 65 85 150 36 70 85 150 36 70 85 150 36 70 85 150
50 85 100 150 50 85 100 150 50 85 100 150 50 85 100 150 50 85 100 150
65 100 130 200 65 100 130 200 65 100 130 200 65 100 130 200 65 100 130 200
36 65 85 100 36 65 85 100 36 65 85 100 36 65 85 100 36 65 85 100
100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
9 14 14 17 9 14 14 17 17 17 40 74 17 17 40 74 17 17 40 74
53 105 143 220 53 105 143 220 53 105 154 220 53 105 154 220 53 105 154 220
76 143 187 330 76 143 187 330 76 154 187 330 76 154 187 330 76 154 187 330
105 187 220 330 105 187 220 330 105 187 220 330 105 187 220 330 105 187 220 330
143 220 286 440 143 220 286 440 143 220 286 440 143 220 286 440 143 220 286 440
25,000 25,000 20,000 20,000 20,000
10,000 10,000 6,000 4,000 3,000
● ● ● ● ●
125, 150, 160, 175, 
100, 125, 150, 160 300, 350, 400 500, 630 700, 800
200, 225, 250
(0.7-0.8-0.9-1.0)×In (0.7-0.8-0.9-1.0)×In (0.8-0.9-1.0)×In (0.8-0.9-1.0)×In (0.8-0.9-1.0)×In

(5-6-7-8-9-10)×In (5-6-7-8-9-10)×In (5-6-7-8-9-10)×In (5-6-7-8-9-10)×In (5-6-7-8-9-10)×In

● ● ● ● ●
100, 160 160, 250 250, 400 630 800
0.4-0.45-0.5-0.56-0.63-0.7-0.8- 0.4-0.45-0.5-0.56-0.63-0.7-0.8- 0.4-0.45-0.5-0.56-0.63-0.7-0.8- 0.4-0.45-0.5-0.56-0.63-0.7-0.8- 0.4-0.45-0.5-0.56-0.63-0.7-0.8-
0.9-1×In 0.9-1×In 0.9-1×In 0.9-1×In 0.9-1×In
16 @ 6Ir 16 @ 6Ir 16 @ 6Ir 16 @ 6Ir 16 @ 6Ir
0.5–1–2–4–6–8-16@6×Ir 0.5–1–2–4–6–8-16@6×Ir 0.5–1–2–4–6–8-16@6×Ir 0.5–1–2–4–6–8-16@6×Ir 0.5–1–2–4–6–8-16@6×Ir
10-15-20-25-30-35-40-45-50-60 10-15-20-25-30-35-40-45-50-60 10-15-20-25-30-35-40-45-50-60 10-15-20-25-30-35-40-45-50-60 10-15-20-25-30-35-40-45-50-60
@1.2×Ir @1.2×Ir @1.2×xIr @1.2×Ir @1.2×Ir
1.5–2–3–4–5–6–7–8-10×In 1.5–2–3–4–5–6–7–8-10×In 1.5–2–3–4–5–6–7–8-10×In 1.5–2–3–4–5–6–7–8-10×In 1.5–2–3–4–5–6–7–8-10×In
0.1 0.1 0.1 0.1 0.1
0.1-0.2-0.3-0.4 0.1-0.2-0.3-0.4 0.1-0.2-0.3-0.4 0.1-0.2-0.3-0.4 0.1-0.2-0.3-0.4
2,400 3,000 4,800 6,900 8,800
1.5–2–4–6–8–10–11-12-13-14-
1.5–2–4–6–8–10–11×In 1.5–2–4–6–8–10–11×In 1.5–2–4–6–8–10–11×In 1.5–2–4–6–8–10–11×In
15×In

0.05 0.05 0.05 0.05 0.05

NA NA NA NA NA
OFF-0.2-0.3-0.4-0.5-0.6-0.7- OFF-0.2-0.3-0.4-0.5-0.6-0.7- OFF-0.2-0.3-0.4-0.5-0.6-0.7- OFF-0.2-0.3-0.4-0.5-0.6-0.7- OFF-0.2-0.3-0.4-0.5-0.6-0.7-
0.8-1×In 0.8-1×In 0.8-1×In 0.8-1×In 0.8-1×In
NA NA NA NA NA
0.1-0.2-0.3-0.4 0.1-0.2-0.3-0.4 0.1-0.2-0.3-0.4 0.1-0.2-0.3-0.4 0.1-0.2-0.3-0.4

OFF-0.5–1-1.6 4)×In OFF-0.5–1-1.6 4)×In OFF-0.5–1-1.6 4)×In OFF-0.5–1-1.6 4)×In OFF-0.5–1-1.6 4)×In

Terminal Screw,  Terminal Screw,  Terminal Screw,  Terminal Screw,  Terminal Screw, 
Terminal Bus Bar Terminal Bus Bar Terminal Bus Bar Terminal Bus Bar Terminal Bus Bar

Horizontal/Vertical Cable Horizontal/Vertical Cable Horizontal/Vertical Cable Horizontal/Vertical Cable Horizontal/Vertical Cable

Switchgear Switchgear Switchgear Switchgear Switchgear


(Line & Load, Line Only) (Line & Load, Line Only) (Line & Load, Line Only) (Line & Load, Line Only) (Line & Load, Line Only)
105/140 105/140 140/186.5 140/186.5 210/280
165 165 260 260 320
86.5 86.5 110 110 135
Overview

ETU Part Name LCD Display / ICON (N type is not applicable)

Etu Setting Mode Indication


Measure Mode Indication
Trip Equip. Name Long/Short time pick-up N Phase Earth Leakage Indication
ETU Frame current setting Protection Setting
Setting Lock Indication
ETU Type (Rotary knob) (Rotary knob)
Battery Status Indication
ETU In Test Kit Terminal Unit Indication

LCD Display ETU Setting Button LED (Run, Trip, Alarm)


(D/A/E Type) (N Type : only 1 button) Phase Indication Measurement Value Indication

ETU Type / AF
Trip Unit
Type Model (AF) HGP100, HGP160, HGP250 HGP400 HGP630 HGP800
Rated Current (A) 40 100 160 250 250 400 630 800
Display Type ETU-25-GD ETU-63-GD ETU-63-GD ETU-80-GD
Energy-meter Type ETU-25-GE ETU-63-GE ETU-63-GE ETU-80-GE

Overview of Trip Unit Function Characteristic Curve

GD GE Remark

˙Dial 2 ea, Key button 4 ea ˙Dial 2 ea, Key button 4 ea Dial setting (Ir, Isd)
HMI
˙Segment LCD ˙Segment LCD
˙L (Dial, Key button) ˙L (Dial, Key button)
10,000
˙S (Dial, Key button) ˙S (Dial, Key button)
Protection
120

˙I (Key button) ˙I (Key button) 5,000 Ir = 0.4~1.0 X In


100
80

˙RP (Key button)


60
50
40
2,000
˙IR, IS, IT ˙IR, IS, IT, I unbalance (per phase)
30
t (minute)

1,000
20

˙Iavg, Imax, Imin


˙V, phase to neutral, phase to 500
10
8

phase,
6
5

200
4

˙P, total/per phase, power


3

factor 100
2

Measurement ˙Q, total/per phase 1


50
˙S, total/per phase
Tr = 10~60s at 1.2 X Ir
˙Active(kW), reactive(kVAR),  20
apparent(kVA) 10
˙F, THD (I, V, per phase, VLN, 5
VLL)
˙Harmonic (15th), Demand I, P 2
Isd = 1.5 ~ 10 X Ir
˙Trip event: 20 ea ˙Trip event: 20 ea  External power supply 1
History / I2t ON
(phase, type, time) (phase, type, time) (DC 24 V)
Event 0.4
˙System event: 32 ea
0.3
0.2
˙Self-power ˙Self-power ˙ETU Self power 0.2
External power (DC 24 V) running current 0.1 I2t OFF 0.1
Power
- 250 A or less : over 30 % In 0.05
- Etc. : over 15 % In 0.04
0.03
0.02
Battery ● ●
0.01
˙Test terminal ˙Test terminal External power supply
t < 10ms
˙ZSI OUT : 250 AF (DC 24 V) 0.005

Add-on ˙ZSI IN/OUT : 630 AF, 800 AF 0.002


function ˙Trip / alarm counter Ii=1.5 ...11In
˙Run time counter over 50 % In, 0.001
0.5 1 2 3 4 5 6 7 8 910 20 5 6 7 8 9 10 20 30 40 50
every 24 h
I / Ir I / In
˙RS-485 MODBUS-RTU External power supply
Communication
(DC 24 V)
Current (number of rating current)
˙LED 3 ea ˙LED 3 ea
˙Run LED / Trip LED ˙Run LED / Trip LED /
Indication
/Alarm LED (90 % Alarm LED (90 % blinking, 
blinking, 110 % keeping) 110 % keeping)
Trip Unit – GD/GE Type

Protection
Overload : Long time protection (Ir)
Protect the overload with the adjustable time delay and pick-up range.

Short Circuit : Short time protection (Isd)


Protect the short-circuit with the adjustable time delay and pick-up range.

Short Circuit : Instantaneous protection (Ii)


Protect the short-circuit with the adjustable pick-up range.

Display
Move the page & Setting
Status LED
• Run LED : Lighting when the circuit breaker is under load.
• Trip LED : Lighting when the circuit breaker is tripped.
• Alarm LED : Flashing in I > 0.9×Ir, Lighting in I > 1.1×Ir

Button
• Change the trip unit settings & move the page on the display.
Confirm the setting
• There are 4-button.(Up/Down/Menu/Reset)
Status LED Move the mode & Reset

Protection Setting Range

GD/GE Type
L Long-time Protection
Dial setting 0.4 0.45 0.5 0.56 0.63 0.7 0.8 0.9 1
t

Pick-up [A] Ir = ×In


Button setting 0.9 ~ 1.25 배, 1A 단위로 설정(최소 설정, In=40 A인 경우 16 A)
Ir
tr
Time delay [s] Button setting 10 15 20 25 30 35 40 50 60
tr =
Isd

accuracy ±20 % 1.2×Ir 10 15 20 25 30 35 40 50 60


tsd

Ii
Thermal memory 20 minutes
I S Short-time Protection
Pick-up [A]
Isd = Ir× dial setting 1.5 2 3 4 5 6 7 8 10
accuracy ±15 %
Button I2OFF 0.1 0.2 0.3 0.4
setting I2ON 0.1 0.2 0.3 0.4
Time delay [s] tsd=
Non triping time 0.08 0.14 0.23 0.35
Maximum time 0.14 0.2 0.32 0.5
I Instantaneous Protection
In = 40 A
Pick-up [A] Button 100 A 1.5 2 4 6 8 10 11 12 13 14 15
Ii=
accuracy ±15% setting 160 A
In ≥ 250 A 1.5 2 4 6 8 10 11
Time delay [s] Maximum time ≤ 0.05
RP Reverse Power
Pick-up [A] Button setting 1 ~ 1,000 kW, step 1
Time delay [s]
Button setting 1 ~ 40 sec, step 0.1
accuracy ±15 %

Q
※ The default setting of Thermal function is disable.
※ RP Protection function is available to GE type.
Non ※ RP Protection trip in the case of phase difference, corresponding to 103° ≤ φ ≤ 257°
Trip Trip
P
-RP
Dimensions

HGP100, 160, 250

35 35
45 45 Motor Operator
35 35
35 35 25.5
4

105 MOT Center Line


11

11

14.2 90

1.5
132.7

Mounting
screw
M4 x L85
64.5

26 48.2
55

13.95
CL CL CL

51
44
144.1
144

165
205
146

205
146
144

CL
64.5

12.2
55

56.2

44
47
132.7

Ø8 MOT
Ø8 .2 Center
23 .2
23 Line
105 105 77
82.5 99.5
86.5 169.5
94.5
109.54

HGP400, 630

Motor Operator
61.5 61.5 61.5 61.5
46.546.5 Interpole barrier 46.546.5
44.1
46.5 46.5 8
139 MOT Center Line
Mounting hole
15

15

130 2.3
20.7
246

MOT
Mounting Center
Trip button Line
98.3

screw
100

78.8
83
77

CL CL CL M5 x L98
70
322
260
230
200

200
230
260
322

Mounting hole
41

18.1 CL
100

CL
83

24

82.4
70
115.8

Mounting
246

146.3

screw
Ø1 M5 x L98
3
15

15

30 30 30
8
140 140 44 97.5
96.5
105 122.5
110 133
124 237
160
228.2

HGP800

Motor Operator
210
70 70 Interpole barrier
70 10 42
16

Mounting hole
16.9
8 37

160
131 MOT Center Line
274.8

Mounting
screw 2.3
Trip button M6 x L110
125

49.4 92.8
99.3

C
L C
L MOT Center Line
451
320
287
278

90.2

Mounting hole
70
99.3
125

CL CL
34.8
274.8

81.2
90.8

70

10
119 42
128 135
135 147
149.5 275
198
282.2

※ Dimensions for mounting body / Terminal connections bus / Panel cover cutting : Refer to HGP catalog on homepage
※ When installing the product in close contact, please consider tolerances for external dimensions.
Order Information

Order Code

HGP 250 X -G 3P T4 S 00 00 C 00016 F

① ② ④ ⑤ ⑥ ⑦ ⑧ ⑩ ⑫
Model Name Frame Size Classification- No. of Product Connection Signal Frequency Trip Device
250 AF Poles Category Method Device Characteristics
③ (AUX/ALT) ⑨ ⑪
Short-Circuit Trip Device Rated
Breaking (SHT/UVT) Current
Category Code

① Model Name ④ Classification-250 AF ⑦ Connection Method ⑩ Frequency

Molded Case Circuit Breaker / - Terminal Height (24-26 mm) 10) S Front Connection C 50/60 Hz
HGP
Earth Leakage Circuit Breaker BS 4) Straight Type of Bus Bar Packaging Z DC
New Type Terminal Height
-G 2)
(21.5 mm) BE 11) Spreader Type of Bus Bar Packaging
P Plug-in PC/CBM Attached
Line Side:Plug-in
F
Load Side:Front Connection
X Plug-in PC/CBM Not Attached

② Frame Size ⑤ No. of Poles ⑧ Signal Device (AUX/ALT) ⑪ Rated Current

50D 50 AF 3P AC 3 pole 00 Not Attached 002.5 2.5 A


125D 125 AF 4P AC 4 pole 10 AUX 1C 006.3 6.3 A
160D 160 AF D3 DC 3 pole 20 AUX 2C .
.
100 100 AF D4 DC 4 pole 01 ALT 1C .

160 160 AF 11 AUX 1C + ALT 1C 00800 800 A


250 250 AF 21 AUX 2C + ALT 1C
400 400 AF 31 5) AUX 3C + ALT 1C
630 630 AF 32 5) AUX 3C + ALT 2C
800 800 AF

③ Short-Circuit Breaking Category Code 1) ⑥ Product Category ⑨ Trip Device (SHT/UVT) ⑫ Trip Device Characteristics

AC Molded Case Circuit Breaker 00 Not Attached For Protecting Overload Short-Circuit
F 8) 36 kA T4 9) Ambient Temperature of 40 °C S1 SHT AC 100 - 120 V Thermal Fixed/Instantaneous
-
Fixed (MTM - FF)
S 65 6)/ 70 7) kA T5 Ambient Temperature of 50 °C S2 SHT AC 200 - 230 V
Thermal Adjustable/Instantaneous
H 85 kA Electronic 3) S3 SHT AC 380 - 415 V F
Fixed (MTM - JF)
X 150 kA EN Normal S4 SHT AC 440 - 480 V Thermal Adjustable/Instantaneous
H
NA Switch-Disconnector ED Display S5 SHT DC 24 V Adjustable (MTM - JJ)
Thermal Fixed/Instantaneous Fixed
DC EA Ammeter S6 SHT DC 100 - 110 V N
(MTM - FF) + 4P N Phase Protection
F 10 kA EE Energy Meter U1 UVT AC 100 - 120 V Thermal Adjustable/Instantaneous Fixed
FN
S 55 kA Electronic for Generator 12) U2 UVT AC 200 - 230 V (MTM - JF) + 4P N Phase Protection
H 85 kA GD Display U3 UVT AC 380 - 415 V Thermal Adjustable/Instantaneous
HN Adjustable (MTM - JJ) + 4P N Phase
X 100 kA GE Energy Meter U4 UVT AC 440 - 480 V Protection
Motor Protection U5 UVT DC 24 V Electronic
MP For Motor Protection U6 UVT DC 100 - 110 V - Not Applicable (ETU)
※ 1) Based on AC 440/460 V
2) Only applicable to mechanical type of Switch-Disconnector Motor Protection
HGP100, 160, 250 AC, DC  DS Switch-Disconnector No Thermal/Instantaneous
(Can't be applicable to 50D, 125D, -
Adjustable (MCP - OJ)
160D, 250 of motor protection, etc)
3) 50D, 125D, 160D : Electronic type N/A 8) F type is for overseas and ship. Switch-Disconnector
4) Applicable to both Line part /  9) For DC products, only T4 is applicable. - No Protection Function (DSU)
Load part, HGP400~800 10) Discontinued March 2020
5) Applicable to HGP400 ~ 800 11) Applicable to both Line part / Load part,
6) HGP50D, 125D, 160D, 100, 160, 250 AF HGP400
7) HGP400, 630, 800 AF 12) Applicable to 3P only
Korea

Head Office 75, Yulgok-ro, Jongno-gu, Seoul, Korea Tel: +82-2-746-7419, 7960 Fax: +82-2-746-8452

Sales Office 5th Floor 55, Bundang-ro, Bundang-gu, Seongnam-si, Tel : +82-31-8006-6698, 6756 Fax : +82-31-8006-6835
Gyeonggi-do, Korea

Factories 700, Bangeojinsunhwan-doro, Dong-gu, Ulsan, Korea


223, Sapyong-ro, Nam-gu, Ulsan, Korea (Seonam)

R&D Center 17-10, Mabuk-ro 240beon-gil, Giheung-gu, Yongin-si,


Gyeonggi-do, Korea

Branch Offices

Atlanta 6100 Atlantic Boulevard, 2nd FL., Norcross, GA30071, U.S.A Tel : +1-678-823-7839 Fax : +1-678-823-7553

Osaka 5th Floor Nagahori Plaza Bldg. 2-4-8 Minami Senba, Chuo-ku, Tel : +81-6-6261-5766~7 Fax : +81-6-6261-5818
Osaka 542-0081, Japan

Moscow World Trade Center, Ent.6, #412, Krasnopresnenskaya Nab.12, Tel : +7-495-258-1381
Moscow, 123610, Russia

Dubai Unit 205, Emaar Square Building No.4 Sheikh Zayed Road, Tel : +971-4-425-7995 Fax : +971-4-425-7996
Dubai 252458, U.A.E

Frankfurt Hyundai Electric & Energy Systems Co., Ltd Tel : +49-160-9755-3165 Fax: +49-69-7409-3934
Olof-Palme-Strasse 13, 60439 Frankfurt am Main

Bangkok 19th Floor, Unit 1908, Sathorn Square Office Tower, 98 North Tel : +66-02-115-7920 Fax : +66-2-115-7898
Sathorn Road, Silom, Bangrak, Bangkok 10500, Thailand

www.hyundai-electric.com

You might also like