Principle of Explosion Protection
Principle of Explosion Protection
Principles of
Explosion Protection
Table of Contents
Foreword 3
IP degrees of protection 54
Table 1
Procedure for the assessment of the
zone classification acc. to BetrSichV,
EX-RL and VDE 0165 55
Table 2
Explosion protection at a glance 56
Annex 1
Sample of an installation certificate 57
Annex 2
Sample of a hot work permit 58
Annex 3
Bibliography 59
Annex 4
Harmonized standards to Directive
94/9/EC 60
The fundamental experiments made by Dr.-Ing. The guiding principles issued in 1935 on the
e.h. Carl Beyling, a mining engineer, relating to mounting of electrical installations in hazardous
safety against firedamp of specially protected production areas and storage rooms (VDE
electrical motors and apparatus in coal mines 0165/1935) were to be the first German regulati-
was a decisive step in the development of ons on the protection of hazardous installations.
explosion protection. The governing design prin-
ciples of firedamp protection devices on electri- The fundamental revision of these regulations
cal machines, transformers and switchgear began with the VDE regulations 0171 ”Con-
dating from 1912 were based on the results of structional regulations for explosion protected
these experiments. As protective measures, the apparatus” which finally came into force in 1943.
following types of protection were accepted: They provided the manufacturers of electrical
equipment for use in explosive atmospheres
Miner”s lamp • Flameproof enclosure (at that time called with the necessary documents for a safe design
closed encapsulation) and construction. This regulation not only
• Plate encapsulation described the individual types of protection and
• Oil immersion their scopes of application, but also included a
• Close meshed screen number of constructional specifications and
introduced the identification marking (Ex) for the
Since 1924 only incandescent lamps were per- electrical apparatus made in compliance with it.
mitted for lighting hazardous areas, the luminous
element of which was hermetically sealed. The The governing principles and specifications of
incandescent lamps had to be protected with the VDE regulations 0165 and 0171 constituted
strong glass bells which also tightly enclosed the the basis of the police decree dated October 13,
lampholder. 1943 for electrical apparatus in hazardous loca-
tions and in mines subject to the hazard of fire-
Light switches had to be installed outside of the damp. The police decree primarily aimed at the
hazardous locations, and in the case of a failure manufacturers of electrical apparatus. It laid
or the lack of explosion-protected lighting, down that explosion protected electrical equip-
access to these locations was only permitted ment was only allowed to be put in circulation,
with safety lamps. Therefore, in general electrical installed and operated if it conformed to the so-
installations in hazardous locations were dispen- called VDE regulations and had successfully
sed with. passed the type and routine tests specified wit-
hin.
In accordance with the ”Technical directive on The old classification may still be applied for exi-
flammable liquids” (TRbF), flammable liquids are sting installations during the transitional period
divided into four classes according to their flash stated in the Operational Safety Decree.
points:
If they are whirled up, combustible dusts that
When the Operational Safety Decree (BetrSichV) are evenly distributed in a layer of less than
came into force, this classification was replaced 1 mm and at normal room heights can also
by the classification according to the Hazardous completely fill a room with an explosive dust/air
Substance Decree: mixture.
Oil terminal
Zone 0
Zone 0 mainly encompasses areas such as the
inside of enclosed containers, pipes and appa-
ratus that contain flammable liquids. The res-
pective operating temperature lies above the
flash point. The potentially explosive atmosphere
Ex-protected torch for use in Zone 0: specially certified for lies above the surface of the liquid and not in the
the increased requirements in this hazardous area
liquid. Most gases of flammable liquids are hea-
vier than air and spread in a similar way to
liquids.
During normal, trouble-free operation, ignition Detailed information on all zones can be found in
sources must be explosion-proof. the chapter ”Erection and operation of electrical
The use of all apparatus that satisfies the requi- installations in potentially explosive areas”.
rements for Zone 0 and Zone 1 apparatus is
permitted.
According to Directive 94/9/EC, apparatus for
Zone 2 must comply with the Category 3 G.
Zone 20
Apparatus for Zone 20 shall be specially appro-
ved for this purpose, e.g. grain silos. Construc-
tional requirements for apparatus for this zone
where protection is afforded by the surrounding
enclosure, can be found in DIN EN 50281-1-1.
Further standards, e.g. for apparatus in the type
of protection Intrinsic Safety, are being prepa-
red. According Directive 94/9/EC, apparatus for
Zone 20 must comply with the Category 1D.
Zone 21
Among others, Zone 21 encompasses mills,
warehouses for coal or grain, and the area sur-
rounding filling stations. Here explosive clouds of
dust can develop due, for example, to the occa-
sional escaping of dust from the opening. The
risk of hazards due to dust deposits is often
underestimated. Explosive dust/air mixtures can
develop due to the formation of a smoulder spot
or of a low temperature carbonization gas, as
well as due to the deflagration of a low tempera-
ture carbonization gas or to the whirling-up of
gas caused by glowing combustion. According
to Directive 94/9/EC, apparatus for Zone 21
must comply with the Category 2D.
X CE marking and contents of the EC certificate of conformity In a potentially explosive atmosphere the
atmosphere can become explosive due to local
and operational conditions.
XI VMinimum criteria to be taken into account by the member states for the
authorization of testing laboratories The scope of application of this directive does
not include:
• medical equipment designed for use in
The purpose of this directive is the assimilation medical areas,
of the statutory stipulations of the member sta- • apparatus and protective systems with which
tes of the European Union concerning apparatus an explosion hazard is only possible if
and protective systems for use in potentially explosives or chemically unstable substances
explosive atmospheres. are present,
• apparatus intended for use in domestic and
As of July 1, 2003 it replaced any existing direc- non-commercial surroundings in which an
tives concerning explosion protection on a Euro- explosive atmosphere can only rarely be
pean level. The European Parliament fixed July formed, and then only as a result of an
1st, 1996 as the date for the conversion of the inadvertent leakage of fuel,
new directive into national law. • personal protective outfits,
• ocean-going vessels and mobile offshore
The four chapters of the disposing part are sub- plants, as well as the equipment on board of
divided into 16 clauses. In the chapters refe- these vessels or plants,
rence is made to the annexes I to XI, which • vehicles and the associated trailers that are
include 7 modules exclusively intended for the transportation
of people by air, road, rail, or water, and
Scope of application transportation means designed for the
The directive, also known as the ATEX directive, transport of goods by air, public road and
applies to apparatus and protective systems railway systems, or water. Vehicles intended
that are designed for use in potentially explosive for use in potentially explosive atmospheres
atmospheres. Safety devices and control are not excluded and,
systems for use outside of potentially explosive • possibly, products for military purposes, if this
atmospheres also come under this directive. is deemed necessary by any of the member
This applies when such devices are required for states of the European Union.
the safe operation of apparatus and protective
yes no
Electrical
apparatus
Motor
with internal
yes combustion
no
Documentation Documentation
from a notified body from manufacturer
EC-Type Examination
Internal production control
Marking
Group II Each piece of apparatus and each protective
II 2D Category 2 (Zone 21 apparatus) (D = dust) system must be marked in a clear and indelible
manner with the following minimum data:
• manufacturer”s name and address
Group II • CE marking
II 3D Category 3 (Zone 22 apparatus) (D = dust) • designation of the series and of the type
• serial number, when required
• the year of construction
• the community marking for explosion-
protected apparatus in accordance with the
directive 76/117/EEC in conjunction with
the marking relating to the category
• the letter ”G” for apparatus group II for areas
in which explosive mixtures of gas,
Putting into circulation and vapour or mist with air mixtures are present
commissioning of products and/or the letter ”D” for areas where an
The member states must not forbid, restrict or explosive atmosphere can form due to dust.
impede the putting into circulation and commis-
sioning of apparatus, protective systems and In addition and where required, any details that
devices that conform to the terms of this direc- are indispensable for the safety of operation also
tive. Similarly, the putting into circulation of com- have to be affixed.
ponents covered by a certificate of conformity
shall not be forbidden, restricted or impeded if
they are to be built into a piece of equipment or Provisional arrangements
a protective system in line with this directive. From 1.3.1996, the date on which the directive
first became applicable, to the completion of
The EU member states assume conformity with harmonization on 1.7.2003 there was a transitio-
this directive and with the conformity asses- nal period during which the old regulations and
sment procedures if the apparatus, protective the new directive could be applied parallel to
systems and devices are accompanied by the each other. This long transition period facilitated
EC Certificate of Conformity and if the products the implementation of the new quality assurance
are provided with the CE mark. system according to the requirements of the
Products that do not yet meet the requirements directive for the manufacturers. The apparatus
of this directive may be displayed at exhibitions, must be marked clearly so that the user can tell
fairs and demonstrations, if a visible label clearly whether the ”old” or the ”new” directive was
points to the fact that it will not be possible to applied.
purchase the product until compliance with the
directive has been ensured.
• Directive 73/23/EEC
This directive does not apply to ”Electrical
apparatus for use in explosive atmospheres”
(Exclusion as per Annex II of the directive)
• Directive 89/336/EEC
Type label according to new ATEX directive 94/9/EC This directive is to be applied to any products
that may cause electromagnetic interferences
or the operation of which may be impaired by
such interferences
eLLK 92036/36
• Directive 89/392/EEC
CEAG Sicherheitstechnik GmbH
Article 1, clauses 4 and 5 of the directive
PTB Nr. Ex-92.C.1801 X clearly state that this directive is not to be
applied to explosion-protected electrical
EEx ed IIC T4 110-254 V 50-60 Hz apparatus
Lampe: G13-IEC-1305-2 110-230 V DC
Ser. Nr.: D189115 Tu ≤ 50 °C
Type label according to previous directive
Zone 21 Annex II B
An area in which an explosive atmosphere in the Criteria for the selection of apparatus and pro-
form of a cloud of combustible dust found in the tective systems
air can form occasionally under normal ope-
rating conditions. Unless otherwise specified in the explosion pro-
tection document taking into account the risk
Zone 22 evaluation, apparatus and protective systems
An area in which an explosive atmosphere in the are selected in accordance with Directive
form of a cloud of combustible dust found in the 94/9/EC.
air normally does not occur or occurs for a
short period only under normal operating con- Zone Category
ditions. 0 or 20 1
1 or 21 1 or 2
With combustible dusts it is also necessary to 2 or 22 1, 2 or 3
consider the layers, deposits and accumulations
as a source for possible explosive atmospheres. Annex III
Normal operation is understood as being when Warning sign for marking areas in which explo-
installations are used according to the specified sive atmospheres can occur.
parameters.
With this decree, that came into force on Annex 1: Minimum requirements for work
October 3, 2002, among other things, Direc- equipment in acc. with § 7, Section
tive 1999/92/EC was converted into German 1, No. 2
law. Within the scope of the interim provisions Annex 2: Minimum requirements for the
in the BetrSichV, it replaces the ElexV for the improvement of the safety and
field of explosion protection. health protection of employees
when using work equipment
Table of contents Annex 3: Zone classification of potentially
Section 1 explosive atmospheres
General regulations Annex 4: A: Minimum requirements for the
§ 1 Scope of application improvement of the safety and
§ 2 Definitions health protection of employees
who could be endangered by
Section 2 potentially explosive atmospheres
§ 3 Assessment of degree of hazard B:Criteria for the selection of equip-
§ 4 Requirements relating to the provision ment and protective systems
and use of work equipment Annex 5: Testing of special pressure appara-
§ 5 Potentially explosive atmospheres tus according to § 17
§ 6 Explosion protection document
§ 7 Requirements relating to the quality of As this table of contents shows, the BetrSichV
work equipment does not only lay down rules for the field of
§ 8 Further protective measures explosion protection, but it also replaces a
§ 9 Information and instruction series of other decrees, e.g. the decree on
§ 10 Testing of work equipment flammable liquids or the pressure tanks
§ 11 Records decree. Due to the large scope of the rulings
of the decree, it is not necessarily easy to find
Section 3 the individual provisions of the EC Directive
Special regulations for installations discussed in the previous section immediately.
requiring supervision However, they have all been incorporated in
§ 12 Operations accordance with the European law. The Ger-
§ 13 Required permits man legislator made avail of the aforementio-
§ 14 Testing before putting into operation ned possibility to expand on the minimum
§ 15 Recurrent tests requirements of the directive during conver-
§ 16 Prescribed special tests sion into national law, inasmuch as the Ger-
§ 17 Testing of special pressure apparatus man law includes clearly defined requirements
§ 18 Accident and damage reports for testing apparatus before putting it into
§ 19 Test certificates operation for the first time, for recurrent tests
§ 20 Notice of defects and testing after apparatus repairs.
§ 21 Approved supervisory authorities
§ 22 Supervisory authorities for installations
requiring supervision owned by the
Federal Government
§ 23 Operation of portable pressure apparatus
within the boundaries of an industrial
plant
Section 4
Joint regulations, concluding provisions
§ 24 Commission for operational safety
§ 25 Breaches of regulations
§ 26 Punishable offences
§ 27 Provisional rulings
inert gas
Sand
Oil filling filling
Oil immersion ”o” – EN 50 015 Pressurization ”p” – EN 50 016 Sand filling ”q” – EN 50 017
General
requirements
Flameproof enclosure ”d” – EN 50 0158 EN 50 014 Increased safety ”I” – EN 50 019
Potting
”n”
compund
Types of protection
Cooper Crouse-Hinds GmbH 24
Oil immersion ”o” Pressurization ”p”
EN 50 015/VDE 0170/0171, Part 2 EN 50 016/VDE 0170/0171, Part 3
Definition: A type of protection for electrical appa- The type of protection Pressurization prevents
ratus where the complete electrical apparatus or the penetration of an explosive atmosphere into
parts of electrical apparatus are rendered safe the enclosure containing electrical apparatus.
by immersing them in oil, so that the explosive This is achieved by means of an inert gas inside
atmosphere cannot come into contact with the the enclosure that is maintained at a pressure
potential ignition source. above that of the surrounding atmosphere. The
With this type of protection, the ignition source is overpressure of at least 0.5 mbar can be main-
so deeply immersed in an oil-filled enclosure that tained with or without continuous purging with
a transmission of the flame to the area above the inert gas.
oil level is prevented. This requires that the ther- As a rule, air serves as an inert gas. Previously
mal output fed to the oil, the thermal energy and this type of protection was called separate
the resulting energy density be taken into ventilation ”f”.
account. There are two types of pressurization:
• Pressurization with continuous purging
This type of protection is chiefly applied to swit- • Pressurization with leakage compensation
chgear and transformers. With such switchgear,
Example of pressurized apparatus the switching arc is drawn in oil and does not, The inert gas must enter into or exit the enclo-
therefore, come into contact with the explosive sure outside of the hazardous area. With both
mixture. Besides making sure that a sufficient oil types, the enclosure of the apparatus and all its
level is provided in any operating position of the ducts must be purged prior to operation by a
switchgear, the use of a suitable oil that must not volume of gas that equals the five-fold volume of
decompose as a result of the switching arc is of the enclosure. During operation the overpres-
special importance. In addition to this, care has sure must be monitored and, if the overpressure
to be taken to ensure that the temperature of the drops, a warning signal given or the apparatus
switchgear does not rise too high. An increased switched off.
oil temperature could, in turn, become an ignition Normally, a flow gauge is used in conjunction
source. The long term quality of the oil must also with a time lag relay to monitor the purging. The
be monitored, as soot changes the properties of time lag relay starts running at the same time as
the oil. purging. As soon as the required volume of inert
gas has flown through, the time lag relay relea-
Oil-immersed switchgear was widely used by the ses the switching-on of the apparatus that is
chemical industry for the local switching of built into the enclosure. If the purging fails or
motors. As a result of the transition to remote there is a drop in the overpressure during opera-
controls and an increase in the number of tion, the flow gauge or a manometer closes a
interlocks, it has lost much of its significance. contact which switches off the apparatus or
Nowadays oil-immersed switches are only instal- gives a warning signal.
led in exceptional cases. Moreover, the use of oil- The encapsulation of the apparatus must con-
immersed switches for portable equipment is not form to a minimum degree of protection IP 40 to
permitted. They also require a lot more mainten- EN 60529. It must prevent the propagation of
ance. Repairs are more difficult, because the oil flames, sparks or ignitable particles to the
box has to be removed prior to starting. This is potentially explosive atmospheres.
often undesirable inside the work area.
Examples for pressurization ”p”
• Electrical machinery with higher rating
• Switch cabinets
• Control panels
• Switch rooms
• Transformers
• Measuring instruments
• Resistor instruments
• Liquid starters
• Luminaires
• Current and voltage transformers
• Communication devices
Limiting temperature at the end of time tE R* °C 160 175 185 210 235
2
B
If the rotor and the stator take different times to EN 50 028/VDE 0170/0171, Part 9
heat up, the shorter time will be taken as tE. The With the type of protection encapsulation ”m”,
1 type label and the certificate of approval of the those parts that are capable of igniting an explo-
A motor state the time tE and the ratio of the star- sive atmosphere are embedded in a compound
tE ting current IA to rated current IN. with sufficient resistance to environmental influ-
0 ences. The explosive atmosphere can neither be
The protection devices must keep the specified ignited by sparking nor by heating, both of
t (1) in h t (2) in s tripping times within a tolerance of which may occur within the encapsulation.
+/-20 %.
Fig. 2: Explanation how to calculate the time tE Duromers, thermoplastics and elastomers with
A max. permissible ambient temperature Fig. 3 shows the characteristic of a thermal relay and without fillers and/or other additivies may be
B temperature in rated operation with an example for checking. The relay, that is used as compounds. The properties of the com-
C limiting temperature
t time
set at the rated current of the motor, triggers at pound must fulfil the requirements of EN 50 028
θ temperature 7.4 times the rated current within a period that is (e.g. temperature index T1 to IEC 60216-1) wit-
1 heating-up in rated operation shorter than the time tE. The relay is suitable for hin the given temperature range.
2 heating-up with motor being stalled protecting the motor. The selection of the compound for a specific
application depends on the function that the
40 The protection devices must also switch off the compound has to fulfil in the apparatus. The
motor in the event of the failure of one phase. encapsulation must ensure the efficiency of the
Here, current-dependent thermal overcurrent type of protection, even in the event of permissi-
20
t in s
relays or circuit breakers can be used if, for ble overloads and certain internal fault conditi-
example, they are equipped with a phase failure ons.
11 10 protection to VDE 0660.
The compound may contain hollow spaces for
With motors in connection the protective the accommodation of components such as
5 device must fulfil the following conditions. In the relays, transistors etc. up to a volume of 100
seized motor and with phase failure, the tripping cm3.
time shall be tested with 0.87 times the motor
starting current, whereby the tripping time must If the compound in encapsulated apparatus is
2
be within the time tE. This test is necessary to directly exposed to the surroundings, the com-
detect the increased temperature caused by the pound must comply with the requirements of
1 unequal loads of the windings, as it cannot be EN 50 014 for non-metallic materials.
3 4 5 6 7,4 8 identified by means of the mains-current con-
IA /IN sumption. Examples for encapsulation ”m”
• Relays, signal and control units
Fig. 3: Tripping characteristic of the thermal relay In general, electrical motors of the type ”increa- • Transistors, sensors
from cold sed safety” may only be used in continuous • Film resistors, indicators
Time tE of the motor to be protected 11 s operation and for normal, seldom recurring • Ballasts (conventional type)
IA/IN of the motor to be protected 7.4 starts so as to prevent that the rises in tempera- • Electronic ballasts
ture occurring during the start exceed the per- • Subfractional horsepower motors
missible limiting temperatures. In the case of • Solenoid valves
motors in the low-voltage range, thermal motor
C = 15 Ω (Cd)
Constructional requirements clearances are laid down in EN 50 020.
C =5,6 Ω (Cd) e. g. when U =/≤ 060 V 0,5 mm
10 µF
Any components on which the intrinsic safety when U =/≥ 750 V 1,4 mm
depends (with the exception of transformers
3 µF
which are subject to special conditions), must The voltage U is the sum of the voltages of the
(Sn) not be charged with more than 2/3 of their rated intrinsically safe and the non-intrinsically safe cir-
1,0 µF
current, rated voltage or rated capacity, even in cuits. This clearance is not required,
(Cd) the event of faults (e. g. mains voltage at the – if the leads of the intrinsically safe or the non-
0,3 µF input side of electronic circuits). intrinsically safe circuits are furnished with an
earthed screen, or,
0,1 µF
Types of limiting modules – if, with safety level -ib- electrical apparatus,
the insulation of the leads of the intrinsically
0,03 µF safe wires withstands an AC test voltage of
Safety barriers with diodes 2000 V. In addition to this, care must be taken
0,01 µF Sub-assemblies comprising diodes or Zener that no inductive or capacitive interferences
1V 3V 10 V 30 V 100 V 300 V 1000 V
diodes that are protected by a fuse or a resistor from the non-intrinsically safe circuit can result
may be used as safety barriers between intrinsi- in the intrinsically safe circuit.
Fig. 2: Capacitive circuits cally safe circuits and a non-intrinsically safe cir-
Minimum igniting voltages to be applied to group IIC cuit. The input current of such barriers must be
electrical apparatus. The curve marked Sn is only to such that they can be connected to a mains Apparatus for intrinsically safe
be applied to electrical apparatus not containing any supply with a maximum short-circuit current of circuits
cadmium, zinc, magnesium or aluminium. 1.5 kA.
As with all other types of protection, generally all
Apparatus with galvanic isolation associated electrical apparatus used in the in-
1H
Transformers that, for example, are built into trinsically safe circuit and the intrinsically safe
500 mH intrinsically safe power supplies must ensure a apparatus must be tested and certified. Accor-
safe galvanic isolation between the primary and ding to EN 50014 the only exception is appara-
the secondary circuit. The data that is relevant tus where, according to the data given by the
200 mH
for the intrinsically safe circuit is determined by manufacturer, none of the values 1.2 V; 0.1 A;
the output characteristic of the transformer and 20 µJ or 25 mW is exceeded.
100 mH
any external circuits (voltage limitation by diodes,
50 mH
current limitation by resistors or by the electro- Intrinsically safe apparatus where the electrical
nics). data and the thermal behaviour can be clearly
I defined and that conform to the applicable con-
20 mH II A
Isolation of intrinsically safe structional requirements, do not need to be
II B tested or certified.
10 mH circuits from non-intrinsically This applies, for example, to:
safe circuits • switches
5 mH
• plugs and sockets
• terminal boxes
2 mH
II C Connection pieces • measuring resistors
In order to avoid any mistakes when connecting
• single semi-conductor components
or bridging conductors, the connection pieces
1 mH • coils (moving coil instruments)
for intrinsically safe circuits must be safely isola-
• capacitors
500 µH ted from the connection pieces of a non-intrinsi-
• electric position sensors (DIN 19 234)
cally safe circuit. For this purpose the connec-
tion terminals of the intrinsically safe circuit can,
200 µH It is absolutely essential to comply with the
for example, be installed at a distance of at least
general requirements according to EN 50 014
50 mm from the connection pieces of each non-
100 µH and with the requirements for the design of
5 mA 10 mA 20 mA 50 mA 100 mA 200 mA 500 mA 1A intrinsically safe circuit or they can be separated
enclosures and connection boxes with regard to
by an isolating barrier or an earthed metal bar-
the surface resistance or the choice of alumi-
rier. These barriers must either reach up to 1.5
Fig. 3: Inductive circuits nium alloy (surface resistance of plastic enclosu-
mm from the enclosure wall or they must ensure
Minimum igniting currents to be applied to res < 109 ohms).
a minimum clearance of 50 mm between the
electrical apparatus containing cadmium, zinc,
connection pieces.
magnesium or aluminium at E = 24 V.
Technical terms
Intrinsically safe electrical systems
All the interconnected electrical apparatus docu-
mented in a system description, where the cir-
cuits that are to be used wholly or partly in a
potentially explosive atmosphere are intrinsically
safe.
System description
A document drawn up by the system design
engineer in which the electrical apparatus, the
electrical characteristics there of and the
characteristics of the connecting leads are
described. The term ”system design engineer”
designates a person who is responsible for the
intrinsic safety of the system.
Technical terms
Cap lamp
An apparatus comprising a headpiece, a
connecting cable and rechargeable secondary
cell(s)/battery in a container.
Constructional requirements
The cap lamp must be designed in such a way
that, if a fuse or thermal cicuit breaker is used as
over-current protection,
Firedamp-protected cap lamp with nickel-cadmium • the rated voltage does not exceed 6 V,
battery • the current does not exceed 1.5 A when ope-
rated as intended,
• the lamp rating is not higher than 6 W,
• the circuit behaves as if it only contains active
resistances.
EN 50 284 VDE 0170/0171, Part 12-1: It supplements the standards EN 50 014 and
”Special requirements for the design, testing and EN 50 020 to EN 50 028 and is intended to
marking of electrical apparatus in apparatus adapt the safety level provided for by these
Group II, Category 1G” standards to the extremely high risks.
This European standard lays down detailed
requirements for apparatus in apparatus In order to eliminate the ignition hazards that can
Group II, Category 1G. The apparatus must be emanate from the electrical circuits of the appa-
designed in such a way that it guarantees a very ratus, the necessary measure of safety must eit-
high degree of safety in normal service. her be guaranteed, even if two faults that are
Category 1 apparatus is intended for use in independent of each other occur, by applying a
potentially explosive atmospheres in which single constructional protection measure, or, if
explosive mixtures of air with gases, vapours or one constructional protection measure fails, it
mists occur continuously, for long periods or fre- must be ensured by a second, independent
quently. This standard also applies to apparatus constructional protection measures.
that is mounted in the barriers between different
potentially explosive atmospheres. It also inclu- Permissible individual constructional
des requirements for apparatus that is installed protection measures are:
outside the potentially explosive atmosphere, • Apparatus and circuits in accordance with
but that is connected electrically to Category 1 the requirements of EN 50 020, safety
apparatus (associated apparatus). level ”ia”
• Encapsulated apparatus in accordance with
the requirements of EN 50 028 supple-
mented by the additional requirements of
this standard.
Requirements according to the thickness t of the barrier
(i) t ≥ 3 mm, no additional measures Combinations of constructional
Type of construction (iii) (iv)
protection measures
(ii) Electrical apparatus must fulfil the requirements
3 mm > t ≥ 1 mm 1 mm > t ≥ 0.2 mm t < 0.2 mm
of two standards of the series EN 50 014 to EN
(“X“ symbol) (“X“ symbol)
50 020 (ib) and EN 50 028 independently of
a) Barrier each other. These combined standardized types
of protection must be based on different physi-
Less hazardous area2) – standardized
Hazardous cal protection principles. It must be possible to
type of test them independently of each other. The
area1)
protection and adjacent table illustrates the possible combinati-
– no ignitable Type of protection ons of barriers with the types of protection
Electrical
Barrier apparatus sparks during Intrinsic Not permissible where barrier elements are used.
operation Safety “ib“
(e.g. no open Apparatus and parts thereof for use in Zone 0
switching must also be built in such a way that
contacts) • ignition sources due to impact or friction
sparks are excluded.
b) Barrier and gap In the case of apparatus with parts that
move during operation, light metals must
Less hazardous area2) – standardized not be used at the possible friction or
Hazardous type of impact points or at other accessible points.
area1)
protection and • no ignition hazards due to dangerous elec-
– no ignitable trostatic charges can occur. Special conditi-
Electrical
Barrier3) apparatus – standardized type of protection sparks during ons apply to enclosures and parts of enclo-
operation sures made of moulded plastic
(e.g. no open
Gap3) switching Connection technique
contacts) As far as possible, connections for Zone 0
apparatus and parts thereof should be located
c) Barrier and ventilation outside the Zone 0.
The type of protection ”n” applies to electrical The ”hermetically sealed devices”, the ”sea-
apparatus of the apparatus category 3G, that, led devices” and the ”encapsulated devi-
under normal and certain abnormal operating ces” are based on the fact that the explosive
conditions, are not able to ignite a surrounding atmosphere and the potential ignition source
explosive atmosphere. These operating conditi- remain safely isolated from each other. The
ons are laid down by the manufacturer as part ”enclosed switching devices” are modelled
of the electrical and mechanical design data and on the familiar type of protection ”Flameproof
it is essential that the user observe them. The enclosure” to.
aim of this type of protection is to find an econo- With EN 50 018 the ”non-ignitable compo-
mical compromise between the normal industrial nent” ignition is prevented by constructional
standard and the high safety requirements for measures, while, at the same time, the type of
the types of protection for apparatus in the gas is taken into consideration. The marking
Category 2G. ”nC” is used for this group of measures, whe-
reby the permissible type of gas (IIA, IIB, IIC)
General requirements must also be stated. The ”restricted breathing
As with the already familiar types of protection enclosure” is another permissible explosion
for the apparatus category 2G, the general protection measure with the marking with ”nR”.
requirements for electrical apparatus (e.g. sur- The enclosure is designed in such a way that an
face temperature, design, cables, clearances explosive atmosphere can only enter it in a
and creepage paths, …) also apply here. restricted measure. The ”simplified pressu-
rization” is modelled on the familiar type of pro-
tection ”Pressurization”, whereby simplified
Potential ignition sources
measures were approved. This apparatus is
Basically distinction is made between non-spar-
marked with ”nP”.
king apparatus, that does not give off any
A further explosion protection measure is the
potential ignition sparks during operation, and
”restricted energy apparatus” with the mar-
apparatus that gives off arc or sparks or produ-
king ”nL” and the marking for the suitable gas
ces hot surfaces during normal operation. In the
group (IIA, IIB, IIC). This is based on the type of
case of this apparatus, that, on principle, fea-
protection ”Intrinsic safety”, whereby the safety
tures potential ignition sources, it is necessary to
factors are less stringent.
take additional protective measures to allow its
safe operation.
Documentation
As it is possible to have a combination of various
Non-sparking apparatus
explosion protection measures for apparatus
Depending upon the type of apparatus (e.g.
category 3G, it is strongly recommended that
electric machines, luminaires), non-sparking
the operator study the associated documenta-
apparatus must fulfil additional conditions, so
tion carefully, because all the safety instructions
that no potential ignition sources can develop
issued by the manufacturer must be observed
during normal operation. In addition to the appa-
for maintaining safety.
ratus category 3G, the apparatus is also marked
with ”nA”, whereby this combination of letters
stands for ”non-sparking apparatus”.
Hermetically sealed devices ”nC” Sealed devices ”nC” Encapsulated devices ”nC”
Enclosed switching device ”nC” Non-sparking apparatus ”nA” Non-ignitable component ”nC”
Retricted energy apparatus ”nL” Restricted breathing ”nR” Simplified pressurization ”nP”
Apparatus for
Zones 0,1 No ignitable hot surfaces
Apparatus no
designed for Zone 2 Arcs or sparks
(EN 50 021 ”n”)
yes
Recognized
Energy restriction
industrial standard
Safety factor 1 to EN 50 021
IEC 61241-1 IEC 61241-2 IEC 61241-3 IEC 61241-4 IEC 61241-5
Electrical apparatus Methods Classification of areas Electrical apparatus; Electrical apparatus –
protected by enclosures for determining where combustible dust type of protection intrinsic apparatus
are or may be present pressurization ”p” (pD)
EN 61241-3:199X-XX
IEC 61241-1-1 IEC 61241-2-1 E DIN IEC 31H/47/CDV E DIN IEC 31H/67/CD IEC 31H/84/CD
Design and test Method for determining (VDE 0170/0171 Part 1505): (VDE 0170/0171 Part 15-4): [Intended as
EN 50281-1-1:1998-09 minimum ignition 1995-05 1997-08
VDE 0170/0171 Part 15-5]
DIN EN 50281-1-1 energy of dust [Intended as [Intended as
(VDE 0170/0171 EN 50281-2-1:1998-09 VDE 0165 Part 102] VDE 0170/0171 Part 15-4]
Part 15-1-1): 1999-10 DIN EN 50281-2-1
(VDE 0170/0171
Part 15-2-1): 1999-11
IEC 61241-2-3
Methods for deter-
mining the minimum
ignition energy of
dust/air mixtures
Edition: 1994-09
[under modification, work
shift to CEN/TC 305]
IEC 61241-2-4
Methods for determi-
ning minimum ignition
energy of dust
[under modification, work
shift to CEN/TC 305]
Table taken from EN 50 028-1-1 (VDE 0170/0171, part 15-1-1) 1999-10.3 page 3
Zone 10
Zone 10 covers areas in which an explosive
atmosphere is present for long periods or fre-
quently.
Zone 11
Zone 11 covers areas in which the occurrence
of an explosive atmosphere as the result of the
stirring-up of dust deposits is to be expected
occasionally for short periods.
The manufacturer shall develop and manufac- With regard to areas with combustible dust, the
ture electrical apparatus for use in potentially German translation of EN 50281-1-2 as the Ger-
explosive atmospheres in accordance with the man standard DIN VDE 0165, Part 1-2, ”Electri-
requirements of Directive 94/9/EC. cal apparatus with protection by the enclosure –
If specified in the standards, testing by an inde- selection, installation and maintenance, in the
pendent testing station must be arranged. The edition dated November 1999, applies.
approvals issued by the testing station and/or
the declarations issued by the manufacturers If the installer is not also the operator, the instal-
are to be placed at the disposal of the operator. ler shall issue an installation certificate at the
It is the duty of the manufacturer to manufacture operator”s request. This certificate confirms that
each piece of electrical apparatus in such a way the electrical installation conforms to the valid
that it complies with the test documentation and requirements. If such a certificate is available,
the test samples. Finally, he is also obligated to additional testing by the operator prior to com-
subject each piece of explosion-protected appa- missioning is no longer necessary.
ratus manufactured to a routine verification
and test and, after successful completion of
this test, to mark the apparatus accordingly. If
”special conditions” apply to the use of the
apparatus, the manufacturer must provide the
installer or the operator with this information in a
suitable form together with the apparatus.
North America NEC 505 Zone 0 (gas) Zone 1 (gas) Zone 2 (gas)
IEC / EN Zone 20 (dust) Zone 21 (dust) Zone 22 (dust)
450°C T1 T1
300°C T2 T2
280°C T2A
260°C T2B
230°C T2C
215°C T2D
200°C T3 T3
180°C T3A
165°C T3B
160°C T3C
135°C T4 T4
120°C T4A
100°C T5 T5
85°C T6 T6
NEMA IP
3 IP 54
3R IP 54
3S IP 54
4 and 4X IP 56
5 IP 52
6 and 6P IP 67
12 and 12 K IP 52
Degrees of protection against foreign matter designated by the first code No.
Degree of protection
First
code
No. Brief description Definition
0 No special protection –
1 Protected against solid The object probe, a ball of 50 mm dia.
foreign bodies 50 mm dia. must not fully penetrate *)
and bigger
2 Protected against solid The object probe, a ball of 12.5 mm dia.
foreign bodies 12.5 mm dia. must not fully penetrate *)
and bigger
3 Protected against solid The object probe of 2.5 mm dia.
foreign bodies 2.5 mm dia. must not penetrate at all *)
and bigger
4 Protected against solid The object probe of 1 mm dia.
foreign bodies 1 mm dia. must not penetrate at all*)
and bigger
5 Dust protected Ingress of dust is not totally prevented, but
the dust must not enter in such an amount
as to interfere with satisfactory operation or
with the safety of the apparatus.
6 Dusttight No ingress of dust
*) Note: The full diameter of the object probe must not pass through any opening of the enclosure.
2. If yes:
Do electrical
installations/apparatus
have to be taken into
operation in
a hazardous area?
If yes, then:
4. Decision
based on TABLE 2
4.2 Type of
installation according
to zone
Installationcertificate 1)
Date: Order-No.:
Building: Plant:
________________ _________________
Place, Date Signature
1
) Up to final regulation
Permit for welding, burning and other hot work, for drilling, grinding, impact and calking work, for the use of non-explosion
protected apparatus.
A 1. Contractor: Building: Tel.: Foreman:
2. Place and kind of work
”Explosion protection: Commentary on Fähnrich Ralph/Mattes, Hatto. Erich Schmidt Verlag GmbH, Berlin
ExVO and BetrSichV”
ISBN 3-503-01881-6
”ZH 1/10 Rules on health and safety protection at work; Employers´ Liability Insurance Jedermann-Verlag, Heidelberg;
Explosion protection rules” Company of the Chemical Industry Werbe Druck Winter, Sandhausen
”VDE regulations: Selection for explosion protection;2004-03” VDE VDE Verlag Berlin
Electrical installations and equipment in Olenik, Heinz/Dose, Wolf-Dieter/ Hüthig & Pflaum Verlag, Heidelberg
potentially explosive atmospheres Rading, Herbert F. ISBN 3-8101-0130-3
Mining decree on the general certification Gazette No. 54, Part 1 Bundesanzeiger Verlags mbH
of firedamp-protected electrical apparatus (1983)
(mining decree on the approval of electrical apparatus
– ElZulBergV)
The new equipment safety law (1980) Jeiter, W. Verlag C. H. Beck, Munich
ISBN 3-4063-7260-0
Safety coefficients of flammable gases and vapours; Narbert, K./Schön, G. Deutscher Eichverlag GmbH
Braunschweig
Directives for the prevention of ignition hazards Central union of the Employers Carl Heymanns Verlag KG,
as a result of electrostatic charges – Liability Insurance Association, Cologne
Directives ”Static electricity” BER 132 Central Office for
Industrial Medicine,
Bonn
New procedure for the testing and certification Dreier H./Hofer D. PTB Info No. 4 (1980)
of explosion-protected electrical apparatus
The data was compiled and verified with due care in keeping with the latest standards
and regulations. The prevailing technological and statutory rules are binding.
No liability will be assumed for any damages that may arise from the use of this
data.
Explosion-protected
● Floodlights
● Portable lamps
● Switchgear
● Terminal boxes
Cooper Crouse-Hinds GmbH
● Intrinsically safe signal conditioning Neuer Weg-Nord 49, D-69412 Eberbach
Phone +49 (0) 62 71/8 06-5 00,
● eXLink Fax +49 (0) 62 71/8 06-4 76
Internet www.ceag.de
e-mail [email protected]