Few factors are to be considered or taken care of while wiring a field instrument to control panel.
Level 1
High noise susceptibility level to the medium level: Analog signals of less than 50 V and discrete
instrument signals of less than 30 V.
• Foundation Fieldbus
• 4-20 mA and 4-20 mA with HART
• RTD
• Thermocouple
• Millivolt/pulse
• Discrete input and output signals. Example: pressure switches, valve position’s limit
switches, indicating lights, relays, solenoid coils.
• All wiring connected to components related to sensitive analog hardware like strain
gauges.
Level 2:
Low susceptibility: Switching signals of greater than 30 V. Analog signals greater than 50 V, and
120-240 AC feeders rated less than 20A.
Examples:
• Discrete input and Discrete output DC signals like pressure switches, valve position’s
limit switches, indicating lights, relays, solenoid coils.
• Discrete input and Discrete output AC signals including pressure switches, valve
position’s limit switches, indicating lamps/lights, relays, solenoids coils.
• 20-240 AC feeders of less than 20 amps
Level 3:
For example, all 4-20 mA signals shall rout on separate cables from all other signals under Noise
Susceptibility Limit -1. The same applies to all other signal types. From the junction boxes to the
control room, the cables for every Noise Susceptibility (NSL) level can share the identical cable tray
or trench. The separation distance between NSL-1 and NSL-2 and strong electromagnetic
interference such as motors, generators, transformers above 100 KVA shall be at least two meters.
The separation distance between NSL-1 and NSL-2 and power cables rated above NSL-3 should
be at least 1 to 1.5 meters.
Besides, all emergency shutdown (ESD) signals should have their Own cables, junction boxes, and
also marshaling cabinets. They also have to be segregated based on the signal type as discussed
cases above. It is common to use twisted pair wire when wiring process instrumentation. when two
wires are twisted together, many of the electromagnetic interferences are canceled out, so twisted
pair wiring is more proof against electrical noise than untwisted wiring. To add another level of
protection from the electromagnetic noise is a ground shield is added over the twisted pair cable.
Field interface multi-core cables connected to junction boxes in the field, transmitting conventional
4-20 mA signals from all sorts of field transmitters, individually, are going to be connected to
marshaling racks. From the marshaling cabinet racks, the signals are going to be connected to the
I/O cards of the DCS and ESD system cabinets through pre-fab cables.
In the following figure below there are various types of field instruments connected to the control
room via a field junction box. A close picture of the connection from a starting point to the destination
is shown in it.
Instrument signals can be carried by wiring with a conductor size of at least 18 AWG is
recommended. Selecting conductors of 18awg or larger increases the reliability and makes
connections easier.
Insulation should be high-quality thermoplastic rated for the voltage to be used ( max 30 V). The
standard colors for two-conductor instrumentation cables ar red (+ve) and black (-Ve). Other colors
are also available.
The cable jacket should be rated for the proposed use and instrument cable is available for all of
the common general uses (e.g. conduit, tray, outdoors, direct burial, etc.).
Also, be sure the jacket is unaffected by any chemicals or oils that it may encounter. If the cable is
to be run in conduit, make sure the jacket is of the smooth one. The soft, rubbery jackets make
pulling difficult and might result in cable damage.
Also Read:
• Transmitter Wiring
• 4-20mA versus Fieldbus Junction Box
• Types of PLC Wiring
• Configure HART Transmitter
Cable terminations
Proper terminations result in trustworthy connections and help to eliminate problems like ground
loops and electromagnetic interference. Instrument wiring terminations are usually made to screw
terminals or compression terminals. Either one can be made reliable.
Be careful and take care when installing instrument wiring in proximity to higher voltage wiring. Any
wires carrying an AC signal of 120V or more are a possible source of electromagnetic interference,
and instrument signal cables should be installed at a safe distance from them.
If instrument cables must cross over an AC power and control cables, the two should be separated
by an adequate distance, and the crossing should be made at right angles to minimize induction.
Instrumentation systems have two types of grounds: The electrical or power ground and the
instrument ground. It’s important to understand that these two grounding systems have entirely
different purposes. The main purpose of the power ground is safety. All metallic or conducting
equipment should be connected to this power ground. The primary purpose of an instrument ground,
contrarily., is to protect instrumentation from electromagnetic interference. To implement this
successfully, any part of the protective shielding system must be connected to the ground at one
point and one point only.
Grounding them at both ends may result in ground loops which happen to be one of the main causes
of the signal noise.
Instrument Types
Transmitters are common input field devices. A transmitter typically consists of electronic cards that
interfaces to a sensor, which, in turn, measures some physical quantity of a process parameter.
The electronics read the signal from the sensor, do any conversion necessary, and then transmit a
signal that is proportional to the quantity being measured.
A temperature transmitter, for example, may measure temperature with a sensor called a
thermocouple or an RTD, perform compensation and linearization, and transmits a 4-20mA signal
representative of the temperature to a controller.
Transmitters have the following electrical configurations, as shown in the below figures. A field
powered transmitter takes power for its electronics package from a source in the field and transmits
a signal (usually isolated) on the two dedicated wires.
4 Wire Transmitter
A four-wire transmitter is the same as told above. But it takes its 24VDC power from a central power
source, and the power is transmitted to the device along the same cable that it carries the transmitted
signal back to the control system.
3 Wire Transmitter
Three-wire transmitters use two wires to power the transmitter and transmit it’s signal back on a
third wire. The instrument signal is non-isolated (referenced to common).
2 Wire Transmitter
Two-wire transmitters get power from the instrument signal itself without affecting its accuracy.
Two-wire current transmitters are very popular because of their simplicity, and the standard zero
offset guarantees that electronics will always have at least 4mA to operate on.
Source: IEEE-518, Guide for the Installation of Electrical Equipment to Minimize Electrical Noise
Inputs to Controllers from External Sources.