Microgrid Protection
Microgrid Protection
ABSTRACT | The proliferation of distributed energy resources the transmission system because they can potentially result
is setting the stage for modern distribution systems to operate in loss of many distribution systems. Within the past dec-
as microgrids, which can avoid power disruptions and serve ade, however, technological advancements and government
as resources for fast recovery during macrogrid disturbances. incentives facilitated significant integration of distributed
Microgrids are, therefore, major assets to improve the energy resource (DER) units with conventional “passive” dis-
grid resilience. However, the offered resilience is seriously tribution systems. This resulted in the emergence of “active”
undermined if microgrids are not properly protected in the distribution systems [1], which can evolve into microgrids
event of faults within their own boundaries. Distribution [2]. A microgrid is defined as a coordinated group of DER
protective devices cannot reliably protect microgrids due to the units that service a set of loads through a distribution system
variable and often limited short-circuit capacities of microgrids. with the capability to 1) operate connected to the conven-
Moreover, the research on microgrid protection has not led to tional power grid (i.e., the macrogrid); 2) operate islanded
a commercially available microgrid relay to date and has little from the macrogrid; and 3) provide smooth transition
prospect of reaching that level in the near future. As a result, between the macrogrid-connected and islanded modes [3].
the existing options for reliable microgrid protection remain A distribution system that operates as a microgrid brings suf-
effectively the subtransmission and transmission system ficient generation close to load and so can maintain the power
protective devices, e.g., directional overcurrent, distance, and supply in the event of macrogrid faults. In addition, if a micro-
differential relays. Although years of operation in macrogrids grid has excess generation capacity, it can provide the macrogrid
support these relays, their performance for microgrids is yet to with system recovery resources, thus decreasing the frequency
be analyzed. This paper presents such analysis for different relay and duration of outages. Such features add flexibility to the
types by considering various fault and generation conditions in aforementioned architecture and make a microgrid a tremen-
a microgrid. Time-domain simulations are used to identify the dous asset to improve the grid resilience to macrogrid failures.
scenarios where the relays function correctly as well as the However, the resilience offered by a microgrid will be
problematic conditions, on which future research should focus. in jeopardy if the microgrid is not properly protected during
This paper also presents a short review on direct current (dc) the short-circuit faults that occur within its own boundaries.
microgrids and their protection requirements. Although microgrids are erected at the distribution level of
the legacy grid, the available distribution protective devices,
KEYWORDS | Direct current (dc) microgrid protection; such as fuse and recloser [4], are not suitable candidates for
distributed energy resources (DERs); distribution protection microgrid protection due to various reasons, an important
system; electronically coupled distributed generation (ECDG), one of which is the complete dependence of these devices
induction-machine-based distributed generation (IMDG); on local current magnitude. The short-circuit capacity of the
macrogrid; microgrid; microgrid protection; mesogrid macrogrid can be larger than that of the relatively small DER
units of a microgrid by more than one order of magnitude,
I. I N T RODUC T ION making the fault current levels over the macrogrid-connected
The legacy power grid has a top-down architecture from and islanded modes of a microgrid sharply different. Such a
the generation to transmission to distribution systems. This big difference makes setting and coordination of existing dis-
structure offers limited resilience to faults and failures in tribution protective devices difficult and often unattainable.
A variety of methods have been published in the last
Manuscript received September 1, 2016; revised December 12, 2016; accepted few years to address microgrid protection issues [5]–[9].
February 7, 2017. Date of publication March 22, 2017; date of current version
June 16, 2017.
Meanwhile, given the sensitivity of reliable protection, exten-
A. Hooshyar is with the Electrical Engineering and Computer Science Department, sive testing and verification is needed for a protection scheme
York University, Toronto, ON M3J 1P3 Canada (e-mail: [email protected]).
R. Iravani is with the Electrical and Computer Engineering Department, University
to reach a commercial level, and the published research on
of Toronto, Toronto, ON M5S 3G4 Canada (e-mail: [email protected]). microgrid protection has not come close to this level yet. In the
Digital Object Identifier: 10.1109/JPROC.2017.2669342
0018-9219 © 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications standards/publications/rights/index.html for more information.
1332 Proceedings of the IEEE | Vol. 105, No. 7, July 2017
Authorized licensed use limited to: Universidad Tecnologica de Pereira. Downloaded on November 29,2020 at 02:53:41 UTC from IEEE Xplore. Restrictions apply.
Hooshyar and Iravani: Microgrid Protec tion
rural microgrids, and there exist considerable social, aspects of the microgrid. A necessary step to tackle micro-
economical, political, and environmental incentives/ grid control/protection issues is to identify its modes of
pressure to integrate renewable energy-based sources operation as follows.
with off-grid microgrids. Therefore, off-grid micro- 1) Macrogrid-Connected Mode: In the macrogrid-con-
grids will potentially be the fastest growing microgrid nected mode, each DER unit includes an LC that operates
type and remain as a member of microgrid family in the unit based on locally measured current and voltage,
terms of requirements and challenges. and their byproducts. The microgrid’s SC-EMS generates
DER reference signals, which are needed to coordinate the
operation of DER units. In the macrogrid-connected mode,
B. DER Units
SC-EMS also has the option to receive information from the
DER units are divided into electronically coupled and macrogrid, e.g., control commands, to adjust the microgrid
rotating-machine-coupled units. The main reason for this internal operation.
categorization is that the interface medium exhibits the 2) Islanded Mode: In this mode of operation, LCs and
dominant characteristics of a unit in terms of protection SC-EMSs are responsible only for the internal operation
and control. of the microgrid. Control strategies for islanded and mac-
1) ECDG Units: In this group, an alternating current/ rogrid-connected modes of microgrid are often different,
direct current (ac–dc) voltage–sourced converter (VSC) e.g., in macrogrid-connected mode all DER units can pos-
provides the interface medium between the source and sibly operate in PQ-control mode while after transition to
the microgrid [11], [12]. Depending on the power genera- islanded mode, a specific set of DER units need to operate in
tion capacity of the source, the VSC is either three phase or voltage-frequency control mode, and such a control transi-
single phase. The adopted DG technologies that use VSC- tion must be determined and managed by SC-EMS.
based coupling include solar-photovoltaic (PV) systems, 3) Mesogrid Mode: We define a mesogrid as a cluster of
Type-4 wind-turbine-generator systems, and medium- and microgrids, each including its LCs and SC-EMSs, which are
high-speed gas-turbine-generator systems. An ECDG unit is connected to a host macrogrid and operate in a prespeci-
either a nondispatchable unit or a dispatchable unit. In a fied coordinated manner. Each microgrid, within the mes-
nondispatchable unit, the primary source is often controlled ogrid, operates as a virtual power plant based on the control
and operated under a maximum-power-point-tracking commands that are generated by its SC-EMS and commu-
(MPPT) strategy [13]. nicated to LCs within the microgrid. The second (higher)
2) Rotating-Machine-Coupled DG Units: This category layer of the SC-EMS, i.e., the mesogrid SC-EMS, receives
adopts rotating machines as the coupling medium and information from the macrogrid and from each individual
includes the following: microgrid and, on that basis, specifies control/operation
• type-1 wind-turbine-generator units, which utilize responsibilities of each microgrid with respect to its PCC.
squirrel cage induction machines (SCIMs);
• type-3 wind-turbine-generator units, which incor-
D. DC Microgrid
porate doubly-fed induction machines (DFIM);
• diesel-generator units, which adopt filed-controlled Although high-voltage dc (HVDC) technologies have
SMs; been extensively utilized, the concept of medium-voltage
• conventional (low-speed) gas-turbine-generator (MV) and low-voltage (LV) dc microgrid and its protection
units, which use field-controlled or permanent- requirements are still in infancy. In contrast to ac micro-
magnet SMs. grids, which have been contemplated for a wide range of
existing ac systems, dc microgrids have been considered and
investigated only for specific applications, including: 1) LV
C. Microgrid Control (up to 1500-V dc) data centers [15]; 2) MV (up to 35-kV dc)
Control strategies for microgrids include distributed, systems at electric ships [16]; and 3) MV collector system
centralized, and hierarchical controls [14]. Some inherent of offshore wind power plants. Recent technical literature
characteristics of the microgrid—such as high degree of proposes LVDC distribution systems as dc microgrids for
imbalance and the diversity of DER units—impose chal- building applications [17]. Protection issues are among the
lenges to devise a viable control for all operating scenarios. main challenges that have hindered widespread deployment
Furthermore, accommodating the two distinct operat- of dc microgrids.
ing modes (that is, the islanded and macrogrid-connected
modes) and the requirement for transition between these III. M IC RO GR I D PRO T EC T ION
modes further adds to the complexity of the microgrid con- CH A R AC T ER IST ICS A N D A D OP T ED
trol. Since controls of electronically coupled units have large T E ST M IC RO GR I D
impact on the microgrid transient behavior, particularly Although a significant amount of research has been carried
subsequent to faults, they significantly affect protection out on microgrid protection, a protective relay that takes
microgrid characteristics into account has not been manu- and 60 Hz. This solidly grounded system is made up of two
factured to date. The following issues make protection of microgrids—namely Microgrid 1 and Microgrid 2—that are
microgrids rather uniquely challenging. radial, but meshed topologies also can be obtained by clos-
1) The fault current levels of microgrids are hugely ing switches S1, S2, and S3. The detailed specifications and
different in the macrogrid-connected and islanded the power flow results of the system can be found in [19]. In
modes. this paper, R ijdenotes the relay next to bus ilooking toward
2) The presence of generation units and complex bus j. The relays’ sampling rate is 5 kHz, and the full-cycle
operating scenarios in macrogrids together with discrete Fourier transform is used for phasor measurement.
the possibility of widespread blackouts as a result Three DG units are added to the benchmark system.
of macrogrid protection failures justify major 1) DG1: This is either an ECDG or an IMDG unit rated
investment to develop sophisticated protection at 4 MW and connected to bus 6. The specifications
systems for macrogrids. Depending on its size of the ECDG and IMDG units are as follows.
and configuration, a microgrid also can raise pro- – ECDG: The full-scale VSC of this unit is controlled
tection challenges similar to those observed for by the rotating reference frame control system [11],
a macrogrid. Some microgrid features—such as and its fault current is limited to 1.2 pu. The inter-
potentially large phase imbalance—can make its face transformer is rated at 5 MVA, 4.16/12.47 kV,
protection even more difficult. However, the fail- X =0.07 pu, with dYG winding connection. The
ure of a microgrid during a fault does not impact source and the converter that provides the dc volt-
a wide area, thereby limiting the investment in age are modeled by a controllable current source
microgrid protection. because the dynamics on the source and grid sides
3) A significant portion of generation units are of an ECDG unit are effectively decoupled through
expected to be interfaced with a microgrid through the dc link capacitor during the short span of a
VSCs, which exhibit unconventional fault behavior, fault.
including small short-circuit currents. – IMDG: This wind unit includes either an SCIM or
The North American version of the CIGRE MV bench- a DFIM. The controllers of the DFIM are similar
mark system, shown in Fig. 2, exemplifies the above features. to the system developed in [20], unless otherwise
1) Its short-circuit ratio can exceed 20. stated. The transformer of the unit is rated at 5
2) The combination of different switch statuses can cre- MVA, 0.575/12.47 kV, X =0.07 pu, with dYG wind-
ate topologies similar to those of transmission systems. ing configuration. The turbine model is similar to
Moreover, the current imbalance factor (defined by a commercial wind turbine [21], and the nominal
[18]) can reach 20% due to single-phase laterals. power is achieved at wind speed Vw =13 m/s.
3) More than half of the load can be supplied by VSC- 2) DG2: This unit includes two 4.3 MVA SMs connected
based units added to the original system. to bus 8 through a transformer rated at 10 MVA,
Therefore, this paper uses the PSCAD/EMTDC simula- 4.16/12.47 kV, X =0.07 pu, with dYG winding con-
tion of this mesogrid, which has been derived from a real nection. The subtransient reactances of the SMs are
MV network that covers a small town and its neighboring Xd″ =0.18 and Xq ″ =0.21 pu. DG2 can supply the
rural area. The rated voltage and frequency are 12.47 kV entire load, making the system capable of operating
off-grid. DG2 is disconnected during the macrogrid-
connected mode.
3) DG3: This unit is similar to DG2, but has only
one SM.
A. DG Fault Ride-Through
The integration of large renewable energy power plants
Fig. 2. CIGRE benchmark MV system [19]. with transmission systems has led to grid codes mandating that
B. DG Power Factor
Unlike conventional SM-based sources, the fault cur-
rent angle of a VSC-interfaced source—either ECDG or
Fig. 3. Fault ride-through curve for renewable sources in the
DFIM unit—is determined by the VSC’s control system.
European Union [22].
Therefore, besides the fault ride-through capability, some
transmission grid codes lay down specific requirements
renewable energy sources remain connected to the grid during for the power factor (PF) of renewable energy plants dur-
faults. This requirement, commonly referred to as fault ride- ing faults. In order to boost the voltage stability of system,
through, is defined through a stepwise/linear voltage versus European grid codes typically require generation of reac-
time-after-fault curve similar to the one shown in Fig. 3 [22]. As tive current following the onset of a fault. For instance, the
long as the operating point at the point of connection (PC) of a reactive current versus PC voltage of a renewable energy
renewable energy plant is above this curve, the plant must not plant in Spain must be situated inside the shaded area of
be tripped. The parameters along the voltage and time axes in Fig. 4 [27]. On the other hand, in terms of the reactive
Fig. 3 vary among different grid codes and are identified based current generated by a renewable energy plant, North
on various factors, including the characteristics of the protec-
American grid codes do not differentiate between fault
tion system. For example, tc learis normally around 150 ms,
and normal condition, during which a 0.95 plus positive-
which is about the maximum time taken by the primary protec-
sequence PF at the PC is typically required [28].
tion in transmission systems to clear a fault. During this period,
At the distribution level, a close-to-unity PF is usually
the renewable energy plant must be able to withstand close-to-
zero voltages. maintained by DG units during faults, since the voltage is
In contrast, distribution systems have generally fol- supported by the grid [24]. This practice can be followed
lowed the guidelines of the IEEE Standard 1547 in terms in a macrogrid-connected microgrid as well. However, reac-
of DG integration, which prohibits the formation of unin- tive current support by the DGs may be required to maintain
tentional islands energized by DG units [23]. Among a voltage stability during the islanded mode, resulting in low
variety of anti-islanding protection techniques, the most PF at the PC of a DG unit over faults. As a result, the protec-
commonly adopted is the active approach in which a DG tion system of a microgrid might face different PFs during
unit checks the response of the grid to a small disturbance macrogrid-connected and islanded modes.
created by the interface VSC. The disturbance signal is It is to be noted that the PF of a DG unit during a fault
effectively nulled if the grid fully supports the voltage at may vary due to the response time of the unit’s control
the DG’s PC, and is amplified otherwise. A fault in the system to regulate the current angle. For instance, the
vicinity of a DG unit prevents such voltage support by renewable energy plants that follow the curve of Fig. 4 are
the grid, hence tripping of the unit. A recent study shows allowed to have high PFs or even absorb reactive power in
that commercially available VSCs by six different vendors the first 150 ms of a fault. Thus, the protection system of
trip within ten cycles after the inception of a fault in their a microgrid must be able to cope with a wide PF range for
proximity [24]. DG units.
Meanwhile, if a fault-resilient microgrid of a decent size
and complexity is to be materialized, then DG units must
remain connected to the microgrid during disturbances in
the same way that large power plants satisfy the fault ride-
through requirement of transmission grid codes. DG units
with full-scale VSCs can ride through faults using a breaking
chopper circuit that restricts the VSC’s dc link voltage [25].
In addition to a chopper circuit, the fault ride-through capa-
bility for type-3 wind turbines is made possible through a
crowbar circuit that shorts the rotor winding of the DFIM
to limit the overcurrents passing through the rotor-side Fig. 4. Reactive current versus voltage for renewable sources in
VSC [26]. It should be mentioned that the voltage versus Spain [27].
Fig. 7. Positive-sequence torque angle of R45 and R83 for the fault
of Fig. 5(b) when the ECDG unit operates at 10% of its rated power. Fig. 9. Current control loop and the interface of an ECDG unit.
Fig. 11. VSC current for the fault of Fig. 10: (a) instantaneous Fig. 13. Negative-sequence torque angle of R45 for ABG and
currents; and (b) magnitude of sequence currents. CG faults at bus 10.
Fig. 15. The imbalance factor during the fault of Fig. 10 at DG1 PC Fig. 16. Zero-sequence torque angle of R45 for ABG and AB faults
and R83. at bus 10.
Fig. 17. Phase torque angles of R83 during the fault of Fig. 10.
B. Distance Relays
In addition to insensitivity of overcurrent relays to
ECDG units’ small fault currents, the potentially huge
difference between the fault currents during the macro-
grid-connected and islanded modes of a microgrid with
ZAG = Zf + Rg ( _______
IA L + K o I oL )
I + I
AL
A R
(9)
MAG
in which K ois the zero-sequence compensation factor [41].
The zero-sequence component is present in both the numer-
ator and the denominator of MAG in (9). Fig. 25(a) shows
the impedance calculated by the AG element of R65 when
the BC fault of Fig. 24 is changed to an AG fault. For unity
PF operation of the ECDG unit, the imaginary part of ZAG is
about 25% of the 0.9 Ωreactance to the fault—pinpointed
by a yellow circle in Fig. 25(a). When the ECDG unit gen-
Fig. 24. R65 operation during a BCG fault at bus 4. (a) Distance erates the rated reactive current, ZAG moves outside zone 1
element characteristic. (b) Current angles for PF =1. (c) Current
angles for PF =
0.
after the initial fault transients die out.
The zero-sequence current angle of the ECDG unit is not If the ECDG unit generates a lower-than-rated I +L dur-
affected by the VSC, and is related to the prefault voltage ing the fault, which is likely due to the renewable sources’
angle. Given that the power flow levels are not huge in a intermittency, the effect of ECDG unit’s PF on the relay is
microgrid, I oL and I oR are almost in phase. On the other hand, overshadowed by ∠ K o. For instance, Fig. 26 also displays
all sequence components of an SM fault current (i.e., IAR in the sizeable underreach of R65 when the ECDG unit gener-
(9)) are aligned for an AG fault. Therefore, since I +L is sub- ates 10% of its rated capacity and ∠K ois negative. It should
stantially smaller than the remote-end currents, the angle of be noted that different relay performances in Figs. 25(a)
MAG’s numerator is similar to that of I oL . On the other hand, and 26 occur during exactly the same fault condition, for
the denominator of MAG can be written as I +L + (1 + K o ) I oL . which a distance relay is expected to measure identical
Hence, the angle of the denominator of MAG can deviate impedances.
from ∠I oL based on: 1) the relative magnitude and angle 3) Effect of Intermediate Infeed: It was demonstrated
of I oL and I +L ; and 2) the zero-sequence compensation fac- that the significant phase difference between the local and
tor, which depends on the conductor physics and feeder remote currents of a distance relay in a microgrid with
spacing.Fig. 25(b) depicts that for unity PF operation of ECDG units causes protection malfunction. Similar phase
the ECDG unit, I +L leads I oL by about 60° and causes MAG to differences also exist between local and intermediate infeed
have a negative imaginary part, resulting in the overreach currents, and can adversely impact the performance of a dis-
of the blue graph in Fig. 25(a). In contrast, I +L lags I oL by 30° tance relay. The impedance measured by the BC element
when the ECDG unit generates the rated reactive current in of a distance relay in the presence of intermediate infeed
Fig. 25(c), thus pushing the imaginary part of MAG toward currents is
V I. I M D G U N I TS
The discussion on the effect of IMDG units on microgrid
protection for each relay starts with SCIM and is then
extended to DFIM wind DG units. DG1 is either an SCIM-
based unit or a DFIM-based unit.
of the ac and dc components of the fault current, and θis the reactive impedance. Therefore, a negative-sequence direc-
fault inception angle. tional element can reliably identify the direction of unbal-
An SCIM-based wind turbine rotates close to the syn- anced faults if the system is energized by SCIM-based units.
chronous speed, so the machine slip is almost zero and the Fig. 30(a) depicts the sequence currents recorded by R65
frequency of the fault current’s ac component in (11) is if the fault of Fig. 28 is changed to a BCG fault. The sig-
close to the nominal frequency. Conversely, the rotor speed nificant negative-sequence component displayed in this fig-
of a DFIM varies within a ±30% range around the synchro- ure results in a 30% plus imbalance factor during the fault.
nous speed commensurate with the wind speed, and (1 − s ) Since the angle of this negative-sequence current is similar
in (11) is between 0.7 and 1.3. Therefore, the frequency of to that of an SM, ∠T − is correctly situated in the middle of
the current’s ac component is between 42 and 78 Hz for a the forward zone in Fig. 30(b).
60-Hz system. The current of the DFIM during the above A conventional DFIM control system regulates only
fault for a subsynchronous and a supersynchronous wind the positive-sequence current [20], making the negative-
speed is shown in Fig. 29(a), where the current frequencies sequence circuit of a DFIM similar to that of an SCIM, and
are close to 50 and 72 Hz. In contrast, the frequency of the rendering negative-sequence directional elements applica-
voltage, which is normally a memorized voltage for a positive- ble. Meanwhile, DFIM controllers have been improved to
sequence directional element, is 60 Hz. Commercial relays cope with phase imbalance through a negative-sequence
include a frequency tracking unit that measures the voltage current control loop that suppresses I − at the DFIM termi-
frequency and updates the digital filters used to calculate the nal [49]. Suppose DG1 is a DFIM-based wind turbine that
voltage and current phasors accordingly. Meanwhile, since has negative-sequence current suppression capability, and
the current frequency is substantially different from the volt-
the fault of Fig. 29 is changed to a BCG fault. As opposed to
age frequency for this fault, the current phasors measured by
SCIM currents in Fig. 30, the negative-sequence current of
60-Hz digital filters are not correct, and the angles of the cur-
the DFIM in Fig. 31(a) decays to around zero within a cou-
rent phasors fluctuate. Conversely, the angle of voltage pha-
ple of cycles after the beginning of the fault. The negative-
sor is uniform, and so the ∠T + curves in Fig. 29(b) oscillate
sequence circuit of the DFIM is no longer represented by a
widely and are irrespective of fault direction.
single impedance, and the angle of the negative-sequence
If the voltage and current frequencies are measured
current fluctuates sharply. As a result, ∠T −is not uniform in
separately and their respective digital filters are updated
accordingly, correct voltage and current phasors with fixed Fig. 31(b) and exits the forward zone 20 ms after the fault
angles are measured. However, since these phasors corre- inception, falsely detecting a reverse fault.
spond to different frequencies, their phase difference still 2) Overcurrent Feature: The magnitude of SCIM fault
rotates and a positive-sequence directional element fails to currents is often large enough to trigger overcurrent relays.
determine the fault direction. However, similar to ECDG units, the relative magnitude of
b) Unbalanced faults: The negative-sequence circuit DFIM fault currents depends on the DG unit’s PF and fault
of an SCIM is similar to that of an SM, and consists of a resistance. In addition, the magnitude of DFIM fault currents
is considerably impacted by the features and parameters of
Fig. 29. Operation of directional element of R65 for a balanced Fig. 30. Operation of directional element of R65 for a BCG fault
fault at bus 4 when DG1 is a DFIM-based wind turbine. (a) Phase A at bus 4 when DG1 is an SCIM-based wind turbine. (a) Sequence
current. (b) Positive-sequence torque angle. currents. (b) Negative-sequence torque angle.
The faulted phase C has the largest current, while the cur-
rents of phases A and B are nearly equal. Meanwhile, if I −is
not suppressed by the DFIM, both the absolute and rela-
tive magnitude of the fault currents change in Fig. 32(b).
The presence of the negative-sequence current and unity
PF for the p ositive-sequence circuit makes the current of
phase A larger than the currents in the other phase. For this
case, the crowbar circuit is activated if at least one of the
three phase rotor currents exceeds 1.2 pu. If the threshold
for activating the crowbar circuit is changed to 2 pu, the
magnitude of the positive-sequence current changes in Fig.
32(c), as a result of which the current declines in phase A
whereas it rises in the two faulty phases. The details of the
controllers’ effects on DFIM fault currents are outside the
scope of this paper; the objective of the above analysis is to
demonstrate that a relay that relies only on current mag-
Fig. 31. Operation of directional element of R65 for a BCG fault nitude in microgrids with DFIM-based wind DG units is
at bus 4 when DG1 is a DFIM-based wind turbine. (a) Sequence impacted by factors other than the fault condition, and is
currents. (b) Negative-sequence torque angle.
thus unreliable.
Fig. 32. DFIM current for a BCG fault at bus 4. (a) With I −
suppression capability. (b) Without I −suppression capability and
1.2-pu threshold for crowbar. (c) Without I −suppression capability Fig. 33. Operation of the distance element of R65 for the fault of
and 2-pu threshold for crowbar. Fig. 23 when DG1 is (a) An SCIM; and (b) A DFIM.
trajectory, which is irrespective of the fault location. The from power loss during normal operation. Solid-state break-
false impedance in this figure is caused by the incorrect cur- ers normally employ integrated gate commutated thyristor
rent phasors that are measured using 60-Hz digital filters, (IGCT) instead of insulated gate bipolar transistor (IGBT),
while the actual current frequencies are 50 and 72 Hz. If the which is common in VSCs, to reduce power loss over normal
current phasors are measured using 50- and 72-Hz digital operation. These losses can be largely eliminated through
filters, distance relay still misoperates because impedance hybrid breakers, which interrupt dc current through joint
must be measured using voltage and current phasors that operation of parallel-connected mechanical and solid-state
correspond to the same frequency. devices. Although effective, hybrid breakers are hard to eco-
2) Unbalanced Faults: Within the initial few cycles of an nomically justify for microgrids, particularly for LV systems.
unbalanced fault, i.e., when distance protection normally In general, solid-state and hybrid dc breakers have relatively
operates, an SCIM acts broadly similar to an SM. There- low technology readiness levels for LV and MV systems [52].
fore, a distance relay measures a relatively accurate imped-
ance for a zone-1 fault. However, if the fault is in zones B. DC Protective System
2 or 3, for which the relay introduces a delay, the SCIM
1) DC Faults: For dc fault and protection analysis,
starts absorbing reactive power, as a result of which SCIM
Microgrid 2 of the test mesogrid is converted to a two-wire
currents lead the remote and intermediate infeed currents.
1.5-kV dc system, with which DG3 and loads are integrated
Therefore, a distance relay that measures SCIM fault cur-
through VSCs. The following analysis includes both TN-S
rents is in danger of overreach.
and IT grounding methods. For TN-S method, the ground
A DFIM’s control system can regulate the PF at the DG
is in the middle of the dc capacitors of the VSCs. For IT
unit’s PC if an unbalanced fault is not very severe, and so
method, one of the poles is grounded. The buses are con-
the angle of DFIM fault currents is not determined by the
nected through underground cables, which are modeled
angle of prefault voltages. Therefore, distance relays are
using the frequency-dependent cable model of PSCAD, ena-
endangered by the effect of remote and intermediate infeed
bling traveling wave analysis.
currents during unbalanced faults in microgrids with DFIM
units in the same way that distance relays malfunction in There are basic differences between the features and
the presence of ECDG units. stages of dc and ac faults. The pole-to-ground (PG) fault
current measured at bus 13 of the system in the case of IT
V II. PRO T EC T ION OF D C M IC RO GR I DS grounding is shown in Fig. 34(a). The fault is bolted, and its
time and location are t =1 s and 1 km downstream from bus
One of the chief impediments to the realization of dc grids
13. To illustrate how the fault evolves, it is not cleared in
arises from the protection challenges posed by the dc fault Fig. 34(a). Unless the VSCs are modular multilevel, which is
behavior of VSCs. These challenges concern lack of cost- not normally the case for microgrid voltage levels, the main
effective dc circuit breakers and fast, yet selective and sensi- sources of a fault current immediately after the inception of
tive dc protective relays. Given the diversity of dc breakers a fault are the dc capacitors of the VSCs. The capacitance
and their potential interaction with different components of underground cables also supplies the fault, but their
of a dc system, the types and features of breakers should be
taken into account when developing the protection scheme
of a dc microgrid. Therefore, although the details of dc
breaker technologies are beyond the scope of this paper,
they are briefly reviewed in this section.
A. Circuit Breaker
A typical ac circuit breaker is a mechanical device that
opens at the current zero crossing. The absence of a zero
crossing in a dc renders ac breakers inapplicable to dc
microgrids, unless the breaker is rated for higher voltage and
current levels, which is not economical [50]. Nevertheless,
electromechanical breakers have been developed for dc sys-
tems, but these breakers cannot typically meet the speed
requirements for protection of VSCs. Thus, solid-state
breakers have been proposed for dc systems. These breakers
do not rely on a natural zero crossing of current and push
the current down to zero by applying a voltage that opposes
the voltage across the breaker. Solid-state breakers have sig- Fig. 34. DC fault current at bus 13 for a bolted fault. (a) IT
nificantly shorter operating times [51], but they often suffer grounding. (b) TN-S grounding.
2
Some VSCs can block a dc fault current by generating a voltage that
Fig. 35. Current9 during the fault of Fig. 34(b) for different VSC opposes the ac system voltage. To do so, extra modules are required,
parameters and components. making the VSC economically less feasible for microgrid applications.
Fig. 37. Current for the fault of Fig. 34(b) in the presence of fault Fig. 38.Current traveling waves for the fault of Fig. 34(b).
resistance.
1) The relay should be able to differentiate between successive traveling waves is not often easy. This issue has
in-zone and out-of-zone faults well before the fault been illustrated in Fig. 38, which displays the traveling
current reaches its final value. waves associated with the PG fault current of Fig. 34(b).
2) The selectivity and sensitivity of an overcurrent dc As shown in this figure, detecting the arrival time of the sec-
relay are severely impaired by fault resistance. This ond wave is made more difficult by a modest 10 Ω resistance.
problem is especially pronounced in microgrids This fault is 1 km away from the measurement location.
since the voltage levels are relatively low whereas Closer faults and presence of noise can further obscure the
the fault resistance can be primarily determined by second traveling wave. In addition to technical problems,
the ambient conditions at the fault location, which traveling-wave-based relays are among the most expensive
are independent of the voltage level. For instance, transmission system relays, and so are not economically
the current for the PG fault of Fig. 34(b) in the pres- viable for microgrids.
ence of 1 Ωand 10 Ωfault resistance is shown in
Fig. 37. For Rf = 1 Ω, the current can be mistaken for V III. CONC LUSION
a fault in a farther protection zone. For Rf = 10 Ω ,
the change in the current is tiny and similar to load In order for a microgrid to continue operation when a fault
variation even though 10 Ω is not known as a high occurs during the islanded mode, the DG units should ride
fault resistance. Fig. 37 demonstrates that, in addi- through the fault. Consequently, the relays have to identify
tion to overcurrent protection, fault resistance can the faulty component using the fault currents and voltages
also affect a relay that operates based on the rate of of DG units, which are often different from those of con-
current rise. ventional sources. The performance of commercially avail-
A common approach for fault location utilizes the able relays was examined for a benchmark test system. It
traveling waves caused by a fault [53]. This approach has was shown that the unconventional negative-sequence
been tailored for ac fault protection as well [54]. The exist- current, dependence of the relative magnitude of phase
ing traveling-wave-based protection methods, which are currents on the VSC’s PF and fault resistance, and limited
currently applied only at HV levels, mostly use communi- positive-sequence current are among the fault signatures
cation to find the arrival times of fault-induced traveling of ECDG units that impact directional overcurrent relays.
waves at the two ends of a line. The difference between the These units also can affect distance relays because the angles
two arrival times along with the wave propagation velocity of their fault currents are independent of the prefault volt-
can identify the fault location. This method can be modi- ages. Differential relays can overcome these problems, but
fied to use the measurements at one end of a line/cable at a considerably higher cost, the details of which were
only using outlined. Besides sharing some problematic features with
ECDG units, IMDG units also can cause relay misoperation
t − t by making the fault current frequency dependent on the
xf = ν ____
2
1
(12)
2
induction machine’s slip. Furthermore, different DFIG con-
in which xfis the distance between the relay and the fault, ν trol systems can lead to distinct currents for the same fault
is the wave propagation velocity, and t 1 and t2 are the arrival conditions, causing different relay responses. A brief review
times of the first two traveling waves. A major problem for of dc microgrids demonstrated that the stages of a fault and
applying this method to a dc microgrid is the difficulty in protection requirements are different for dc and ac systems.
precise identification of the second wave’s arrival time t2, The effect of short lines/cables and fault resistance can make
particularly if the current is polluted by noise. Since feeder/ protection of dc microgrids more challenging than that of
cable lengths in a microgrid are typically short, separating other dc grids.
R EFER ENCES [19] Benchmark Systems for Network Integration [33] SEL-751A Feeder Protection Relay—Manual,
of Renewable and Distributed Energy SEL, Pullman, WA, USA, Jan. 2013. [Online].
[1] “Development and operation of active Resources, Standard C6.04.02, Apr. 2014. Available: https://www.selinc.com/SEL-751A
distribution networks,” CIGRE, Tech. Rep.
457, Apr. 2011. [20] R. Pena, J. C. Clare, and G. M. Asher, [34] E. Nasr-Azadani, C. A. Cañizares, D. E.
“Doubly fed induction generator using back- Olivares, and K. Bhattacharya, “Stability
[2] R. H. Lasseter, “Smart distribution: Coupled to-back PWM converters and its application analysis of unbalanced distribution systems
microgrids,” Proc. IEEE, vol. 99, no. 6, pp. to variable-speed wind-energy generation,” with synchronous machine and DFIG based
1074–1082, Jun. 2011. Proc. Inst. Electr. Eng.—Electr. Power Appl., distributed generators,” IEEE Trans. Smart
[3] “Microgrid-1, engineering, economics and vol. 143, no. 3, pp. 231–241, May 1996. Grid, vol. 5, no. 5, pp. 2326–2338, Sep. 2014.
experience,” CIGRE, Tech. Rep. 635, Oct. [21] K. Clark, N. W. Miller, and J. J. Sanchez- [35] Distributed Generation Technical Interconnection
2015. Gasca (Apr. 2010). Modeling of GE Wind Requirements—Interconnections at Voltages 50
[4] S. H. Horowitz and A. G. Phadke, Power Turbine-Generators for Grid Studies General kV and Below, Hydro One Netw., Toronto, ON,
System Relaying, 3rd ed. New York, NY, USA: Electric (GE) Version 4.5. [Online]. Available: Canada, Mar. 2013.
Wiley, 2008. http://ceee.hust.edu.cn/yuanxm/973/ [36] H. H. Zeineldin, Y. A.-R. I. Mohamed, V.
[5] A. A. Memon and K. Kauhaniemi, “A critical images_1/2012082054141805.pdf Khadkikar, and V. R. Pandi, “A protection
review of AC microgrid protection issues and [22] (Mar. 2013). ENTSO-E Network Code for coordination index for evaluating distributed
available solutions,” Electr. Power Syst. Res., Requirements for Grid Connection Applicable to generation impacts on protection for meshed
vol. 129, pp. 23–31, Dec. 2015. all Generators, European Network of distribution systems,” IEEE Trans. Smart
[6] S. A. Hosseini, H. A. Abyaneh, S. H. H. Transmission System Operators for Electricity Grid, vol. 4, no. 3, pp. 1523–1532, Sep. 2013.
Sadeghi, F. Razavi, and A. Nasiri, “An (ENTSO-E), Brussels, Belgium. [Online]. [37] P. M. Anderson, Analysis of Faulted Power
overview of microgrid protection methods Available: http://networkcodes.entsoe.eu/ Systems. Hoboken, NJ, USA: Wiley, 1995, ch. 6.
and the factors involved,” Renew. Sustain. wp-content/uploads/2013/08/130308_Final_
Version_NC_RfG1.pdf [38] IEEE Guide for Design, Operation, and
Energy Rev., vol. 64, pp. 174–186, Oct. 2016. Integration of Distributed Resource Island
[7] L. Che, M. Khodayar, and M. Shahidehpour, [23] IEEE Application Guide for IEEE Std Systems with Electric Power Systems,
“Adaptive protection system for microgrids: 1547(TM), IEEE Standard for Standard, 2011.
Protection practices of a functional Interconnecting Distributed Resources with
Electric Power Systems, Standard, 2009. [39] A. Sinclair, D. Finney, D. Martin, and P.
microgrid system,” IEEE Electrific. Mag., vol. Sharma, “Distance protection in distribution
2, no. 1, pp. 66–80, Mar. 2014. [24] F. Katiraei, J. Holbach, and T. Chang, systems: How it assists with integrating
[8] E. Sortomme, S. S. Venkata, and J. Mitra, “Impact and sensitivity studies of PV distributed resources,” IEEE Trans. Ind. Appl.,
“Microgrid protection using communication- inverters contribution to faults based on vol. 50, no. 3, pp. 2186–2196, May 2014.
assisted digital relays,” IEEE Trans. Power generic PV inverter models,” Ontario Grid
Connection Study, Toronto, ON, Canada, [40] Line Distance Protection REL670 Application
Delivery, vol. 25, no. 4, pp. 2789–2796, Oct. Manual, document 1MRK 506 315-UENABB,
2010. Tech. Rep., May 2012.
Vasteras, Sweden, Dec. 2012. [Online].
[9] H. H. Sharaf, H. M. Zeineldin, and E. [25] J. F. Conroy and R. Watson, “Low-voltage Available: www.05.abb.com/global/scot/
El-Saadany, “Protection coordination for ride-through of a full converter wind turbine scot387.nsf/veritydisplay/1d6bacf573307830
microgrids with grid-connected and islanded with permanent magnet generator,” IET c1257b0c0046292a/$file/1MRK506315-
capabilities using dual setting directional Renew. Power Gen., vol. 1, no. 3, pp. 182–189, UEN_C_en_Application_manual__
overcurrent relays,” IEEE Trans. Smart Grid, Sep. 2007. REL670_1.2.pdf
to be published. [26] R. Cardenas, R. Pena, S. Alepuz, and G. [41] G. Ziegler, Numerical Distance Protection:
[10] “Protection of distribution systems with Asher, “Overview of control systems for the Principles and Applications, 4th ed. Erlangen,
distributed energy resources,” CIGRE, Tech. operation of DFIGs in wind energy Germany: Publicis, 2011, ch. 6.
Rep. 613, Mar. 2015. applications,” IEEE Trans. Ind. Electron., vol.
60, no. 7, pp. 2776–2798, Jul. 2013. [42] A. Carta, N. Locci, C. Muscas, and S. Sulis,
[11] A. Yazdani and R. Iravani, Voltage-Sourced “A flexible GPS-based system for
Converters in Power Systems: Modeling, [27] (May 2011). Procedure for Verification synchronized phasor measurement in
Control, and Applications. Hoboken, NJ, USA: Validation and Certification of the electric distribution networks,” IEEE Trans.
Wiley, 2010. Requirements of the PO 12.3 on the Response of Instrum. Meas., vol. 57, no. 11, pp. 2450–
Wind Farms and Photovoltaic Plants in the 2456, Nov. 2008.
[12] R. Teodorescu, M. Liserre, and P. Rodriguez, Event of Voltage Dips, Version 9. [Online].
Grid Converters for Photovoltaic and Wind Available: http://www.aeeolica.org/uploads/ [43] Manual: SIPROTEC, Distance Protection,
Power Systems. Hoboken, NJ, USA: Wiley, documents/1306-pvvc-n9-english.pdf 7SA522-V4.7, Siemens, Germany, Sep. 2013.
2011. [Online]. Available: https://www.downloads.
[28] (Dec. 2005). Interconnection for wind energy, siemens.com/download-center/Download.
[13] N. Femia, G. Petrone, G. Spagnuolo, and M. United States of America Federal Energy
Vitelli, Power Electronics and Control aspx?pos=download&fct=getasset&mandato
Regulatory Commission, Docket No. RM05-4- r=ic_sg&id1=DLA06_1186
Techniques for Maximum Energy Harvesting in 001, Order No. 661-A. [Online]. Available:
Photovoltaic Systems. Boca Raton, FL, USA: www.ferc.gov/EventCalendar/ [44] W. A. Elmore, Protective Relaying: Theory and
CRC Press, 2012. Files/20051212171744-RM05-4-001.pdf Applications, 2nd ed.New York, NY, USA:
[14] D. E. Olivares et al., “Trends in microgrid Marcel Dekker, 2004, p. 260.
[29] F-PRO 4000—Distribution Protection &
control,” IEEE Trans. Smart Grid, vol. 5, no. 4, Management Relay User Manual, ERLPhase [45] E. Casagrande et al., “A differential sequence
pp. 1905–1919, Jul. 2014. Power Technologies, Winnipeg, Canada, component protection scheme for microgrids
[15] G. AlLee and W. Tschudi, “Edison redux: 380 2013. [Online]. Available: http://www. with inverter-based distributed generators,”
Vdc brings reliability and efficiency to erlphase.com/downloads/manuals/F_ IEEE Trans. Smart Grid, vol. 5, no. 1, pp. 29–
sustainable data centers,” IEEE Power Energy PRO_4000_manual.pdf 37, Jan. 2014.
Mag., vol. 10, no. 6, pp. 50–59, Nov. 2012. [30] IRV Integrated Protection, Control & Metering [46] [Online]. Available: https://selinc.com/
[16] G. F. Reed, B. M. Grainger, A. R. Sparacino, IED, ZIV Grid Automation, ZIV Grid products/351/
and Z. H. Mao, “Ship to grid: Medium- Automation, Bilbao, Spain, 2012. [Online]. [47] [Online]. Available: https://selinc.com/
voltage DC concepts in theory and practice,” Available: http://www.gridautomation.ziv.es/ products/311L/
IEEE Power Energy Mag., vol. 10, no. 6, pp. doc-downloads/literature/manuals/ [48] C. B. Cooper, D. MacLean, and K. Williams,
70–79, Nov. 2012. BIRV1203Av14.pdf “Application of test results to the calculation
[17] E. Rodriguez-Diaz, F. Chen, J. C. Vasquez, J. [31] J. Roberts and A. Guzman, “Directional of short-circuit levels in large industrial
M. Guerrero, R. Burgos, and D. Boroyevich, element design and evaluation,” in Proc. 21st systems with concentrated induction-motor
“Voltage-level selection of future two-level Annu. Western Protective Relay Conf., loads,” Proc. Inst. Electr. Eng., vol. 116, no. 11,
LVdc distribution grids: A compromise Spokane, WA, USA, Oct. 1994. pp. 1900–1906, Nov. 1969.
between grid compatibiliy, safety, and [32] K. Zimmerman and D. Costello, [49] L. Xu and Y. Wang, “Dynamic modeling and
efficiency,” IEEE Electrific. Mag., vol. 4, no. 2, “Fundamentals and improvements for control of DFIG-based wind turbines under
pp. 20–28, Jun. 2016. directional relays,” in Proc. 63rd Conf. unbalanced network conditions,” IEEE Trans.
[18] IEEE Recommended Practice for Monitoring Protective Relay Eng., Mar. 2010, Power Syst., vol. 22, no. 1, pp. 314–323, Feb.
Electric Power Quality, Standard, 2009. pp. 1–12. 2007.
[50] H. Pugliese and M. von Kannewurff, [52] Review of DC Circuit Breakers for Submarine Networks. London, U.K.: Spriner-Verlag,
“Discovering DC: A primer on dc circuit Applications, Defence Science Technology 2010, ch. 1.
breakers, their advantages, and design,” IEEE Organisation, Victoria, Australia, [54] [Online]. Available: https://selinc.com/
Ind. Appl. Mag., vol. 19, no. 5, pp. 22–28, Sep. Mar. 2012. [Online]. Available: http://www. products/SEL-T400L/
2013. dst.defence.gov.au/sites/default/files/
[51] A. Maqsood and K. Corzine, “DC microgrid publications/documents/DSTO-TN-
protection: Using the coupled-inductor solid- 107420PR.pdf
state circuit breaker,” IEEE Electrific. Mag., [53] M. M. Saha, J. J. Izykowski, and E.
vol. 4, no. 2, pp. 58–64, Jun. 2016. Rosolowski, Fault Location on Power
A BOU T THE AU THOR S Reza Iravani (Fellow, IEEE) received the B.Sc., M.Sc., and Ph.D. degrees in
electrical engineering.
Ali Hooshyar (Member, IEEE) received the B.Sc.
Currently, he is a Professor at the University
degree from Isfahan University of Technology,
of Toronto, Toronto, ON, Canada. His research
Isfahan, Iran, the M.Sc. degree in electrical engi-
interests include power system dynamics and
neering from the University of Tehran, Tehran,
applications of power electronics in power
Iran, and the Ph.D. degree in electrical engineer-
systems.
ing from the University of Waterloo, Waterloo,
ON, Canada, in 2014.
He was a Postdoctoral Fellow with the Cen-
tre for Applied Power Electronics, University of
Toronto, Toronto, ON, Canada. He joined the
Electrical Engineering and Computer Science Department, York Univer-
sity, Toronto, ON, Canada, in 2015. His research interests include protec-
tion and control of renewable energy systems and smart grids.
Prof. Hooshyar is an Editor of the IEEE Transactions on Smart Grid.
He has been recognized as one of the exceptional reviewers of the IEEE
Transactions on Power Delivery and one of the best reviewers of the IEEE
Transactions on Smart Grid.