Theory Report Telecontrol

This document discusses remote terminal units (RTUs) which are used to monitor and control electrical infrastructure from a central location. It describes different types of RTUs like D20, ERTU, and PMRTU. It also discusses the components that make up RTUs like cards, processors and modems. Additionally, it covers communication protocols, media like radios and antennas, and polling techniques used by RTUs to exchange data with the central control system.

Uploaded by

Tebogo Makola
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
142 views

Theory Report Telecontrol

This document discusses remote terminal units (RTUs) which are used to monitor and control electrical infrastructure from a central location. It describes different types of RTUs like D20, ERTU, and PMRTU. It also discusses the components that make up RTUs like cards, processors and modems. Additionally, it covers communication protocols, media like radios and antennas, and polling techniques used by RTUs to exchange data with the central control system.

Uploaded by

Tebogo Makola
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

TELECONTROL

Telecontrol is the section that deals with the monitoring and remotely controlling of the
plant. Control can open and close the breaker, turn SEF on and off, and turning ARC on
and off. Abnormal conditions can be quickly spotted with the use of Telecontrol

SCADA

Supervisory control and data acquisition is the system which is responsible for the whole
communication between RTU and the controller; it refers to the exchange of data
between devices for the purpose of providing a supervisory function.

RTU

RTU is a Remote Terminal Unit acts as an interface to the plant to allow control and
monitoring thereof

It collects data from the plant or apparatus and sends it to the master

It is used basically for monitoring and controlling of the plant.

Types of RTUs
D20

It consists of:

 The main circuit breaker that is supplied by the DC from the charger in the
substation. This main circuit breaker power the RTU.
 The power supply unit which supply all the cards of the RTU
 Main processor (D20 ME) which serves as the main memory of the RTU and all
the configuration to the RTU are done through this processor.
 Config port where you connect a cable when configuring/diagnosing the RTU.
 RS 422 MODEM
 Cards or modules

CARDS FOUND ON D20 RTU

 D20 A Analogue input card


- This card monitors the analogues of the plant (volts, amps, watts, and vars)
from the transducer

- A transducer convert energy to another form, for instance transducer will


convert the 110V from a VT to 5mA signal which is wired to the IDF and then
to the RTU. A 5mA input to the RTU will give a 2048 digital output
- It has 32 analogue inputs

 D20 S STATUS / DIGITAL INPUT CARD

This card monitors the status of the apparatus in the substation in the form of alarms or
indication. It has 64 status input.

 D20 K CONTROL OUTPUT CARD

This card is where all the controls of the RTU are executed.

 D20 C COMBINATIONAL CARD


This is the combination of all the cards in the D20 RTU, it has analogue inputs, control
outputs and digital inputs.

ERTU (TALUS) RTU

Also used in substations, ERTU stands for Enhanced Remote Terminal Unit

It consists of:

- The memory bus- where you find the FSK modem and the quick card.
- The plant bus where you find the analogue input card, digital input and secure
control card.

CARDS FOUND IN TALUS

QUICK CARD

This card is the main memory of the RTU and it is the one which is responsible for
the communication between the RTU and the apparatus; the RTU configurations are
done on this card.

This card is found on the first slot in the memory bus.

CONTROLLER CARD (RTUC)

This card serves as the main memory of the RTU; it is the one which is responsible
for the communication between the RTU and the apparatus.
This card is used where the quick card is not available and it must work together with
the SIOC to make the quick card.

SERIAL INPUT OUTPUT CARD

This card is used together with the controller card to make the quick card.

It connects the RTU plant I/O cards to the controller card.

SIGNAL CONDITIONING CARD

This card is used to set/give the cards address on the plant bus.

It is connected on the plant card, and then connected to the STC via the 34 way
ribbon cable.

SIGNAL TERMINATION CARD

This card connects the plant card to the RTU krono blocks.

PMRTU
These are RTU’s that are mounted on poles to monitor re-closers that are mounted
on poles.

 The PMRTU is powered by an auxiliary supply of 220V from a transformer


and has a backup supply of two 13.8V batteries connected in parallel.

 We use the program “WSOS” to program the PMRTU, its used to upload
the configuration file onto the PMRTU.

REPEATER

A radio repeater is a combination of a radio receiver and a radio transmitter that receives
a weak or low-level signal and retransmits it at a higher level or higher power, so that the
signal can cover longer distances without degradation

A repeater is normally found in a high, elevated area, such as a hill or mountain.

COMMUNICATION MEDIUM

This is the medium of communication used by the RTU to communicate with the master
station. The communication between the RTU and the master can take place through
wireless link where data is transmitted through air via radio waves or through fixed links
where there’s a dedicated path from the plant to the master
Different communication mediums have different baudrates. A baudrate is the speed at
which the RTU communicates with the master/controller. It is the rate at which the status
is sent to the master and/or which the controllers control execution or command is sent to
the RTU.

Types of Communication medium

GPRS Modem

A modem (modulator-demodulator) is a device that modulates an analog carrier signal to


encode digital information, and also demodulates such a carrier signal to decode the
transmitted information. The goal is to produce a signal that can be transmitted easily and
decoded to reproduce the original digital data.

A Vodacom or MTN SIM card is used

It has a baudrate of 9600bd

GPRS Modem is used where there is no signal for other communication medium because
they are expensive (the data is expensive)

DIGITAL RADIO
It sends and receives data from Eskom Repeaters, it uses a baudrate of 9600bd

ANALOGUE RADIOS

They are being phased out because of their low speeds, susceptible to noise and fault
finding is not so easy. The baudrate: up to 1200bd

MICROWAVE

They are used in substations where there’s a BME


meaning that the fixed link will be used

Baudrate: 19200bd

ANTENNAS
An antenna (or aerial) is an electrical device which converts electric power into radio
waves, and vice versa.

TYPES OF ANTENNAS
 Corner reflector

 GPRS antenna ( door stopper)

 Omni-directional antenna – it transmit and receives data in all direction. It’s used
in the substation and PMRTUs.
Antenna Gain(dBi)

Corner reflector 9.69


Yagi 3-element 7.09
Yagi 7-element 11.10
Loaded whip 6.15
Yagi 12-element 13.66
Folded dipole 4.72

The maximum RTU radio transmit power is 5W. Therefore any radio currently
transmitting at a higher level should be turned down to 5W.
For RTU radios transmitting at the normal level of 5W:
• High-gain omni-directional antennas (e.g. loaded whips) should never be used.
• Normal-gain omni-directional antennas (e.g. half-wave dipole or folded dipole
antennas) should not be used outside the UHF cell, i.e. not further than 30km from the
repeater it is working to.
• 3-Element Yagi antennas can be used any distance from a repeater, up to a maximum of
40km.
• Corner reflectors may only be used at distances greater than 30km from a repeater.
• For RTUs further than 40km from a repeater, path profiles should be done to all co-
channel repeaters within a 180km radius to determine the level of interference. Based on
the results a Corner Reflector, 7-element Yagi, or in extreme cases, a 12-element Yagi
may be used.
If in terms of the above criteria, if an existing antenna is incorrect, or if the signal level at
any RTU is better than -80dBm, then the RTU radio should be set to transmit on low
power, i.e. 1W. Any antenna could then be used, although it should be considered that at
1W the maximum forward range would be less than 30 km.
If adequate range can not be achieved when the radio is set to 1W, then the radio
transmit power should be adjusted to a level between 1W and 5W that results in a
repeater receive level of -90dBm.
UHF and VHF

VHF and UHF Band Communications Signal radiation in these frequency ranges get very
little ionospheric reflection. As a result, communications in these ranges tend to be line-
of-sight and over a short distance. Line-of-sight means exactly what the name says the
transmitter and receiver must be within a straight visual sighting line from each other.
Buildings and uneven terrain may affect the transmission. The lower part of the UHF
band and the VHF band is also used for mobile communications and television.
The UHF frequency is less susceptible to noise/interference. The VHF is not used
because of this problem

PROTOCOLS

Protocol refers to the language of communication used to send the information from
the RTU to the master and vice versa. It is the language at which the RTU
communicates with the master.

TYPES OF PROTOCOLS USED

DNP 3: it is a world-wide protocol, it is used on area radios and fixed link

ESTEL-it is an Eskom protocol, developed by Eskom, it is used on fixed link

ESTEL VARIANT: it is also an Eskom protocol, it is used on area radios and also on
fixed links.

SOLICITED
Information is only provided on request.

APPLICATION OF THE SOLICITED/POLLED SYSTEM

Fixed links

Fast baudrates

Normally this is found in substations

UN-SOLICITED
Information is reported without a request, it reports only when there are changes. The
master however does a sequential background poll a few times per day to check the
health status’s of its RTU’s.

APPLICATION OF THE UNSOLICITATED SYSTEM

Multiple access communications system

Low baudrate systems

This system is normally used in PMRTUs

IDF

The IDF is used to connect the plant and the RTU. The IDF is a 2 part frame which
consists of two sides, vertical A and IDF vertical B. IDF vertical A being the RTU side
and IDF vertical B being the plant side.

IED

Intelligent Electronic Device communication is the transfer of information utilizing

a particular protocol between the RTU and compatible Protection equipment via different
communication media. Example: Protection Relay
With the introduction of IEDs (intelligent electronic device) IDFs are going to be phased
out.

By using IEDs fault finding is going to be easy, this will also limit cable faults and false
alarms

IDF B is used to connect the indications, controls and analogues from the HV.

TYPES OF CABLES

Coaxial cable

The coaxial cable is the cable which is used on PMRTU to connect the antenna
through the fly lead to the radio or modem.
It sends the data from the RTU to the antenna so it can be send to the repeater.

Fly lead cable

This is the cable which is used to connect the coaxial cable from the antenna to
the network radio or modem.

Com cable

This is the cable which connects the PMRTU to the radio or modem
for communication purpose. There are three comm cables on the PMRTU namely:

RTM1202= connects the digital radio and GPRS to PMRTU.

RFM 01 = connects the analogue radio to the PMRTU.

Monitoring cable

The cable is used to monitor the communication between the RTU and the master.

The cable have three connectors; one connector is connected to the modem or radio,
another connector is connected to the comm port of the RTU (comm cables
connector) and the last connector is connected to the laptop for monitoring purpose so
whatever that is send and transmitted to the master is seen on the laptop.

This cable is used in PMRTU.


ADVC RS-232 Port to PC Cable

ADVC PC
(DB9 (DB9
Female) Female)
====== ======
RX 2 -------- 3 TX
TX 3 -------- 2 RX
GND 5 -------- 5 GND

TYPES OF CONNECTORS

a). DBN connectors

These are connectors which are used when we make cables male and female
connector

b). BNC connectors

These are connectors found on fly led for analogue radios (small once)

c). N connectors

These are connectors used on coax cable and is for digital radios
1.1 Colour Coding

We have different types of RTU’S such as Talus and D20 RTU. The two RTU’s has
different cable pairs.

TALUS RTU D20 RTU

1. Ten (10) pair cable 1. Twenty (20) pair cable

2. Twenty five (25) pair cable 2. Forty (40) pair cable

3. Fifty (50) pair cable

TYPES OF WIRES USED IN TELECONTROL

a). Jumper wires

b). Function wires

c). Common wires

JUMPER WIRES

 Black

 Red

FUNCTION WIRES

 Blue

 Orange

 Green

 Brown

 Grey
COMMON WIRES

 White

 Red

 Yellow

 Black

 White with a blue strip

 Red with a blue strip

 Yellow with a blue strip

 Black with a blue strip

COMMON AND FUNCTIONAL WIRES MAKE UP THE COLOUR CODING

COLOUR CODING FOR TALUS RTU (25 PAIRS)

White White White White White Red Red Red Red Red
Blue Orange Green Brown Grey Blue Orange Green Brown Grey

White White White White White Red Red Red Red Red
Blue Orange Green Brown Grey Blue Orange Green Brown Grey

White White White White White


Blue Orange Green Brown Grey

COLOUR CODING FOR D20 RTU (40 PAIRS)

White with a blue strip = W/B

Red with a blue strip = R/B

Yellow with a blue strip = Y/B


Black with a blue strip = BL/B

White White White White White Red Red Red Red Red
Blue Orange Green Brown Grey Blue Orange Green Brown Grey

Yellow Yellow Yellow Yellow Yellow Black Black Black Black Black
Blue Orange Green Brown Grey Blue Orange Green Brown Grey

W/B W/B W/B W/B W/B R/B R/B R/B R/B R/B
Blue Orange Green Brown Grey Blue Orange Green Brown Grey

Y/B Y/B Y/B Y/B Y/B BL/B BL/B BL/B BL/B BL/B
Blue Orange Green Brown Grey Blue Orange Green Brown Grey

CLASSES
On digital inputs, we have different types of classes.

A class shows the importance of the alarm, class 1 is more important than class. Alarms
are classified so that when there’s data trafficking, the important one will go first.
Single bit

double bits
BREAKER INDICATIONS

transit 00
close 01
open 10
transit 11

SOFTWARES USED
WSOS: Windows Switchgear Operating System, it is used to configure NULEC breakers.

Tview management suite: used to program Trio digital radio, it can also be used for
diagnostics.

ConfigPro: used to configure the D20 RTU

Fieldcomm: used for fault finding in different types of RTUs

Unicon: used to configure the Talus

MAINTENANCE

The purpose of Telecontrol maintenance is to ensure the maximum availability and


reliability of Telecontrol Plant

Types of Maintenance

a). Breakdown Maintenance

This type of maintenance is also known as Run to Failure (RTF) or Failure Based
Maintenance, Is reactive and is only scheduled and executed when a plant failure has
occurred.

b). Condition Based Maintenance

The purpose of CBM also known as Reliability Centred Maintenance (RCM) is to


ensure consistently adequate plant performance.

Maintenance shall be scheduled and executed whenever the performance of individual


plant drops below the region’s performance targets.

c). Preventative Maintenance

PM also known as Use Based Maintenance or Time Based Maintenance is executed


after regular periods of time. PM shall be scheduled annually based on the maintenance
plan and its execution should have a lower priority than that of breakdown or condition
based maintenance.

TWO LEVELS OF PREVENTATIVE MAINTENANCE


MINOR PREVENTATIVE MAINTENANCE

The purpose of minor preventative maintenance is to investigate, test and verify the
settings and operation of the Telecontrol plant and its components. These components
include:

a). The RTU itself (including the health of the peripherals and IED’s, sustained alarms
and analogue values)

b). The Telecommunications system (Data radio, co-axial cable and connectors,
antenna etc)

c). The power supply system (Voltages and fuses)

Major Preventative Maintenance

Minor preventative maintenance is included under major preventative maintenance.


The additional purpose of major maintenance is to verify the integrity of the following
Telecontrol components:

a). The interface to the protection/metering – and DC systems (e.g the IDF and IED
cables)

b). The SCADA master station database

c). All Telecontrol records

Preventative Maintenance Intervals

Minor preventative maintenance shall follow a three year cycle; i.e. all RTUs, PMRTUs
and IRTUs shall undergo minor maintenance at least once in every three years

Major preventative maintenance on the other hand shall follow a six year cycle; i.e. all
Telecontrol plant shall undergo major maintenance at least once every six years

ABBREVIATIONS
IDF = Intermediate Distribution Frame
IED = Intelligent Electronic Device
I/O = Input/Output
RF = Radio Frequency
RTU = Remote Terminal Unit
SCADA = Supervisory Control And Data Acquisition
UHF = Ultra High Frequency
GPRS = General Packets Radio Service
WSOS = Windows Switchgear Operating System
Kbps = kilobits per second
BME =Bandwidth Management Equipment
SEF =Sensitive Earth Fault
ARC =Auto-reclose
DC = Direct Current
AC = Alternating Current
DNP3 - Distributed Network Protocol
RX – receive
TX – transmit