Assembly Features: Host + - Diagnostic Bus
Assembly Features: Host + - Diagnostic Bus
GT*
Features Assembly
Function
Connection
t177582_eng.xml
Diagnostic Shield/
Alarm Bus Host Screen
+- GND
-+
Bulk
Date of issue 2017-08-08
Address
T
x10 x100
Trunk
T 1 ... 4
x1
T
Bulk
-+
Release date 2017-08-08 13:37
T
+-
Alarm Diagnostic
Bus
General specifications
Design / Mounting Motherboard based
Supply
Connection redundant
Rated voltage Ur 19.2 ... 35 V SELV/PELV
Rated current Ir 12 A
Power dissipation typ. 0.4 W per segment
Fieldbus interface
Number of segments 4 simplex
Terminating resistor 100 Ω integrated
Indicators/operating means
Fault signal VFC alarm 1 A, 50 V DC, normally closed
Rotary switch bus addressing, gateway-specific
Galvanic isolation
Fieldbus segment/Fieldbus segment functional insulation acc. to IEC 61010, rated insulation voltage 50 Veff
Fieldbus segment/Supply functional insulation acc. to IEC 61010, rated insulation voltage 50 Veff
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013
Standard conformity
Electromagnetic compatibility NE 21:2011
Degree of protection IEC 60529
Fieldbus standard IEC 61158-2
Shock resistance EN 60068-2-27
Vibration resistance EN 60068-2-6
Ambient conditions
Ambient temperature -40 ... 70 °C (-40 ... 158 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Relative humidity < 95 % non-condensing
Shock resistance 10 g , 11 ms
Vibration resistance 1 g , 10 ... 150 Hz
Pollution degree max. 2, according to IEC 60664
Corrosion resistance acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection type plug-in terminals , spring terminal and screw terminal
Core cross-section 2.5 mm2
Housing material Polycarbonate
Degree of protection IP20
Mass approx. 540 g
Mounting DIN mounting rail
Data for application in connection
with hazardous areas
Certificate TÜV 15 ATEX 7735 X
Marking ¬ II 3G Ex ec IIC T4 Gc
Directive conformity
International approvals
IECEx approval IECEx TUR 16.0007X
Approved for Ex ec IIC T4 Gc
Certificates and approvals
Marine approval pending
Date of issue 2017-08-08
General information
Supplementary information Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be
observed where applicable. For information see www.pepperl-fuchs.com.
Release date 2017-08-08 13:37
169 mm (6.6")
39 mm
(1.5")
150 mm (5.9") 135 mm (5.3")
1
180 mm (7.1")
11
10
2
7
4 3
8
4 4
9
4 5
8
4 6
7
4
Description:
1 Motherboard MBHC-FB-4.GT
2 Gateway module
3 Diagnostic module
4 Power supply modules (x 4)
5 Trunk connection
6 Shielding/grounding kit for trunk shields, optional accessory
7 Connections: Volt-free contact alarm and diagnostic bus (x 2)
8 Connection for bulk power supply (x 2)
9 Rotary switches for gateway addressing x1, x10, x100
10 Shield connection
11 Mounting slot for DIN rail mounting
Accessories
HCD2-FBPS-1.23.500 HCD2-FBPS-1.500
Power Output
Voltage (V) 21 ... 23 28 ... 29.5
Current (mA) 500 500
Limit U0 (V) 24 30
Device in ... Type of Protection Required Installation Components
Zone 0/Div. 1 Intrinsically safe Ex ia FieldBarrier
Zone 1/Div. 1 Intrinsically safe Ex ia FieldBarrier
Zone 1/Div. 1 Flameproof Ex d Segment Protector R-SP-E12 or any
Segment Protector installed in Zone 2
Zone 2 Intrinsically safe Ex ic (Entity) Selected Segment Protectors
Div. 2 Non-incendive Any Segment Protector; power module
selection depends on voltage of field device
Safe Area No specific type of protection Segment Protector recommended
For more details on the power supply modules see respective data sheets.
The stationary and mobile Advanced Diagnostic Module (ADM) and related components provide measurement tools for the
fieldbus physical layer. The ADM monitors many quality indicating values of the fieldbus physical layer. An expert system, which
is included, analyzes the values and issues easy to understand messages indicating cause and remedy. The ADM is
recommended for:
- Faster commissioning and plant start-up: Installation issues are known and corrected before loop check commences
- Reliable operation through online monitoring: The quality of the physical layer and installation is monitored making
fieldbus a manageable asset
- Efficient troubleshooting: An expert system guides the user through issues and faults in the fieldbus installation
Many other tools are included that enhance fieldbus installation and upkeep. Please see datasheet on HD2-DM-A.
KT-MB-FB-D-4R.GEN DART high-density Power Hub with generic interface for 4 redundant segments,
slots for 8 power supply modules with 1 diagnostic module.
HCD2-FBPS-1.23.500
HCD2-FBPS-1.500
HD2-GTR-4PA.PN
HD2-GTR-4PA
MB-FB-GTR1
HD2-DM-A*
HD2-DM-B
MBHC-FB-4.HSC* x x x x x
Power Hub Kits
MBHC-FB-4R.HSC* x x x x x
MBs or
KT-MB-FB-D-4R.GEN x x x
MB-FB-GTR1 x x
GW MBs
MBHC-FB-4.GT x x x x x x