Fast Local Voltage Control Under Limited Reactive Power Optimality and Stability Analysis
Fast Local Voltage Control Under Limited Reactive Power Optimality and Stability Analysis
5, SEPTEMBER 2016
Abstract—High penetration of distributed energy resources this centralized problem using information exchanges among
presents several challenges and opportunities for voltage reg- neighboring buses. To balance overall system VAR resources,
ulation in power distribution systems. A local reactive power the second-stage VAR control in [4] relies on a consensus av-
(VAR) control framework will be developed that can fast re-
spond to voltage mismatch and address the robustness issues
eraging protocol. Alternating-direction method-of-multipliers
of (de-)centralized approaches against communication delays (ADMM) has been advocated in [7], [8], while a subgradient
and noises. Using local bus voltage measurements, the proposed iterative solver has been developed by [9]. More recently, a
gradient-projection based schemes explicitly account for the VAR stochastic-approximation approach has been adopted in [10]
limit of every bus, and are proven convergent to a surrogate cen- to handle high system variability and measurement noises.
tralized problem with proper parameter choices. This optimality Nonetheless, all (de-)centralized approaches would require
result quantifies the capability of local VAR control without re-
quiring any real-time communications. The proposed framework
high-quality communication of the measurement and control
and analysis generalize earlier results on the droop VAR control signals, which is not yet a reality for almost all distribution
design, which may suffer from under-utilization of VAR resources systems. Since these optimization-based control methods are
in order to ensure stability. Numerical tests have demonstrated the designed in an open-loop fashion, potential communication
validity of our analytical results and the effectiveness of proposed delays or noises would challenge their optimality and stability
approaches implemented on realistic three-phase systems. for real-time implementations.
Index Terms—Voltage regulation, dynamic system stability, To tackle this, one can design VAR control strategies using
Volt/VAR control, power distribution systems, gradient-projection locally available information such as bus voltage magnitude
methods. measurements [1], [2], [11]. Since power system voltage is
more significantly affected by local VAR inputs compared to
those elsewhere ([12], Section 10.8), a local control framework
I. INTRODUCTION
would very fast and effectively respond to voltage deviation.
0885-8950 © 2015 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
ZHU AND LIU: FAST LOCAL VOLTAGE CONTROL UNDER LIMITED REACTIVE POWER 3795
= [23]. Therefore, the square matrix is of full rank , does not affect very much the power loss terms in (1a)–(1c).
and thus invertible. Hence, relatively constant loss terms can be even captured by
With the graph matrix notation and , all voltage (2c) as an operating-point related voltage profile.
in the LinDistFlow model become Remark 2 (Squared Voltage Profile): The other assumption
used for linearization relates to the squared voltage terms. How-
(4) ever, (10) can be generalized to include the original squared
voltage, instead of , as the input. To keep the squared voltage
where is an diagonal matrix with the -th diagonal difference of (1c), the graph-incidence based reformu-
entry equal to ; and similarly for which captures all 's. lation (2c) and (4) can be modified by substituting the voltage
Similarly, the power balance equations in (2a) and (2b) can be squared vector, with a scaling difference by a factor of 1/2.
respectively concatenated into This way, matrix becomes the linear sensitivity of (squared)
voltage profile due to change in . The exact form of this sen-
(5) sitivity matrix is given by [18], which is closely approximated
(6) by . Based on this modification, the VAR control problem (3)
and the ensuing analysis can be generalized accordingly to use
Solving for and and substituting them into (4) yield the squared voltage term for higher accuracy.
Remark 3 (Meshed Networks): Although the matrix LinDis-
(7) tFlow model in (10) has been derived for tree-topology net-
works, it can also be generalized to meshed networks. Since
or equivalently,
, it is the weighted graph Laplacian matrix.
This exactly coincides with the definition of the system Bbus
(8)
matrix in the popular fast-decoupled power flow (FDPF) model
where the two invertible matrices and for transmission network analysis ([24], Section 6.16). Hence,
. Since , the linear relation the model (10) and the ensuing algorithms also hold for general
from input to the output becomes distribution networks such as ring-topology systems.
Remarks 1–3 corroborate the validity of using the linearized
(9) model (10) for representing realistic distribution networks with
lossy lines, non-flat voltage profile, and even meshed topology.
where denotes the voltage profile This will be further demonstrated by numerical tests for even
under no additional VAR support. three-phase unbalanced cases in Section VI.
Proposition 1: Both and are positive definite (PD). Upon defining the voltage mismatch and rep-
Proof: Picking any non-zero vector of length and resenting by for notational convenience in the rest of the
defining , one can show that paper, the VAR control problem now becomes
(11a)
and faster stabilize the system. Thus, it would decrease the oc- . By scaling each bus with a different stepsize ,
currence and level of abrupt changes in system dynamics, and the most general GP form is
has the potential to prevent local control actions from adversely
affecting the operations of OLTC and other voltage regulating
devices. (18)
To allow for local control schemes, it turns out that the voltage
mismatch norm in (11) needs to be weighted by the PD matrix where the diagonal matrix . Clearly, the
, leading to the following surrogate VAR control problem original GP iteration (17) is a special case of (18) by setting
.
(13) Interestingly, the GP iteration (18) can be easily implemented
by setting the VAR input at all buses to be the instantaneous
. Since always holds, it is feasible to use the
where the objective
latest GP iterate as the network reactive power input by setting
at every iteration . Under this setting, the gradient
(14) direction for any becomes (cf. (9))
This surrogate problem is still convex as is PD. Because of (19)
the box constraint, the weighted error norm with would
attain a different solution compared to the original unweighted Hence, the -th entry of the gradient does not depend
problem (11). However, if every bus has unlimited VAR capa- on the full vector , but only local information on its own bus
bility (i.e., unconstrained case), the optimal solutions to both voltage and VAR input . Hence, the GP iteration (18)
error norm objectives coincide at can be completely decoupled into local updates, as given by
if . This implies that under abundant VAR resources, the
optimal solution to the weighted (13) has the potential to closely
approximate the minimum of the (11). As detailed soon, the sur- (20)
rogate problem (13) will facilitate the development of fast local
control schemes. where denotes the projection at bus to the interval ,
which is again a local computation. The proposed local VAR
IV. GRADIENT-PROJECTION METHOD control design relying on (20) is essentially equivalent to the
centralized GP solver for (13).
This section will introduce our proposed VAR control frame-
Proposition 2: Under constant , the fixed-point of the iter-
work by solving the constrained optimization problem (13). The
ative update (18), or equivalently its local counterpart (20), will
key of solving (13) lies in the separable structure of the con-
achieve the optimum to the VAR control problem (13).
straint. To project a vector to the set , one can threshold
Proof: First, existence and uniqueness of the optimum
it on each coordinate. This motivates one to adopt the gradient-
follows from the strong convexity and none-empty constraint
projection (GP) method, a generic optimization solver for con-
of (13). Furthermore, the first-order optimality condition ([20],
strained problems; see e.g., ([20], Section 2.3). The GP method
Prop. 2.1.2) for (13) implies that holds
extends the iterative first-order gradient methods to solving con-
. Thus, the necessary condition for to be optimum
strained optimization problems like (13). Upon forming the gra-
boils down to
dient direction of (14) by using as
(15) (21)
the simplest GP iteration finds the feasible direction by pro-
jecting the gradient update, as or equivalently,
(16)
where the operator thresholds any input to the constraint set (22)
, and is the stepsize. Clearly, the GP iteration (16)
boils down to the steepest descent method if the optimization would hold for any PD diagonal matrix . This is exactly the
problem is unconstrained. condition that a fixed point to (18) would satisfy.
A more general GP form takes the weighted linear combina- Remark 4 (Features of Local Control): The GP-based VAR
tion of the last iterate and the projection, given by control (20) requires each bus to measure its local voltage mag-
nitude, which can be implemented with minimal hardware up-
(17) dates. The computational requirement is very minimal since
(20) involves only scalar operations. As detailed soon, the GP
where the weighting parameter . This choice of stepsize parameters need to be chosen judiciously to ensure the
ensures that would always satisfy the box con- dynamic stability. However, they can be determined off-line
straint for any iteration , as long as the last iterate . using solely system topology and line admittance information.
Hence, every GP iterate is feasible to (13) as long as Without the network information, it is also possible to develop
3798 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 31, NO. 5, SEPTEMBER 2016
strategy would be more likely to be unstable for large-scale dis- To better understand the effect of , let us assume there are
tribution systems. abundant VAR resources, and thus the projection in (20) is never
active. This is exactly the scenario where instability of the droop
B. Scaled VAR Control control would emerge, as argued at the end of Section V.A.
To address the stability concerns of droop control, we Under this assumption, a closer look at the mismatch error in
will consider other designs of for local VAR control. The (23) yields
Newton's second-order method has been a very popular ap-
(30)
proach to accelerate the convergence of iterative solvers, by
scaling the gradient with the inverse Hessian of the objective; The effective Jacobian now becomes for the local con-
see e.g., ([20], Section 1.3). However, such a scaling method trol update (20). Hence, the sufficient stability condition for (20)
would be problematic when it comes to constrained problem is updated as . As , the delayed VAR
solvers with a projection operator. It can be easily shown that control is more likely to be stable. This analysis corroborates
the fixed-point of the Newton's update generally does not attain that the stability of droop control can be improved by the de-
the optimum solution of a constrained problem that it intends layed design, as pointed out by [3].
to solve ([20], Section 2.4). Hence, we will set for the
iteration (18), and scale it using the inverse of the diagonals of VI. NUMERICAL TESTS
Hessian matrix; i.e., This section presents numerical test results to demonstrate the
effectiveness of the proposed local control methods, for single-
(27)
and three-phase feeder systems. Both static and dynamic sce-
for some . The stability condition of Proposition 3 now narios on the system loading and generation will be considered.
becomes To better compare various algorithms, the desired voltage mag-
nitude is set to be unit in p.u. at every bus , along with
(28) fixed at 1. Each bus is equipped with a certain amount of
PV panels, which are able to offer flexible VAR supply to the
Compared to the droop control, the proposed scaled design feeder via effective inverter design. For the dynamic simulation
can stabilize the system dynamics for any matrix . This offers scenarios, the VAR limits are updated at every time slot
better flexibility for choosing the VAR supply penalty. In addi- based on the given inverter ratings and the instantaneous real
tion, the Hessian based diagonal scaling in (27) helps improve power generated.
the matrix conditioning and would speed up the convergence All numerical tests use the open source simulator OpenDSS
rate. More numerical simulations will be given in Section VI to [26] to solve for the actual power flow, instead of the approxi-
demonstrate this improvement. mate solution using (9). In addition, the actual bus voltage mag-
nitude, instead of the one obtained by the LinDistFlow model,
C. Delayed VAR Control is used for updating the VAR control outputs and numerical per-
With a non-unit stepsize in (20), the most general formance comparisons.
GP update takes the weighted average between the last iterate A. Single-Phase 16-Bus Radial Feeder
and the projection result. This coincides with the delayed
droop control method developed in [3], in the form of A 12 kV radial distribution feeder of 16 buses is first consid-
ered; i.e., the network in Fig. 1 with . Each line segment
(29) has the same impedance of . For the static
case, each bus has a constant load of kVA, and
where can be chosen using either the droop or the scaled abundant VAR resources of kVA. To include
control design. The work in [3] proposes this practical solution the VAR supply penalty, is chosen to be 0.2 at every bus for
to address the instability issues of droop control, along a very the proposed scaled and delayed schemes. The (delayed) droop
general stability condition. The latter can only be used to check control will used based on a linear droop curve of no
a specific distribution system with all case information given, deadband as in Fig. 2, since the voltage limits are set at [0.95,
but does not provide the exact bounds on the stepsize based on 1.05] and VAR limits at kVA.
the graph based matrices as in Proposition 3. 1) Static Scenario: Fig. 3 plots the iterative voltage mis-
Convergence of the GP method could also depend on the match error norm for the local VAR control methods.
choice of , which is not reflected by Proposition 3. As in The centralized solution corresponds to the optimum solution
([20], Section 2.3), the GP method in the form of (18) is con- to (13) with . To provide the benchmark perfor-
vergent as long as is kept constant and is selected using mance under the original unweighted objective, the matrix in
the limited minimization rule or the Armijo rule. The gist of (14) is substituted by , where the scalar is the average of
both rules is to choose adaptively to ensure sufficient de- 's eigenvalues.
cent in the objective value at every iteration. Numerical tests As for the stepsize choice, is chosen to be 0.3 for the scaled
performed in [3] demonstrate that a small and constant choice and delayed control methods, based on the stability conditions
such as , would lead to stable VAR control empiri- in Proposition 3. The stepsize is set to be constant 0.3 at
cally, even if the corresponding droop control is unstable. This every iteration for both delayed schemes. Choices of stepsize
suggests that a small could contribute to diminish the error will be discussed soon in more detail. As depicted by Fig. 3, the
norm in (23) as well. droop control fails to converge to a fixed operating condition,
3800 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 31, NO. 5, SEPTEMBER 2016
Fig. 4. Iterative voltage mismatch error performance for the scaled VAR con-
Fig. 3. Voltage mismatch error versus iteration index for various VAR control trol method with different values.
methods under the static system setting.
stay late in the night. This explains why the midnight load is
observed to be slightly higher than the house base load in the
early morning or afternoon. The installed solar panels have 3
kW peak capacity. The dynamic tests construct the load at every
bus to consist of 18 residential homes. Each home has the same
PV generation profile as in Fig. 6, where the inverter apparent
power limit is 5% higher than the peak capacity of 3 kW.
Fig. 7 illustrates the daily feeder voltage profile without any
VAR support. Peak voltage is observed to happen during noon
time when the load is minimal and the solar generation is at
its peak. Meanwhile, under-voltage violation (below 0.95 p.u.)
has been experienced at the end of feeder, during the evening
time with increasing power demand and decreasing PV gener-
ation. Because of its stability issue, the droop method is not
suitable for dynamic implementation. In addition, the delayed Fig. 8. Daily voltage mismatch error at every minute for the 16-bus case.
method has been omitted since it achieves the same steady-state
performance as the scaled method but at a slower convergence
rate. Hence, the proposed scaled VAR control scheme is imple-
mented here for tackling the dynamic under- and over-voltage
issues, along with the delayed droop method. The parameter and
stepsize settings follow from the static tests, while the droop
slope is time-varying based on the instantaneous VAR limits
computed from the PV generation at every minute. Both local
control schemes update every 5 seconds while the load and PV
generation stay constant within a minute. The voltage mismatch
comparison is illustrated in Fig. 8, which shows that additional
VAR control outperforms the case with no VAR support. More-
over, because of the constant setting, the scaled control
method is more effective in maintaining a flat voltage profile
than the delayed droop design, especially for the evening hours
from 18:00 to 22:00.
Fig. 10. IEEE 123-bus test feeder with solar PV panel locations.
on the IEEE 123-bus test case [28]. Fig. 10 shows the one-line
diagram for this distribution feeder case. In order to show the ef-
fects of inverter VAR control, the four three-phase voltage reg-
ulators are taken out of the 123-bus feeder system. In addition,
the case load information is used to determine the number of res-
idential homes connected to each load bus, while each home's
load demand and PV generation profile are same as Fig. 6. Lo-
cations of the load buses that are equipped with solar panels are
shown in Fig. 10. The feeder voltage profile for this three-phase
system under no VAR support is plotted in Fig. 11 for one time
instance, demonstrating that the system is unbalanced.
Figs. 12(a)–(c) plot the daily voltage mismatch error at all
three phases for the 123-bus case. Similar to Fig. 8 for the
16-bus case, only the scaled and delayed droop control methods
are compared to the case of no VAR support. For the scaled
control, is set to be constant at 0.01 while the delayed droop
slope is again time-varying based on the instantaneous inverter
VAR limits. Both local VAR control methods improve the
voltage support performance over the no VAR support scenario.
Because of its constant minimal VAR penalty, the scaled VAR
control scheme slightly outperforms the delayed droop method.
However, the difference between voltage mismatch error Fig. 12. Daily voltage mismatch error at (a) phase a; (b) phase b; and (c) phase
among all three scenarios is less significant compared to the c for the 123-bus case.
16-bus system in Fig. 8. This less significant voltage regulation
performance is because the 123-bus case has a lower level of
PV penetration (30%) compared to the 16-bus case (100%). voltage mismatch error by half from the baseline case of no
Accordingly, the inverter VAR output would be less effective VAR support.
in attaining the ideal constant voltage profile. Nonetheless, the
scaled VAR control becomes more effective during the evening VII. CONCLUSIONS AND FUTURE WORK
hours at higher voltage violation. As shown by the zoom-in This paper presents a general framework for developing local
view in Figs. 12(a)–(c), the scaled scheme almost reduces the VAR control methods with high penetration of distributed VAR
ZHU AND LIU: FAST LOCAL VOLTAGE CONTROL UNDER LIMITED REACTIVE POWER 3803
resources. By linearizing the distribution network power flow [15] G. Valverde and T. Van Cutsem, “Model predictive control of voltages
model, the VAR control problem is cast as one to minimize in active distribution networks,” IEEE Trans. Smart Grid, vol. 4, no. 4,
pp. 2152–2161, 2013.
the voltage mismatch error. Using the graph matrix represen- [16] IEEE Draft Recommended Practice for Establishing Methods and Pro-
tation, we formulate a weighted error minimization problem cedures That Provide Supplemental Support for Implementation Strate-
under box constraints that represent VAR limits at every bus. gies for Expanded Use of IEEE Standard 1547, IEEE P1547.8/D8, July
2014, Jun. 2014, pp. 1–176.
The gradient-projection (GP) method is evoked for solving this [17] M. Farivar, L. Chen, and S. Low, “Equilibrium and dynamics of local
constrained problem, which naturally decouples into local VAR voltage control in distribution systems,” in Proc. IEEE 52nd Conf. De-
updates requiring only the instantaneous bus voltage magnitude cision and Control (CDC), Dec. 2013, pp. 4329–4334.
information. The GP-based VAR control framework general- [18] B. Zhang, A. Dominguez-Garcia, and D. Tse, “A local control approach
to voltage regulation in distribution networks,” in Proc. 2013 North
izes existing droop and delayed droop control methods, while Amer. Power Symp. (NAPS), Sep. 2013, pp. 1–6.
allows for stability analysis to tune up the parameters based on [19] N. Li, G. Qu, and M. Dahleh, “Real-time decentralized voltage control
the network Bbus matrix. Numerical tests have been performed in distribution networks,” in Proc. 52nd Annual Allerton Conf. Com-
munication, Control, and Computing, Sep. 2014, pp. 582–588.
on single- and three-phase systems using the exact ac power [20] D. P. Bertsekas, Nonlinear Programming, 2nd ed. Belmont, MA,
flow model, which corroborate the analytical results on the per- USA: Athena Scientific, 1999.
formance guarantees of proposed methods for realistic system [21] M. Baran and F. Wu, “Optimal capacitor placement on radial distribu-
tion systems,” IEEE Trans. Power Del., vol. 4, no. 1, pp. 725–734, Jan.
implementations. 1989.
The future research plan for this work includes to investigate [22] H. J. Liu, R. Macwan, N. Alexander, and H. Zhu, “A methodology
the impact of potential asynchronous control updates among dif- to analyze conservation voltage reduction performance using field test
ferent buses, due to the potential lack of coordination [29]. We data,” in Proc. IEEE Int. Conf. Smart Grid Communications, Nov.
2014, pp. 529–534.
are also actively investigating the interactions between inverter [23] D. B. West, Introduction to Graph Theory, 2nd ed. Upper Saddle
VAR control and other voltage regulation devices, as well as River, NJ, USA: Prentice Hall, 2001.
pursuing a distributed VAR control framework which has the [24] A. J. Wood, B. F. Wollenberg, and G. B. Sheble, Power Generation,
Operation, and Control, 3rd ed. New York, NY, USA: Wiley, 2013.
potential to achieve the original unweighted error objective. [25] Common Functions for Smart Inverters, Electric Power Research In-
stitute (EPRI), Smart Inverter Working Group Recommendations, Feb.
2014 [Online]. Available: http://www.epri.com/abstracts/Pages/Pro-
REFERENCES ductAbstract.aspx?ProductId=000000000001026809
[26] OpenDSS Simulation Tool [Online]. Available: http://smartgrid.epri.
[1] K. Turitsyn, P. Sulc, S. Backhaus, and M. Chertkov, “Options for con- com/SimulationTool.aspx
trol of reactive power by distributed photovoltaic generators,” Proc. [27] “Individual household electric power consumption dataset,” UCI Ma-
IEEE, vol. 99, no. 6, pp. 1063–1073, Jun. 2011. chine Learning Repository [Online]. Available: http://archive.ics.uci.
[2] P. Carvalho, P. F. Correia, and L. Ferreira, “Distributed reactive power edu/ml/
generation control for voltage rise mitigation in distribution networks,” [28] IEEE PES Distribution Test Feeders, Sep. 2010 [Online]. Available:
IEEE Trans. Power Syst., vol. 23, no. 2, pp. 766–772, May 2008. http://www.ewh.ieee.org/soc/pes/dsacom/testfeeders.html
[3] P. Jahangiri and D. Aliprantis, “Distributed Volt/VAR control by pv [29] H. Zhu and N. Li, “Asynchronous local voltage control in power distri-
inverters,” IEEE Trans. Power Syst., vol. 28, no. 3, pp. 3429–3439, bution networks,” in Proc. 41st IEEE Int. Conf. Acoustics, Speech and
Aug. 2013. Signal Processing (ICASSP), Mar. 2016, submitted for publication.
[4] B. Robbins, C. Hadjicostis, and A. Dominguez-Garcia, “A two-stage
distributed architecture for voltage control in power distribution sys-
tems,” IEEE Trans. Power Syst., vol. 28, no. 2, pp. 1470–1482, May
2013.
[5] American National Standard for Electric Power Systems and Equip-
ment- Voltage Ratings (60 Hertz), ANSI C84.1-2011 Std. Hao Zhu (M’12) received her B.S. from Tsinghua
[6] M. Farivar, R. Neal, C. Clarke, and S. Low, “Optimal inverter var con- University, Beijing, China in 2006, and the M.Sc.
trol in distribution systems with high pv penetration,” in Proc. IEEE and Ph.D. degrees from the University of Minnesota,
Power and Energy Soc. General Meeting, Jul. 2012, pp. 1–7. Minneapolis in 2009 and 2012, respectively.
[7] E. Dall'Anese, H. Zhu, and G. Giannakis, “Distributed optimal power She is currently an Assistant Professor of ECE
flow for smart microgrids,” IEEE Trans. Smart Grid, vol. 4, no. 3, pp. at the University of Illinois, Urbana-Champaign
1464–1475, Sep. 2013. (UIUC). She worked as a postdoctoral research
[8] P. Sulc, S. Backhaus, and M. Chertkov, “Optimal distributed control associate on power system validation with the
of reactive power via the alternating direction method of multipliers,” Information Trust Institute at UIUC from 2012 to
IEEE Trans. Energy Convers., vol. 29, no. 4, pp. 968–977, Dec. 2014. 2013. Her current research interests include power
[9] B. Zhang, A. Lam, A. Dominguez-Garcia, and D. Tse, “An optimal and system monitoring and operations, dynamics and
distributed method for voltage regulation in power distribution sys- stability, distribution systems, and energy data analytics.
tems,” IEEE Trans. Power Syst., vol. 30, no. 4, pp. 1714–1726, Jul. Dr. Zhu is currently the IEEE Signal Processing Society's Representative on
2015. the IEEE TRANSACTIONS ON SMART GRID, and a steering committee member
[10] V. Kekatos, G. Wang, A. Conejo, and G. Giannakis, “Stochastic reac- for IEEE SMART GRID.
tive power management in microgrids with renewables,” IEEE Trans.
Power Syst., vol. 30, no. 6, pp. 3386–3395, Nov. 2015.
[11] H.-G. Yeh, D. Gayme, and S. Low, “Adaptive var control for distribu-
tion circuits with photovoltaic generators,” IEEE Trans. Power Syst.,
vol. 27, no. 3, pp. 1656–1663, Aug. 2012. Hao Jan (Max) Liu (S’12) was born in Taipei,
[12] A. R. Bergen and V. Vittal, Power System Analysis, 2nd ed. Upper Taiwan. He received his B.S. from Missouri Univer-
Saddle River, NJ, USA: Prentice Hall, 2000. sity of Science and Technology, Rolla, MO in 2011.
[13] Q. Zhou and J. Bialek, “Generation curtailment to manage voltage con- He is currently a Ph.D. candidate of ECE at the
straints in distribution networks,” IET Gener., Transm., Distrib., vol. University of Illinois, Urbana-Champaign (UIUC).
1, no. 3, pp. 492–498, 2007. His current research interests cover the areas of op-
[14] M. Kraiczy, M. Braun, G. Wirth, S. Schmidt, and J. Brantl, “Interfer- timization for power distribution networks and smart
ences between local voltage control strategies of a HV/MV transformer grid technology, including Volt/VAR and conserva-
and distributed generators,” in Proc. 28th Eur. PV Solar Energy Conf. tion voltage reduction studies.
Exhib., Sep. 2013.