0% found this document useful (0 votes)
264 views78 pages

ATP MCA Analysis Manual AT5

MCA Analysis Manual AT5

Uploaded by

kamran719
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
264 views78 pages

ATP MCA Analysis Manual AT5

MCA Analysis Manual AT5

Uploaded by

kamran719
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 78

MOTOR CIRCUIT ANALYSIS (MCA) MANUAL FOR

ALL-TEST PRO 5TM


ALL-TEST Pro, LLC

MCATM MANUAL
Rev. 08-14-2015

ALL-TEST Pro, LLC


PO 1139
Old Saybrook, CT 06475
Phone 860-399-4222 • Fax 860-399-3180
www.alltestpro.com
Table of Contents
Introduction ................................................................................................. 4
Use of this Manual ...................................................................................... 4
ALL-TEST Pro Analysis Philosophy ............................................................ 4
Motor Diagnostic Theory ............................................................................. 5
Basic Electrical Theory & Definitions of Measurement and Calculation Values .... 6
Static – Testing Sequence .................................................................................... 7
Dynamic Signature Analysis ................................................................................. 9
Applying MCA ........................................................................................... 13
Motor Testing Procedure .................................................................................... 14
Initial Readings ................................................................................................... 15
Performing Motor Diagnostics Using MCA ................................................ 15
Condemning Criteria ........................................................................................... 17
Data Analysis Tips .............................................................................................. 17
Condemning Priority ........................................................................................... 18
Condemning Tips ............................................................................................... 18
Unassembled Motor Analysis ............................................................................. 19
Data Interpretation Basic Rules and Tolerances ....................................... 20
Analyzing Measurements and Change ..................................................... 22
Troubleshooting Rules........................................................................................ 22
Winding Contamination ...................................................................................... 23
Rotor Reposition Test ......................................................................................... 23
Insulation Resistance ......................................................................................... 24
Loose Connections ............................................................................................. 25
Predictive Maintenance............................................................................. 25
Implementing Predictive Maintenance ................................................................ 25
Predictive Maintenance Hints ............................................................................. 26
Data Collection and Test Result Issues .............................................................. 27
Data Trending ..................................................................................................... 29
Troubleshooting Motors ............................................................................ 32
Rotor Compensated Test ................................................................................... 32
Rotor Reposition Test ......................................................................................... 33
Rotor Test ................................................................................................. 33
Analysis .............................................................................................................. 35
Appendix 1: ............................................................................................... 38
Different Test Scenarios ..................................................................................... 38
Appendix 2: ............................................................................................... 50

©2015, ALL-TEST Pro, LLC 2 Rev. 08/14/2015


Single and Three Phase Transformer Testing; Using Static Motor Circuit Analysis
Techniques ......................................................................................................... 50
Appendix 3: ............................................................................................... 61
Synchronous Machine Testing With ALL-TEST Pro Instrumentation ................. 61
Appendix 4: ............................................................................................... 68
Appendix 5: ............................................................................................... 69
DC Current Motor Electrical Evaluation Using Motor Circuit Analysis ................ 69
Disclaimer, Copyright & Trademarks......................................................... 77

©2015, ALL-TEST Pro, LLC 3 Rev. 08/14/2015


Understanding Motor Diagnostics using
Motor Circuit Analysis (MCATM)
Introduction
MCA is a very simple and safe method to test electrical windings while the winding is
de-energized. The basic premise of MCA:

In equipment with three phase windings all phases should be identical (same #
turns, same wire size, coil diameter, etc.).Consequently, all characteristics of the
windings should also be similar. If a change occurs in any one of these
characteristics, the change is never for the better, (windings do not repair
themselves) as degradation is taking place. By analyzing the amount and
relationships of the change it is possible to identify the cause of the degradation.
Once the cause and the severity of the degradation are known it is now possible
to determine the necessary action.

Use of this Manual


The purpose of this manual is to provide users of MCA technology tips and guidelines to
follow when performing Motor Diagnostics using the ALL-TEST Pro line of MCA
TM
instruments. This manual is intended primarily for use with the ALL-TEST PRO 5 (AT5).
However, some of the information is applicable to the ALL-TEST PRO 33INDTM (AT33IND).
If the user only has an ALL-TEST PRO 33INDTM, it is designed to only test AC induction with
squirrel cage rotor motor less than 1kV.

ALL-TEST Pro Instrument Philosophy

 Easy and safe to use for both the user and item under test

 Battery operated, light weight and portable

 Effective tests for motors regardless of design, size and construction

 Show fault(s) immediately

 Show changes over time

 Produce multiple measurements for comprehensive analysis

ALL-TEST Pro Analysis Philosophy


Testing and analysis of electrical motors, transformers or any winding is not “black magic
art”. In reality it is very straightforward, if sufficient and proper measurements are performed.

©2015, ALL-TEST Pro, LLC 4 Rev. 08/14/2015


It has been the experience at ALL-TEST Pro that the most accurate and comprehensive
method of determining the true condition of motor windings is by controlling the testing
parameters while the motor is de-energized. This method removes errors and conflicting
results from stray or unknown sources used by other methods.

By injecting a known, low voltage AC sinusoidal, non-destructive signal through the motor
windings, winding faults or weaknesses are not driven to failure. In many cases, potentially
destructive faults can be easily corrected before total winding failure occurs.

Winding faults are indicated by variances in the response to the signal injected through the
windings. These variances cause unbalances in the measured response to the injected
signal. Using MCA faults appear the same regardless of the size or type of the winding.
Motors as small as automobile windshield wiper motors as well as 300 Megawatt Generator
windings have been successfully tested.*

*Very large equipment testing may require the user to perform the measurements to individual coils.
I.e. Coil to coil testing.

Through additional investigation and measurement of these variances in the winding, faults
can be quickly and easily identified, and corrected prior to energizing the winding; which can
lead to total destruction of the motor.

Examples:
A deteriorating Insulation to Ground situation, will normally require immediate
attention. This type of fault can be very dangerous (safety hazard) and lead to
immediate machine failure.

On the other hand a developing turn-to-turn or coil-to-coil fault, especially in low


voltage motors, may degrade over a longer period of time and provide the
opportunity to correct the fault before it becomes a catastrophic failure, thereby,
requiring a complete rebuild or costly replacement.

MCA injects an AC signal through the windings and measures the response of the item-
under-test to this signal to identify any unbalances in the windings that indicate either a
current or a potential fault.

Motor Diagnostic Theory


ALL-TEST Pro MCA instruments are based on proven electrical theory. The motor
system can be represented by developing the basic motor circuit, which is nothing more
than a simple RCL circuit. This circuit represents the various components of the motor
system. Each basic circuit represents one phase of the three phase motor system.
Since each phase of the motor system is identical, each basic circuit should respond the
same way to an applied signal.

To allow the user to obtain the most benefits from ALL-TEST Pro instruments and this
manual, a brief review of electrical theory as applied to Motor Diagnostics is presented
below. A review of this section will help in understanding the results obtained from ALL-

©2015, ALL-TEST Pro, LLC 5 Rev. 08/14/2015


TEST Pro instruments. Additional information is available in any electrical textbook.
ALL-TEST Pro also offers on-site and public training courses to further the user’s
knowledge. For dates and locations of these courses please visit us on our website
www.alltestpro.com.

Basic Electrical Theory & Definitions of Measurement and Calculation Values

R -Resistance is the Direct Current resistance measured in Ω (Ohm). The resistance


should be the same across all phases or fields. Any difference may indicate a potential
problem. Difference can be due to “over-winding”, corrosion, faulty connections, etc.

Z- Impedance is the complex resistance in a coil or winding. Impedance includes


resistance, inductive reactance and capacitive reactance. Impedance is measured in Ω
(Ohm).

Zero impedance in a winding indicates “a shorted” winding. Also, see I/F below.

Note: A coil or winding can have a severe turn-to-turn or coil to-coil fault, but show
“good” when using a MegOhm meter. It can also show a severe Ground Insulation fault
but shows perfectly OK turn-to-turn.

L- Inductance is the property of a changing magnetic flux to create (or induce) a voltage
in a circuit. Inductance is dependent on the number of turns, diameter of the coil, length
of coil, number of the layers and the material in a spool or coil core. Inductance opposes
any change in the current flow through a conductor. The value is a measurement of the
ability of a coil to store magnetic energy. It is measured in Henry (H).

Self-Inductance is the property of a circuit where a change of current in the


circuit creates/induces a voltage in the same circuit due to the magnetic field
created by the changing current.

Mutual Inductance is the concept that current flow through one conductor or
circuit can induce a voltage into a nearby circuit or conductor.

Note: In a three phase induction motor with the rotor in place, inductance unbalances
when performing a static test (rotor in a fixed position) can be the result of unbalanced
mutual inductance due to the rotor angular orientation (More commonly referred to as
rotor position).

Test Value Static (TVS) An AC induction motor is a “Symmetric Alternating Current


Machine”, i.e. the three phases are designed and manufactured to be identical. When a
fault occurs it creates an asymmetry in the AT5 (AT33) measured data. All common
types of faults in the Rotor and in the Stator windings break the symmetry of the
machine (motor), therefore, asymmetry in test data indicates winding and/or rotor fault.

©2015, ALL-TEST Pro, LLC 6 Rev. 08/14/2015


For a Symmetric Alternating Current Machine (motor), the rotor position influences the
inductances (L), impedances (Z), or Phase Angles (Fi) of each stator winding differently
since the rotor position influences the coupling of the L, Z, and Fi between stator
windings and rotor winding.

Test Value Static (TVS)

Test Object 3- Phases

However, due to the Symmetry of the motor the measured/calculated Test Value Static
(TVS) of the stator windings is independent of the rotor position. Note: In practice, TVS
may be slightly influenced by the rotor position, due to inaccuracies during assembly of
the motor or motor parts (manufacturing tolerances), slight differences between stator
windings, flaws in the rotor, measurement inaccuracies, etc. The figure above shows
some measurement on three phases for a “Symmetric Alternating Current Machine” and
the top line illustrates that TVS stays relatively constant with slight deviations at different
rotor positions.

All common types of faults in the Rotor and in the Stator windings break the symmetry
of the motor. As a result, the TVS will change and no longer be independent of the rotor
position. Consequently, a second TVS will no longer be equal to the first TVS (TVS 2 ≠
TVS1).

Static – Testing Sequence

The AT33/AT5 outputs a low voltage sinusoidal signal at frequencies of 50, 100, 200,
400, & 800Hz. The following is true:
 Calculates Test Value Static (TVS) in the “first” rotor position (TVS1).
 Rotor position has little influence on TVS value in a good motor.
 TVS is a motor specific parameter.
 TVS can be used as a Reference (REF) value for detecting fault conditions.
 TVS can be used as a REF value for that specific motor or other motors of exact
same type, manufacturer and manufacture tolerances. (Refer to the figure in

©2015, ALL-TEST Pro, LLC 7 Rev. 08/14/2015


previous page). Just because two motors have the same nameplate
specifications, it does not necessarily mean the two motors are exactly the same.
 A subsequent test with the AT33/AT5 calculates a new TVS (at any rotor
position).
 TVS1 can be compared to TVS2.
 If TVS2 ≠ TVS1 this indicates that a change has occurred in the condition of the
stator and/or rotor.

Dynamic Test

An AC induction motor is a “Symmetric Alternating Current Machine” and when a fault


occurs it creates Asymmetry in the AT33/AT5 measured data. All common types of
faults in the Rotor and in the Stator windings break the symmetry of the machine
(motor), therefore, asymmetry in measuring data indicates winding and/or rotor fault.

All three phases of the motor are connected to the AT33/AT5 and dynamic testing
requires that the user manually rotate the shaft of the motor while the instrument goes
through the testing process. The motor shaft must be turned in a slow and steady
manner without stopping or reversing the rotation. We recommend that a tool should be
used to facilitate a smooth rotation. For this purpose ATP can provide a rotation strap
wrench, which is wrapped around the rotor shaft with a convenient handle for a user to
rotate. The left picture below shows an example of strap wrench and the right picture
shows the strap wrench attached to the motor shaft.

As with the Static test, the AT33/AT5 will test all phases in real-time while the shaft is
moving and current, inductance, impedance, phase angle, current/frequency response,
and other measurements/calculations are made. From these measurements and
calculations two important “Signatures” are presented at the end of the test: Stator
and Rotor.

The following are the recommended rotating speeds when performing dynamic test with
AT33/AT5. However, when testing a motor for the first time, we suggest that the user

©2015, ALL-TEST Pro, LLC 8 Rev. 08/14/2015


perform the dynamic test at a few different speeds to find the optimal one for the
specific motor under test. I.e. the speed which results in relatively smooth and uniform
data points for dynamic test signature.

Maximum recommended rotor shaft rotational speed for 2-pole motor = 100 RPM
Maximum recommended rotor shaft rotational speed for 4-pole motor = 50 RPM
Maximum recommended rotor shaft rotational speed for 6-pole motor = 33 RPM
Maximum recommended rotor shaft rotational speed for 8-pole motor = 25 RPM
Maximum recommended rotor shaft rotational speed for 10-pole motor = 20 RPM
Maximum recommended rotor shaft rotational speed for 12-pole motor = 17 RPM

One way to help perform good dynamic test is to look at the dynamic test bar displayed
on the screen. If the bar moves back and forth uniformly, chances are the dynamic test
will be performed well. However, the users still need to see the final dynamic signature
to determine if the test is good.

The Dynamic test provides the OK, Warn, or Bad alarms for the Stator and Rotor.
Moreover, it provides the valuable Stator & Rotor Signatures. At the end of the Dynamic
test the results can be viewed, stored, or uploaded to the appropriate computer
software.

Note: The image below is generated using the computer software.


Each Phase

Rotor Signature Upper

Stator Signature (3 phases)

Rotor Signature Lower

% Change in Impedance
during rotation

Dynamic Signature Analysis

The Green line is the Stator signature and represents the deviation of the mean values
during rotation for each phase. Note that for Phase 1-3, the Stator signature is slightly
elevated above the other two phases. This indicates the mean values for Phase 1-3 are
slightly higher than the other two phases, but are within acceptable limits and this stator
is considered to be in good condition.

The two black dotted lines represent the Rotor Signature and include an upper and
lower signature. This represents the deviation of the peak values during rotation. As the
output of the instrument is sinusoidal and the response of the motor will be sinusoidal,

©2015, ALL-TEST Pro, LLC 9 Rev. 08/14/2015


there will be peak values both high and low. There are 8 dots for each phase and if this
were an 8-pole motor then this represents 1 full revolution of the motor shaft. If this were
a 2-pole motor then it represents 4 revolutions of the motor shaft. If this were a 12-pole
motor then it represents ¾ of a revolution of the motor shaft. With this Rotor signature
there is a slight variation in the distribution of the peak values, but as they are within our
limit, this rotor is in good condition.

The % change in impedance represents the change in impedance during rotation of the
shaft for that particular phase.
Phase Angle is a relative measurement that indicates the angular difference between
two waveforms of the same frequency. The results are expressed in degrees angular
difference (0 – 900). In the electrical circuit the phase angle expresses the relationship
of the AC current to the applied voltage. This test is included in IEEE Std 1415™-2006
sec 4.3.20 as an effective method to identify winding shorts.

Basic Electrical theory states that:


In a purely Resistive circuit, current & voltage are in-phase. I.e. they both reach the
same point in the waveform at the same time.

In a purely Inductive circuit voltage leads current by 90 degrees. I.e. Voltage reaches it
maximum & minimum value 90 degrees before current.

In a purely Capacitive circuit current leads voltage by 90 degrees. I.e. Current reaches
it maximum & minimum values 90 degrees before voltage.

If the Voltage leads the current the phase angle is positive, if the voltage lags the
current the phase angle is negative.

With MCA testing the phase angle expresses the relationship of the measured current
to the AC voltage applied by the ALL-TEST Pro instruments.

Note: MCA phase angle should not be confused with the 120 degrees electrical
separation between electrical phases in a three-phase system.

I/F- Current/Frequency Response is a test designed primarily to test for coil-to-coil or


turn-to-turn faults. This test is included in IEEE Std 1415™-2006 sec 4.3.33 as an
effective method to identify winding shorts.

For the I/F test the low voltage AC signal is applied to the connected winding/windings,
at a specific frequency and the resultant current is measured. Then the frequency of
the applied AC signal is then doubled and the resultant current is again measured.

The I/F reading is the ratio of the current at the doubled frequency to the current at the
original frequency. This result is displayed as a ratio. I.e. an I/F reading of -50 indicate
that the current at the doubled frequency is 50% lower than the current at the original
frequency.

©2015, ALL-TEST Pro, LLC 10 Rev. 08/14/2015


C- Capacitance is the capability of a body, system, circuit, or device to store electric
charge. It is a measure of the amount of electrical charge stored for a given applied
potential. The unit of capacitance is the Farad (F). The capacitance of a circuit opposes
any change in voltage in the circuit.

The capacitance of a circuit is dependent on the geometry of the system and the
material of the dielectric.

Any capacitors in the motor circuit should be tested separately from the motor.

DF: The Dissipation Factor (DF) is the ratio between the resistive power loss and the
reactive power loss of the insulation material. This is used to detect contaminated or
overheated windings.

Since the insulation material forms a capacitor, an AC voltage


applied across the insulation will cause the system to
react as a capacitive circuit. Ideally the electrical
equivalent circuit would be a simple capacitive circuit,
and all of the current through the circuit would be
C R
capacitive. However, in real life the equivalent
electrical circuit will be a parallel RC circuit. Some of
the current will be capacitive Ic, while some of the
AC
Source~
circuit will be resistive Ir. The two currents have a phase difference of 900. The DF is the
ratio of the resistive current to the capacitive current. DF = Ir / Ic. It is also referred to as
the tan δ.

DF testing is widely used on electrical equipment such as power transformers, circuit


breakers, generators and cables. Also, DF values, trended over time, can help in
detecting problems like contamination, high moisture content and the presence of voids
in the insulation.

When the insulation system begins to degrade or becomes contaminated, the DF will
increase. In addition, the DF is temperature dependent. Measuring DF at too high or
too low temperature can introduce errors and the IEEE recommends performing DF
tests at or near 68 0F (20 °C).

INS- Insulation (to Ground) Test. Measured in Meg-Ohm.


A motor can have a good insulation to ground but fail other phase-to-phase tests and
vice versa. IRG is the most common electrical test performed on electrical systems. The
IRG test is performed by applying a high dc voltage between de-energized current-
carrying conductors (windings) and the machine casing or earth.

According to IEEE Std 43, the insulation resistance is measured after applying DC high
voltage for 1 minute. The motor should be above dew point temperature before testing,
if possible. It is important to correct values to a reference temperature (typically 40 °C)

©2015, ALL-TEST Pro, LLC 11 Rev. 08/14/2015


so that trends and changes in insulation resistance can be readily detected. To correct
the insulation resistance to 40 °C, use the following equation

Rc = KT RT
Rc is the insulation resistance normalized to 40 °C.
KT is the insulation resistance temperature coefficient at temperature of T
RT is the insulation resistance measured at temperature of T.

According to the IEEE Std 43, for the thermoplastic insulation systems

KT=(0.5)(40-T)/10

For the thermosetting insulation systems

1 1
𝐾𝑇 = 𝑒𝑥𝑝 [−4230 ((𝑇+273) − 313)] 40 oC < T < 85 oC

1 1
𝐾𝑇 = 𝑒𝑥𝑝 [−1245 ((𝑇+273) − 313)] 10 oC < T < 40 oC

Contamination, humidity, temperature, and other factors affect insulation resistance values.

The standard recommends choosing test voltages for insulation resistance testing:

The AT5 instrument offers two test voltages: 500V and 1kV. For windings rated over
5kV, a higher test voltage will be needed according to the guidelines above. The
standard also recommends minimum insulation resistance value at 40 oC as shown
below. “kV” is the rated line-to-line rms voltage of 3-phase motor, line to ground voltage
of single phase motor, or rated DC motor voltage.

©2015, ALL-TEST Pro, LLC 12 Rev. 08/14/2015


Note: The IEEE guidelines above provide the recommended voltages and Minimum
Insulation Resistance to ground values. If these procedures or values differ from your
equipment manufactures’ recommendations, follow their guideline.

Applying MCA
ALL-TEST Pro has four instruments designed to perform MCA testing.

ALL-TEST PRO 5TM (AT5) is a Motor Circuit Analyzer for de-energized testing used for
predictive maintenance and troubleshooting winding and rotor faults in motors and
transformers of virtually all sizes and types: Single and 3-phase, AC and DC, even
traction motors and machine tool servos. It performs automated measurements,
performs calculations and comparisons, and gives immediate feedback regarding the
condition of the motor under test using an OK, Warn, or Bad result. When an initial
baseline test is performed a Reference Test Value Static (TVS) can be saved for that
induction motor. Subsequent test results can be immediately compared to the
Reference TVS to instantly show developing problems or changes with the stator or
squirrel-cage rotor (view comparison right on the large, easy to read display). A
Reference TVS can also be established from the starter or motor drive, thereby, making
it easy to detect changes with connections and cables, along with the motor. No need to
access computer software while in the field. It stores over 600 motor and Reference test
records.

ALL-TEST PRO 33INDTM (AT33IND) is a Motor Circuit Analyzer for the de-energized
testing of AC Induction, squirrel-cage rotor motors <1000V for: contamination, winding
faults such as turn to turn & coil to coil, open connections, ground faults, and also
evaluates the condition of the rotor. An initial baseline test is performed and a
Reference Test Value Static (TVS) is saved for that motor. Subsequent test results can
be immediately compared to the Reference TVS to instantly show you developing
problems or changes within the stator or rotor (view comparison right on the AT33 easy
to read display). A Reference TVS can also be established from the starter or motor
drive, thereby, making it easy to detect changes with connections and cables, along
with the motor. No need to access computer software while in the field. It has internal
memory storage for over 800 motor and Reference test records.

©2015, ALL-TEST Pro, LLC 13 Rev. 08/14/2015


ALL-TEST PRO 33EVTM (AT33EV) is used to test the special permanent magnet motor
and motor/generator used in electric and hybrid vehicles. Contact ALL-TEST Pro for
details.

ALL-TEST IV PRO (ATIV) is a Motor Circuit Analyzer for de-energized testing that will
test virtually any motor, generator, transformer, or coil based device. It can be used not
only for incoming inspection and trouble-shooting, but also for PdM or CBM testing
purposes (data trending and time to failure estimation). Use our MCA Analysis Manual
2008 Rev B for analysis assistance.

ALL-TEST PRO 31TM (AT31) is a de-energized motor circuit trouble-shooting tool that
will test a wide variety of motors and some transformers. It will test most AC motors
under 600V and can also be used to test higher voltage motors, depending upon their
resistance, inductance, and impedance. The AT31 should be used in conjunction with
an ohmmeter, as it does not measure resistance (it does perform an insulation to
ground resistance test) – use our MCA Analysis Manual 2008 Rev B for analysis
assistance.

Motor Testing Procedure


It is important to note that a “perfect” 3-phase motor is very difficult to find based upon
manufacturing tolerances, etc. In other instances, motors may have a particular
difference in design in order to meet special operating applications.

IND

Used to test AC three-phase squirrel cage induction motors with rated voltage less than
1000 V. It performs the Static, Dynamic, Insulation resistance to ground, DF &
capacitance tests.

Z/

Used to test all types of AC/DC motors, generators and transformers. It performs the
Static, Insulation resistance to ground, DF & Capacitance, Phase Angle, I/F, Impedance
and Inductance tests. It may be necessary to perform additional steps to isolate rotor or
stator faults.

1 Phase AC Test

Applicable to AC single-phase motors or other single coil devices. It performs the Static,
Insulation resistance to ground, DF & Capacitance, Phase Angle, I/F, Impedance and
Inductance test.

©2015, ALL-TEST Pro, LLC 14 Rev. 08/14/2015


DC Test

Applicable to different types of DC motors as well as individual coils. Each test option
includes Insulation Resistance to Ground, Phase Angle, I/F, Impedance and Inductance
test. DF & Capacitance are only available when the test is performed directly at the motor
connections.

Initial Readings

In a few cases, some motors may exhibit unusual levels of unbalance(s) with respect to
Fi, I/F, L, and/or Z results. This can occur for a number of reasons, including:

1) Stator winding to rotor bar ratio and position.


2) Stator winding design (lap versus concentric coil).
3) Other tolerance-related issues including rotor casting voids.
If unusual unbalances are detected with the instrument, there are several ways of
isolating the cause including:
 For AC induction squirrel-cage rotor motor <1000V use the Dynamic test
mode.
 Make a short series of additional tests using the AT5 (see Rotor
Reposition Test in the Motor Troubleshooting Section).

Performing Motor Diagnostics Using MCA


Motor/Winding Analysis

Performing motor/winding analysis has been greatly simplified with the development of
advanced diagnostic tools such as the AT33IND and AT5 with their comprehensive internal
analytics coupled with easy-to-use computer software for analysis, reporting, and data
storage. However, even as good as these tools are, sometimes additional information and
testing may be required before the final condition of a machine can be accurately assessed.

To help maximize the data obtained from the ALL-TEST Pro tools, the next few sections will
provide the analyst the procedures, techniques, suggestions and methods necessary to help
the analyst properly and accurately diagnose most winding faults using Motor Circuit
Analysis (MCA).

The basic rule for MCA is: If the data indicates a good winding then the winding is generally
good. However, if MCA indicates a fault then additional testing should be performed before
condemning a winding.

1) The test leads that are supplied with the AT5 instrument are customized Kelvin
leads. If a different size of Kelvin clips is needed, please contact ALL-TEST Pro.
Note: The repeatability of the resistance readings can be improved by using a small
wire brush to clean surface oxidation from connection points and by lightly

©2015, ALL-TEST Pro, LLC 15 Rev. 08/14/2015


squeezing the test jaws together while lightly twisting the clips on the connection
point to ensure as solid a connection as possible.

2) The AT5 uses a Kelvin bridge ohmmeter for making the DC resistance
measurement with a resolution of 0.01 mΩ. Note: For MCA purposes the DC
resistance measurements are used to detect problems related to connections and
are not used to detect winding faults (TVS, Dynamic Test, Fi and I/F are much better
indicators for winding faults).

Sample Test Results AC Induction

IND Test Mode

©2015, ALL-TEST Pro, LLC 16 Rev. 08/14/2015


Z/ test mode

Note: In Z/ test mode computer software will only state “Good Stator Winding” when all
values are “Green”.

Condemning Criteria

This information pertains to testing 3-phase, AC induction motors. How to properly test and
analyze for other motor types, transformers, etc. is covered in other sections of this manual.

Data Analysis Tips

When a motor testing program is first implemented it is expected that between 20- 40% of
the motor systems tested may exhibit some alarm condition. When a motor is in an alarm
state, this does not necessarily mean that the motor will fail or that it should be stopped
immediately, but that the measured values have exceeded pre-determined limits established
for most common motors. The software alarm limits of the MCA BASICTM and MCA PROTM
are established for standard 3-phase squirrel-cage induction motors. Some motors may
have a special design, which can cause the measured values to be normally outside of
these standard limits. In fact, many new motors will have an unbalance in inductance and
impedance, due to rotor bar winding ratio. Therefore, it is virtually impossible to establish
limits for all possible design configurations. Of these cases, it is necessary for the analyst to

©2015, ALL-TEST Pro, LLC 17 Rev. 08/14/2015


evaluate these readings on a case-by-case basis. The software and AT5 instrument will flag
any motor test that exceeds these limits to inform the analyst that they are outside of the
generic alarm limits. The following analysis tips provide a method for more closely
evaluating these special circumstances. Following the Analysis tips are various Scenarios
using actual readings. Reviewing these scenarios will provide additional insight into
determining how to evaluate the test data.

NOTE: It is highly recommended that users and analysts review this information carefully.
There may be circumstances were more narrow alarm limits are appropriate and please
contact our technical support team for further information.

Condemning Priority

The MCA BASICTM and MCA PROTM software simply generate the alarms when the
measured values exceed pre-determined limits. However, not all faults are the same. The
guidelines provided below will help the analyst place priority upon the alarms generated by
the software.

One of the first considerations regarding winding faults should always be motor criticality.
Obviously, the most critical motors should be afforded a higher priority than less critical
motors. The second consideration is the type and location of the fault (connection, winding,
rotor, etc). Additional considerations include availability of spares, maintenance schedules
and other plant operations. These priorities assume that the test data is valid and good
connections were made during the testing process. Bad test lead connection can negatively
impact all readings. Non-repeatable test results should be considered suspect and
investigated further.
1) Winding shorts are generally more severe than contamination or rotor faults,
therefore, motors with TVS warning and/or unbalances in I/F & Fi should be
evaluated first, to determine the condition of the winding.
2) Motors with alarms in TVS, Fi & I/F as well as inductance and/or impedance
should be evaluated next. It may be necessary to perform a rotor reposition or
rotor compensated test to separate rotor from winding faults. For AC induction
squirrel-cage rotor <1000V and the rotor shaft is accessible the dynamic test
should be performed.
3) Motors exhibiting small Resistance unbalances alone generally have the lowest
priority (If you have company or equipment manufacturer condemning criteria and
procedures then follow their guidance).

Condemning Tips
1) Never condemn a motor from the Motor Control Center. Faults in the cabling or
connections between the test point and the motor itself can cause unbalanced
readings or changes in readings. Before condemning a winding always perform a
confirming test at the motor with the motor leads disconnected from the
supply cabling.
a) To determine whether the fault is in the motor or the cabling retest the
motor at the next connection point between the motor and the starter
or motor drive.

©2015, ALL-TEST Pro, LLC 18 Rev. 08/14/2015


b) A rotor reposition test may be necessary to separate rotor from winding
faults when evaluating the motor using unbalances of Fi and/or I/F
(Refer to the Troubleshooting section of this manual for the Rotor
Reposition Test).
2) Generally, never condemn a motor based just on an unbalanced
inductance or impedance alone (may require additional testing). The Rotor
Bar/Winding Ratio can cause a large unbalance in mutual inductance, as
well as small unbalances in the I/F & Fi readings.
3) Always verify the reading before condemning a motor. Stored energy in a
motor system can corrupt the data set. Remember, it is much easier to
take readings again than it is to remove the motor.
4) Winding shorts are first indicated by unbalances in TVS comparison,
Stator Signature, or unbalances with Current/Frequency response (I/F)
and/or Phase Angle (Fi).
5) Loose connections are indicated by unbalances in winding resistance
measurements.
6) Winding contamination or overheated windings are indicated with the
dissipation factor measurement.
7) Problems of stator or rotor can be separated by performing the dynamic
test, assuming the motor is an AC induction squirrel-cage rotor motor
<1000V. If different motor type then additional testing may be required to
identify the exact problem. Details are provided within this manual.
8) Never condemn a motor if the readings are not repeatable. EMI (induced
voltages from adjacent energized conductors) or the motor shaft turning
will also give inconsistent readings.

Unassembled Motor Analysis

If the rotor is removed from the stator the mutual inductance created by the stator magnetic
field inducing a voltage into the rotor will no longer create an inductance unbalance.
Therefore, the only part of the basic motor circuit that is responding to the injected AC signal
from the instrument is the stator winding and stator iron. Any unbalances caused by rotor
bar/winding ratio error are eliminated. Therefore, the fault criteria are much tighter for motors
tested when the rotor is removed. Below are the tolerances for motors stators only (motors
with the rotor removed).

Note: Experience has proven that these tolerances hold true regardless of the size of the
motor. MCA software alarms are only designed for motor with rotor assembled. For a test
with an unassembled motor, the following is the guideline to get the conclusion.

Test Result Tolerance


Resistance (R) <5%
Impedance (Z) <3%
Inductance (L) <3%
Phase Angle (Fi) +/- 0*
Current frequency Response (I/F) +/- 0*

©2015, ALL-TEST Pro, LLC 19 Rev. 08/14/2015


TVS, Stator & Rotor Signatures Not Applicable
Insulation Resistance See INS section as previously described

This table is only applicable to motors with the rotor removed

*Small variations may be acceptable. I.e. Fi 76.1°, 76.0°, 75.9°

Data Interpretation Basic Rules and Tolerances


There are specific rules that encompass virtually all test applications of three phase
motors in which the motors are assembled and a rotor is installed. The common
method for testing is from an MCC or disconnect with the rotor stationary.

Assembled Motor Analysis

If the rotor is installed in the stator the mutual inductance of the rotor may cause large
inductance unbalances which will result in a large impedance unbalance. The Rotor
Bar/Winding ratio may also cause small unbalances in I/F and Fi.
Note: The guidelins for “BAD” warning of R, Z, L, DF, Fi, I/F and Insulation Resistance also
apply to transformer test and coil test under the DC test menu.

Test Result Tolerance Detail


Resistance (R) <5% Likely loose or faulty connections
Impedance (Z) <5% If random wound <1000V, unbalance might be
and Inductance due to rotor position or motor design. If form
(L) wound then a fault may have occurred.
Dissipation Likely winding contamination or overheated
Factor (DF) >6% windings
Phase Angle +/- 2 digits Indicates a winding short: 74, 75, 76 OK; 74, 74,
(Fi) (degree) from 76 suspect; 73, 73, 76 failed
average
I/F +/- 2 digits (%) Indicates a winding short: -44, -45, -46 OK; -44,
from average -46, -46 suspect; -42, -45, -45 failed
TVS >3% Likely change in condition of the winding or rotor
Dynamic Test Stator: >1.5% Likely stator winding issue
Rotor: >15% Likely rotor issue
Insulation See INS Guide Indicates poor insulation to ground (I.e. ground
Resistance fault)

Resistance (R): Unbalances in resistance are an indicator of loose connections, pitted


contactors, cold solder joints, etc. In some cases the resistance unbalance can be the result
of test lead clip placement. Always retake the resistance measurements if a resistance
unbalance exists. Changes in the resistance measurements with repetitive readings indicate
test lead or test lead connection issues. Attempt to clean the connection location and then
retake the resistance readings. If the readings were taken at the motor control center taking

©2015, ALL-TEST Pro, LLC 20 Rev. 08/14/2015


reading progressively closer to the motor will normally locate the high resistance
connection(s).

Inductance (L) and/or Impedance (Z) Unbalance: When a squirrel cage rotor is installed
in the motor, inductance unbalances are possible, especially with smaller less expensive
motors. If this does occur these unbalances are usually the result of the unbalanced mutual
inductance created by the unequal rotor bar/winding ratios resulting from rotor position. To
verify that this unbalance is the result of the rotor position, the rotor reposition test should be
performed (See section on Rotor reposition test).

Dissipation Factor (DF): Dissipation factor is used to indicate the capacitive property of the
insulation materials used in the motor. When the insulation degrades over time and
becomes less resistive due to the contamination or overheating, the dissipation factor will
increase. Along with dissipation factor, capacitance is measured which can help trend the
insulation property changes in the long term. As DF and capacitance are directly related to
one another, when either one returns an invalid test result, e.g. out of range, then it means
the other test result is not valid either.

IRG – Insulation Resistance to Ground: IRG is the most common electrical test
performed on electrical systems to test the insulations capability to withstand voltage. The
IRG test is performed by applying a high dc voltage between de-energized current-carrying
conductors and the machine casing or earth. The insulation resistance value is proportional
to the insulation material thickness and inversely to the conductor surface area. In addition,
the physical and chemical properties of the insulation materials play a critical role in terms of
resistance, for example, resistivity of the insulation, void distribution inside the material,
resistance to being oxidized and thermal expansion/shrink all play important roles in overall
insulation resistance and the capability of the insulation system to withstand voltage.

Phase Angle (Fi): The amount of lag between the applied voltage and the resulting current
in the basic motor circuit is one of the most sensitive of measurements used to detect
winding faults in the motor circuit. Fi is usually one of the first measurements to change
when the insulation system degrades (Winding short). Unbalances of >1 degree from the
average indicate a winding short. The Fi readings should be ≥ 15° and < 90°.

Current Frequency Response (I/F): Degraded winding insulation systems respond


differently at different frequencies. The I/F measurement are also one of the first indications
of winding system degradation. The I/F readings should be between -15 to -50. All I/F
reading should be balanced within 2 digits (percent). Unbalances of >2 digits from the
average indicate winding shorts. A spread of >4 digits between maximum and minimum I/F
measurements, also indicates winding faults. These readings are for non-compensated rotor
position at the motor. However, if a winding fault is indicated additional testing may be
necessary to verify the winding fault.

TVS (Test Value Static): Makes measurements on all three phases and calculates a “Test
Value Static”, which when compared to a baseline “Reference Value Static”, becomes a
powerful combined fault indicator for Rotor and Stator faults. The “Reference Value Static” is
normally saved from the first time the motor is tested (a baseline test) or can be saved from

©2015, ALL-TEST Pro, LLC 21 Rev. 08/14/2015


a known good motor of the exact same motor type (manufacturer, model, manufacturing
tolerances, ect.).

Dynamic Test (Test Signature): Measures, in real time during manual rotation, a number
of values in all three phases which together forms the “Test Signature” for the rotor and
stator. The "Test Signature” is then automatically analyzed in the AT5/AT33 and gives the
user immediate results for Stator and Rotor status. The “Test Signature” can also be
uploaded to the MCA software and evaluated further.

Analyzing Measurements and Change


Data interpretation of collected AT33 or AT5 data can be performed through the MCA
software.

Troubleshooting Rules

Following are the basic rules for troubleshooting with the AT33 and AT5:

Shorted Windings:

Developing windings faults, as well as shorted windings, are evaluated by viewing the TVS
as well as Fi and I/F readings of similar coils or between phases:

Dynamic Test (Stator Signature) – Experience show that the stator signature is
more sensitive in detecting the problem with the stator. This proprietary and patented
method provides WARN or BAD warnings once winding faults exist in stator
windings. Moreover, as the Dynamic test also evaluates the rotor we recommend
that this test is done as a final confirming test before condemning a motor. Assuming
of course, the motor is an AC induction squirrel-cage rotor motor <1000V.

Test Value Static (TVS) – When a new TVS value is compared to the Reference
TVS acquired previously, if the difference is greater than 3% then it’s most likely that
a winding fault has occurred (rotor fault can also cause a change in TVS). A Warning
limit of >1.5% may be appropriate for form wound squirrel-cage rotor motors. A
narrower limit can be determined by static testing the motor in several different rotor
positions. I.e. if TVS varies <1% in multiple rotor positions then a more narrow alarm
may be appropriate.

Phase Angle (Fi) – The maximum phase angle difference between any two phases
should be within 2 digit of the average reading. For example, a reading of 76/75/76
would be good because the maximum difference is 1. A reading of 77/75/76 would
be bad.

Current Frequency Response (I/F) – The maximum difference of the current


frequency response between any two phases should be within 2 digits. For example,
a reading of –45/-45/-46 would be good. A reading of -44/-45/-46 would be bad.

©2015, ALL-TEST Pro, LLC 22 Rev. 08/14/2015


In certain cases, if only TVS provides warning while phase angle and/or I/F are “Green”, or if
TVS is “Green” while phase angle and/or I/F are in alarm, it is suggested to do the following:

1) If AC induction squirrel-cage rotor motor <1000V perform the Dynamic test.


2) If AC induction above 1000V then perform a rotor compensated winding test to
determine if the stator winding has a fault.

As the dynamic test result can be sensitive to the specific operation, i.e. how the rotor shaft
is rotated, in case of a warning is provided, the user should check the dynamic test result
immediately on the instrument display by pressing “Stator” or “Rotor”. A valid dynamic test
always comes with solid lines of stator signature with rotor signature data distributed above
and below the line. When any “strange” test results show up, for example, the image below
shows an example that looks like the 1st phase test is OK while the other two tests are not
valid. The reasons that this happens include:
1) Rotor shaft is rotated at significantly different speed, for example, the rotation
changes abrupt from slow to fast or from fast to slow.
2) The shaft is turned at uniform speed; however, it is not the right speed for testing a
particular motor. Therefore, the user needs to try several different speeds to
determine the best speed appropriate for testing.
3) Due to certain time constant issue, the instrument cannot respond timely and
correctly on the signals reflected back from the object under test.

In some situations when the rotor is rotating too fast, the instrument may display the
message that disconnection is happening and stops working. In such case, the user needs
to turn the shaft at relatively uniform speed. If it still happens, then the speed needs to be
reduced.

If the dynamic test produces a warning, the user should try multiple times at different speed
to see if the warning results from rotation error. If the user can get good results with one
dynamic test then likely the motor is good. To study it further, it is suggested to perform a
detailed rotor test assuming the user has already confirm the stator is in good condition, or
best to apply energized ESA test which is the most reliable means to detect rotor problems.

Winding Contamination Dissipation factor is the major indication of winding contamination.


DF measurement over 10% indicates a serious contamination issue. Sometimes high
contamination can also point to a low insulation resistance to ground measurement.

Rotor Reposition Test To verify that the Impedance (Z) and/or Inductance (L) unbalance is
the result of rotor bar/winding ratio unbalances it is necessary to evaluate the relationship of

©2015, ALL-TEST Pro, LLC 23 Rev. 08/14/2015


the Z & L unbalances. If the unbalances are related to the rotor, they will change relationship
by changing the position of the rotor.For example, if there are inductances of 17/18/19 and
values of impedances are 24/26/29 with the rotor at its existing position. Then rotate the
shaft approximately 90 degrees (1/4 turn) the values should change relationship, such as
inductances of 16/19/17 and impedance values of 23/30/25. This indicates that the
unbalances are due to rotor position.

Insulation Resistance The insulation resistance (Meg-Ohm reading) will show a breakdown
of insulation between the winding conductors and ground. According to IEEE Std. 43, the
insulation resistance is measured after applying DC high voltage for 1 minute. The motor
should be above dew point temperature before testing if possible. It is important to correct
values to a reference temperature (typically 40 °C) so that trends and changes in insulation
resistance can be readily detected. Contamination, humidity, temperature, and other factors
affect insulation resistance values. The standard recommends choosing these test voltages
for insulation resistance testing:

The AT5 and AT33 instruments offer two voltages: 500V and 1kV. For windings rated
over 5kV, an instrument capable of producing a higher test voltage will be needed
according to the guidelines above.

The standard also recommends minimum insulation resistance value at 40oC as shown
below. “kV” is the rated line-to-line RMS voltage of 3-phase motor, line to ground
voltage of single phase motor, or rated DC motor voltage.

©2015, ALL-TEST Pro, LLC 24 Rev. 08/14/2015


Note: The IEEE guidelines above provide the recommended voltages and minimum Insulation
Resistance to ground values. If these procedures or values differ from your equipment
manufactures’ recommendations, follow their guideline. AT5 and AT33 adopt different insulation
resistance diagnostic rules. Please refer to the user manuals, respectively.

Loose Connections Loose connections or glazing on contacts will show as resistance


unbalances. The maximum resistance unbalance should be 5%.

Predictive Maintenance
As early as the 1960’s, many companies realized that by routinely monitoring the
operating condition of rotating equipment it is possible to obtain an advanced warning of
operational or other problems that would impact continued efficient operation. This early
warning provides time to remove the machine from operation and affect minor repairs
and adjustments before catastrophic failures occur.

This maintenance philosophy, referred to as Predictive Maintenance (PdM), has


escalated since the early 1980’s, with the introduction of microprocessor based data-
collectors. Many of the machines’ operating characteristics, such as temperature,
pressure, oil condition, vibration and performance can be trended to identify changes.
However, one of the glaring holes in predictive maintenance has been the inability to
easily & accurately identify faults within electrical equipment, such as motors,
transformers, solenoids and other like equipment. One of the main reasons for this was
the lack of available easy-to-use predictive maintenance instruments for testing motors
or other electrical equipment.

Predictive maintenance instruments should be:


 Hand-Held
 Easy to use
 Provide output in Conventional Units

Implementing Predictive Maintenance


Implementing a successful predictive maintenance program requires more than
purchasing an instrument and taking data. Predictive maintenance programs when
successfully implemented require a complete understanding of the PdM process.

Successful predictive maintenance consists of three phases - Detection, Analysis and


Correction. Each one of these phases is important in its own aspect. Problems are
created when short cuts are taken and phases are skipped or combined.

Detection The detection phase involves periodically monitoring the operating


characteristics of the selected equipment. These values are trended, compared
to previously recorded data from that machine or similar machines, then
compared against pre-determined or published standards and/or reviewed for
any change.

©2015, ALL-TEST Pro, LLC 25 Rev. 08/14/2015


During the detection phase, the data collection process should be done
quickly and carefully, with the intent of monitoring as many machines as
possible. When a change is detected, additional data may be necessary, to
determine the cause of the machine’s condition change. This is done during the
analysis phase.

In most cases, the MCA data taken during the detection phase may be sufficient
to identify developing shorts or other winding issues. But at times, additional data
or testing needs to be performed to more accurately identify the problem.

It is usually a waste of time to perform these tests for a more detailed analysis
during the detection process, as it slows down the detection process. Most
experienced predictive maintenance departments have recognized the
importance of separating these two processes.

Analysis The analysis process involves taking additional and perhaps different
types of tests than the detection process. This additional testing may require
disconnecting the motor from the load, turning the shaft or separating the motor
leads and requires more time to take the data. Since usually only a few machines
during the detection inspection exhibit any significant change, it is usually more
time effective to only take the data necessary to identify a change during the
detection process, and then go back for a more detailed look once a change is
detected.

However, if the plant site is remote or has other access limitations, these may
justify more detailed data be taken during the detection process.

Correction The correction phase involves correcting and eliminating the problem
that triggered the analysis. This may require cleaning a motor, tightening
connections, or a complete motor rewind. The exact type of correction and
repairs are determined by the analysis. Details for correcting and eliminating
these problems are outside the scope of this manual.

Predictive Maintenance Hints


The following recommendations are from over 30 years experience with MCA using the
ALL-TEST Pro line of motor testers. It should be remembered that these are
recommendations only and are designed as suggestions to provide for the optimum
program. It may not be possible to implement each and every suggestion in all
applications:
1) When performing Predictive Maintenance (PdM) on three phase induction
squirrel-cage rotor electric motors, comparison of a new TVS to a REF TVS is
the preferred method to detect changes in the condition of the stator. If a TVS
REF is not available then evaluating the unbalance of Fi and I/F is desired.
However, if a non-form wound motor and specific to analysis of Fi and I/F, it is
desirable to try and place the rotor in the same position each time (I.e. Place
the shaft key at the 12 o’clock position) as this will minimize changes from

©2015, ALL-TEST Pro, LLC 26 Rev. 08/14/2015


data collection to data collection due to rotor position (Specific to evaluation
using unbalances of Fi and/or I/F you may want to use AT31 in conjunction
with the AT5 to perform a rotor compensated test).

2) Specific to evaluation using unbalances of Fi and/or I/F when the initial test is
performed, if variations in the inductance measurements >5% between
phases, perform a rotor reposition test in order to determine if the variation is
due to the rotor bar/winding ratio or if there is a rotor fault. These variations
may be normal or the unbalance may be due to rotor position. Review the
rotor position section of this manual for further clarification.
3) The upper limit of equipment size that can be successfully tested is primarily
dependent on the DC resistance and impedance of the windings. For best
accuracy the winding’s DC resistance needs to be between 0.01 and 999
ohm in each phase. The windings capacitance & inductance, plus cable
length can also impact the range of equipment that can be tested.
Additionally, with large machines separating coils and testing individually can
improve detection accuracy.
4) Always mark your motor leads and collect data in the same order so that
MCA software records and analyzes the data in the same order. Establish a
pattern when numbering the leads for example left to right, front to back, or
top to bottom. This also provides consistency in readings.

This consistency also helps identify in which phase the fault occurred, i.e. if an increase
in resistance in 1-2 and 1-3 occurs, then you should check the phase 1 connections.

Data Collection and Test Result Issues


There are issues inherent with faulty motors and with data collection process of motors
in an industrial environment. Following are some of those issues when collecting data
with the AT5/AT33 and their resolution:

Bad Results Including Non-Repeatable Measurements

EMI (Electro-Magnetic Induction) can cause problems with test results. This usually only
occurs when testing from the MCC. EMI can come from heavily loaded cables located
directly next to the cables from the motor that is being tested. The values are normally
in the milli-Volt range and not always detectable with a multi-meter or voltmeter. Use the
EMI feature of the AT31 to measure the EMI level. If the EMI cannot be removed then
the motor must be tested directly at the motor connection point.

Motor Rotor Turning. If the shaft in the machine being tested is rotating, it will induce a
voltage into the basic motor circuit. This will affect all of the readings.

Note: To determine whether the bad result is caused by EMI or rotating shaft, use the
Rotor feature of the AT31. If the shaft is rotating the bar graph on the screen will move

©2015, ALL-TEST Pro, LLC 27 Rev. 08/14/2015


back and forth across the display screen of the AT31. If the bar graph moves erratically
across the screen check the EMI level using the EMI feature of the AT31.

No Connection (Beeping) In case of an open circuit, AT5/AT33 will start beeping. Test
closer to the motor to find the open circuit. The open circuit may be in the test leads. Check
them for continuity.

Capacitors or Lightening Arrestors in the motor circuit will filter the test results and create
incorrect readings which can provide false positives or false negative results. Always
disconnect any capacitors or lightening arrestors connected to the motor circuit.

Non-Repeatable Resistance Measurements EMI interference will cause non-repeatable


resistance values (see Bad Results above). Contamination in the motor or cabling can
cause non-repeatable resistance readings. So can carbon buildup or heavy contamination in
cabling. Disconnect the motor leads at the motor connection box and retest. Poor
connections at the test clips will normally affect the resistance only, but it may affect other
readings also, depending upon severity. If a resistance unbalance exists from the MCC
always retake readings directly at the motor with incoming phase leads disconnected before
condemning the motor (as the source of the unbalance). If resistance phase measurements
are repeatable from one test to another the resistance unbalance is most likely in the motor
or cabling. If resistance measurements do change from one test to another the fault is most
likely the result of poor connections at the test leads. Clean the connections thoroughly until
repeatable readings are obtained.

Servo-motors & Machine tool Motors Some machine tool and servo-motors have
permanent magnet rotors which may affect the I/F & Fi measurements. The I/F & Fi
readings will be repeatable but outside standard tolerances. Testing permanent magnet
rotors may require special procedures (See Appendix 4). Trending the differences in the
highest and lowest I/F & Fi readings will provide additional indication of winding degradation.
Rotor faults can also cause the difference between the I/F & Fi readings to increase, it is
suggested that a rotor reposition test be performed to verify a rotor fault.

Synchronous Motor Testing Synchronous motors windings will also test for shorts in the
rotor windings. If the Auto test indicates winding shorts, the short could be either in the stator
or in the rotor windings. To determine which winding is shorted rotate the shaft
approximately 900 and retake the readings (large multiple-pole synchronous motors may
only require that the shaft be moved a small distance- 5°). If the fault remains in the same
phase as the original test the short is most likely in the stator winding. If the fault shifts to
another phase the fault is most likely in the rotor. The synchronous motor rotor winding are a
single winding, evaluating them is done by trending or comparing current reading to a
baseline. Large salient-pole synchronous motors may require special testing considerations.
See the addendum found later in this manual or contact our technical support team for
further information.

©2015, ALL-TEST Pro, LLC 28 Rev. 08/14/2015


Transformers Testing transformers can identify winding shorts, high resistance
connections, open windings, and insulation to ground fault detection; as well as internal
circuit impedance unbalance. By using MCA you can compare readings to similar windings
or transformers and look at variations and patterns between phases. Testing different types
of transformers may require a special procedure (See Appendix 2:).

Wound Rotor Motor Testing wound rotor induction motors will also identify shorts in the
rotor windings. If the Auto test indicates winding shorts, the shorts could be either in the
stator or in the rotor windings. The windings of a wound rotor motor are tested using the slip
rings. The same tolerances apply to the 3 phase rotor windings as to the stator. If the rotor
tests good, the fault is in the stator.

Data Trending

Trending test data collected over a period of time is another powerful tool for predictive
maintenance. To perform the trending analysis in MCA, a minimum of 2 data points is
required. And the comparison is performed between the first test data and the baseline.
The trending analysis depends on the baseline the user has chosen. By default, the
baseline is the earliest test data which is located on the top of the data group and marked
with “B”. The user can use up or down arrow to choose the baseline they prefer.

Note: the trending curves displayed on MCA software may not be the values for alarm
calculations.

©2015, ALL-TEST Pro, LLC 29 Rev. 08/14/2015


Trending Analysis for 3 Phase AC Motor and Individual Coil Test
Test Alarm Troubleshooting Detail
Result Limit

Resistance 5% Check for loose connection. For each test data, find
(R) the maximum
difference between
each phase and the
average value. Then
compare the ratio
difference.

Impedance 5% Special care should be taken before For each test data, find
(Z) condemning a motor only due to Z unbalance. the maximum
difference between
each phase and the
average value. Then
compare the ratio
difference.

Inductance 5% Special care should be taken before For each test data, find
(L) condemning a motor only due to L unbalance. the maximum
difference between
each phase and the
average value. Then
compare the ratio
difference.

Phase 2o If L or Z unbalance is >5% then perform rotor First find the maximum
Angle (Fi) compensated winding test to confirm the difference between any
issue. If AC induction squirrel-cage rotor two phases for each
motor <1000V then perform the Dynamic test. test data. Then
compare the difference.

I/F 2% If L or Z unbalance is >5% then perform rotor First find the maximum
compensated winding test to confirm the difference between any
issue. If AC induction squirrel-cage rotor two phases for each
motor <1000V then perform the Dynamic test. test data. Then
compare the difference.

©2015, ALL-TEST Pro, LLC 30 Rev. 08/14/2015


TVS 5% Either stator or rotor may have a problem. If Change in percentage
AC induction squirrel-cage rotor motor of the latest data over
<1000V then perform the Dynamic test to the baseline
determine cause for this change. If >1000V
induction squirrel-cage rotor then follow
testing procedures for winding and rotor
analysis.

Dissipation 10% Contaminated or overheated windings. The latest test data is


Factor analyzed.
(DF)

Insulation 5 MΩ Grounded windings. The latest test data is


Resistance analyzed.

Trending Analysis for DC and 1 Phase AC Motor

Test Result Alarm Troubleshooting Detail


Limit

Resistance 5% Check for loose connection. For each winding, the


(R) relative change of the
latest data over the
baseline.

Impedance 5% Non-repeatable measurements when For each winding, the


(Z) testing armature circuit can indicate relative change of the
excessive carbon dust buildup. latest data over the
baseline.

Inductance 5% Non-repeatable measurements when For each winding, the


(L) testing armature circuit can indicate relative change of the
excessive carbon dust buildup. latest data over the
baseline.

Phase Angle 2o Potential Winding faults. For each winding, the


(Fi) absolute change of the
latest data over the
baseline.

I/F 2% Potential Winding faults. For each winding, the


absolute change of the
latest data over the
baseline.

Dissipation 10% Contaminated or overheated windings. The latest test data is


Factor (DF) analyzed.

Insulation 5 MΩ Grounded windings. The latest test data is


Resistance analyzed.

©2015, ALL-TEST Pro, LLC 31 Rev. 08/14/2015


Troubleshooting Motors

Rotor Compensated Test


When there is an alarm from TVS, phase angle or I/F, and the motor is an AC
induction squirrel-cage rotor <1000V then perform the Dynamic test. On other types
of equipment and Z or L unbalance is >5% then to determine if change relates to the
winding and not rotor position we suggest a rotor compensated test be performed.
This requires both an AT31 (or an instrument that measures in real-time inductance
or impedance) and an AT5 instrument.
1) Find rotor positions of maximum impedance corresponding to every two
phases.
a) Connect the AT31 to two phases, e.g. Phase 32, then turn shaft
until the maximum impedance value is obtained.
b) Mark the rotor position.
c) In the same way, mark the rotor positions for Phase 21 and Phase
13 where maximum impedance occurs.
2) Start Z/ menu test. Skip the DF/C test and insulation test. The yellow test
lead is not connected.
3) Go directly to the 3-phase static test.
4) Ignore the instructions on the instrument display. Instead, do the following:
a) Connect Kelvin test leads 32 from AT5 to the Phase 3 and Phase 2
terminals on the motor.
b) Leave Test lead 1open. I.e. not connected.
c) Turn the rotor to the marked position of maximum impedance for
Phase 32.
d) After the measurement of Phase 32, AT5 will start beeping due to
test lead 1 not connected.
e) Ignore the beeping; turn the rotor to the position of maximum
impedance for Phase 21. Keep test lead 2 connected, disconnect
test lead 3 (do not connect it to anything), connect test lead 1.
f) AT5 stops beeping and starts the measurement. Once it’s
completed, AT5 will start beeping again.
g) Ignore the beeping; turn the rotor to the position of maximum
impedance for Phase 13. Keep test lead 1 connected, disconnect
test lead 2 (do not connect it to anything), and connect test lead 3.
h) AT5 stops beeping and starts the measurement.
i) Then the rotor compensated test is completed. Save the test
results.
j) Run MCA software to upload the test data and perform the 3 Phase
AC individual analysis. If no Yellow or Red alarm is indicated for the
parameters of impedance, inductance, phase angle and I/F, it
means the motor is in good condition.
Note: the time interval between every two measurements (the time AT5 keeps
beeping) should be limited to less than 5 minutes.

©2015, ALL-TEST Pro, LLC 32 Rev. 08/14/2015


Rotor Reposition Test
Using the AT5 instrument Z/ test menu, a short series of tests may be performed in
order to determine whether the unbalanced readings are due to the rotor or to the stator
design. The steps are simple:
1) Note the position of the rotor after saving the original readings. Slightly rotate the
shaft about 10 degrees from its original position and remeasure the motor
windings with the connections as they were originally taken.
2) Reference the previous reading and note if the unbalance has shifted with the
rotor movement. If it has or if the readings are inconclusive, retake the
measurements at 90 or 180 degrees from the present position.
3) If the readings remain unbalanced in the original position, the stator windings are
most likely faulted; if the readings shift with the rotor position, perform a rotor test
as outlined in the motor troubleshooting guide.

Shifting Readings Example


T1-T2 T1-T3 T2-T3
Impedance 0 o 47 53 58
Inductance 0o 9 10 11
Impedance 10 o 53 58 47
Inductance 10 o 10 11 9
Impedance 10o+90o 58 47 53
Inductance 10o+90o 11 9 10
Note: The readings will not be exact, this is just an example

Maintained Readings Example


T1-T2 T1-T3 T2-T3
Impedance 0 o 47 53 58
Inductance 0 o 9 10 11
Impedance 10 o 47 53 58
Inductance 10o 9 10 11
o
Impedance 10 +90 o 47 53 58
o
Inductance 10 +90 o 9 10 11
Note: The readings will not be exact, this is just an example
Rotor Test
One of the important features of the AT5 is the ability to perform a complex analysis of a
three phase motor rotor.

Note: If AC induction squirrel-cage rotor motor <1000V then evaluate the condition of
the rotor using the Dynamic test mode.
Rotor test is only performed for a 3 Phase AC induction with squirrel-cage rotor motor
>1000V after stator is determined to be fault-free. The rotor test is also a detailed
study for the rotor issues after the dynamic test reveals possible rotor problems. For
motors with 4 poles or less, inductance measurements for 3 phases are collected at

©2015, ALL-TEST Pro, LLC 33 Rev. 08/14/2015


a minimum of 48 different positions for one complete rotation (360°). In other words,
one test has to be performed for every 7.5o of rotation. For motors with 6 poles or
more, a minimum of 72 tests must be performed, i.e. one test every 5o.
Note: if the motor can be run coupled to a load then Electrical Signature Analysis
(ESA) using the ALL-TEST PRO On-Line II TM instrument is the best means of
analyzing the rotor when testing squirrel-cage rotor AC induction motors of any
voltage.
To precisely determine every test position, an angle gauge can be attached to the
rotor to determine each rotation angle step. Or the users can find polar graph chart
online and print it and attach it to the motor frame with rotor shaft going through the
center. An example is provided at the end of this section.

Rotor Test steps


1) Select Rotor Test option, then connect the three test leads to the motor’s three
phases

2) The instrument starts the measurement, then will show the frequency determined.
The user can choose this frequency or select another frequency at their
discretion.

Note: the frequency can be changed during the testing process. However, the same
frequency should be used for all phases and positions.
3) Each time, the test is performed on three phases the results are displayed as
shown below.
a) When the rotor is turned to the next position, press the “REMEASURE”
and it will perform another measurement. The results of each
measurement must be hand recorded and then entered into the
optional MCA PRO software or into some other spreadsheet
application (Microsoft Excel or similar).
b) To change frequency, choose “fHz”, highlight the desired frequency,
then press “OK” key.

©2015, ALL-TEST Pro, LLC 34 Rev. 08/14/2015


c) When all rotor tests are completed, choose “EXIT”.

NOTE: The more accurate the positioning of the rotor the more accurate the
analysis will be. It is recommended to attach a rotating protractor or use a piece of
circular graph paper attached to the shaft to provide maximum accuracy.
4) When a complete set of data has been taken the results should be graphed
using the Rotor Test feature either of the MCA PRO software or by using
some other spreadsheet or graphics program such as Microsoft Excel.
Analysis
1) The readings will not be identical but should result in a repeating pattern as
the shaft is rotated. If the pattern varies, there is rotor, casting, or air gap
problems.
2) Rotor and casting problems show as a sudden change in one location on the
motor while air gap problems change consistently around the rotor.
3) The resulting waveforms should be even and 120 degrees out of phase from
each other. There are a number of cases where these readings will deviate:
a) Large deviations at the peak or valley of at least one waveform will
identify high resistant points in copper rotor bars, possibly where
the bar is welded to the shorting ring.
b) Similar deviations will indicate broken rotor bars or in small
inexpensive aluminum rotors, the rotor laminations may not be set
properly, leaving variations in the resistance of each rotor bar (low
quality motor).
c) A more common problem in many electric motors (some
manufacturers have more challenges than others) is casting voids.
This is usually found as a flat point at the incline or decline on at
least two of three sine waves.
d) Eccentric rotor problems are normally found when the inductance
tapers off or the waveform moves higher or lower (arcs from right to
left).

In addition to the internal analysis, the MCA also requires users’ input to help make
accurate diagnostic conclusions. A table listing common rotor problems is provided in
the optional MCA PRO software, which is listed below.

©2015, ALL-TEST Pro, LLC 35 Rev. 08/14/2015


Examples of Different Inductance Waveforms for Rotor Analysis
3.5
3.4
3.3
3.2
3.1 Series1
3 Series2
2.9 Series3
2.8
2.7
2.6
Good Rotor - curves need to be symmetrical but not
Bad
1 3 5 Rotor
7 9 11 13Example
2.5

necessarily "perfect" sine waves. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71

large
deviation

Bad Rotor Example Bad Rotor Example


1.4
1.35
1.3
1.25
1.2 T1
1.15 T2
1.1 T3
1.05
1
0.95
Bad Rotor Example 0.9 Bad Rotor Example
12 1 2 3 4 5 6 7 8 9 10 11

Bad Rotor Example Bad Rotor Example

©2015, ALL-TEST Pro, LLC 36 Rev. 08/14/2015


A Sample of Polar graph

©2015, ALL-TEST Pro, LLC 37 Rev. 08/14/2015


Appendix 1:
Different Test Scenarios
Over 30 years experience in conducting motor testing using MCA has identified these
common scenarios. The section below provides a sample display and brief write up of each
scenario.

Scenario 1: A good motor test results

This is a typical complete test performed by AT33 or AT5 IND test mode for a 3 Phase AC
induction motor with squirrel-cage rotor <1000V. Both static tests and dynamic tests show
“OK” in green.

©2015, ALL-TEST Pro, LLC 38 Rev. 08/14/2015


An example of a good motor tested by AT5 Z/ mode is shown below.

©2015, ALL-TEST Pro, LLC 39 Rev. 08/14/2015


Scenario 2: Unbalance in Impedance and Inductance

A complete AT5 Z/ test mode shows all parameters are balanced except impedance and
inductance. Never draw any conclusion simply based on inductance and/or impedance
unbalance alone. In such case, a rotor compensation test is needed to determine if the
unbalance is due to influence from rotor.

©2015, ALL-TEST Pro, LLC 40 Rev. 08/14/2015


Rotor Compensation Test Result for Good Windings

The rotor compensation test results show the impedance and inductance are well balanced.
Therefore, it is confirmed the unbalance comes from the rotor influence. Note: for rotor
compensation test procedures, please refer to AT5 user manual.

©2015, ALL-TEST Pro, LLC 41 Rev. 08/14/2015


Scenario 3: Shorted winding AT33 or AT5 IND Test

With the AT33 or the AT5 IND test mode, the fact that one of the stator signature lines is
significantly higher than the other two signatures means the problems are with the stator
windings. At the same time, the TVS shows 7.6% deviation from the original reference TVS
value, which is also an indication of the shorted winding.

©2015, ALL-TEST Pro, LLC 42 Rev. 08/14/2015


AT5 Z/ Test

In a similar situation, a full AT5 Z/ test shows unbalance in Phase Angle and I/F.

©2015, ALL-TEST Pro, LLC 43 Rev. 08/14/2015


If only the Z/ test mode is performed and alarm is provided by Phase Angle and/or I/F, then
a rotor compensation test is required. The test above shows the results which confirms the
winding is shorted since a rotor compensation test also provides the alarm, i.e. the
unbalance in Phase Angle and/or I/F is not due to rotor influence only, but largely from
problematic stator windings.

©2015, ALL-TEST Pro, LLC 44 Rev. 08/14/2015


Scenario 4: Grounded Winding while all other parameters are OK

An example of grounded winding test using the AT5 Z/ test mode. Note: The insulation test
diagnostic rule is different between the AT5 and AT33. The insulation resistance diagnostic
rule provided in this manual is for AT5. If you are using an AT33 please refer to the user
manual for details.

Note: if the user has different insulation resistance test equipment, the measurements and
diagnostics can be manually input by clicking on “Manual Values” in the MCA software,
which will override the instrument test results.

©2015, ALL-TEST Pro, LLC 45 Rev. 08/14/2015


Scenario 5: Low Insulation Resistance and High Dissipation Factor

Low insulation resistance combined with high dissipation factor is a strong indicator of the
seriously degraded winding insulation.

©2015, ALL-TEST Pro, LLC 46 Rev. 08/14/2015


Scenario 6: Resistance Unbalance

A typical case of resistance unbalance resulting from loose connection which lies in Phase 3
and causes the increase in resistance when measuring Phase 3-2 and Phase 1-3.

©2015, ALL-TEST Pro, LLC 47 Rev. 08/14/2015


Scenario 7: Rotor Test

There are two steps for rotor test analysis: the user’s input and the analysis performed by
the software. The example above shows the case that the user believes the motor is good
while the analysis shows there is a likely rotor faults because the three curves are not
symmetrical.

Above is a rotor test example that both the user and the software analysis show the rotor
fault exist.

©2015, ALL-TEST Pro, LLC 48 Rev. 08/14/2015


Scenario 8: DC test and Trending

A direct test on a DC series motor. The individual diagnostic are only performed on the
insulation resistance and contamination since the theory of phase balance does not apply to
DC motor. A useful tool for DC motor diagnostics is the trending, as shown below.

The trending of the armature shows alarms due to the significant increase of impedance and
inductance trended over time.

©2015, ALL-TEST Pro, LLC 49 Rev. 08/14/2015


Appendix 2:
Single and Three Phase Transformer Testing; Using Static Motor Circuit Analysis
Techniques
Howard W. Penrose, Ph.D

Introduction

Field and shop testing of pole and pad mount transmission and distribution (T&D)
transformers can be costly and time consuming. With the onset of utility generation
deregulation across the country, T&D becomes a greater issue due to varying power demands
and power quality. A simple test method for quickly and accurately testing the condition of
T&D equipment is a necessity as, if a transformer fails, both the end user and generating
facility will complain. Through the use of an existing technology, originally designed for motor
winding testing, an initial transformer evaluation can be performed.

For conceptual reasons, consider that an AC induction electric motor is a transformer with a
rotating secondary. In this way, the capabilities that static Motor Circuit Analysis (MCA)
provides an electric motor can be extended to a transformer. These include detecting winding
shorts, high resistance connections, open windings and insulation to ground fault detection as
well as preliminary internal circuit impedance balance. Specific information on the transformer
is not required for most applications of MCA because the test equipment is used as a winding
comparator.

An MCA device which provides readings of resistance, impedance, inductance, phase


angle and a special test called current/frequency response (I/F) has been applied to
transformers, for the purposes of this paper. Because the test method is off-line, the MCA
device generates its own voltage and frequency output. Therefore, the ALL-TEST IV
PROTM motor circuit analyzer (ATIV) was selected (Editor- ALL-TEST PRO 5 is the
recommended replacement for the ATIV). This unit weighs less than 2 lbs, is handheld,
and has a proven track record with AC/DC motors and generators from fractional to over
10 MW.

The first set of transformers tested included pole and pad mount transmission and
distribution transformers from a few kVA to over 2500 kVA with primary voltage ratings of
480 Volts to 28.8kV. Following initial testing and analysis, procedures were developed to
allow for general testing of any type of pole and pad mount transformer with a simple
resistance greater than 0.001 Ohms. The results included the capability of testing the
primary and secondary of any type of transformer in about 5 to 10 minutes with a greater
than 99% success rate on either wet or dry-type transformers.

©2015, ALL-TEST Pro, LLC 50 Rev. 08/14/2015


Basic Transformer Concepts

To understand the basic concepts of a transformer, we shall start with an “ideal transformer,”
or a theoretical transformer that has no losses. The purpose of the transformer is to convert
one level of voltage and current to another level of voltage and current for distribution and
application purposes. This is achieved by having a primary winding located close to
secondary winding and allowing for mutual induction to occur between the windings.

When a sine-wave voltage is applied to the primary windings a magnetic field is established
that expands and contracts based upon the applied frequency. This field interacts with the
secondary winding producing a voltage within the secondary that is directly proportional to the
turns ratio, while current is inversely proportional to the turn’s ratio.

Equation 1: Voltage Turns Ratio

N1 / N2 = a

Where N1 is the number of turns in the primary and N2 is the number of turns in the
secondary

Equation 2: Current Turns Ratio

N2 / N1 = 1/a

For example, an ideal transformer with 100 turns in the primary and 50 turns in the secondary,
with 480 Volts applied to the primary and a 100 amp load on the secondary would have: a
voltage turn ratio of 2; a current turn ratio of ½; a 480 V1, 50 A1 load reflected on the primary
and a 240 V2, 100 A2 load on the secondary.

Equation 3: Load Impedance

ZL = V2 / I2

Equation 4: Equivalent Primary Impedance

Z1L = a2ZL

Equations 3 and 4 can be used to reference the impedance from the secondary to primary.
This can also be used inversely. Internal impedance can be matched to load impedance as
found in Equation 5.

Equation 5: Internal Impedance

ZS = a2ZL = Z1L

In a “real transformer” there are certain losses, including core losses (hysteresis and eddy-
currents), the magnetizing current, and leakage. In addition, supply voltage and load currents
may have harmonic loads and other issues that would impact the effectiveness of a

©2015, ALL-TEST Pro, LLC 51 Rev. 08/14/2015


transformer. The purpose of static MCA is to reduce or eliminate these issues to isolate
transformer testing.

Transformer Types and Connections

Transformers of both single and three phase have a variety of connection types for a variety
of loads. In a three-phase circuit, these connections are: Wye-Delta; Delta-Wye; Delta-Delta;
and Wye-Wye. Single-phase, pole mounted transformers normally have a single-winding
primary with a two-winding or center-tapped secondary.

Three phase transformer connections are developed for a variety of applications:

1. Delta-Delta: Lighting and power applications, normally used when power loads are
greater than lighting loads.
2. Open-Delta: Lighting and power applications, used when lighting loads are greater
than power loads.
3. Wye-Delta: Power applications, used when stepping power up in voltage (i.e.: 2400 to
4160 Volts).
4. Wye-Delta: Lighting and power applications.
5. Open Wye-Delta: Will allow 57% capacity if one phase is disabled.
6. Delta-Wye: Normally provides a 4-wire on the secondary which allows for balanced
single-phase loads between neutral and each phase.

Figure 1: Delta-Delta Transformer

H1 I aI X1

V I/√3 V/a

H2 X2
H3
X3

©2015, ALL-TEST Pro, LLC 52 Rev. 08/14/2015


Three phase transformer connections are labeled H1, H2, and H3 on the primary and X1, X2,
X3, with X0 as the neutral, on the secondary.

Figure 2: Delta-Wye Transformer

I aI/√3
H1 X1
X2

V X0

V/a √3V/a

H2 X3
H3

Figure 3: Wye-Delta Transformer

I √3aI
H1 X1
H2

H0 V/√3a

V V/√3

H3 X2
X3

Figure 4: Wye-Wye Transformer

I aI
H1 X1
H2 X2

H0 X0

V V/√3 V/√3a V/a

H3 X3

©2015, ALL-TEST Pro, LLC 53 Rev. 08/14/2015


Figure 5: Delta-Wye Transformer Connection

H1 H2 H3

X0 X1 X2 X3

Figure 6: Delta-Delta Transformer Connection

H1 H2 H3

X1 X0 X2 X3

Single-phase pole mounted transformers are often connected and labeled H1 and H2 on the
primary and X1, X2 (center tap), and X3.

Figure 7: Single-Phase Transformer Connection

Motor Circuit Analysis Basics

©2015, ALL-TEST Pro, LLC 54 Rev. 08/14/2015


Motor Circuit Analysis is the art of troubleshooting and pinpointing faults within an inductive or
capacitive circuit by using readings of resistance, impedance, inductance, phase angle,
insulation resistance and I/F. The ALL-TEST PRO 5 static MCA instrument outputs a low
voltage, 50 to 800 Hz sinusoidal signal which it then evaluates the response of the device
under test. These readings relate as follow:

1. Resistance (Ohms): The simple DC resistance of the circuit.


2. Inductance (Henries): The magnetic strength of a coil.
3. Capacitance (Farads): Measurement of leakage.
4. Inductive Reactance (XL): The AC resistance of a coil. XL = 2πfL
5. Capacitive Reactance (XC): XC = 1/(2πfC)
6. Phase Angle (Fi, degrees): The angle of the lag of current to voltage.
7. Impedance (Z): The complex resistance of an AC circuit. Z  R 2  ( X L  X C ) 2
8. Current/Frequency Response (I/F): Percentage change in current when the frequency
is doubled by the instrument, as I = V / Z.
9. Insulation Resistance (Meg-Ohms): Measurement of leakage to ground, ground-wall
insulation strength.

When taken as a group, these readings can assist the analyst in determining, first, if a fault
exists, then the type of fault. Using the AT5™, these readings can be taken in less than 5
minutes per transformer. The key to MCA testing is to compare readings between similar
windings or transformers and to look at the variations and patterns between phases.

Figure 8: Motor Circuit Analysis Instrument

©2015, ALL-TEST Pro, LLC 55 Rev. 08/14/2015


Transformer Field Test

The initial set of tests were performed using the same type of procedure that would be used
on an electric motor, first for the primary windings, then for the secondary windings. Table 1
represents a sample of one of 30 transformers that were tested over a period of 90 minutes.

Table 1: Initial Transformer Test Data (Using the ATIV): 2500 kVA Transformer

Primary Secondary

H1-H2 H1-H3 H2-H3 X1-X2 X1-X3 X2-X3

Resistance 258.5 48.45 153.3 0.198 0.125 0.132

Impedance 15633 11028 11035 566 411 420

Inductance 24878 17552 17562 902 655 669

I/F -50 -23 -18 -44 -46 -44

Phase 9 90 90 90 85 90
Angle

Meg-Ohm >99 >99

An issue that became immediately apparent was the unusual and extremely unbalanced
readings. All of the tests identified similar results and it was also noticed that resistance varied
from test to test and that the impedance and inductance changed from test to test. Upon
evaluation of these phenomena, two theories were developed:

1. The sinusoidal voltage output of the ALL-TEST PRO IV was inducing into the opposite
set of windings resulting in reflected impedance and inductances that would increase
during each test because of a resulting static charge.
2. Electro-Magnetic Interference (EMI) from surrounding operating equipment,
transformers, lighting, etc. would cause stray currents because the transformer
windings and core would act as an excellent EMI antennae. This scenario would
explain varying resistances from test to test.

To resolve both issues, the connections on the side opposite of the side being tested should
be grounded to a proper earth ground. The result was predicted to shunt all induced currents
direct to ground resulting in the ability to fully test just the winding being tested. This would
also allow for tighter testing tolerances. The results are found in Table 2 and test time
remained under 5 minutes per transformer.

©2015, ALL-TEST Pro, LLC 56 Rev. 08/14/2015


Table 2: Final Transformer Test Data (ATIV): 2500 kVA Transformer

Primary Secondary

H1-H2 H1-H3 H2-H3 X1-X2 X1-X3 X2-X3

Resistance 3.703 3.623 3.648 0.103 0.100 0.096

Impedance 220 217 218 15 14 14

Inductance 87 86 86 2 2 2

I/F -49 -49 -49 -48 -48 -49

Phase 88 88 88 75 75 75
Angle

Meg-Ohm >99 >99

These results were found to be repeatable in all cases. Transformers that tested bad tended
to have drastic variations in readings.

Table 3: Shorted Transformer (ATIV)

Primary Secondary

H1-H2 H1-H3 H2-H3 X1-X2 X1-X3 X2-X3

Resistance 116.1 98.2 48.5 0 0.005 0.005

Impedance 4972 1427 2237 0 1 1

Inductance 7911 2267 2237 0 0 0

I/F -33 -29 -29 0 -20 -20

Phase 23 21 20 0 5 5
Angle

Meg-Ohm 9.132 0

©2015, ALL-TEST Pro, LLC 57 Rev. 08/14/2015


It was found that the 500 kVA transformer had a shorted primary with damage between the
primary and secondary windings.

Transformer Testing Procedure

Figure 9: Transformer Test

The results of the study produced simple test procedures for both three-phase pad and single-
phase pole mounted transformers. The key to testing any type of transformer is to ground all
of the leads on all of the connections of the winding opposite of the winding being tested.

A good transformer should have unbalances less than:

1. Resistance: No more than 5% unbalance.


2. Impedance: < 5% unbalance
3. Inductance: < 5% unbalance
4. Phase Angle: No more than 1 degree between phases
5. I/F: No more than 2 digits difference and the readings should fall between –15 and –
50.
6. A “shift” in readings should be flagged for further testing or trending. For instance, a
winding that tests as I/F: -48; -48; -46 and Phase Angle: 70o; 70o; 69o, should be
checked further.

Normally, a winding is beginning to experience inter-turn shorts when the Phase Angle and
I/F begin to shift. A corresponding unbalance in inductance and impedance indicates a severe
fault. A change in Phase Angle with a fairly balanced I/F normally indicate a phase short.

The basic steps for three phase transformer testing are as follow:

1. All of the leads on the side opposite of the side being tested must be firmly shorted
together with a comparable wire size of the transformer being tested. Battery cables
with clamps are suitable for doing this. Using too small of a wire (like a #10AWG with

©2015, ALL-TEST Pro, LLC 58 Rev. 08/14/2015


alligator clips) will give false readings. The wires that are shorted together should be
solidly attached to a known good ground.
2. Test the primary from H1 to H2, then “retest” to verify that the readings are repeatable.
If they are not repeatable, check the ground and continue.
3. Test from H1 to H3, then H2 to H3, and, finally a ground insulation test.
4. Save the readings and check condition.
5. Test the secondary winding by first checking X1 to X2, then “retest” to verify that the
readings are repeatable. If they are not repeatable, check the ground and continue.
6. Test from X1 to X3, then X2 to X3, and, finally, a ground insulation test.
7. Save the readings and check condition.

Single-phase transformers are tested slightly differently and require a known reading for the
primary to be compared to, such as with a similar transformer or a past test on the same
transformer. The basic steps for single phase transformer testing are as follow:

1. All of the leads on the side opposite of the side being tested must be firmly shorted
together with a comparable wire size of the transformer being tested. Battery cables
with clamps are suitable for doing this. Using too small of a wire (like a #10AWG with
alligator clips) will give false readings. The wires that shorted together should be solidly
attached to a known good earth ground.
2. Test the primary from H1 to H2, then “retest” to verify that the readings are repeatable.
If they are not repeatable, check the ground and “retest.”
3. Ground the primary then test X1 to X2, then “retest” to verify that the readings are
repeatable. If they are not, then check the ground and “retest.”
4. Test from X2 to X3, then save readings. Compare the second and third reading to
each other and the first reading to a standard.
These procedures can be used on three phase pad mount and single-phase pole mount
transformers regardless of connection type.

Conclusion:

Static Motor Circuit Analysis techniques provide an excellent method for analyzing the primary
and secondary windings of both three-phase pad and single-phase pole mounted
transformers. A simple procedure incorporating grounding the side opposite of the side being
tested allow for very accurate test results. Measurements of resistance, impedance,
inductance, phase angle, current response and insulation resistance can be compared for
troubleshooting purposes and measurement patterns for pinpointing faults.

Test equipment required for MCA testing transformers must have the following capabilities:
1. Resistance, impedance, inductance, phase angle, I/F and insulation resistance in
engineering units.
2. Sine-wave voltage output in a variety of frequencies.
3. Onboard memory with software to upload and download readings.
4. Cost effective and accurate.

©2015, ALL-TEST Pro, LLC 59 Rev. 08/14/2015


The procedures described require about five minutes per transformer with greater than 99%
test result accuracy.

Bibliography

Sarma, Mulukutla S., Electric Machines: Steady-State Theory and DynamicPerformance, PWS Publishing
Company, 1994.

Nasar, Syed A., Theory and Problems of Electric Machines and Electromechanics, Schaum’s Outline
Series, 1981.

Edminster, Joseph, et.al., Electric Circuits Third Edition, Schaums Electronic Tutor, 1997.

Hammond, et.al., Engineering Electromagnetism, Physical Processes and Computation, Oxford Science
Publications, 1994.

US Department of Energy, et.al., Keeping the Spark in Your Electrical System, US DOE, October, 1995.

Penrose, Howard W. Ph.D, “Static Motor Circuit Analysis: An Introduction to Theory and Application” IEEE
Electrical Insulation Magazine, July/August 2000, p. 6.

©2015, ALL-TEST Pro, LLC 60 Rev. 08/14/2015


Appendix 3:
Synchronous Machine Testing With ALL-TEST Pro Instrumentation

Dr. Howard W. Penrose, Ph.D.

Introduction

In order to further understand the application of motor circuit testing and analysis on
synchronous electric motors (synchronous machines), it is important to have a brief
overview of the operation of a synchronous motor, most common faults, common test
methods, how the ALL-TEST IV PRO™ works with large synchronous motors, basic steps
for analysis of synchronous stators and rotors, and, expected test results (Editor- ALL-
TEST PRO 5 is the recommended replacement for the ATIV). In this paper, we will
discuss these various aspects, referencing other materials for additional details.

About Synchronous Machines

Large synchronous motors have two basic functions:

 The first is to improve the electrical power factor in a plant. In any plant with large
inductive loads, such as motors and transformers, current begins to lag behind
voltage (poor power factor). When this becomes severe enough, the plant requires
significantly larger amounts of current to perform the same amount of work. This
can cause voltage sag and overheating of electrical components. A synchronous
motor can be used in such a way as to cause little to no impact on power factor,
or can be used to cause current to lead voltage to correct power factor problems.
 The second method of operation is to absorb pulsating loads, such as reciprocating
compressors. Once a synchronous motor has achieved synchronous speed, it has
coils which ‘lock’ in step with the electric motor’s rotating magnetic fields from the
stator. If a torque pulse occurs (such as at the top of a reciprocating compressor
stroke), the motor may come out of synch with the rotating fields. When this
occurs, a special winding on the rotor called an amortisseur winding (see
synchronous construction below) absorbs the energy from the torque pulse,
keeping the rotor in synch.

The basic construction of a synchronous motor is straightforward. There are three sets
of windings, a stator, a rotor, bearings, and either a generator (brushless) or a ‘static
exciter’ (brush-type). The windings consist of: A standard three phase winding, very
similar to a standard induction electric motor; A set of field coils, which are DC coils made
of round wire for small machines and rectangular or ribbon wire on larger machines; And
an amortisseur winding, which is similar to an induction motor rotor squirrel cage.

©2015, ALL-TEST Pro, LLC 61 Rev. 08/14/2015


The starting methods for both the brush-type and brushless synchronous motors are
similar. The starting circuit will be different for both. Following is a description of the basic
mode of operation, followed by a brief description of the differences:

During the starting phase of a synchronous motor, it acts much the same as a standard
induction motor. The stator receives an electrical current and a rotating magnetic field is
developed (the speed = (120 * applied frequency) / # of poles). This field generates a
current in the amortisseur winding, which is used to develop starting torque by generating
its own magnetic field which interacts with the stator magnetic field in the air gap and
causes the rotor to follow the stator magnetic fields. As the rotor starts to catch up to the
stator fields, DC current is injected into the rotor field coils, creating north and south
magnetic pairs (rotor coils are always found in pairs). These lock in step with the stator
magnetic fields and follow at the same speed as the stator fields, whereas a standard
induction motor always lags behind.
In a brush machine, the DC source for the rotor fields usually comes from a ‘static’
(electronic) starter, which converts a supplied AC power to DC. In most cases, the output
DC is varied through the starting cycle. The drive may also be set up to short out the field
coils of the machine to avoid rotor saturation and the resulting extremely high currents on
the stator. Once the rotor begins to turn, DC is supplied to assist the motor in developing
torque. The DC voltage is supplied through a pair of slip rings and brushes.

In a brushless machine, a DC generator is installed directly on the shaft of the


synchronous motor. As the synchronous motor starts, the generator provides very little
DC through its commutator. As the speed increases, the DC voltage also increases,
helping the motor generate torque then lock in step at synchronous speed. In this type
of machine, the generator is wired directly to the rotor fields.

There are also machines that have a generator mounted on the shaft of the rotor that
feeds a separate control. This is used to first short the windings and then control the
amount of DC fed to the rotor, just as the brush machine.

Most Common Synchronous Motor Faults


Large synchronous motors tend to be well built and sturdy. They are often overbuilt with
material to withstand the severe loads that are applied. The most common failures for
industrial synchronous machines, in order, are:

 Bearings due to general wear and contamination


 Rotor fields – due to high temperatures, these will often burn up from the inside
out
 Amortisseur windings – mostly in reciprocating loads. Because of the amount of
energy absorbed, the winding bars will often crack. In particular if the rotor fields
are beginning to fail and short, making it easier for the rotor to fall out of ‘synch.’
 Stator windings – general wear and contamination. Stator windings in
synchronous machines tend to be ‘form wound’ and heavily insulated.

©2015, ALL-TEST Pro, LLC 62 Rev. 08/14/2015


Almost all of the winding faults that occur in a synchronous motor start between
conductors in the rotor or stator coils.

Common Test Methods, Strengths and Weaknesses


Following are the traditional test methods for evaluating the condition of a synchronous
motor:

 Insulation resistance testing: Using applied DC voltages as specified by IEEE 43-


2000, a potential is placed between the stator windings and ground. This
measures only direct faults between the stator windings and the stator frame. Is
also performed through the slip rings on a brush type machine.
 Polarization Index: Is a 10 minute to 1-minute ratio of insulation resistance. This
has been traditionally used as a method to gage the condition of the insulation
between the stator windings and frame. As with insulation resistance testing, this
can also be performed through the slip rings on a brush type machine. As stated
in IEEE 43-2000, this test method is only truly valid on pre-1970 insulation
systems.
 High Potential testing: Most common on large machines is DC high potential
testing which is performed at a value of twice the motor nameplate voltage plus
1000 volts, times the square root of 3. On an existing insulation system, this value
is often reduced to 75% of the potential voltage. This test highly stresses the
insulation system and is potentially damaging (per IEEE Std’s 388 and 389). This
type of test should NEVER be applied to the rotor windings of a synchronous
motor.
 Surge Comparison testing: Evaluates the turn-to-turn condition of the stator only
by comparing the waveforms of two windings when a fast rise time pulse of twice
the voltage plus 1000 volts. If there are correctable issues, such as contaminated
windings, this test may damage the motor windings.
 Partial Discharge testing: Is a non-destructive test method that measures radio
frequencies from discharges in voids within the insulation system of the motor
windings. This is effective for trending on machines that are over 6.6 kV and only
provide a brief warning from 4 kV. It does not detect any rotor faults.
 Motor Current Signature Analysis: Was designed for rotor testing of induction
motors.
 Voltage Drop Test: Requires that the motor is disassembled. A 115 AC voltage is
applied to the rotor windings and the voltage drop is measured with a voltmeter
across each coil. If there is a short, the voltage drop will vary more than 3%.
The above list does not include equipment for mechanical testing of synchronous motors.

About the ALL-TEST Pro Instrument

The ALL-TEST IV PRO™ (Editor- ALL-TEST PRO 5 is the recommended replacement


for the ATIV) is a simple electronic instrument that performs in much the same manner

©2015, ALL-TEST Pro, LLC 63 Rev. 08/14/2015


as a multi-meter, except that it provides a series of readings that cover the AC parameters
of the motor circuit. It is a data collector and tester that sends a low voltage DC signal for
simple resistance testing, in the same manner as a milli-Ohm meter, and a low voltage,
high frequency AC signal for AC readings. The instrument then measures and calculates
test results in engineering units of resistance, impedance, inductance, phase angle,
current/frequency response and an insulation resistance test to ground.

The primary differences between electronic testing of power equipment versus traditional
power methods are:

 A more complete view of the motor circuit, including influences from changes in
the condition of rotor field coil insulation.
 One instrument for a large range of equipment size. The test is limited only to the
simple resistance range of the instrument (0.010 Ohm to 999 Ohms).
 Non-destructive – no harmful voltage is applied.
 Easier data interpretation – A few simple rules for data interpretation (See data
interpretation below).
 Hand held vs. equipment that may weigh from 40 lbs to well over 100 lbs.
 Internal power source for the instrument.

As an insulation system ages, or if the insulation system is contaminated and it is effecting


the integrity of the insulation, the electrical circuit of the motor changes. Because the
rotor is an integral part of the circuit, changes to the electrical integrity of the rotor circuit
and insulation system are directly reflected through the stator windings, as well. This
allows both immediate troubleshooting and long-term trending of the motor.

Unique test information allows the ALL-TEST Pro Instruments to view enough parameters
of the insulation system to detect and isolate:
 Shorted stator windings
 Shorted rotor fields
 Broken amortisseur winding bars
 Air gap eccentricity
 Winding contamination (rotor and stator)
 Ground insulation faults

Basic Steps for the Analysis of Synchronous Machines with ALL-


TEST Pro Instruments

The steps for testing synchronous machines are similar to those for evaluating the
condition of standard induction motors. However, because there are field coils on the
motor rotor, a few additional steps are involved when troubleshooting a fault.

When testing a synchronous machine from the motor control center or starter:

©2015, ALL-TEST Pro, LLC 64 Rev. 08/14/2015


 De-energize the equipment. Ensure that secondary sources of power are also de-
energized.
 Perform the standard ALL-TEST IV PRO™ (now AT5) tests on the stator following
the menu prompts on the instrument.
 Evaluate the test results (See Expected Test Results)
 If a fault is indicated, begin troubleshooting:
o Adjust the position of the rotor, as much as possible, up to 45 degrees (any
movement will do if the rotor is difficult to turn, but no less than 5 degrees)
o Re-perform the tests and review the readings. If the fault has shifted, or
changed by more than a digit, then the fault most likely is located in the
rotor.
o If the fault remains stationary (does not change with rotor position), then
disconnect the leads at the motor terminal box and retest. If a fault is still
indicated, it is most likely in the stator, if not, it is most likely in the cable.

The average test time, other than troubleshooting, is approximately 3-5 minutes.

When testing a disassembled synchronous machine, it is important to remember that the


readings will be very different without the rotor in place:

 Perform the ALL-TEST IV PRO™ Auto test (AT5 Z/ test mode) on the stator and
evaluate the test results. This will provide an immediate indication of any faults.
 For the rotor test:
o Perform the Auto test and compare to a past reading; or,
o Perform the Auto test and compare to an ‘identical’ rotor; or,
o Perform the Auto test across each field coil instead of a voltage drop test.
o All parameters for all three should meet the evaluation limits.

Because of the style of testing, these results can be trended and compared between like
machines.

Other applications for motor circuit testing include evaluation and acceptance, and predictive
maintenance.

Expected Test Results

As mentioned in the last section of this paper, the test results are similar to those found in
three phase induction machines. Fault patterns are very straightforward and apply regardless
of equipment size, within the test range of the ALL-TEST Pro Instruments. Following is a brief
overview of the test measurements and their results for basic troubleshooting:

 Simple resistance measurements: Are an indicator of high resistance connections,


loose connections or broken conductors in the circuit. This test is important, especially
if the resistance problem is in one spot as, based upon I2R, a resistive spot will put out
a great deal of heat energy (in Watts). For instance, a 0.5 Ohm resistance across a
point in a circuit that is seeing 100 Amps would give off: (100Amps2)(0.5 Ohms) =

©2015, ALL-TEST Pro, LLC 65 Rev. 08/14/2015


5,000 Watts (5kW) worth of energy. This is about the same energy used to turn 6
horsepower worth of electric motor.
 Inductance measurement: Is an indicator of magnetic strength of a coil and the
influence of other coils on one coil. It is impacted by the number of turns in a circuit,
the dimensions of the coils and the inductance of other coils. This measurement, by
itself, is only a good indicator of the condition of the amortisseur winding and rotor
eccentricity. Inductance will only show a shorted winding if it is severe.
 Impedance measurement: Is the measurement of the complex resistance in the circuit.
It can be used, much like inductance, for checking the amortisseur winding and rotor
condition. However, when used along with inductance, it can be used to detect
overheated windings and winding contamination quickly. By viewing the relationship
of inductance and impedance between each phase: If the inductance and impedance
are relatively parallel, then any inductive and impedance unbalance is in the
relationship between the rotor and stator (rotor position); If they are not parallel, this is
an indication of an insulation problem such as insulation breakdown or winding
contamination.
 Phase angle and I/F (Current/Frequency): Are both indicators of insulation faults
between turns in the stator or rotor.
 Insulation Resistance: Evaluates the insulation to ground and will only indicate when
the insulation has failed.

The test limit recommendations, as outlined in the “Guideline for Electronic Static Winding
Circuit Analysis of Rotating Machinery and Transformers,” are as follow:

Table 1: Test Limits (peak-to-peak values)

Measurement Limits

Resistance 5%

Impedance ~ 5%*

Inductance ~5%*

Phase Angle +/- 1

I/F +/- 2

Insulation Resistance > 100 M-Ohms

*Can exceed this value if measurements are parallel.

Following is an overview of the troubleshooting rules:

©2015, ALL-TEST Pro, LLC 66 Rev. 08/14/2015


 Shorted Windings:
o Shorted windings can be evaluated by viewing the phase angle and I/F
readings from the instrument on similar coils or between phases:
o Phase Angle (Fi) – The phase angle should be within 1 digit of the average
reading. For instance, a reading of 77/75/76 would be good because the
average reading is 76. A reading of 74/77/77 would be bad.
o Current Frequency Response (I/F) – The current frequency response should
be within 2 digits of the average reading. For instance, a reading of –44/-45/-
46 would be good. A reading of -40/-44/-44 would be bad. However, a reading
such as -42/-44/-44 should be considered suspect.
 Winding Contamination and Rotor Position
o The position of the rotor within the electric motor may cause a natural phase
unbalance. Winding contamination will also cause phase unbalances. Evauate
the DF %..
o Rotor Position – Rotor position unbalances can be evaluated by looking to see
if the inductance and impedance values are fairly balanced. For instance, if
there are inductances of 17/18/19 and impedances of values 24/26/29, then the
unbalance is due to rotor position. This may also be the case if the inductances
are 5/5/5 and the impedances are 8/9/8.
o Winding Contamination – Can also be found as overheated (burned) windings.
These conditions are the result of changes to the insulation due to breakdown
of the insulation system.

Conclusion
Through a set of simple rules and instructions, the ALL-TEST IV PRO™ (now AT5) provides
an excellent tool for troubleshooting and trending the condition of synchronous machines. The
test is performed using simple, non-destructive test measurements that allow for a more
complete view of the motor stator and rotor circuit than any other test. Test evaluation is
simple and direct, regardless of equipment size or type.

Bibliography

 Guideline for Electronic Static Winding Circuit Analysis of Rotating Machinery and
Transformers, BJM Corp, ALL-TEST Division, 2001.
 Penrose, Howard W. Motor Circuit Analysis: Theory, Application and Energy Analysis,
SUCCESS by DESIGN, 2001.

©2015, ALL-TEST Pro, LLC 67 Rev. 08/14/2015


Appendix 4:
Page intentionally left blank

©2015, ALL-TEST Pro, LLC 68 Rev. 08/14/2015


Appendix 5:
DC Current Motor Electrical Evaluation Using Motor Circuit Analysis

Howard W. Penrose, Ph.D

Introduction
Electrical testing of Direct Current (DC) electric motors is a challenge within industry,
manufacturing and repair centers alike. The key issue has to do with the ability to compare
one coil to the next, should exact information not be provided. In this article, the issue of
simple tests to increase the confidence of testing and analysis conclusions using Motor Circuit
Analysis (MCA) shall be discussed.

The term MCA is derived from a test method that provides information on the basic
components of an AC or DC electric motor. These basic components include: resistance,
measured in Ohms; impedance, measured in Ohms; inductance, measured in Henries;
the induction winding phase angle, measured in degrees; and, insulation resistance,
measured in Meg-Ohms. The instrument that will be referred to in this article provides
these readings by generating a low voltage, true sine-wave, alternating current
(impedance, inductance, phase angle), signal at frequencies from 100 to 800 hertz, a low
voltage DC signal for resistance, and 500 or 1,000 volts DC for the insulation resistance
test. In addition, a special test called I/F is performed in which the applied frequency is
doubled and a ratio results from the change in the winding impedance. This test is
introduced to identify early winding shorts that may exist in the winding. Using the applied
data, the condition of a DC motor winding can be evaluated through coil comparisons,
comparisons to known readings, or by trending changes to the windings over a period of
time.

The DC electric motors that will be included in this article are: series, shunt, and
compound DC motors. Some of the basic tests described can be performed on
permanent magnet, DC servo, DC machine tools, and others (although brushless DC
motors are evaluated in a similar fashion to AC motors). The types of DC electric motors
can be described by their windings and connections.

©2015, ALL-TEST Pro, LLC 69 Rev. 08/14/2015


DC Motor Theory

Direct Current electric motors operate under a basic principle of electricity: interaction
between two magnetic fields positioned at an angle from each other will attract/repel
resulting in movement. In the case of a DC electric motor, power is provided to a stator
field and an armature creating magnetic fields that are, electrically, about 90 degrees from
each other. The resulting attraction/repulsion of the armature from the field generates a
torque and the armature turns.

The basic components of a DC electric motor include:

 Frame – Makes up the outer structure of the machine. It is used to mount most of
the other components of the motor.
 Fields – Are coils mounted on field pole pieces that generate a stationary magnetic
field.
 Interpoles – Are coils that are placed between the field coils that generate a field
that is used to prevent excessive sparking of the brushes.
 End shields – Also called bearing housings, are used to house the brushes, brush
rigging, and to house the shaft bearings, holding the armature centered in the
frame.
 Brush rigging – Holds and positions the brushes above the armature commutator.
Usually, a tension device is used to maintain a constant pressure on the brushes.
 Brushes – Are used to provide DC to the armature. The brushes ride on the
commutator.
 Commutator – Consists of many copper bars that are separated by mica. Each
bar is connected to coils in the armature.
 Armature – Is the rotating portion of the motor that contains coils.

Unlike most AC motors, DC motors require separate power to be provided to both the
fields and the armature. The DC provided to the stator fields generate a constant North
and South set of fields. DC provided to the armature generates North and South fields
that are 90 electrical degrees from the stationary field. As the armature generates a
torque and moves towards the appropriate North or South pole, the brushes change
position on the commutator, energizing another set of coils 90 electrical degrees from the
stationary field. This actually makes the armature an Alternating Current component as
the current will travel in one direction, based upon brush position, then in another direction
as the motor operates. The brushes are set in such a position that they are electrically
“neutral” (no induced current from the stator fields) in order to reduce sparking. In most
DC motor connections, by varying the armature voltage, the operating speed may be
changed. One general danger that is inherent in DC motors is that if field current is lost
while armature current is maintained, the motor may take off and the speed increase until
the armature self-destructs.

©2015, ALL-TEST Pro, LLC 70 Rev. 08/14/2015


The three basic winding types that can be used to identify the type of DC motor include:

 Series: Normally found in applications that need a high starting torque. They
consist of a set of field windings of large wire and relatively few turns, marked S1
and S2, that are connected in series to the interpoles and armature, marked A1
and A2 (See Figure 1). Series connected motors are normally used as traction
motors and have a very low basic resistance.

Figure 1: Series Motor

A1 A2 S1 S2

 Shunt: Normally found in applications that require constant speed. They consist
of a set of field windings of smaller wire with many turns, marked F1 and F2 for
single voltage and F1, F2, F3 and F4 for dual voltage, and A1 and A2 for the
interpoles and armature (See Figures 2). Shunt connected motors are normally
used as crane and machine tool motors and have a relatively high basic resistance.

Figure 2: Shunt Wound Motor

F1 A1 A2 F2

©2015, ALL-TEST Pro, LLC 71 Rev. 08/14/2015


 Compound: Combine the benefits of both the series and shunt wound motors.
They provide a relatively high torque with a basic resistance to a change in
operating speed. The connections combine both the series and shunt connections
(See Figure 3). Compound motors are the most common and are commonly found
in industrial manufacturing.

Figure 3: Compound Wound Motor

F1 A1 A2 S1 S2 F2

As it can be seen, there are few coils to compare to each other in an assembled DC
machine. However, procedures can be developed for winding testing that provide a high
level of test result confidence.

Common DC Motor Electrical Faults

There are a number of common DC motor electrical faults of which the most common will
be described here. These result from issues specific to DC motor design as a result of
temperature, friction and internal contaminants such as carbon or graphite.

One of the most common causes of winding faults in a DC motor is from winding
contamination from carbon or graphite (carbon) dust from the brushes. The fine powder
permeates all of the stationary and rotating windings and will create a path between
conductors or between conductors to ground. Carbon is often trapped and problems
aggravated further through cleaning and maintenance practices when the carbon is blown
with compressed air or the armature is cleaned and baked. In either case, the carbon
may become tightly packed in corners, usually just behind the commutator. This will end
as a ground fault or shorted turns right at the commutator connection.

Another common fault, that is often not considered, is cooling of the DC machine. This
may occur because cooling passages are blocked, the armature is turned too slow with
no additional cooling, or from dirty filters (the most common cooling-related fault).
Temperature is the greatest enemy of electrical equipment, particularly the insulation
system, of which the life will be reduced by half for every 10 degrees centigrade increase
in temperature (accepted rule of thumb). As the insulation weakens, its reliability
decreases until winding faults between turns occur. In addition to the insulation system
degrading, brushes also degrade faster, causing increased wear on the commutator and
additional carbon contamination of the windings.

©2015, ALL-TEST Pro, LLC 72 Rev. 08/14/2015


Another fault that is related to heat is generated from practices that have the fields
energized with the armature at rest (de-energized). This is a common mode of operation
that requires a separate blower to provide cooling to the motor that normally has filters
that must be kept clean. This type of fault normally results in shorted shunt coils, reducing
the motor’s ability to produce torque and may end with the dangerous condition of
armature over speed if not maintained properly.

The commutator also provides opportunities for faults, as well as an indicator of motor
operation and condition. A properly operating DC motor will have a fine glaze of carbon
on the commutator with the bars looking uniform. Burned commutator bars, streaked
glazing, heavy carbon, or overheated commutator conditions indicate potential problems
that should be addressed.

Armature Testing

DC armatures are the most time consuming but easiest component to test. There are
three basic methods that will be introduced: trending; assembled; and, disassembled. In
the case of trending, all measurements are used, however, in the case of assembled and
disassembled testing a bar to bar impedance measurement will be used. Impedance is
viewed because the armature is an AC component and simple resistance measurements
may miss some faults including shorts and grounds. Trending will be reviewed in an
overall trending procedure for DC motors later in this article.

When testing an assembled DC motor armature, the best method is to perform what’s
commonly known as a bar-to-bar test using the motor brushes. In the case of a DC motor
that has two brushes, none of the brushes needs to be raised, in the case of a DC motor
that has four or more sets of brushes, all but two sets 90 degrees from each other need
to be raised, which takes them out of the testing circuit. Make sure that good contact is
maintained on the commutator by ensuring that 90%+ of the brush is in contact with the
commutator bars and that the commutator bars are clean. If they are not clean, polish
the armature gently, using an approved method, before testing. If the commutator is badly
worn, it will need to be disassembled and the commutator “turned and undercut,” in which
case a disassembled bar to bar test would be appropriate. Once set, mark the position
of one bar on the commutator, then bring the bar to a position where it is just under the
leading edge of one of the brushes. In the assembled test, you will probably be covering
at least one and a half bars with the brush. Perform an impedance test, mark down the
reading, and move the armature so that the leading edge of the brush is over the next
commutator bar. Take the next impedance reading and continue until each bar has been
tested. A good result will show a consistent pattern, while an inconsistent pattern will
identify a poor armature.

Disassembled bar-to-bar testing is similar to assembled testing, other than the armature
is out of the frame and the tester has full access to the commutator. In this case, the
tester will use an armature fixture or test leads to connect from bar to bar. The spacing
between each impedance reading should be constant and about 90 to 180 degrees from
each other. The first bar should be marked and testing continues until one leg of the

©2015, ALL-TEST Pro, LLC 73 Rev. 08/14/2015


testing fixture or test lead has made it 360 degrees around the commutator. Mark the
impedance for each bar-to-bar test then look to ensure that there was a consistent pattern.

Series Motor Testing

Series electric motors are very challenging to troubleshoot as they do not provide sets of fields
to compare to. Readings may be taken from S1 to S2 and A1 to A2 then trended over time
or compared to other similar machines.

When trending the readings over time, simple resistance readings must be corrected for
temperature, usually relative to 25oC. Impedance and Inductance normally has limited
change due to temperature while the phase angle and I/F readings will remain constant,
regardless of temperature. Variations in the I/F and phase angle will indicate shorted
turns, while changes in Impedance and Inductance will normally indicate dirty windings.

Comparing like motors will require additional information. The operator will have to
ensure that the motor is of the same manufacturer and design, as well as speed, power,
etc. The “model” motor must be new or rebuilt to original manufacturer’s specifications.
When performing comparative readings, the testing temperature should be similar from
motor to motor, however, the I/F and phase angle readings can be directly compared.
These readings should not change more than +/- 2 points for I/F and +/- 1 degree for
phase angle. A common error when series field windings are rebuilt, although less
common that shunt coils, is an incorrect replacement of wire size, which will impact the
ability of the motor to generate torque.

Shunt Motor Testing

Dual voltage shunt motors provide the ability to compare two sets of windings while single
voltage motors will have the same test procedure as testing series motor windings, using
F1 to F2 as opposed to S1 to S2. With dual voltage, the shunt windings are labeled F1
to F2 and F3 to F4 allowing the analyst to test and compare these two sets of windings.

When testing and troubleshooting the readings over time, simple resistance readings
must be corrected for temperature, usually relative to 25oC. Impedance and Inductance
will change more than a series wound motor because of the higher simple resistance of
the circuit. The phase angle and I/F will remain constant, within 1 to 2 points, regardless
of temperature. Variations in the I/F and phase angle will indicate shorted turns, while
changes in Impedance and Inductance will normally indicate dirty windings. Comparisons
between F1 to F2 and F3 to F4 should be less than 3% in resistance, inductance and
impedance and no more than 1 point different in I/F or phase angle.

Like motors can be tested and compared the same as series wound motors. When
possible, the motors should be tested, when trending readings, at the same temperature
as the previous tests. For instance, within minutes of shutting down operating equipment
or before starting equipment, this allows for the tests to be performed at like temperatures.

©2015, ALL-TEST Pro, LLC 74 Rev. 08/14/2015


Compound Motor Testing

In place testing, trending and troubleshooting is much simpler with a compound motor.
Single voltage compound motors are normally labeled A1 to A2, S1 to S2 and F1 to F2,
dual voltage compound motors are normally labeled A1 to A2, S1 to S2, F1 to F2 and F3
to F4. A key additional point to a compound wound motor is that the series winding is
normally wound on top of the shunt winding, allowing for possible faults between these
two windings.

Trending a compound motor, the tests are normally taken from the DC drive terminals.
Standard MCA tests using the ALL-TEST PRO 5 involve low voltage, higher frequency
signals that will not harm the output electronics of the equipment, reducing the need to
disconnect the leads from the drive while testing. However, if the analyst wishes to check
insulation resistance between the series and shunt windings, the leads must be
disconnected from the drive. When trending from the DC drive, test A1 to S2 and the two
field leads then perform a 500 Volt insulation resistance test between the S2 and F1 leads
and compare to previous tests or similar motors, in either case, insulation resistance
readings should remain above 100 Meg-Ohms. As mentioned in series and shunt motor
testing techniques, the I/F and phase angle readings should not change more than 1 point
between tests, over time, the series and field windings will vary dramatically from each
other, however.

Troubleshooting compound motors should be performed at the motor, itself. Disconnect


all motor leads and separate them. Test the series and field windings as outlined in the
series and shunt winding instructions, then perform an insulation resistance test between
the series and shunt windings, the insulation resistance should be greater than 100 Meg-
Ohms.

General DC MCA Testing Notes

Several key points can be made using MCA testing on any type of DC motor:

1. Any I/F reading outside the range of –15 to –50, for instance, -56, indicates a
winding fault.
2. If the test shows an infinite resistance between leads of the same circuit indicates
an open winding.
3. An increase in simple resistance between tests, when corrected for temperature,
indicates a loose connection, in particular when impedance and inductance
readings change. A reduced simple resistance, when corrected for temperature,
may indicate a short, usually accompanied by changes in impedance, inductance,
phase angle and I/F.
4. When testing like motors, the I/F and phase angle should not change more than 2
points, any difference greater than this should prompt a full analysis.
5. Changes when testing through the armature circuit should prompt a bar to bar test.

©2015, ALL-TEST Pro, LLC 75 Rev. 08/14/2015


By following these simple instructions, using an MCA device, will allow you to capture
early faults long before the equipment fails during operation. If performing tests as part
of a predictive maintenance program, the interval should be at least those shown in Table
1.

Table 1: DC Motor Test Frequency


Test Type Non-Critical General Critical
General 1 year 6-9 months 3-6 months
Maintenance
Predictive 6 months 3 months 1 month
Maintenance
Armature Test 1 year 6 months 3 months

General maintenance tests are those that are not trended over time. Usually accompanied
with vibration, bearing greasing, commutator inspection and brush inspection. Predictive
maintenance testing normally involves trending readings over time looking to detect potential
faults then to determine the best time to remove the motor for corrective maintenance. Once
a potential fault is detected, the testing frequency should increase until it is determined that
the motor needs to be removed. A complete armature test should be performed either in
conjunction with a general or predictive maintenance test due to the high stresses at the
commutator and carbon contamination.

Conclusion

General electrical testing of direct current electric motors is made much easier with new
techniques available with static motor circuit analysis. For the first time, early turn faults
can be detected in series, shunt and armature windings before they take equipment out
of operation. Predictive maintenance tests can be performed from the drive with
troubleshooting tests being performed at the motor. In general, the tests are relatively
quick, requiring less than five minutes per motor for predictive maintenance testing, with
additional time required for troubleshooting. Overall, MCA testing dramatically improves
DC motor testing over the traditional methods of continuity tests.

©2015, ALL-TEST Pro, LLC 76 Rev. 08/14/2015


Disclaimer, Copyright & Trademarks
Notice of Service/Trademark Rights
The trademarks, service marks and logos (collectively, the "Marks") set forth below are
registered and unregistered trademarks and/or service marks owned by ALL-TEST Pro, LLC in
the United States and certain other countries throughout the world. Nothing contained in this
manual should be construed as granting, by implication, estoppels or otherwise, any license or
right to use any of the Marks without the written permission of ALL-TEST Pro, LLC. Any misuse
of the Marks or any Content, except as provided in this Statement, is strictly prohibited and
may violate trademark laws.
Other brands or product names used in this manual are trademarks and/or service marks of
their respective owners, should be treated as such, and may be registered in various
jurisdictions.

1) ALL-TEST PRO® is a Registered Trademark of ALL-TEST Pro, LLC


2) MCA BasicTM, MCA PROTM, and ALL-TEST PRO 5™, are all Trademarks of
ALL-TEST Pro, LLC.

Disclaimer:

Documents published by ALL-TEST Pro, LLC are provided "as is" without warranty of
any kind, either expressed, implied or statutory, including, but not limited to any
warranties of merchantability, fitness for a particular purpose, or non-infringement.

ALL-TEST Pro, LLC shall not under any circumstances be liable to any person for any
special, incidental, indirect or consequential damages, including, without limitation
damages resulting from use of or reliance on the information presented, loss of profits or
revenues or costs of replacement goods, even if informed in advance of the possibility of
such damages.

Reasonable efforts have been made to ensure the accuracy of the information presented.
However, ALL-TEST Pro, LLC assumes no responsibility for the accuracy of the information.
Product information is subject to change without notice. ALL-TEST Pro, LLC may make
improvements and/or changes in the products and/or the programs described in these
publications at any time without notice.

Information in this document is: © 2015, ALL-TEST Pro, LLC All Rights Reserved

You may cite or refer to information published in this manual, except as provided below, but
you may not reproduce or distribute such information in whole or in part without the prior
written permission of ALL-TEST Pro, LLC. You may not reproduce or distribute any image from
the Manual, without securing advance written consent from ALL-TEST Pro, LLC. To request such

©2015, ALL-TEST Pro, LLC 77 Rev. 08/14/2015


permission, send email to [email protected], including your name, address and a description
of the purpose of your intended distribution and the information you would like to distribute.

You may print, reproduce and use the information in, and retrieve files containing software or
images from ALL-TEST Pro, LLC for non-commercial, personal, or educational purposes only,
provided that you (i) do not modify such information, and (ii) include any copyright originally
included with such information and this notice in all such copies.

Nothing contained herein shall be construed as conferring by implication or otherwise any


license or right under any patent or trademark of ALL-TEST Pro, LLC or any third party. No other
rights under any copyrights of ALL-TEST Pro, LLC or any other party are granted herein, except
as expressly stated above.

©2015, ALL-TEST Pro, LLC 78 Rev. 08/14/2015

You might also like