TYPICAL INSTALLATION – MODEL TP-2
The TP-2 senses the electical power input to a motor (horsepower). The Output is a 4-20 Milliamp LOOP POWERED analog
signal proportional to power.
VOLTAGE CAPACITY
120 Volts AC are taken from two of the phases. If the motor Select the capacity by turning one (or two) of the Dip
starter already has a 120 Volt control transformer, it can be Switches on:
used. Otherwise, install a separate transformer. It is OK if
the secondary is grounded. BE SURE TO NOTE WHICH TWO Full Scale HP
PHASES SUPPLY THE TRANSFORMER. 460 Volt (nominal) Primary
SPECIFICATIONS
ACCURACY
• 2%
RESPONSE TIME
• 500 MS
TEMPERATURE
• 0-50° C
DIMENSIONS
• 3" x 3.9" x 1.75" high
(77mm x 100mm x
ANALOG OUTPUT 45mm)
4-20MA Loop Powered. Max. Loop voltage 28 VDC • Window .5" (13mm)