IEEE Short Circuit Protection
IEEE Short Circuit Protection
2
Engineering Bulletin EDP-1
Dependable (2004-1)
Protection
For An
Electrical
Distribution
System
Part 1
A Simple Approach
To
Short Circuit
Calculations
Bussmann
Electrical Distribution System
These sections include, among others: Capacitor discharge currents can normally be
110-9 Interrupting Rating neglected due to their short time duration. Certain IEEE
110-10 Component Protection (Institute of Electrical and Electronic Engineers) publications
230-65 Service Entrance Equipment detail how to calculate these currents if they are substantial.
240-1 Conductor Protection
250-95 Equipment Grounding Conductor Protection Asymmetrical Components
517-17 Health Care Facilities - Selective Coordination Short circuit current normally takes on an asymmetrical
characteristic during the first few cycles of duration. That is,
Compliance with these code sections can best be it is offset about the zero axis, as indicated in Figure 1.
accomplished by conducting a short circuit study and a
selective coordination study.
The protection for an electrical system should not only
be safe under all service conditions but, to insure continuity
of service, it should be selectively coordinated as well. A
C
coordinated system is one where only the faulted circuit is
U
isolated without disturbing any other part of the system. R
Overcurrent protection devices should also provide short- R TIME
circuit as well as overload protection for system E
components, such as bus, wire, motor controllers, etc. N
T
To obtain reliable, coordinated operation and assure
that system components are protected from damage, it is
necessary to first calculate the available fault current at Figure 1
various critical points in the electrical system.
Once the short-circuit levels are determined, the In Figure 2, note that the total short circuit current Ia is
engineer can specify proper interrupting rating require- the summation of two components - the symmetrical RMS
ments, selectively coordinate the system and provide current IS, and the DC component, IDC. The DC component
component protection. is a function of the stored energy within the system at the
initiation of the short circuit. It decays to zero after a few
General Comments on Short-Circuit Calculations cycles due to I2R losses in the system, at which point the
Short Circuit Calculations should be done at all critical short circuit current is symmetrical about the zero axis. The
points in the system. RMS value of the symmetrical component may be deter-
These would include: mined using Ohm`s Law. To determine the asymmetrical
- Service Entrance component, it is necessary to know the X/R ratio of the
- Panel Boards system. To obtain the X/R ratio, the total resistance and total
- Motor Control Centers reactance of the circuit to the point of fault must be
- Motor Starters determined. Maximum thermal and mechanical stress on
- Transfer Switches the equipment occurs during these first few cycles. It is
- Load Centers important to concentrate on what happens during the first
half cycle after the initiation of the fault.
Normally, short circuit studies involve calculating a
bolted 3-phase fault condition. This can be characterized
as all three phases “bolted” together to create a zero
impedance connection. This establishes a “worst case”
condition, that results in maximum thermal and mechanical
stress in the system. From this calculation, other types of
fault conditions can be obtained.
3
Electrical Distribution System
4
3 ø Short-Circuit Current Calculations –
System A System B
3Ø Single Transformer System 3Ø Double Transformer System
Available Utility Available Utility
S.C. MVA 100,000 S.C. KVA 500,000
Fault X1
Fault X1
1 1
400A Switch 400A Switch
5
3ø Short-Circuit Current Calculations – Procedures and Methods
Ohmic Method
3Ø Short Circuit Calculations, Step 9. The symmetrical motor contribution can be
Ohmic Method approximated by using an average multiplying factor
Most circuit component impedances are given in ohms associated with the motors in the system. This factor varies
except utility and transformer impedances which are found according to motor design and in this text may be chosen
by the following formulae* (Note that the transformer and as 4 times motor full load current for approximate
utility ohms are referred to the secondary KV by squaring calculation purposes. To solve for the symmetrical motor
the secondary voltage.) contribution:
1000 (KVsecondary)2
Step 1. †X utility Ω = •I
sym motor contrib = (4) x (Ifull load motor)
S.C. KVA u tility
Step 10. The total symmetrical short-circuit RMS current is
(10)(%X**)(KVsecondary)2 calculated as:
Step 2. X trans Ω =
KVA trans ††
Itotal S.C. sym RMS = (IS.C. sym RMS ) + (Isym motor contrib)
(10)(%R**)(KVsecondary)2
Rtrans Ω = Step 11. Determine X/R ratio of the system to the point of
KVA trans
fault.
Step 3. The impedance (in ohms) given for current
transformers, large switches and large circuit breakers is Xtotal Ω
X/Rratio =
essentially all X. Rtotal Ω
Step 4. Xcable and bus Ω. Step 12. The asymmetrical factor corresponding to the X/R
Rcable and bus Ω. ratio in Step 11 is found in Table 8, Column M m . This
multiplier will provide the worst case asymmetry occurring
Step 5. Total all X and all R in system to point of fault. in the first 1/2 cycle. When the average 3-phase multiplier
is desired use column Ma.
Step 6. Determine impedance (in ohms) of the system by:
Step 13. Calculate the asymmetrical RMS short-circuit
ZT = √(RT)2 + (XT)2 current.
Step 7. Calculate short-circuit symmetrical RMS amperes IS.C. asym RMS = (IS.C. sym RMS) x (Asym Factor)
at the point of fault.
Step 14. The short-circuit current that the motor load can
Esecondary line-line
IS.C. sym RMS = contribute is an asymmetrical current usually approximated
√3 (ZT) as being equal to the locked rotor current of the motor.
•As a close approximation with a margin of safety use:
Step 8. Determine the motor load. Add up the full load
motor currents. The full load motor current in the system is •Iasym motor contrib = (5) x (Ifull load motor)
generally a percentage of the transformer full load current,
depending upon the types of loads. The generally Step 15. The total asymmetrical short-circuit RMS current is
accepted procedure assumes 50% motor load when both calculated as:
motor and lighting loads are considered, such as supplied Itotal S.C. asym RMS = (IS.C. asym RMS) + (Iasym motor contrib)
by 4 wire, 208Y/120V and 480Y/277V volt 3-phase
systems.)
*For simplicity of calculations all ohmic values are single phase distance one way, later compensated for in the three phase short-circuit formula by the factor, √3.
(See Step 7.)
**UL Listed transformers 25 KVA and larger have a ±10% impedance tolerance. Short circuit amperes can be affected by this tolerance.
†Only X is considered in this procedure since utility X/R ratios are usually quite high. For more finite details obtain R of utility source.
•A more exact determination depends upon the sub-transient reactance of the motors in question and associated circuit impedances. A less conservative
method would involve the total motor circuit impedance to a common bus (sometimes referred to as a “zero reactance bus”).
††Arithmetical addition results in conservative values of fault current. More finite values involve vectorial addition of the currents.
Note: The ohms of the circuit components must be referred to the same voltage. If there is more than one voltage transformation in the system, the ohmic
method becomes more complicated. It is recommended that the per-unit method be used for ease in calculation when more than one voltage transformation
exists in the system.
6
3ø Short-Circuit Current Calculations – Procedures and Methods
25' 0.0379
X= x = 0.000158 — 0.000158
1000 6
25’ - 500 kcmil
6 Per Phase (Table 5)
Service Entrance 25' 0.0244
Conductors in Steel Conduit R= x = 0.000102 0.000102 —
1000 6
2000A Switch
Fault X1
1 1
Total R and X = 0.000962 0.00551
Motor Contribution M M
7
3ø Short-Circuit Current Calculations – Procedures and Methods
R = 0.000962 0.000962 —
Fault X1 1 1
400A Switch
LPS-RK-400SP Fuse
(Table 3) X = .00008 — 0.00008
50’ x
X= .0379 = 0.00189 — 0.00189
50’ - 500 kcmil 1000
Feeder Cable (Table 5)
in Steel Conduit
50’ x
R= .0244 = 0.00122 0.00122 —
1000
Fault X2
2 2
.00748 =
X/Rratio = 3.43
.002182
Note: See Ohmic Method Procedure for Formulas. Actual motor contribution
will be somewhat smaller than calculated due to the impedance of the
feeder cable.
8
3ø Short-Circuit Current Calculations – Procedures and Methods
1600A Switch
KRP-C-1500SP Fuse
(Table 3) X = .000050 — .00005
480
IS.C. sym RMS = = 31,405A
√3 (.008824)
.008688 =
X/Rratio = 5.62
.001545
9
3ø Short-Circuit Current Calculations – Procedures and Methods
X = .008688 — .008688
Adjusted Impedance R = .001545 .001545 —
to fault X1
1 1
400A Switch
X = .00008 — .00008
LPS-RK-350SP Fuse
20' x .0327 = —
X= .000327 .000327
1000 2
20' - 2/0 (Table 5)
20' x .0812 =
2 Per Phase R= .000812 .000812 —
Copper in PVC Conduit 1000 2
Total R and X (480V) = .002357 .009095
(208)2 x (.002357)
Rtotal = = .000442 .000442 —
(208V) (480)2
208
IS.C. sym RMS = = 29,911A
√3 (.004015)
.003628 =
X/Rratio = 2.10
.001722
10
3ø Short-Circuit Current Calculations – Procedures and Methods
Per-Unit Method
3ø Short Circuit Calculation Per-Unit Method* Step 9. The symmetrical motor contribution can be
The per-unit method is generally used for calculating approximated by using an average multiplying factor
short-circuit currents when the electrical system is more associated with the motors in the system. This factor varies
complex. according to motor design and in this text may be chosen
as 4 times motor full load current for approximate
After establishing a one-line diagram of the system, calculation purposes. To solve for the symmetrical motor
proceed to the following calculations: ** contribution:
***
† PUX utility KVAbase Isym motor contrib = (4) x (Ifull load motor)
Step 1. =
S.C. KVA utility
Step 10. The total symmetrical short-circuit rms current is
calculated as:
(%X•)(KVAbase )
Step 2. PUX trans = ••
(100)(KVAtrans) Itotal S.C. sym RMS = (IS.C. sym RMS) + (Isym motor contrib)
(%R•)(KVAbase) Step 11. Determine X/R ratio of the system to the point of
PUR trans = fault.
(100)(KVAtrans)
PUX total
X/Rratio =
(XΩ)(KVAbase) PURtotal
Step 3. PUXcomponent (cable, =
switches, CT, bus) (1000)(KV) 2
Step 12. From Table 8, Column Mm, obtain the asymmetrical
factor corresponding to the X/R ratio determined in Step
(RΩ)( KVAbase) 11. This multiplier will provide the worst case asymmetry
Step 4. PURcomponent (cable, = occurring in the first 1/2 cycle. When the average 3-phase
switches, CT, bus) (1000)(KV) 2
multiplier is desired use column Ma.
Step 5. Next, total all per-unit X and all per-unit R in system
to point of fault. Step 13. The asymmetrical RMS short-circuit current can
be calculated as:
Step 6. Determine the per-unit impedance of the system by:
IS.C. asym RMS = (IS.C. sym RMS) x (Asym Factor)
PUZ total = √(PURtotal)2 + (PUX total)2
Step 14. The short-circuit current that the motor load can
Step 7. Calculate the symmetrical RMS short-circuit current contribute is an asymmetrical current usually approximated
at the point of fault. as being equal to the locked rotor current of the motor.***
As a close approximation with a margin of safety use:
KVAbase
IS.C. sym RMS = ***I = (5) x (Ifull load motor)
√3 (KV)(PUZtotal) asym motor contrib
Step 8. Determine the motor load. Add up the full load Step 15. The total asymmetrical short-circuit RMS current
motor currents.(Whenever motor and lighting loads are is calculated as:
considered, such as supplied by 4 wire, 208Y/120 and
••
480Y/277 volt 3 phase systems, the generally accepted ItotalS.C. asym RMS = (IS.C. asym RMS) + (Iasym motor contrib)
procedure is to assume 50% motor load based on the full
load current rating of the transformer.)
* The base KVA used throughout this text will be 10,000 KVA.
** As in the ohmic method procedure, all ohmic values are single-phase distance one way, later compensated for in the three phase short-circuit formula by the
factor, √3. (See Step 7.)
• UL Listed transformers 25KVA and larger have a ± 10% impedance tolerance. Short circuit amperes can be affected by this tolerance.
† Only per-unit X is considered in this procedure since utility X/R ratio is usually quite high. For more finite details obtain per-unit R of utility source.
*** A more exact determination depends upon the sub-transient reactance of the motors in question and associated circuit impedances. A less conservative
method would involve the total motor circuit impedance to a common bus (sometimes referred to as a “zero reactance bus”).
•• Arithmetical addition results in conservative values of fault current. More finite values involve vectorial addition of the currents.
11
3ø Short-Circuit Current Calculations – Procedures and Methods
10,000
Available Utility PUX = = 0.0001 — 0.0001
S.C. MVA 100,000 100,000,000
(3.45) (10,000)
1500 KVA Transformer, PUX = = 0.2300 — 0.2300
480V, 3Ø, (100) (1500)
3.5%Z, 3.45%X, .56%R
(25') (.0379)
x x (10,000)
(1000) (6)
25’ - 500kcmil PUX = = 0.00685 — 0.00685
6 Per Phase (1000) (.480)2
Service Entrance
Conductors in Steel Conduit
(25') (.0244)
x x (10,000)
(1000) (6)
PUR = = 0.0044 0.0044 —
(1000) (.480)2
2000A Switch
(.00005) (10,000)
PUX = = 0.00217 — 0.00217
KRP-C-2000SP Fuse (1000) (.480)2
M M
PUZtotal = √(0.0417)2 + (0.2391)2 = .2430
10,000
IS.C. sym RMS = = 49,489A
√3 (.480)(.2430)
.2391 =
X/Rratio = 5.73
.0417
* Asym Factor = 1.294 (Table 8)
12
3ø Short-Circuit Current Calculations - Procedures and Methods
Adjusted Impedance
to Fault X1
PUX = .2391 — .2391
PUR = .0417 .0417 —
Fault X1 1 1
400A Switch
LPS-RK400SP Fuse
(.00008) (10,000)
PUX = = .0034 — .0034
(1000) (.480)2
50’ x
(.0379) x (10,000)
1000
PUX = = .0822 — .0822
(1000) (.480)2
50’ - 500kcmil
Feeder Cable in
Steel Conduit 50’ x (.0244) x (10,000)
1000
PUR = = .0529 .0529 —
(1000) (.480)2
2 2
Total PUR and PUX = .0946 .3247
Motor Contribution M M
.32477
X/Rratio = = 3.43
.09465
13
3ø Short-Circuit Current Calculations – Procedures and Methods
Available Utility
S.C. KVA 500,000 10,000 =
PUX = .02 — .02
500,000
(.6) (10,000)
PUR = = .06 .06 —
(100) (1000)
(30') (.0303)
x x (10,000)
(1000) (4)
PUX = = .0099 — .0099
(1000) (.48)2
30' - 500kcmil
4 Per Phase
Copper in PVC Conduit (30') (.0220)
x x (10,000)
(1000) (4)
PUR = = .0072 .0072 —
(1000) (.48)2
1600A Switch
(.00005) (10,000)
KRP-C-1500SP Fuse PUX = = .0022 — .0022
(1000) (.48)2
10,000
IS.C. sym RMS = = 31,405A
√ 3 (.48)(.383)
14
3ø Short-Circuit Current Calculations – Procedures and Methods
X1 = .3771 — .3771
Adjusted Impedance to R1 = .0672 .0672 —
Fault X1
1 1
400A Switch
(.00008) (10,000)
PUX = = .0035 — .0035
LPS-RK-350SP Fuse (1000) (.48)2
(20') (.0327)
x x (10,000)
(1000) (2)
PUX = = .0142 — .0142
20’ - 2/0 (1000) (.48)2
2 Per Phase
Copper in PVC conduit
(20') (.0812)
x x (10,000)
(1000) (2)
PUR = = .0352 .0352 —
(1000) (.48)2
(.998) (10,000)
PUX = = .4435 — .4435
(100) (225)
225KVA Transformer,
208V, 3Ø (.666) (10,000)
.998%X, .666%R PUR = = .296 .296 —
(100) (225)
.8383 =
X/Rratio = 2.10
.3984
15
3ø Short-Circuit Current Calculations – Procedures and Methods
SYSTEM B
Fault Study Summary
Bus Record Voltage Available RMS Duties
Name L-L 3 Phase Momentary
(Sym) (Asym)
X1 480 31,363 40,141
X2 208 29,980 31,425
16
3ø Short-Circuit Current Calculations – Procedures and Methods
Point-to-Point Method
The application of the point-to-point method permits the At some distance from the terminals, depending upon wire size, the L-N fault
current is lower than the L-L fault current. The 1.5 multiplier is an
determination of available short-circuit currents with a approximation and will theoretically vary from 1.33 to 1.67. These figures are
reasonable degree of accuracy at various points for either based on change in turns ratio between primary and secondary, infinite
3ø or 1ø electrical distribution systems. This method can source available, zero feet from terminals of transformer, and 1.2 x %X and
1.5 x %R for L-N vs. L-L resistance and reactance values. Begin L-N
assume unlimited primary short-circuit current (infinite bus). calculations at transformer secondary terminals, then proceed point-to-point.
17
3Ø Short-Circuit Current Calculations – Procedures and Methods
25' - 500kcmil
Step 3. IS.C.= 1804 x 28.57 = 51,540A
6 Per Phase
Service Entrance 1.732 x 25 x 51,540 =
Conductors in Steel Conduit Step 4. f= 0.0349
6 x 22,185 x 480
2000A Switch 1
Step 5. M= = .9663
1 + .0349
KRP-C-2000SP Fuse
Step 6. IS.C.sym RMS = 51,540 x .9663 = 49,803A
Fault X1
1
IS.C.motor contrib = 4 x 1,804 = 7,216A
400A Switch
Fault X2
50' - 500 kcmil
Feeder Cable Step 4. Use IS.C.sym RMS @ Fault X1 to calculate "f"
in Steel Conduit
1.732 x 50 x 49,803 =
f= .4050
22,185 x 480
1
Step 5. M= = .7117
1 + .4050
Fault X2
2
Motor Contribution
M Step 6. IS.C.sym RMS = 49,803 x .7117 = 35,445A
18
3Ø Short-Circuit Current Calculations – Procedures and Methods
LPS-RK-350SP Fuse
Fault X2
1
M= = .4286
1 + 1.333
Comparison of Results
System A System B
Ohmic Per-Unit TRON® PTP Ohmic Per-Unit TRON® PTP
Sym. Asym. Sym. Asym. Sym. Asym. Sym. Sym. Asym. Sym. Asym. Sym. Asym. Sym.
X1 X1 31,405 40,355 31,405 40,355 31,363 40,145 33,215
W/O Motor 49,489 64,039 49,489 64,039 49,992 64,430 49,803 X2 29,911 31,380 29,911 31,380 29,980 31,425 29,731
W/Motor 56,705 73,059 56,705 73,059 58,414 77,308 57,019
X2
W/O Motor 35,621 40,929 35,621 40,929 36,126 41,349 35,445
W/Motor 42,837 49,949 42,837 49,949 44,847 53,111 42,661
Notes:
1. OHMIC and PER UNIT methods assume 100% motor contribution at X1,
then at X2.
2. TRON modeled 100% motor contribution by assuming 1500 HP load,
located at Point X2.
3. PTP method added symmetrical motor contribution at X1, then at X2.
19
1ø Short-Circuit Current Calculations – 1ø Transformer System
20
1ø Short-Circuit Current Calculations –1ø Transformer System
(1.22) (10,000)
PUX = = 1.6267 — 1.6267
(100) (75)
75KVA, 1Ø Transformer,
1.22%X, .68%R
(.68) (10,000)
PUR = = .9067 .9067 —
(100) (75)
Negligible Distance
400A Switch
2(.00008) (10,000)
PUX = = .0278 — .0278
LPN-RK-400SP Fuse (1000) (.240)2
25' x
2x .0379 x 10,000
1000
PUX = = .3289 — .3289
(1000) (.240)2
25'
25' - 500kcmil 2x x .0244 x 10,000
1000
Magnetic Conduit PUR = = .2118 .2118 —
(1000) (.240)2
10,000
IS.C. sym RMS = = 16,984A
L-L @ 240V (.240) (2.4532)
Note: See "Data Section" for impedance data for the electrical components.
21
1ø Short-Circuit Current Calculations – 1ø Transformer System
400A Switch
(.00008) (10,000)
PUX* = = .0556 — .0556
LPN-RK-400SP Fuse (1000) (.120)2
25' x
2x .0379 x 10,000
1000
PUX** = = 1.316 — 1.316
(1000) (.120)2
25' x
25' - 500kcmil 2x .0244 x 10,000
1000
Magnetic Conduit PUR** = = .8472 .8472 —
(1000) (.120)2
10,000
IS.C. sym RMS = = 20,041A
L-N @ 120V (.120) (4.158)
Note: See "Data Section" for impedance data for the electrical components.
* The multiplier of two (2) is not applicable since on a line to neutral fault, only
one switch pole is involved.
** Assumes the neutral conductor and the line conductor are the same size.
22
1ø Short-Circuit Current Calculations – 1ø Transformer System
100 =
Step 2. Multiplier = 71.43
1.40
x x
75KVA, 1Ø Transformer, Step 4. f = 2 25 22,322 = .2096
1.22%X, .68%R 22,185 x 240
1.40%Z
120/240V
1 = .8267
Negligible Distance Step 5. M=
1 + .2096
LPN-RK-400SP Fuse
25' - 500kcmil
Magnetic Conduit
23
1ø Short-Circuit Current Calculations – 1ø Transformer System
100 =
Step 2. Multiplier = 71.43
1.40
Step 5. M= 1 = .6139
1 + .6288
400A Switch
Step 6. IS.C. L-N (X1) = 33,483 x .6139 = 20,555A
LPN-RK-400SP Fuse
* Assumes the Neutral conductor and the line conductor are the same size.
25' - 500kcmil
Magnetic Conduit
Comparison of Results
Per-Unit Method vs. Point-to-Point Method
Per-Unit PTP
Method Method
X1
Line-Line 16,984A 18,453A
Line-Neutral 20,041A 20,555A
24
Data Section
0
Table 2. Current Transformer Reactance Data
0.5 1 2 5 10 20 50 100 200 500 1000 Approximate Reactance of Current Transformers*
Self-Cooled Transformer Rating in MVA
Reactance in Ohms for
This table has been reprinted from IEEE Std 141-1986, IEEE Recommended Primary Current Various Voltage Ratings
Practice for Electric Power Distribution for Industrial Plants, Copyright© 1986 Ratings - Amperes 600-5000V 7500V 15,000V
by the Institute of Electrical and Electronics Engineers, Inc with the 100 - 200 0.0022 0.0040 —
permission of the IEEE Standards Department. 250 - 400 0.0005 0.0008 0.0002
Table 1.2. Impedance Data for Three Phase Transformers 500 - 800 0.00019 0.00031 0.00007
KVA %R %X %Z X/R 1000 - 4000 0.00007 0.00007 0.00007
3.0 3.7600 1.0000 3.8907 0.265 Note: Values given are in ohms per phase. For actual values, refer to manu-
6.0 2.7200 1.7200 3.2182 0.632 facturers' data.
9.0 2.3100 1.1600 2.5849 0.502
15.0 2.1000 1.8200 2.7789 0.867 This table has been reprinted from IEEE Std 241-1990, IEEE Recommended
30.0 0.8876 1.3312 1.6000 1.5 Practice for Commercial Building Power Systems, Copyright© 1990 by the
45.0 0.9429 1.4145 1.7000 1.5 Institute of Electrical and Electronics Engineers, Inc. with the permission of
75.0 0.8876 1.3312 1.6000 1.5 the IEEE Standards Department.
112.5 0.5547 0.8321 1.0000 1.5
150.0 0.6657 0.9985 1.2000 1.5 Table 3. Disconnecting Switch Reactance Data
225.0 0.6657 0.9985 1.2000 1.5 (Disconnecting-Switch Approximate Reactance Data, in Ohms*)
300.0 0.6657 0.9985 1.2000 1.5 Switch Size Reactance
500.0 0.7211 1.0816 1.3000 1.5 (Amperes) (Ohms)
750.0 0.6317 3.4425 3.5000 5.45 200 0.0001
1000.0 0.6048 3.4474 3.5000 5.70 400 0.00008
1500.0 0.5617 3.4546 3.5000 6.15 600 0.00008
2000.0 0.7457 4.9441 5.0000 6.63 800 0.00007
2500.0 0.7457 4.9441 5.0000 6.63 1200 0.00007
Note: UL Listed transformers 25KVA and greater have a ±10% tolerance on 1600 0.00005
2000 0.00005 1 Pole
their nameplate impedance.
3000 0.00004
Table 1.3. Impedance Data for Single Phase Transformers
4000 0.00004
Suggested Normal Range Impedance Multipliers**
X/R Ratio of Percent For Line-to-Neutral Note: The reactance of disconnecting switches for low-voltage circuits
kVA for Impedance (%Z)* Faults (600V and below) is in the order of magnitude of 0.00008 - 0.00005
1Ø Calculation for %X for%R ohm/pole at 60 Hz for switches rated 400 - 4000 A, respectively.
25.0 1.1 1.2–6.0 0.6 0.75
37.5 1.4 1.2–6.5 0.6 0.75 *For actual values, refer to manufacturers’ data.
50.0 1.6 1.2–6.4 0.6 0.75
This table has been reprinted from IEEE Std 241-1990, IEEE Recommended
75.0 1.8 1.2–6.6 0.6 0.75
Practice for Commercial Building Power Systems, Copyright© 1990 by the
100.0 2.0 1.3–5.7 0.6 0.75
Institute of Electrical and Electronics Engineers, Inc. with the permission of
167.0 2.5 1.4–6.1 1.0 0.75
the IEEE Standards Department.
250.0 3.6 1.9–6.8 1.0 0.75
333.0 4.7 2.4–6.0 1.0 0.75
500.0 5.5 2.2–5.4 1.0 0.75
* National standards do not speciify %Z for single-phase transformers. Consult
manufacturer for values to use in calculation.
** Based on rated current of the winding (one–half nameplate kVA divided by
secondary line-to-neutral voltage).
Note: UL Listed transformers 25 KVA and greater have a ± 10% tolerance on
their impedance nameplate.
This table has been reprinted from IEEEStd 242-1986 (R1991), IEEE
Recommended Practice for Protection and Coordination of Industrial and
Commercial Power Systems, Copyright© 1986 by the Institute of Electrical
and Electronics Engineers, Inc. with the permission of the IEEE Standards
Department.
25
Data Section
This table has been reprinted from IEEE Std 241-1990, IEEE Recommended Practice for Commercial
Building Power Systems, copyright © 1990 by the Institute of Electrical and Electronics Engineers,
Inc. with the permission of the IEEE Standards Department.
26
Data Section
Ampacity Busway
Plug-In Feeder High Impedance
Copper Aluminum Copper Aluminum Copper
225 28700 23000 18700 12000 —
400 38900 34700 23900 21300 —
600 41000 38300 36500 31300 —
800 46100 57500 49300 44100 —
1000 69400 89300 62900 56200 15600
1200 94300 97100 76900 69900 16100
1350 119000 104200 90100 84000 17500
1600 129900 120500 101000 90900 19200
2000 142900 135100 134200 125000 20400
2500 143800 156300 180500 166700 21700
3000 144900 175400 204100 188700 23800
4000 — — 277800 256400 —
Note: These values are equal to one over the impedance per foot for
impedances in Table 7, Page 28.
27
Data Section
28
Data Section
Asymmetrical Factors
Table 8. Asymmetrical Factors Selective Coordination (Blackout Prevention)
Ratio to Symmetrical RMS Amperes Having determined the faults that must be
Short Circuit Short Maximum 1 phase Maximum 1 phase Average 3 phase interrupted, the next step is to specify Protective
Power Factor, Circuit Instantaneous RMS Amperes at RMS Amperes at
Devices that will provide a Selectively Coordinated
Percent* X/R Ratio Peak Amperes Mp 1/2 Cycle Mm 1/2 Cycle Ma*
(Asym.Factor)* System with proper Interrupting Ratings.
0 ∞ 2.828 1.732 1.394
1 100.00 2.785 1.697 1.374 Such a system assures safety and reliability
2 49.993 2.743 1.662 1.354 under all service conditions and prevents needless
3 33.322 2.702 1.630 1.336
4 24.979 2.663 1.599 1.318
interruption of service on circuits other than the one
5 19.974 2.625 1.569 1.302 on which a fault occurs.
6 16.623 2.589 1.540 1.286
7 14.251 2.554 1.512 1.271 The topic of Selectivity will be Discussed in the
8 13.460 2.520 1.486 1.256
next Handbook, EDP II.
9 11.066 2.487 1.461 1.242
10 9.9301 2.455 1.437 1.229
11 9.0354 2.424 1.413 1.216 Component Protection (Equipment Damage Prevention)
12 8.2733 2.394 1.391 1.204 Proper protection of electrical equipment
13 7.6271 2.364 1.370 1.193 requires that fault current levels be known. The
14 7.0721 2.336 1.350 1.182
15 6.5912 2.309 1.331 1.172
characteristics and let-through values of the
16 6.1695 2.282 1.312 1.162 overcurrent device must be known, and compared
17 5.7947 2.256 1.295 1.152 to the equipment withstand ratings. This topic of
18 5.4649 2.231 1.278 1.144 Component Protection is discussed in the third
19 5.16672 2.207 1.278 1.135
Handbook, EDP III.
20 4.8990 2.183 1.247 1.127
21 4.6557 2.160 1.232 1.119
22 4.4341 2.138 1.219 1.112
23 4.2313 2.110 1.205 1.105
24 4.0450 2.095 1.193 1.099
25 3.8730 2.074 1.181 1.092
26 3.7138 2.054 1.170 1.087
27 3.5661 2.034 1.159 1.081
28 3.4286 2.015 1.149 1.076
29 3.3001 1.996 1.139 1.071
30 3.1798 1.978 1.130 1.064
31 3.0669 1.960 1.122 1.062
32 2.9608 1.943 1.113 1.057
33 2.8606 1.926 1.106 1.057
34 2.7660 1.910 1.098 1.050
35 2.6764 1.894 1.091 1.046
36 2.5916 1.878 1.085 1.043
37 2.5109 1.863 1.079 1.040
38 2.4341 1.848 1.073 1.037
39 2.3611 1.833 1.068 1.034
40 2.2913 1.819 1.062 1.031
41 2.2246 1.805 1.058 1.029
42 2.1608 1.791 1.053 1.027
43 2.0996 1.778 1.049 1.024
44 2.0409 1.765 1.045 1.023
45 1.9845 1.753 1.041 1.021
46 1.9303 1.740 1.038 1.019
47 1.8780 1.728 1.035 1.017
48 1.8277 1.716 1.032 1.016
49 1.7791 1.705 1.029 1.014
50 1.7321 1.694 1.026 1.013
55 1.5185 1.641 1.016 1.008
60 1.3333 1.594 1.009 1.004
65 1.1691 1.517 1.005 1.001
70 1.0202 1.517 1.002 1.001
75 0.8819 1.486 1.0008 1.0004
80 0.7500 1.460 1.0002 1.0001
85 0.6198 1.439 1.00004 1.00002
100 0.0000 1.414 1.00000 1.00000
*Reprinted by permission of National Electrical Manufacturer's Association from
NEMA Publication AB-1, 1986, copyright 1986 by NEMA.
29