0% found this document useful (0 votes)
49 views

Profibus: in The Process Industries #2

The document discusses PROFIBUS PA and its physical layer known as MBP. MBP uses Manchester encoding and bus powering to allow data and power transmission over the same cable. It can be interfaced with PROFIBUS RS485 networks using various devices that support different speeds up to 12 Mbps. This flexible architecture allows MBP segments to be distributed anywhere in a plant and connected to a PROFIBUS master system.

Uploaded by

Vijayachandran K
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
49 views

Profibus: in The Process Industries #2

The document discusses PROFIBUS PA and its physical layer known as MBP. MBP uses Manchester encoding and bus powering to allow data and power transmission over the same cable. It can be interfaced with PROFIBUS RS485 networks using various devices that support different speeds up to 12 Mbps. This flexible architecture allows MBP segments to be distributed anywhere in a plant and connected to a PROFIBUS master system.

Uploaded by

Vijayachandran K
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 52

PROFIBUS

in the Process Industries #2


Audio: call (641) 715-3222
use access Code: 597-800-879
(no audio via the web)
We will begin at 2:00pm ET, 1:00pm CT, 12:00n MT, 11:00am PT

Questions (live version): Enter your question at any time during the
presentation in the “Question and Answer” frame. We’ll address it
at the end of the webinar.

Questions (archived version): Email your question to


[email protected]. We’ll answer in a day or two.
www.us.profibus.com 1
Presenters

Moderator: Mike Aldridge, Technical Director, PTO.


PTO is the non-profit, member-supported organization
that educates North America about PROFIBUS and
PROFINET.
.

Presenter: Ron Mitchell,


PROFIBUS Consulting Engineer,
RC Systems LLC
Certified PROFIBUS Network Engineer
Certified PA Network Engineer

www.us.profinet.com 2
Webinar Sponsors

www.us.profinet.com 3
Training Sponsors

www.us.profinet.com 4
Resources
• Archived Webinars, us.profibus.com:

Archived Webinars
PROFIBUS Process #1

www.us.profinet.com 5
PROFIBUS PA

MBP
PROFIBUS PA Physical Layer

www.us.profibuwww.us.profibus.com
www.us.profibus.com 6
s.com
PROFIBUS PA Physical Layer - MBP
• References to PROFIBUS PA Imply Use of
MBP (An IEC 61158-2 Physical Layer)
– Typically For Use in Explosive Environments

www.us.profibus.com 7
PROFIBUS PA Physical Layer - MBP
• Protocol Is Based on Standard PROFIBUS
DPV0 and DP Extended (DPV1) Protocol
– DPV0 Basic For Cyclic I/O & Diagnostics
• Input Process Variables, Output Set Points, etc.
• Reporting Measurement Failure, Zero Point Error, etc.
– DPV1 Extensions For Acyclic Messages
• On-Demand Access of Device Parameters
– Reading Measured Value Attribute, i.e., Pressure
– Setting Measuring Units, i.e., Atm, mm Hg, mm H2O, etc.
– Standard Master Controls I/O Data Exchange for
All Field Devices
www.us.profibus.com 8
PROFIBUS PA Physical Layer - MBP
• MBP Physical Setup
– Physical Layer Based on MBP(-IS) from IEC 61158
• Manchester-encoded, Bus-Powered (Intrinsically Safe)
– Synchronous Data Transfer With Manchester Coding
– Power AND Data Are Transferred Via the Same Cable
– Different Components Than RS485 for the Physical Setup
(Cable, Connectors, Termination…)
– Rules Regarding Topology and Length According to
MBP(-IS)
– Transmission Rate Is 31.25Kbaud
– Same as FF – Both Came From SP50

www.us.profibus.com 9
PROFIBUS PA Physical Layer - MBP
• FF Uses Two Protocols: HSE & FF
• PROFIBUS Uses a Single Protocol, Regardless
of the Medium
– RS485
SD LE LEr SDr DA SA FC DU.. FCS ED

– MBP
P SOF SD LE LEr SDr DA SA FC DU.. CRC EOF

www.us.profibus.com 10
PROFIBUS Physical Layers - MBP
• PROFIBUS RS485 - MBP Interfaces
– Non-Transparent, High-Speed
• Siemens
– DP/PA Link & Couplers: Up to 12,000,000 bits/sec

DP/PA Link DP/PA Segment Coupler

www.us.profibus.com 11
PROFIBUS Physical Layers - MBP
• PROFIBUS RS485 - MBP Interfaces
– Transparent, Low-Speed
• Pepperl+Fuchs
– SK1: 93,750 bits/sec
• Siemens
– DP/PA Coupler: 45,450 bits/sec

DP/PA Segment Coupler


(Used Stand-Alone)

www.us.profibus.com 12
PROFIBUS Physical Layers - MBP
• PROFIBUS RS485 - MBP Interfaces
– Transparent, High-Speed
• ABB
– LD 800P: Up to 12,000,000 bits/sec

www.us.profibus.com 13
PROFIBUS Physical Layers - MBP
• PROFIBUS RS485 - MBP Interfaces
– Transparent, High-Speed
• Pepperl+Fuchs
– SK2: Up to 12,000,000 bits/sec
– FieldConnex Power Hub : Up to 12,000,000 bits/sec

www.us.profibus.com 14
PROFIBUS PA Physical Layer - MBP
• PROFIBUS RS485 - MBP Interface
– Non-Transparent, High-Speed
PLC/
DCS

RS485
12Mbaud

Siemens DP/PA Link + Couplers(1-5)


Link & Couplers
GSD
Slave address ⇒ MBP-IS
31.25 Kbaud

www.us.profibus.com 15
PROFIBUS PA Physical Layer - MBP
• Non-Transparent, High-Speed Interface –
Device Addressing
1
RS485 PROFIBUS
Addresses 1 - 125
RS485 PROFIBUS
RS485/MBP Link Interface is Available
an RS485 Slave With an Up to 12MBaud
ADDRESS

9
24 V Coupler Has
NO
ADDRESS
Addresses 3 - 125
Available for
MBP Devices

DCS/PLC Master Does


Not See MBP Slave
3 4 Directly by Address

PROFIBUS MBP 31.25Kbaud


www.us.profibus.com 16
PROFIBUS PA Physical Layer - MBP
• Non-Transparent, High-Speed Interface Device
Addressing – Flexible Architecture
– Drop Into Process Areas Wherever Needed RS485 PROFIBUS
– Each Interface Has a Separate Address Space Addresses 1 - 125
1 Available
PROFIBUS RS485
Up to 12MBaud

9 23 11
24 V 24 V 24 V
MBP PROFIBUS MBP PROFIBUS MBP PROFIBUS
Addresses 3 - 125 Addresses 3 - 125 Addresses 3 - 125
Available Available Available

3 4 3 4 3 4
www.us.profibus.com 17
PROFIBUS MBP @ 31.25Kbaud PROFIBUS MBP @ 31.25Kbaud
PROFIBUS MBP @ 31.25Kbaud
PROFIBUS PA Physical Layer - MBP
• PROFIBUS RS485 - MBP Interface
– Transparent, Low-Speed – Siemens, P+F

One PROFIBUS
1 RS485-MBP Address Space
PROFIBUS RS485 1-125
at 45.45, 93.75kbaud Coupler

24 V 24 V

GSD GSD GSD GSD

3 9 10 15
PROFIBUS MBP @ 31.25Kbaud www.us.profibus.com
PROFIBUS MBP @ 31.25Kbaud
18
PROFIBUS PA Physical Layer - MBP
• PROFIBUS RS485 - MBP Interface
– Transparent, High-Speed – ABB, P+F
RS485-MBP One PROFIBUS
PROFIBUS RS485
Up to 12MBaud Coupler Address Space
1 1-125

24 V 24 V

GSD GSD GSD GSD

3 9 10 15
PROFIBUS MBP @ 31.25Kbaud www.us.profibus.com
PROFIBUS MBP @ 31.25Kbaud
19
PROFIBUS PA Physical Layer - MBP
• Flexible Architecture – All Interface Solutions

PROFIBUS RS485
High-Speed Discretes – Front-End & Back-End
PROFIBUS
Master
System

MBP Segments Can be Distributed


Along RS485 Bus as Needed…Not
Required to Originate at Master MBP MBP MBP
Segment Segment Segment

AS-Interface AS-Interface AS-Interface


www.us.profibus.com 20
Bus Bus Bus
PROFIBUS PA Physical Layer - MBP
• Connection Technology - MBP

www.us.profibus.com 21
PROFIBUS PA Physical Layer - MBP
• Connection Technology - MBP

www.us.profibus.com 22
PROFIBUS PA Physical Layer - MBP
• MBP Network Termination

Termination:
•Acts as a shunt
•Prevents Reflections (Secondarily)

www.us.profibus.com 23
PROFIBUS PA Physical Layer - MBP
• What Does Intrinsic Safety Get You?
– Elimination of Use of Expensive Traditional
Technologies
• Explosion Proof Instruments/Enclosures
• Pressurized Enclosures
• Purged Enclosures
• Submersion
– Oil
– Sand

www.us.profibus.com 24
PROFIBUS PA Physical Layer - MBP
• MBP Network Setup Rules – Intrinsically
Safe Models
– Entity Model – “Concentrated” Capacitance
& Inductance
• Original IS Model (1950s) – Used for 4-20mA
– FISCO Model – “Distributed” Capacitance &
Inductance
• Fieldbus Intrinsically Safe COncept

www.us.profibus.com 25
PROFIBUS PA Physical Layer - MBP
• Key Advantages of FISCO vs Entity Model
– Higher Bus Current, Allowing More Field Devices per
Segment
– Elimination of Cable Parameter Calculations
– Simplification of the Safety Documentation – Just a
List of Devices
– Addition of New Devices Without Reviewing the
Segment for Intrinsic Safety

www.us.profibus.com 26
PROFIBUS PA Physical Layer - MBP
• MBP Network Setup Rules – Maximum
Segment Lengths
– Theoretical Maximums Based on Cable
Type

Possibly Existing Wiring / Instrumentation Cable


www.us.profibus.com 27
PROFIBUS PA Physical Layer - MBP
• MBP Network Setup Rules – Maximum
Segment/Spur Lengths
– Hazardous Area Cable Length Maximums
for Different Models Using Type A Cable

60m

www.us.profibus.com 28
PROFIBUS PA Physical Layer - MBP
• MBP Device Requirements For Intrinsic
Safety Models: Entity, FISCO
– Uses the “Manchester-Encoded Bus
Powered” Physical Layer in Accordance
With IEC 61158-2
– Acts As a Passive Current Sink (Only One
Power Source Allowed On a Segment)
– Basic Current Consumption ≥ 10 mA

www.us.profibus.com 29
PROFIBUS PA Physical Layer - MBP
• MBP Device & Power Source Requirements
For All Intrinsically Safe Segments - No
Matter Which Model Is Used
– The Device Parameters (Ui, Ii, Pi), Must Satisfy
the Following Conditions In Relation to the
Power Source Parameters (Uo, Io, Po ):
• Ui ≥ Uo for the Power Source
• Ii ≥ Io for the Power Source
• Pi ≥ Po for the Power Source

www.us.profibus.com 30
PROFIBUS PA Physical Layer - MBP
• MBP Device Requirements For FISCO
Intrinsically Safe Model
– The Device Parameter Requirements Shown Here
Are For FISCO-Certified Instruments
• Ci ≤ 5 nF
• Li ≤ 10 µH

www.us.profibus.com 31
PROFIBUS PA Physical Layer - MBP
• MBP Cable Requirements For FISCO
Intrinsically Safe Model
– Cable Used in FISCO Installation Must Meet
the Following:
• Resistance: 15 Ω/km < R’ < 150 Ω /km
• Inductance: 0.4 mH/Km ≤ L’ ≤ 1 mH/km
• Capacitance: 45 nF/km ≤ C’ ≤ 200 nF/km

www.us.profibus.com 32
PROFIBUS PA Physical Layer - MBP
• Network Topology – Entity Model
Spur
Lines
PROFIBUS RS485

Star

Termination (Main) Line


24 V
At Ends of
Longest PROFIBUS MBP T Branch Termination
Cable Run
At Ends of
Longest
Cable Run
Entity And/Or FISCO Certified Devices
www.us.profibus.com 33
PROFIBUS PA Physical Layer - MBP
• IS Calculations – Entity Model
– Since the Entity Model Imposed No Capacitance
& Inductance Requirements on Either Devices or
Cable, They Must Be Incorporated Into the IS
Calculations
• The Common Device Parameters Must Be Checked
(Ui ≥ Uo , Ii ≥ Io , Pi ≥ Po)
• Additionally, the Following Conditions Must Be
Satisfied:
– (Lcable + ∑Li devices) ≤ Lo of Power Source
– (Ccable + ∑Ci devices) ≤ Co of Power Source
www.us.profibus.com 34
PROFIBUS PA Physical Layer - MBP
• Network Topology – FISCO Model
Spur
Line
PROFIBUS RS485

Star

Termination (Main) Line


24 V
At Ends of
Longest PROFIBUS MBP T Branch Termination
Cable Run
At Ends of
Longest
Only FISCO Certified Devices Cable Run

(and Associated Apparatus)


www.us.profibus.com 35
PROFIBUS PA Physical Layer - MBP
• IS Calculations – FISCO Model
– Relationship of Device/Power Source
Parameters Are Implicit for FISCO-Certified
Devices and Components
Power Supply Field Device
Uo O 17.5V Ui P 17.5V
Io O 380mA Ii P 380mA
Po O 5.32W Pi P 5.32W
--- Ci O 5nF
--- Li O 10uH

– Maximum Segment & Spur Lengths Must be


Observed
36
PROFIBUS PA Physical Layer - MBP
• Calculating IS Load – How Many Devices?
– Total Current Consumption:
• ∑Iq + <Active Components I Usage> + Highest IFDE
– Most Field Barriers, Segment Protectors, Short-Circuit-Protected
Junction Boxes Use Some Current & Induce Some Voltage Drop.
Two Types Are:
• Current-Limiting (Limits SC Draw to 40-60mA)
- Check Trip Current
• Fold-Back (Disconnects SC, Draws 2mA)

– FISCO Power Source Delivers ~115mA(IIC)


– Entity Power Source Delivers ~80mA(IIC)
www.us.profibus.com 37
PROFIBUS PA Physical Layer - MBP
• Calculating IS Load – How Many Devices?
– Voltage Must Be 9V at End of Cable Run
• Calculate Voltage Drop for Cable Run and Current
Draws of the Devices
– Type A Cable Resistance Is 44 Ω/Km
– Quick & Dirty Calculation
• Assume All Devices at “Last” Drop
– If Calculated Voltage is <9V, Recalculate Using Real
Network Geometry

www.us.profibus.com 38
PROFIBUS PA Physical Layer - MBP
• Calculating Bus Load – How Long?
– Devices Require 9V to Operate
• Type A Cable Resistance is 44Ω/km (.044 Ω /m)V?
Uout=12.8V
225m 225m 225m 225m

P/S 20mA
18mA 18mA 17mA 17mA
100m

• Voltage at Last Device =


12.8V- [.044 Ω /m*(100m*18mA + 325m*18mA +
550*17m+775*17mA+1000*20mA)]
• Voltage at Last Device = 12.8V- (.0792V + 0.2574V +
0.4114V+0.5797V+0.88V) = 12.8V – 2.21V = 10.59V 
www.us.profibus.com
39
PROFIBUS PA Physical Layer - MBP
• Non-IS Calculations
– Only Concerned About Total Current Draw &
Voltage at Last Device

www.us.profibus.com 40
PROFIBUS PA Physical Layer - MBP
• High-Power Trunk Line Concept
– High Voltage /Current On Trunk Line (30V/500mA)
• Assumes No “Hot” Maintenance On Trunk Line
• Trunk Lies in Div 2 Area
• Can Get Longer Trunk Line, More Power
– Field Barriers Are Utilized to Interface the Trunk to the
IS Spurs (Galvanic Isolation Between Trunk & Spurs)
• Energy Is Limited On the Spur Connections
– One Device Per Spur
• Spurs Are Short-Circuit Protected
• Spurs May Be 120m In Length
www.us.profibus.com 41
PROFIBUS PA Physical Layer - MBP
• High-Power Trunk Line Concept

PROFIBUS RS485

P/S Class I/Div 2


30V, 500mA

Barrier Barrier Barrier

Intrinsically Safe SC Protection Class I/Div 1 Isolated

FISCO or Entity Devices


www.us.profibus.com 42
PROFIBUS Physical Layers - MBP
• High-Power Trunk Line Concept
– Vendors With Field Barrier Solutions
• ABB, FB-900 Series

www.us.profibus.com 43
PROFIBUS Physical Layers - MBP
• High-Power Trunk Line Concept
– Vendors With Field Barrier Solutions
• Moore-Hawke, RMA-100 Series

www.us.profibus.com 44
PROFIBUS Physical Layers - MBP
• High-Power Trunk Line Concept
– Vendors With Field Barrier Solutions
• MTL/Relcom, 9311-FB & 9312-FB
• Pepperl+Fuchs, FieldConnex Power Hub

www.us.profibus.com 45
PROFIBUS Physical Layers - MBP
• High-Power Trunk Line Concept
– Vendors With Field Barrier Solutions
• Stahl, 9411/21 Series

www.us.profibus.com 46
PROFIBUS Physical Layers - MBP
• High-Power Trunk Line Concept
– Vendors With Field Barrier Solutions
• Stonel, 4610xx & 4650xx Series

www.us.profibus.com 47
PROFIBUS Physical Layers - MBP
• High-Power Trunk Line Concept
– Vendors With Field Barrier Solutions
• Turck, MBD48-T415/Ex

www.us.profibus.com 48
PROFIBUS PA Physical Layer - MBP
• MBP Redundancy – Moore-Hawke Solution

www.us.profibus.com 49
PROFIBUS PA Physical Layer - MBP
• MBP Redundancy – Siemens Solution

www.us.profibus.com 50
Resources
• More training available, see us.profibus.com:

Certified Network Engineer training


PROFIBUS
And
PROFINET

Upcoming Webinars
PROFIBUS Process
2, 3 & 4

www.us.profinet.com 51
• Thank You.
• PROFIBUS in the Process Industries
Webinar # 3
Monday July 28th
2:00pm ET

www.us.profinet.com 52

You might also like