Gas insulated
• SF6 gas insulated switchgear with extremely • Maintenance free and complete safety with
ring main unit compact and robust design no exposure to live parts
• 12 kV, 630 A, 21 kA for 3 sec • Mandatory safety interlocks ensuring
• Metal enclosed design with IP54 protection operator safety
• IAC classified 21kA/1s • Manufactured according to ISO 9001, 14001
• Both sides extensible and OHSAS 18001
• Stand alone vacuum circuit breakers or • Complete solutions, including applications for
switch disconnectors remote control and monitoring
• Type tested according to latest IEC standards • Recyclable and very low environmental impact
• Robotically welded SS304 tank
• Vacuum circuit breaker with high mechanical
endurance of 10000 operations
Technical data
C Module V Module
Switch Earthing Vacuum circuit Earthing
disconnector switch breaker switch
Rated voltage kV 12/13.8 12/13.8 12/13.8 12/13.8
Rated frequency Hz 50/60 50/60 50/60 50/60
Power frequency withstand voltage kVrms 38 38 38 38
- across disconnector kVrms 45 45 45 45
Lightning impulse withstand voltage kVp 95 95 95 95
- across isolating distance kVp 110 110 110 110
Rated normal current* A 630 630 630 630
Breaking capacities
- active load breaking current A 630
- closed loop breaking current A 630
- cable charging breaking current A 25 25 (Class C2)
- line charging breaking current A 1 10 (Class C2)
- earth fault breaking current A 75
- earth fault cable and line charging A 43.5
- short circuit breaking current kA 21
Making capacity kAp 52.5/54.6 52.5/54.6 52.5/54.6 52.5/54.61)
Short time current (3-sec) kA 21 21 21 21
Short time current (1-sec) kA 21 (Earthing 21 (Earthing
circuit) Circuit)
Electrical & mechanical classes E3, C2, M1 E2, M0 E2, C2, S1, M1+3000, E2, M0
M2 (Optional)
Rated operating sequence - 0-0.3 sec-CO-3 min-CO
Rated filling level for insulation 0.02 MPa
Internal arc classification AFLR 10kA 0.1s / AF 21kA 1s
1) Earthing operation is through vacuum circuit breaker, hence no making capacity is assigned.
Dimensions
— —
For more information, please contact NOTE:
service department at Data and illustration are not binding. We reserve the right
ABB India Limited to make changes in the course of technical development.
Plot No. 79, Street No. 17, MIDC Estate,
Satpur, Nashik, Maharashtra -422 007, India
Tel: +91 253-2201200 Fax: +91 253-2351260
1VYN403090-109 Rev.0
abb.com/mediumvoltage