Installation and Service Manual: Wall Mounted Gas Condensing Boiler
Installation and Service Manual: Wall Mounted Gas Condensing Boiler
en
These instructions include the Benchmark Commissioning Checklist and should be left with the
user for safe keeping. They must be read in conjunction with the Flue Installation Guide.
Dear customer,
Thank you for purchasing this appliance.
Please read this manual carefully before using the product and keep it in a safe place for future reference.
In order to ensure continued safe and efficient operation we recommend that the product is regularly maintained. Our Service
and After Sales organization can assist with this.
2 Introduction ................................................................................................8
2.1 Symbols used .......................................................8
2.2 Abbreviations ........................................................8
2.3 General ..................................................................8
2.3.1 Manufacturer’s liability .............................................8
2.3.2 Installer’s liability .....................................................9
2.3.3 User’s liability ..........................................................9
02092014 - 7619497-02 1
Contents
5 Installation ................................................................................................19
5.1 Regulations governing installation ...................19
5.2 Choice of the location ........................................20
5.2.1 Type plate .............................................................20
5.2.2 Location of the boiler .............................................20
02092014 - 7619497-02 2
6 Commissioning ........................................................................................42
6.1 Control panel .......................................................42
6.2 Check points before commissioning ................43
6.2.1 Preparing the boiler for commissioning .................43
6.2.2 Hydraulic circuit .....................................................43
6.2.3 Electrical connections ...........................................43
02092014 - 7619497-02 3
Contents
9 Troubleshooting .......................................................................................63
9.1 Error codes ..........................................................63
9.2 Shutdowns and lock-outs ..................................63
9.2.1 Blocking .................................................................63
9.2.2 Lock out .................................................................65
11 Appendix ...................................................................................................71
11.1 User instruction card ..........................................71
11.2 Gas boiler system commissioning
checklist ..............................................................72
11.3 Service record .....................................................73
02092014 - 7619497-02 4
EC declaration of conformity
02092014 - 7619497-02 5
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
6 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
Choose Building
Regulations Notification
Route
R000696-01
02092014 - 7619497-02 7
2. Introduction Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
2 Introduction
DANGER
WARNING
CAUTION
2.2 Abbreviations
2.3 General
8 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 2. Introduction
02092014 - 7619497-02 9
2. Introduction Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
2.4 Homologations
2.4.1. Certifications
10 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 3. Safety instructions and recommendations
DANGER
DANGER
3.2 Recommendations
WARNING
CAUTION
02092014 - 7619497-02 11
3. Safety instructions and recommendations Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
Casing components
Only remove the casing for maintenance and repair operations. Put
the casing back in place after maintenance and repair operations.
Instructions stickers
The instructions and warnings affixed to the appliance must never be
removed or covered and must remain legible during the entire lifespan
of the appliance. Immediately replace damaged or illegible
instructions and warning stickers.
Modifications
Modifications may only be made to the boiler after the written
permission of BAXI to do so.
12 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 4. Technical description
4 Technical description
1
1 Flue gas outlet/Air intake (Combustion air/flue gas
2
adapter 60/100)
2 Casing/air box
3 15 3 Outlet for measuring combustion gases
4 4 Ignition/ionization electrode
T004783-A
15 Automatic air vent
02092014 - 7619497-02 13
4. Technical description Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
Combi 24 - 28 - 35
System 18 - 24
3 4
T003807-A
The casing fitted to the boiler is also used as an air box. Air is sucked
in by the fan and gas injected into the venturi by the fan intake. The
fan rotation speed is set according to the settings parameters, the
thermal energy requirement and the temperatures measured by the
temperature sensors. The gas and air are mixed in the venturi. The
gas/air ratio ensures that the quantities of gas and air are adjusted to
each other. This provides optimum combustion on the entire output
range. The gas/air mixture is fed into the burner on top of the
exchanger.
14 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 4. Technical description
4.4.2. Combustion
Control of the boiler ensures reliable delivery of heat. This means that
the boiler treats external negative influences in a practical manner
(notably when the water-flow is insufficient or there are problems with
air supply). In the presence of such influences, the boiler doesn’t
switch into locking mode, but first reduces his power and, depending
on the nature of the circumstances, will be temporarily out of service
(blocking or stop). The boiler will continue to supply heat as long as
the situation does not become dangerous.
4.4.5. Adjustment
02092014 - 7619497-02 15
4. Technical description Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
The boiler is fitted with a safety device to prevent the shortage of water
based on temperature measurements. By reducing its output when
the water flow rate is in danger of becoming insufficient, the boiler
continues to operate as long as possible. In case of insufficient ΔT
≥ 50°C flow or an excessive increase in flow temperature, the boiler
will enter shutdown mode for 10 minutes. When there is no water in
the boiler, or if the pump is not running, the system is locked
(breakdown)
700
600
1 Combi 24 - 28
500
2 2 Combi 35
400 1
300 317
20 kW
30 kW
H Manometric height central heating circuit
253
127
24 kW
100
0
0 200 400 600 800 1000 1200 1400 1600
860 1030 1250 1500
Q (l/h)
R000684-A
16 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 4. Technical description
System 18
H (mbar)
600
500
300 18 kW
H
280
0
0 200 400 600 800 1000 1200 1400 1600
775
Q (l/h)
R000685-A
System 24
H (mbar)
600
500
300
H
253 20 kW
200
24 kW
Q Water flow ( ΔT=20K)
127
100
0
0 200 400 600 800 1000 1200 1400 1600
860 1030
Q (l/h)
R000365-A
02092014 - 7619497-02 17
4. Technical description Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
18 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 5. Installation
5 Installation
WARNING
02092014 - 7619497-02 19
5. Installation Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
The identification plate on top of the boiler features the boiler serial
number and important boiler specifications, for example the model
and unit category. The dF and dU codes are also stated on the type
plate.
R000697-A
5
(1) Clearance when operating
36
(1) 8
5
5
(2) Clearance for maintenance
≥2
50
4
36
(2)
0 0
10
R000698-A
20 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 5. Installation
WARNING
CAUTION
n Safety rating
Z Z Zones
1 2 3
0 OZ Breakdown of the exterior zone
OZ B Bathtub or shower tray
02092014 - 7619497-02 21
5. Installation Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
184
90
243
364
368
46
76
664
541
35
5 (1) 52 1 = 117
1 2 = 184
2 3 = 251
3
4
4 = 316
230
209
187
151
R000699-B
22 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 5. Installation
CAUTION
1 2 During mounting, cover up the connection points for the
air supply and the combustion gas exhaust, to protect the
boiler and its connections from dust. Only remove this
3 protection at the time when these connections are made.
1. Determine the position of the two fixing holes. Make sure that the
holes are level. Drill 2 holes with a Ø of 8 mm.
2. Insert the rawplugs with a Ø of 8 mm. Secure with Ø 6 mm bolts
and corresponding washers.
3. Mount the boiler using the suspension bracket on the back of the
boiler.
R000409-A
CAUTION
°C
bar
R000410-B
02092014 - 7619497-02 23
5. Installation Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
4
2 A PRV safety valve is fitted to the flow side of the boiler as
standard.
R000737-A
24 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 5. Installation
CAUTION
1. Connect the cold water inlet pipe to the domestic cold water
connection k.
2. Connect the domestic hot water outlet pipe to the domestic hot
water connection m.
CAUTION
1
4 The domestic water pipes must be connected in
2 accordance with prevailing provisions.
4 Carry out any soldering work required at a safe
distance from the boiler or before the boiler is fitted.
4 If using synthetic pipes, follow the manufacturer’s
(connection) instructions.
R000738-A
Initial pressure of the Volume of the expansion vessel depending on the volume of the installation (in litres)
expansion vessel 100 125 150 175 200 250 300 > 300
0.5 bar 4.8 6.0 7.2 8.4 9.6 12.0 14.4 Volume of the installation x 0.048
1 bar 8.0(1) 10.0 12.0 14.0 16.0 20.0 24.0 Volume of the installation x 0.080
1.5 bar 13.3 16.6 20.0 23.3 26.6 33.3 39.9 Volume of the installationx 0.133
(1) Factory configuration
02092014 - 7619497-02 25
5. Installation Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
CAUTION
R000739-A
CAUTION
CAUTION
26 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 5. Installation
R000700-A
R000701-A
(2)
R000702-A
≥ 500
(1) Set the discharge pipe at a gradient of at least 50 mm per
metre, maximum horizontal length 5 metres.
≥ 2.5° (1)
(2) Holes in the soak-away must face away from the building.
R000703-A
02092014 - 7619497-02 27
5. Installation Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
≥ 2.5° (1) Pumped into an internal discharge branch (e.g. sink waste)
downstream of the trap
(3)
R000704-A
(2)
R000705-A
Check that the automatic bleed valve is open: This is visible on the
right on top of the boiler. If necessary, the air vent can be closed off
with the cap that can be found next to it.
R000350-A
28 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 5. Installation
WARNING
CAUTION
5.7.1. Classification
02092014 - 7619497-02 29
5. Installation Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
5.7.2. Outlets
T
J,K
U
N
R D A
M C E
I I I I
S
F B
F J,K
L A
A
G H H
I
30 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 5. Installation
Concentric
If using a room sealed version, both the combustion gas exhaust
opening and the air supply opening must be connected
L= (concentrically). Refer to the table to determine the maximum pipe
length of the flue gas pipes in room sealed operation.
Eccentric
An 80/80 mm flue gas adapter (accessory) must be fitted
L= for this connection.
n Reduction table
02092014 - 7619497-02 31
5. Installation Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
S Insertion depth 30 mm
S
Mounting
Fit together the combustion gas exhaust pipes, without welding.
60/100mm CAUTION
The boiler is not line- and neutral sensitive. The control unit is fully
integrated with the fan, venturi and gas block. The boiler is fully pre-
wired. The PCB has a connection to the connection box with
instrument panel, via the HMI connector. The PCB has a RS232
connection for a PC/laptop via the RS232 connector. The main
characteristics of the control unit are described in the table below.
32 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 5. Installation
The boiler is fitted with a 3-wire power supply cable (cable length 1,5
m) suitable for a 230VAC/50Hz power supply with phase/neutral/
earth system. The power supply cable is connected to the MAINS
connector. A spare fuse can be found in the housing of the control
system.
CAUTION
5.8.2. Recommendations
WARNING
CAUTION
02092014 - 7619497-02 33
5. Installation Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
A Mains voltage
B Low voltage
4 3 2 1 3 2 1 6 5 4 3 2 1 2 1
+
Enable
- + -
Status BUS BUS On/off On/off-OT connection is only suitable for:
CH DHW Nc C No Tout Tdhw BL SCU HMI OT
4 24V power stealing thermostat
A B 4 Potential free on/off thermostat
R000734-A
4 OT thermostat (iSense or qSense)
34 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 5. Installation
+
Enable
- + -
Status BUS BUS On/off CAUTION
CH DHW Nc C No Tout Tdhw BL SCU HMI OT
Check whether the outside sensor is suitable for this
R000451-A
boiler. A suitable outside sensor can be obtained as an
accessory.
-20 -10 0 10 20
This is only possible with an iSense or qSense.
R000038-A
02092014 - 7619497-02 35
5. Installation Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
+
Enable
- + -
Status BUS BUS On/off C terminals of the connector.
CH DHW Nc C No Tout Tdhw BL SCU HMI OT
4 If the boiler locks out, the alarm can be transmitted via a potential-
R000453-A free contact (maximum 230 VAC, 1 A) on the Nc and C terminals
of the connector.
4 The external 3-way valve (230 VAC, 1 A) can be used when
connecting an indirectly heated calorifier via a volt-free contact.
The neutral position of the three-way valve can be set using
parameter p34. The three-way valve is connected as follows:
- Nc = Central heating
- No = Domestic hot water
- C = Phase on
36 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 5. Installation
+
Enable
- + -
Status BUS BUS On/off 4 +=L
CH DHW Nc C No Tout Tdhw BL SCU HMI OT
4 -=N
R000718-A
DANGER
The control panel for the boiler is connected to connector BUS HMI.
¼See chapter: "Access to the connector block / Boiler HMI", page
4 3 2 1 3 2 1 6 5 4 3 2 1 2 1
34
R000448-A
02092014 - 7619497-02 37
5. Installation Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
GN/ GN/ BR BK BK 1 3 1 1 1
YW YW BK
BR BK BL
PC BL BL
E 1 3 2
2 2 2 2
L N
P
MAINS
PUMP 230V, 50Hz HL FS TR TA PSU
IT 3WV
PUMP PWM
PUMP A 3WV PWM
PUMP
SENSORS
RS232
HMI
R000291-A
WARNING
38 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 5. Installation
CAUTION
First remove the front housing of the boiler so that you can
disconnect the condensate trap.
¼See paragraph: "Open the boiler", page 53
R000431-B
02092014 - 7619497-02 39
5. Installation Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
CAUTION
2
3
4
T000181-B
1. Fill the system with clean tap water (advised water pressure is
between 1 and 2 bar).
2. Check the tightness of the water connections.
3. Turn the boiler on.
R000733-A
contact with the casing and electrical parts of the boiler.
40 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 5. Installation
It is essential that you bleed any air in the calorifier, the conduits or
the taps to prevent the annoying noises likely to be produced during
1
heating or when tapping water. To do this, proceed as follows:
1. Open the valves on all radiators connected to the heating system.
1
2. Set the room thermostat as high as possible.
2
3. Wait until the radiators are hot.
3
4
CAUTION
7 8
R000712-A
02092014 - 7619497-02 41
6. Commissioning Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
6 Commissioning
MainEco Combi 24 - 28 - 35
MainEco System 18 - 24
1 No function
2 Heating water temperature rotary knob
The instrument panel for the connection box has 2 push buttons with
signals. The signals provide information about the operating condition
of the boiler. The RESET button lights up green when the boiler is
connected to the mains. The status signal for the B button can flash
in a range of colours and at different frequencies. The meaning of
these signals can be found in the User instruction card supplied with
the boiler. ¼See also: "User instruction card", page 71
CAUTION
The instrument panel for the connection box also has 2 rotary
knobs. The N rotary knob can be used to set the temperature of the
domestic hot water. The D rotary knob can be used to set the
maximum flow temperature of the heating water. The heating/
domestic hot water function can be switched off by turning the rotary
knob to position off.
42 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 6. Commissioning
WARNING
4 Use the pressure gauge to check the water pressure in the heating
system. The hydraulic pressure must reach a minimum of 0.8
bar. If necessary, top up the water level in the heating system
(recommended hydraulic pressure between 1 and 2 bar).
4 Check the condensate discharge trap; it must be filled with clean
water up to the mark.
4 Check that there are no leaks on the hydraulic connections.
WARNING
02092014 - 7619497-02 43
6. Commissioning Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
CAUTION
44 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 6. Commissioning
WARNING
WARNING
R000736-A
WARNING
CAUTION
T003127-B
The flue gas analyser must have a minimum accuracy of
±0.25% CO2.
02092014 - 7619497-02 45
6. Commissioning Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
The full load status can only be reached via the part load
status.
3. Measure the percentage CO2 in the flue gases (Front panel
removed).
WARNING
There MUST remain a "gap" between the full load and part
load values. The full load value must be 0.4% higher than
the part load value.
3. Briefly press the RESET button to return the boiler to normal
operating status.
46 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 6. Commissioning
Verify Flue Integrity No Is O2 ≥ 20.6% and Yes Check CO & Combustion Ratio at
Indication that products of combustion & inlet CO2 < 0.2% ? Maximum Rate
air are mixing - further investigation is Whilst the boiler is still operating at maximum
required. Check all flue components are insert the analyser probe into the flue gas
correctly assembled, fixed & supported. test point, allowing the reading to stabilise.
Check the flue & terminal are unobstructed.
Verify Integrity of Seals No Is CO < 350ppm Yes Set Boiler to Minimum Rate
Check all burner seals, internal flue seals, and CO/CO2 ratio Allow the combustion to stabilise. Do not
door & case seals. Replace any seals that < 0.004 ? insert probe to avoid ‘flooding’ the analyser.
appear unsound.
Note: Check & record the CO & combustion BOILER OPERATING SATISFACTORILY.
ratio at both maximum & minimum rates NO FURTHER ACTION REQUIRED
before calling 0844 871 1555. Ensure test points are capped, the boiler
case front panel is correctly fitted & secured
and all other commissioning procedures
completed. Complete the ‘Benchmark’
Checklist, recording the CO & combustion
ratio readings as required.
R000715-A
02092014 - 7619497-02 47
6. Commissioning Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
WARNING
CAUTION
T003127-B
The flue gas analyser must have a minimum accuracy of
±0.25% CO2.
4 The full load status can only be reached via the part
load status.
4 See drawing for the position of control screw A for full
load.
3. Set the percentage CO2 for the gas type being used to the nominal
A value. This should always be inside the highest and lowest setting
limit.
B
4 If the percentage CO2 is too low, turn the screw A
anticlockwise for a higher percentage.
4 If the percentage CO2 is too high, turn the screw A
clockwise for a lower percentage.
R000592-B
See drawing for the position of control screw B for part load.
R000591-B
48 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 6. Commissioning
2. Set the percentage CO2 for the gas type being used inside the
highest and the lowest setting limit, as determined after the full
load setting. (Front panel removed).
WARNING
There MUST remain a "gap" between the full load and part
load values. The full load value must be 0.4% higher than
the part load value.
3. Briefly press the RESET button to return the boiler to normal
operating status.
connections.
9. Checking the hydraulic pressure. If necessary, top up the water
level in the heating system (recommended hydraulic pressure
between 1 and 2 bar).
10.Tick the gas category used on the data plate.
11.Explain the operation of the installation, the boiler and the
regulator to the users.
12.Slide the User instruction card supplied into the guides underneath
the connection box.
13.Fill in Commissioning sheet, can be found in the appendix.
14.Give all the instruction manuals to the user.
02092014 - 7619497-02 49
6. Commissioning Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
Factory setting
Parameter Description Adjustment range Combi System
24 28 35 18 24
p1 Flow temperature: TSET 20 to 90 °C 80 80 80 80 80
Domestic hot water temperature: 40 to 65 °C
p2 55 55 55 55 55
TSET
0 = Heating deactivated / DHW deactivated
1 = Heating activated / DHW activated
p3 Heating / DHW mode 1 1 1 1 1
2 = Heating activated / DHW deactivated
3 = Heating deactivated / DHW activated
0 = Comfort
1 = Energy-saving mode
p4 ECO mode 2 2 2 2 2
2 = Management using a programmable
thermostat
1 to 98 minutes
p5 Post-circulation of the pump 2 2 2 2 2
99 minutes = continuous
p17 Maximum fan volume flow (Heating) G20 (x100) 39 39 60 36 47
p18 Maximum fan volume flow (DHW) G20 (x100) 47 56 70 36 47
Minimum fan volume flow (Heating G20 (x100)
p19 11 11 15 11 11
+DHW)
p20 Minimum fan volume flow (offset) G20 80 80 60 80 80
p21 Starting volume flow Do not modify (x100) 23 23 30 23 23
Maximum flow temperature of 20 to 90 °C
p23 90 90 90 90 90
system
Time factor of average flow Do not modify
p24 35 35 35 35 35
calculation (x10 seconds)
Heat curve set point (Maximum 0 to 30 °C
p25 20 20 20 20 20
outside temperature) (Only with an outside temperature sensor)
Heat curve set point (Flow 0 to 90 °C
p26 20 20 20 20 20
temperature) (Only with an outside temperature sensor)
Heat curve set point (Minimum -30 to 0 °C
p27 -15 -15 -15 -15 -15
outside temperature) (Only with an outside temperature sensor)
Minimum pump speed for central 2 - 10 (x 10 %)
p28 heating operation (Setting the pump 2 2 2 2 2
speed)
Maximum pump speed for central 2 - 10 (x 10 %)
p29 heating operation (Setting the pump 7 7 10 10 10
speed)
p30 Antifreeze temperature from - 30 to 0°C -10 -10 -10 -10 -10
0 = Stop
1 = Start(1)
p31 Legionella protection 1 1 1 1 1
2 = Management using a programmable
thermostat
p32 Set point increase for calorifier 0 to 25 °C 15 15 15 15 15
DHW cut-in temperature DHW
p33 from 2 to 15°C 4 4 4 4 4
sensor
0 = Normal
p34 Control of external 3-way valve 0 0 0 0 0
1 = Reverse
0 = Heating and instant domestic hot water
p35 Boiler type 0 0 0 1 1
1 = Heating only
(1) After commissioning, the boiler will operate once a week at 65°C for DHW.
50 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 6. Commissioning
Factory setting
Parameter Description Adjustment range Combi System
24 28 35 18 24
1 = Shutdown without frost-protection
p36 Shutdown input function 2 = Shutdown with frost protection 1 1 1 1 1
3 = Lock-out with frost protection (Pump only)
0 = Not connected
p37 Minimum gas pressure switch (GpS) 0 0 0 0 0
1 = Connected
0 = Not connected
p38 Heat recovery unit (HRU) 0 0 0 0 0
1 = Connected
p39 Flue gas damper running time 0 to 255 seconds 0 0 0 0 0
0 = Operation signal
p40 Fault relay function 1 = Alarm signal 2 2 2 2 2
2 = External 3-way valve
p41 Maintenance message Do not modify 0 0 0 0 0
p42 Service operating hours Do not modify 175 175 175 175 175
p43 Service burning hours Do not modify 30 30 30 30 30
0 = Stop
p44 Venting cycle 1 = Multiple speed pump 1 1 1 1 1
2 = Modulating pump
(1) After commissioning, the boiler will operate once a week at 65°C for DHW.
02092014 - 7619497-02 51
7. Switching off the boiler Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
CAUTION
Drain the boiler and central heating system if you are not
going to use your home or the building for a long time and
there is a chance of frost.
CAUTION
When the heating water temperature in the boiler falls by too much,
the integrated protection system in the boiler starts up. This protection
functions as follows:
4 If the water temperature is lower than 7°C, the heating pump starts
up.
4 If the water temperature is lower than 4°C, the boiler starts up.
4 If the water temperature is higher than 10°C, the boiler shuts down
and the circulation pump continues to run for a short time.
52 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 8. Checking and maintenance
WARNING
WARNING
CAUTION
1
R000346-A
02092014 - 7619497-02 53
8. Checking and maintenance Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
R000405-A
CAUTION
1. Fill the system with clean tap water (advised water pressure is
between 1 and 2 bar).
2. Check the tightness of the water connections.
3. Turn the boiler on.
50 100
°C 20 120
bar
4 0
3 1
2
R000733-A
Check the ionization current at full load and low load. The value is
stable after 1 minute. If the value lies below 3 µA, replace the ignition
electrode.
54 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 8. Checking and maintenance
Check the tightness of the flue gases evacuation and air inlet
connections.
R000406-A
R000350-A
02092014 - 7619497-02 55
8. Checking and maintenance Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
CAUTION
1
First remove the front housing of the boiler so that you can
disconnect the condensate trap.
2
1. Move the lever underneath the hydroblock to the right to
disconnect the condensate trap.
5
2. Remove the condensate trap and clean it.
3. Replace the seal ring for the condensate trap.
6
3 4. Fill the condensate trap with water up to the mark.
5. Press the condensate trap firmly into the j opening provided for
it underneath the boiler. The condensate trap must click into place.
6. Check whether the condensate trap is solidly fitted in the boiler.
4
R000431-B
56 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 8. Checking and maintenance
CAUTION
CAUTION
02092014 - 7619497-02 57
8. Checking and maintenance Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
WARNING
CAUTION
R000433-A
58 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 8. Checking and maintenance
CAUTION
6 5
R000400-A
02092014 - 7619497-02 59
8. Checking and maintenance Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
R000741-A
R000401-A
60 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 8. Checking and maintenance
The expansion vessel is inside the boiler at the rear. To replace the
expansion vessel, the front section of the boiler should be removed
first.
1. Disconnect the flue gas discharge and air flow pipes from the
boiler.
2
2. Remove the connection box.
3. Disconnect all incoming and outgoing pipes from the underside of
the boiler.
4. Disconnect the gas supply pipe GAS / GAZ from the boiler.
1
5. Remove the condensate trap and drain hose.
To check how to remove the condensate trap, see: ¼
"Checking the condensate trap", page 56.
6. Disconnect the expansion vessel hose from the underside of the
T005059-A
boiler.
7. Press down the mounting clip on top of the boiler and remove the
front of the boiler.
1. Bring the tab above the expansion vessel forwards and hold onto
it while disconnecting the expansion vessel.
2 2. Move the expansion vessel slightly upwards and lift the vessel
from the mounting bracket.
3. Tip the expansion vessel forwards and allow it drop slightly.
4. Carefully lift the expansion vessel out of the boiler.
1 3 5. Replace the defective expansion vessel.
6. To re-assemble, perform the above actions in reverse order.
CAUTION
R000351-A
CAUTION
02092014 - 7619497-02 61
8. Checking and maintenance Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
4. Carefully open the main water valve, fill the installation, vent it and,
if need be, top it up with water. The hydraulic pressure must be a
minimum of 0,8 bars. Check for any water leaks.
5. Check the seals on the gas and water connections.
6. Switch the boiler back on.
7. Check the setting of the gas/air ratio and, if necessary, correct it.
¼See chapter: "Checking combustion", page 45
¼See chapter: "Setting the air/gas ratio", page 48
62 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 9. Troubleshooting
9 Troubleshooting
MainEco Combi 24 - 28 - 35
MainEco System 18 - 24
1 No function
2 Heating water temperature rotary knob
The status signal for the B button can flash in a range of colours and
at different frequencies. The meaning of these signals can be found
in the User instruction card supplied with the boiler.
¼See also: "User instruction card", page 71.
CAUTION
9.2.1. Blocking
02092014 - 7619497-02 63
9. Troubleshooting Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
The shutdown codes from the status signals are related to the
shutdown codes that can be read by the Recom software or a suitable
controller. The meaning of the shutdown codes can be found in the
shutdown table:
64 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 9. Troubleshooting
If the blocking conditions still exist after several start up attempts, the
boiler will switch into locking mode (fault). The boiler can only start
operating again once the causes of the lock-out have been rectified
and after pressing the J key.
In the event of a fault, the status signal for the B button flashes
red. The meaning of the error codes is given in the error table:
02092014 - 7619497-02 65
9. Troubleshooting Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
The fault codes from the status signals are related to the fault codes
that can be read by the Recom software or a suitable controller. The
meaning of the error codes is given in the error table:
66 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 9. Troubleshooting
02092014 - 7619497-02 67
9. Troubleshooting Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
68 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 9. Troubleshooting
02092014 - 7619497-02 69
10. Spare parts Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
10 Spare parts
10.1 General
70 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 11. Appendix
11 Appendix
R000392-A
Code C
Flame loss
Communication fault
Parameter error
Miscellaneous
Ignition fault
Fan fault
Parameter error
Miscellaneous
Reinitialisation
Resetting...
PC programming mode
_________________________________ _________________________________
02092014 - 7619497-02 71
11. Appendix Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating
compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
Failure to install and commission according to the manufacturer’s instructions and complete this Benchmark Commissioning Checklist will invalidate the
warranty. This does not affect the customer’s statutory rights.
ALL SYSTEMS
’s instructions Yes
What system cleaner was used?
What inhibitor was used? Quantity litres
Yes No
72 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 11. Appendix
ALL INSTALLATIONS
At max. rate: CO ppm AND CO/CO² Ratio
Record the following:
At min. rate: (where possible) CO ppm AND CO/CO² Ratio
The heating and hot water system complies with the appropriate Building Regulations Yes
The boiler and associated products have been installed and commissioned in accordance with the manufacturer’s instructions Yes
The operation of the boiler and system controls have been demonstrated to and understood by the customer Yes
The manufacturer’s literature, including Benchmark Checklist and Service Record, has been explained and left with the customer Yes
*All installations in England and Wales must be to Local Authority Building Control (LABC) either directly or through a
Competent Persons Scheme. A Building Regulations Compliance will then be issued to the customer.
It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed.
Service Provider
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions.
Signature Signature
Signature Signature
Signature Signature
02092014 - 7619497-02 73
11. Appendix Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
Signature Signature
Signature Signature
*All installations in England and Wales must be to Local Authority Building Control (LABC) either directly or through a
Competent Persons Scheme. A Building Regulations Compliance will then be issued to the customer.
74 02092014 - 7619497-02
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24 11. Appendix
02092014 - 7619497-02 75
11. Appendix Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
76 02092014 - 7619497-02
© Copyright
All technical and technological information contained in these technical instructions, as well as any drawings and technical de
scriptions supplied, remain our property and shall not be multiplied without our prior consent in writing. Subject to alterations.
For Baxi Customer Support and
Technical Advice, contact us at
0844 871 1525
Please note calls may be monitored or recorded
www.baxi.co.uk
e&oe
All descriptions and illustrations provided in this document have been
carefully prepared but we reserve the right to make changes and
improvements in our products which may affect the accuracy of the
information contained in this leaflet. All goods are sold subject to our
standard Conditions of Sale which are available on request.
7619497