Yaskawa Manuals 581
Yaskawa Manuals 581
SPECIFICATIONS/FUNCTIONS
a “;;
CertlflcateNo B 950322945001
YASUAWA
DTSE-S606-9,1
CONTENTS
1 INTRODUCTION.............................................................................................................
3
2 SPECIFICATIONS ...........................................................................................................
5
3 SYSTEM CONFIGURATION ...........................................................................................6
3.1 INTERCONNECTION DIAGRAM ....................................................................................
6
3.2 MAIN CIRCUIT TERMINALS TM1 ................................................................................ ..
8
3.3 CONTROL POWER INPUT TERMINALS TM1 .................................................................
8
3.4 ENCODER (PG) CONNECTOR (CON2) ........................................................................ .
8
3.5 l/O SIGNAL CONNECTOR CON1 ................................................................................ . .
9
3.6 WIRING PRECAUTIONS """""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""""""""""lo
4 DESCRIPTION OF OPERATIONS """""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""""""""""""do
4.1 FUNDAMENTAL OPERATIONS """""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""do
4,2 SETUP """""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""Al
4.3 ZERO-POINT RETURN OPERATION """""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""22
4.4 ZERO-POINT OFFSET AUTOMATIC SETUP OPERATION ““””.”””””””””””””””””””.”””””””23
4.5 AUTOMATIC OPERATION """"""""-"""""-""""".-".. as."".-"."""""""""."."". """."".."" """"""""."""."S."""."""""""""""24
4.6 MANUAL OPERATION '""""
.""."""""""""""""""."".""".""""" """""""""""""". """."".""""""" """"""""."""."".""""" ..""""25
4.7 EMERGENCY STOP OPERATION """""".""""".""•."".."•""""" """"""."".."".."."""" """""."".""."".."".."".""."."26
4,8 JOG OPERATION """-"
""-""""-""
.-"."".""""""""""""""" ".""."""."".."""""""""" """.""."" .."".""""" """"""."""
."""" "."""."26
5 PARAMETER SETTING/MONITORING """""
"."""
"""""
"""""
"""".
""""""""""""""""""""""""""""27
5.1 PARAMETER SETTING """""-".. ".-". s-.."-"""""""""""-"".""." ".."" """""-.""-"""""."""."""""""""""-"""-""""""""""""""27
5.2 OPERATION STATUS MONITOR """"""""""""""""""""""""" """"" """"""""""""""""""""""""""""""""""""""""""""""""""35
5.3 HOW TO USE PARAMETER SETTER (Model JVOP-1OO) ““-””
”””””
.”””.s”.””
”””””
”””””38
5.3.1 Fundamental operatio flow (mode selection, parameter ““”””
”.”””
”””””
number selection) ”””38
5.3.2 Parameter value setting flow (Co-nn, do-nn, Eo-nn) """""
"""""""""""""""""""""""""""""""""""""""""""""39
5.3.3 Monitor operation flow (Uo-nn) """""
"""""
"""""
"""""
"""""
"""""
"""""
"""""""""""""""""""""""""""""""""""""""""""""39
5.3.4 Parameter initial value setting flow (So-nn) """""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""""""""""do
5.3.5 Teaching method """""
""""""""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
""""""""""""""do
5.3.6 Supplementary description (for parameter setter) """"""""""""""""""""""""""""""""""""""""""""""""""""""Al
6 1/0 INTERFACE """""
"""""
"""""
"""""
-."."""+""
"+..""""""
"""""
".."""""
."""."".""
"""""
"""""
"."".""..""..""""""""""""""""""42
6.1 INPUT INTERFACE ""-""""""""".""".""-"."""""""""""."""""".""".""""""""""".""""""."."""."".. """""""""""""""""42
6.2 OUTPUT INTERFACE ............................................................................................. . . . 43
6.3 SUPPLEMENT OF SEQUENCE CONTROL OUTPUT SIGNAL ““””””””””””””””””””””””””””””””””””””44
6.4 TIMING OF SEQUENCE CONTROL SIGNAL """""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""44
6.5 ABS MODE 1 AND 2 """""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
""""""""""""""""""""""""""""""""""""""'"""""45
7 STATUS/ALARM INDICATION """""
"""""
"""""
"""""
"""""
"""""
"""""
"""""
"""""""""""""""""""""""""""""""""""""""""""""47
7.1 STATUS INDICATION (On the point module) """"""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""47
7.2 TROUBLESHOOTING ""."""""
.""."".""".".."""""
"-"""
"".""."""""
"""""
"""""
"""""
"""."
"".""
.""""
"""""""48
8 PRECAUTIONSON APPLICATION"""" ."""" """"""""""""""""""""""""..."..5O
9 OPTION .........................................................................................................................51
9.1 PARAMETER SETTER ................................................................................................
51
9.2 PARAMETER SETTER CABLE ....................................................................................
51
9.3 PG CABLE ..................................................................................................................
51
9.4 PARAMETER SETTING SOFTWARE (Personal computer software) ““””””””””””””””””52
9.5 PERSONAL COMPUTER COMMUNICATION CABLE ““””””””””””””.
””””””.
””””””””52
10 CHARACTERISTICS (Speed-Torque Curve)
""""'"""""""""""""""""""""""""""""""""""""""""""""""""""""""53
11 DIMENSIONS in mm (inches) """""""""""""""""""""""""""""""""""""""""""""'""""""""""""""""""""""""""""""""""""""53
11,1 CONTROLLER """""
"""""
"""""
"""""
""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""53
11,2 DIMENSIONS in mm (inches) .....................................................................................
54
–2–
1. INTRODUCTION
Juspoint IIl is the newest member of our inverter drive family, developed exclusively for
station indexing and positioning control. It is an economical-cost, easy to set, reliable
positioning system designed to drive actuators for Numerical Control machine tools.
The system consists of a motor and a controller. The controller includes YASKAWAS vector-
control inverter “X3000 series” with “Point module” (Positioning control board). The “X3000
series” features high-torque and precise speed control over a full speed ranged from O to
1800r/min. “Point module” can configure up to 120 different parameters for application
flexibility.
The motor is a highly efficient, three-phase AC induction motor, exclusively designed for high
performance vector-control applications. Juspoint IIl positions accurately and rapidly in the
same way as a servo drive and it is ideal for servo driven tool changer applications for
machine tools.
In addition, compared with the cost of conventional AC servo drives, Juspoint Ill is an
economical alternative for tool resting, magazine attachments, Automatic Tool Changers
(ATC), and Automatic Pallet Changers (APC).
FEATURES
■ Juspoint IIl can position up to 511 station numbers.
■ Juspoint Ill can operate rotary and linear axes.
Rotary axes ● Juspoint D can position up to 511 stations equidistantly.
● Juspoint Ill can automatically compensate positioning when the number of
pulse between stations is a fraction.
Linear axes ● Juspoint III can position up to 511 station equidisttitly.
● Juspoint Ill can arbitrarily position up to 45 stations.
■ Juspoint IIl can perform Absolute (ABS) positioning.
Using the motor with a special brake, Juspoint III can perform ABS positioning and no zero-point
return operation is required even without a mechanical clamp when the power is ON.
■ Juspoint III can arrange parameters in up to 4 operation patterns.
■ Juspoint III has 6 operation modes:
Automatic. manual. set-up, zero-point return, automatic zero offset, tind JOG.
■ 120 parameters available for configuring Juspoint III to your specific requirements.
-3-
Juspolnl ❑
Tr. CONROLLER
“v-–l MOTOR
—- ; FQIM WWK
.
X 3000
[d +~-~
Pc _l /0
IM —0
NC
‘‘ ~ ENCOl)ER ‘ F a
MACHINF
91GITAL
[lPERATOR
nL
i.1
‘ ‘
FOR POSITION COtJNTtR
-------- - ~
PLC
NC
--..-11
CPU
‘1
I
Three phases
I J
~ ‘4 !n
200VAC
II
POWER
SUPPLY ;-: I
1. _
~ DANGER
● Do not touch circuit components until CHARGE lamp on X3000 series PC board extinguishes
after turning off AC main circuit power.
The capacitors are still charged and can be quite dangerous. Wait approximately five minutes
after AC main circuit power is OFF.
IMPORTANT
● Bc ~ure to ground Juspoint III using mounting bolts.
● Do not provide c:ip:ic itor or mtignctic contac(or between Juspoint Ill ~md motor.
● Do no~perform [he following tests in the field :
Withstand volt[~ge (cst on any p~irt of the Juspoint ~. II is 2u1electronic device using semiconductors
and vulnerable to higll-volt~~ge.
lnsui~ition resis[aocc test with :t megger. Thi\ test has been m~~de a( the tttctot-y tind need not be
conciuc[ed :lt test run. Excep[ion: If megger-testing is required l’or inspection and main[en:mce
purposes, it should bc :Lpplied only to m;iin circuit and the ground ~md never to the control circuit.
Conduction test 00 control circuits.
–4–
2. SPECIFICATIONS
Table 1.1 Specifications
Model CIMR- 02JP3 04JP3 08JP3 15JP3 1
22JP3 37JP3
Outout kW [HP] 02(1/4) 04 (3/4) 075(1) 15 (2) 2 ? (3) 37 (5)
Cur;ent(A)’ ‘
Power Supply
20
Three phases
.-L–- 30
180 tO 242V 56Hz
45
Three phases
75 110
180 to 253V, 60Hz
__ L-- _I 175
‘-’l
; Speed Resolution ~/~OoOIO 3r/mln) _
Ambient Temperature ~+55’C (+~+131”F)
Power Supply 24VDC (~4V) 250mA
Rotary axis Equldstant staton (Sngle station pulse IS an nteger)
~
Control AxIs
Basic Operation
Rotary
Linear
Lnear
axs
axis
axis
Equldlstant station (Sngle s[atlon pulse IS a fracton)
Equldlstant sta[lon
Arbltrarv station distance
Zero-point return (2-mode) Set-up
1
JOG Manual
>1 Au to_rna~c ~utomatlc zero offset _ _
~ Pos!t[omng Command 9 blt binary code (Max 511 slatlons)
o‘ CtiTrent Posltlon Output 9 b(f binary code
m-
Pos[tlor>ng command Drectlon command Start comrmand Operatng mode Zero point LS
: Input Signal
g Emergent stop Reset Numercal pattern Servo on ABS pos[tlon start
m’ Output signal Poslfon completion Poslttonlng near width Zero speed Alarm Curren[ station
? 4BS ~stlon completion
Backlash Corn]ensatlon ___ 0 to 720~@-rotatjon aj_~Qtor axm.
A~cel Time lo to 5000 rmsec_~Oto 1800r/Mln)
Soft Star[ ProvtdeQ~O to 100m2~&} ‘-:-1
Soft S~opplng Provided
,ABS_PosItIon~ Provld~slng motor wth bra~e~__
..pM[lonln*uracy __ ~below ~At motor axis)
Operation Constant Total 120 parameters (Dlgltal operator JVOP100 or settlnq by p ersonal computer IS also possible ~
Model UAJPEE- DK2K O 2kW 0.4kW O 75kW ~ 1 5kW 2.2kW 3.7kW
outp~ kW (HP) 0 ?4/4) . _ 04 (3/4 L_. 075Q) 3~
!3[2) ! 22 (3)---—.
Raced Curr~nr_ A l_08 29. A.. 74 IL 160
- .—— _
Rated To~que Nm 1 o~ 212 — -- 398_,. 79~ _ IIQ6 _L 1962
~ Maxjrn~rn Torque Nm
..1. _~:’o rated~~~ ~.. ---- _=~---
g M~nt lne~of J (GD2/4J kgcm 60 145_ 9675
~ jn:glatlon Class Class B
Time Rated _ 4070 ED (30mn ) __~070 (20mln )
Ra!g~>eed 1800r/mln (4 pole~.. __
Enclosure
———- ,,
IDAAY-
‘---1
—5
3. SYSTEM CONFIGURATION
3.1 INTERCONNECTION DIAGRAM
—
(1) Specifications of peripheral equipment and cables for main circuit terminals
Table 3.1 Peripheral equipment and cables specifications for main circuit terminals
15.IP3 ]__ ~~Jrj 37JP 3
\l[)del CIMR=__ _02 .1P 3 I- 04JP3 08 J}’ 3
Mclgllc[lc C[)llliicl(ll V<ldcl HI-7E _Hl-20E-
M;IIII circ{lht tvrrl;lr>itl 1 - --–-~-J=-
(’ilhlc SILC 2111111 SLrCu <11:1. M4 Cc!hlc SILC 35,,, !,,: Screw dIiI. M4
c:ihlc< \p~~l[ IC;+lIIIT>
(2) Specifications of cable and receptacle for encoder (PG) terminal and CON2 connection specifications
Table 3.3 Cable and receptacle specifications for encoder (PG) terminal
N;,,nc M,)dcl ~ Rcnli,]-k, I
Sl, <h,ghl ____ ifs 3[()(>ll?()-?~)s-zh
PI,,:
A,>g,)l.+r \lS 7 I [IX 1120 -2~)S-ZN
c’.,hlc (’1.,,,lp MS 31)57-12,\
-., , ,!, ,,. . . . . . . . ..
I (’,,
‘<!hlc,1<11],.rl~lh. 11P 1,1 ~olll.A~(;24 <?,].,,PL’,‘,,
‘1.1L’. ,,,,,1 1,>,Ic,,;lh. ,,,, ;(, l(lo”,.~.,,c c.,,], 1<) he l\L, \lcci [,>
AW(;22 <), I.irycr c<khlc.] I ()\J 11[1..
-6-
(4) Component Layout of Juspoint Ill
I
— Dn\AIKR
❑ Ic 1
POINT
MODULE
/
IN VERTER
Juspeed-F X ]()[)()
,,”,
)1 R s
INPuT
T u Vw
L) UTPUT
Jc
–7-
Q o MAIN CIRCUIT TERMINALS
O.c TM1
“*niL:,6”I+,
Main circuil pnwer Three-phase 200/220” VAC (f I()% )
B1 Al
B? A2
B3 A3
a4 A4
.. B [) A5
B
-8-
3.5 1/0 SIGNAL CONNECTOR CON1
CON I Din
–9-
(2) CONI 1/0 signals
START OPEN –J
STA. NOX CON I -A7
1/0 : Input
Name : Operation command input
Function : Each operation begins with this signal CLOSED.
■ At Automatic Operation
Station number is received at the moment the START signal changes
from OPEN to CLOSED, and the positioning operation is started. Its
speed is V 1 (parameter). Hold CLOSED until [he operation completion
signal (COIN, COIN-A) is output. Changing to OPEN before the
START CON I-B7 completion of indexing causes the machine to stop at the nearest
available station in the running direction. And COIN signal is output,
.. but COIN-A is not output.
■ At Manual Operation
The operation is started in the direction commanded by the F/R signal
at the moment the START signal changes from OPEN to CLOSED. Its
speed is V2 (parameter). When the START signal is turned OPEN, the
machine stops at the nearest tivailable station in the running direction
and COIN signal is output. (COIN-A is not output. )
–lo-
Table 3.11 1/0 signals (Cent’d)
■ Setup Operation
The current station number is received when the START signal c1
from OPEN to CLOSED, and COIN signal, COIN-A signal, and (
current station number received (POS. NO) are output.
■ At Zero-point Return Operation
The zero-point return operation is started when the START signal
changes from OPEN to CLOSED. Hold the OFF signal until the
operation completion signal (COIN) is output. Its speed is V3, V,
(parameter).
■ Jog Operation
The jog operation is started in the direction set by F/R signal whe]
START signal changes from OPEN to CLOSED. Its speed is V6
(parameter). When START signal is turned to OPEN, it stops
simultaneously. This stop position is not in the usual station posi{
and the COIN signal is not output, however, when the machine st
a station position, the COIN signal and station NO.(POS.NO.) ar~
output.
1/0 : Input
Name : Direction command input
Function : Carries out the direction command of an operation.
This is valid only in the following operations:
●Automatic operation (Only valid in the external direction
command mode).
●Manual operation
F/R CON 1-AX ●Jog operation
This input is received at the moment the START signal changt
from OPEN to CLOSED. In order for the signal to be read, in
F/R signal before or at the same time as the START signal, an
for over 10msecs. It becomes CCW or CW when the signal is
changed to OPEN, while CW or CCW when it is changed to
CLOSED. Either may be switched by the parameter setting.
1/0 : Input
Name : Operation mode command input
r
Funl ion : Carri s out the o eration m de that you command.
–11–
Table 3.11 1/0 signals (Cent’d)
All modes are received at the moment the START signal changes from OPEN
to CLOSED. In order for the signal to be read, input mode signal before or at
the same time as the START signal, and hold for over 10msec.
When the START signal changes to CLOSED, if the operation mode is set to
no mode, a “mode set error” is displayed.
1/0 : Input
Name : Zero-point LS signal
Function : Zero-point LS signal at zero-point return operation
■ At zero-opoint return operation (CO- 14=()).
Detecting this signal changing from OPEN to CLOSED decelerates to
V4 from V3. Then detecting the signal CLOSED to OPEN.
Move and position by the zero-point offset from the first Z-phase pulse.
This stopping position is zero-point. Fault occurs if point of the signal
ZRET-LS CON I-A 10 changing CLOSED to OPEN and Z-phase pulse is closer than f] 20
PULSE. In this case, move zero-point 1.S.
1/0 : Input
Name : Emergency stop signal
Function : Emergency stop is carried out when this signal is input in each
operation. The stop position is not the station position.
After stopping, the COIN signal and COIN-A signal are not
output. After an emergency stop, alarm status appears. To release
this alarm status, use the reset signal. After resetting, if the machine
EMG CON1-B10 stops at the station position, the COIN signal is output. If it does
.. not stop at the station position, the COIN signal is not output.
After resetting, the automatic/manual operation may be continued
without carrying out the zero-point return operation/setup operation,
Normally, input CLOSED signal for this signal. The system detects
OPEN, and carries out an emergency stop. With teaching operation
EMG signal is valid. Perform the teaching with CLOSED signal
input.
–12–
Table 3.11 1/0 signals (Cent’d)
1/0 : Input
Name : Servo ON signal
Function : Set this at CLOSED during operation. During CLOSED status,
the motor drive is valid. When the signal is changed to OPEN,
the inverter output is shut-off instantaneously and coasting status
SVON CON1-A1l
results.
After servo is turned ON, automatic/manual operation may be
continued without carrying out zero-point return operationlsetup
operation. With teaching operation, SVON signal is valid.
JOG operation is executed by only CLOSED signal input.
1/0 : Input
Name : Fault reset
Function : When the driver (X3000) or the positioning controlling portion
(point module) detects an error, alarm stop status is held.
<ESET CON1-B1l Signal to return to operation status after removing the cause.
Resets by changing the signal for OPEN to CLOSED to OPEN.
However, reset the SVON signal by OPEN signal input only whe
the alarm occurs in the driver X3000. Reset cannot be executed i
SVON signal is CLOSED.
1/0 : Input
Name : Multiple-pattern selection
Function : More than one operation can be selected by combining two bits.
1/0 : output
Name : Operation completion signal
COIN CON1-A13 Function :The system outputs the completion of each operation mode.
-13-
Table 3.11 1/0 signals (Cent’d)
I 1/0 : output
Name : Automatic positioning completion signal
COIN-A CON1-B13 Function : The system outputs this signal at the completion of positioning in
automatic operation.
-14-
.
Table 3.11 1/0 signals (Cent’d)
1/0 : output
Name : Positioning vicinity signal
Function : The system outputs CLOSED when the controlled machine
approaches the aimed station.
■ Automatic/Manual Operation Mode
The system outputs when the controlled machine comes close to the
station to be positioned. The range of vicinity is set by parameter.
Use this signal when mechanically clamping just before positioning.
After changing the START signal from OPEN to CLOSED, OPEN
NEAR signal is output within 5msec, and positioning action is
NEAR CON I-A14 started.
*: Immediately after turning the system ON, the OPEN NEAR signal
is output.
1/0 : output
Name : Zero speed signal
Function : The system outputs CLOSED when motor speed falls below zero
ZSPD CON I-B14 speed (approximately 10r/min).
This output signal is output independently regardless of operatior
status.
–15–
Table 3.11 1/0 signals (Cent’d)
1/0 : output
Name : Error signal
Function : The system outputs CLOSED when an alarm is detected at the
driver or the positioning controller. In this case, power is shut
down and the motor goes into zero-speed status. However, only
alarm signal in the driver X3000 is base-blocked. Alarm status is
held, and is released by reset signal.
Alarm indication
11
ndication Contents of alarm
–16-
Table 3.11 1/0 signals (Cent’d)
■ At Setup Operation
The system outputs the specified station number after completion of the
setup operation.
POS,NOO CON1-B15
POS,NO1 CON I-A16 *: After confirming COIN signal changing
POS,N02 CON1-B16 OPEN+ CLOSED, receives this signal.
POS,N03 CON1-A17 *: “()” is output after the system is turned ON, after zero-point return, and
POS,N04 CON I-B17 after the zero-point offset automatic setup operation. When automatic
POS,N05 CON1-A18 setup operation (CO- 15), the system outputs the value set to (CO- 15)
POS,N06 CON1-B18 after completing the zero-point return.
POS,N07 CON1-A19 *: “()” is output during JOG operation and after an emergency stop.
POS,N08 CON1-B19 When the controlled machine is stopped at a station after JOG operation
and after resetting following an emergency stop, the station number is
output.
1/0 : output
Name : Memory storage in ABS mode completed
Function : After turning ON the ABS.ST OPEN signal and stopping the motor
at the same time in the ABS mode, the system stores the current
A,BS.READY CON1-A20
position information into memory and outputs the completion
signal (CLOSED). Maintain the 24VDC power source until this
output turns to CLOSED. A special brake motor is required to use
the ABS mode.
1/0 : output
(
OPT. OUT() CON 1-B20 Name : Preliminary output
Function :
—
1/0 : Power source, or COM signal
Name : +24 V(power source)
CON 1-A21
24V Function : This signal shows that power (+24V) is being supplied (Power may
CON I-B21
also be supplied from TM 1- 1.), or represents the COM signal in the
case of +24V common.
1/0 : Input
Name : Memory storage command in ABS mode
Function : After detecting the change of this signal from CLOSED to OPEN
-. in the ABS mode, the system stops the motor and stores the position
information into memory when the motor is completely stopped.
ABS.ST CON1-A23 Then the system outputs the ABS. READY CLOSED signal.
When the CLOSED input is detected for 0.5sec. or more after the
power is supplied, the position information memory is read and the
state before the power shutoff will be regained. The system then
outputs the ABS. READY OPEN signal. This will function only
in the ABS mode.
d
-17-
Table 3.11 1/0 signals (Cent’d)
..
–18–
3.6 WIRING PRECAUTIONS
(1) Use twisted pair shielded cables for PG feedback circuit.
Cable length may be up to 10Om. For wiring, connect the cables in the shortest distance and cut
off the surplus. (Refer to Table 3.2.)
(2) For grounding cables, use as large size as possible.
Class 3 grounding ( 10OQ or less) is recommended.
Grounding must be provided at one point. If motor is insulated between machines, use another
grounding method to ground the motor.
(3) To prevent noise malfunction, take the following actions:
“ Locate Juspoint III or 1/0 reference setter precisely.
● Provide a surge absorbing circuit to relay coils, magnetic contractors, solenoids, etc.
● Separate main circuits (high-voltage circuits such as AC lines or motor power lines) and signal
circuits more than 30cm. Do not run them in the same duct or bundle them together.
● Provide a noise filter to the power supply or input circuits when the power supply is shared with
electrical welders or discharging machines, or when there is a high-frequency noise generating
source near the unit.
● Use shielded cable for 1/0 signal wiring and the shielding treatment should be preformed at
TM 1-2 (OV) terminal of the point module.
(4) Radio Frequency Interference Preventive Actions (R.F.1)
No preventive actions for radio frequency interference are provided to Juspoint ~ since it is an
industrial device. Therefore, if it is used in a residential area or radio frequency interference
causes any problems, provide a line filter at the main circuit power supply input side.
(5) Since cable cores used for PG feedback circuit or signal circuits are very thin, do not apply
bending force or tension force to the cables.
–19–
4. DESCRIPTION OF OPERATIONS
r
1 I 1
Turning ON (Other than ABS mode)
I e“--
Zero-point return
YES II I
+
1 1 1
Setup Zero-point return Automatic operation Manual
-> operation
[ I
I
I
I
Setup*
I I t
When (CO- 15=0), the setup operation is necessary after zero-point return.
In the case of (CO- 15#0), no setup operation is requested since the system executes the setup
operation for (CO- 15) atuomatically~
OPEN CLOSED CLOSED OPEN + CLOSED Zero-point offset amount automatic setup operation
–20-
4.2 SETUP
■ Function The system sets the station number of the controlled machine currently stopped.
To carry out setup operation, it is necessary that the machine be stopped at any one of
the station positions and mechanically clamped. Otherwise, carry out setup operation
after zero-point return.
When (CO- 15=0), the setup operation is necessary after zero-point return. In case of
(CO- 15#0), no setup operation is requested.
Automatic/manual operation without setup operation after turning the system ON
results in an alarm (exept in the ABS mode).
If the backlash correction is not “O”, always carry out zero-point return before setup
operation (except in the ABS mode).
r 1
Input the current station number
L
STA.NOO to STA.N08
Select setup operation mode. MODEO to MODE2
+
I
I
SVON OPEN —
MODE
STA. NO
.. 1
START OpEN ~ I
POS. NO
-21-
4.3 ZERO-POINT RETURN OPERATION
■ Function The system carries out positioning of the machine and stops it at the zero-point.
Return to zero-point used zero-point LS signal.
Detecting start signal changing from OPEN to CLOSED.
Start zero-point return operation direction by CO-05 speed by V3.
Detecting zero-point LS signal changing from OPEN to CLOSED decelerate to V4.
Then detecting zero-point LS signal changes CLOSED to OPEN.
● At zero-point return operation O (CO-14=0)
Move and position by the zero-point offset preset from the first Z-phase pulse of PG.
● At zero-point return operation 1 (CO-14=1)
Move and position by the zero-point offset preset.
Running speed V3, V4 is set by parameter (EO-20 to -23, EO-30 to -33).
J
Input of START signal after the above START OPEN + CLOSED
i
1 I
■ Time chart Fig. 4.5 shows the time chart of zero-point return operation.
SVON OPEN
MODE
START OPEN
ZRET - LS OPEN ~
CO-14=1
CO-14=0
PG A, B“pdse .r...r~~fs~’.~.. –
Z pulse n n n
COIN .“””””””~OpEN~cLOsED-
SPEED ~v’~vl—.
Fig. 4.5 Time Chart of Zero-point Return Operation
–22-
4.4 ZERO-POINT OFFSET AUTOMATIC SETUP OPERATION
■ Sequence Fig. 4.6 shows the sequence of zero-point offset setup operation.
1-..
Input of START signal :~fter the above START OPEN + CLOSED
J
~-– J
1
1
COIN signal is output within 5msec,
COIN OPEN or CLOSED - OPEN 1
and auto setup operation starts.
L-.
Detection of zero-point LS signal.
And zerc>-point offset is automz~tically set.
—A
I
r-
+- -.
Moving in reverse after detection on zero-point
COIN OPEN + CLOSED
LS signal, and stopping at the original position. 1
■ Time Chart
SVON CLOSED ——
MODE
START OPEN —
n n n n
PG Z pulse
PG A, B pulse ~~ r f r
co 14=0 Offset +J
-. co 14=1 Offset
F
ZRET - LS OPEN —
COIN ~Op~N~cLOsEm
SPEED
~v5~
-23-
4.5 AUTOMATIC OPERATION
Function The system moves the controlled machine to the station of the commanded number,
positions it and stops it there.
In the case of a rotating axis, the shortest path control which determines the shorter
distance direction is used.
The direction can be fixed or commanded externally.
When START signal is changed from CLOSED to OPEN during automatic
operation, the machine is positioned and stopped temporarily y at the nearest station in
the running direction at that moment. Then COIN signal is output. (COIN-A signal
is not output.) From this status, any operation mode is possible to use.
Running speed V 1 is set by parameter (EO-00 to -03).
Time Chart Fig. 4.9 shows the time chart of automatic operation.
SVON CLOSED
MODE —
STA. NO
START OPEN
COIN-A
COIN CLOSED
NEAR CLOSED ~–—–.–.
POS. NO
/ \
Fig. 4.9 Time Chart of Automatic Operation
-24-
4.6 MANUAL OPERATION
■ Function The system positions the machine and stops at each station by manual operation.
Select manual mode and direction and make START signal CLOSED, and operation
will start. When making START signal OPEN, the machine will be positioned and
stopped at the nearest available station in the operation direction.
Running speed V2 is set by parameter (EO- 10 to - 13).
I
+ )
Note: After start of operation, COIN-A signal is output OPEN, and continues to be output even after completion of
opemt ion.
■ Time Chart Fig. 4.11 shows the time chart of manual operation.
F/R
MODE
START OPEN
COIN CLOSEI)
NEAR CLOSED ~~
..
POS. NO
SPEED
_/-—v2~
Fig. 4.11 Time Chart of Manual Operation
-25-
4.7 EMERGENCY STOP OPERATION
■ Function When emergency stop signal (EMG) is OPENED during any operation, emergency
stop is carried out. Normally, the stop position is not a station. (deceleration stop)
After an emergency stop, output is stopped, and alarm status appears. To release this,
perform after reset.
After an emergency stop, COIN, COIN-A, and NEAR are output OPENED. When
the machine is stopped at any station after resetting, COIN, NEAR signals are output
CLOSE. COIN-A is output CLOSED.
When emergency stop operation is performed after a setup operation, there is no need
for zero-point return operation/setup operation after reset.
Manual/automatic operation is possible without any preparation.
After selecting JOG operation mode and F/R signal, changing the START signal from
OPEN to CLOSED causes operation to start in the commanded direction.
And the machine stops at the same time the START signal is changed to OPEN.
Normally the stop position is not a station.
During JOG operation, COIN, COIN-A, NEAR signals are output OPENED at the
same time as the start of operation, and OPEN signals are output even after
completion.
However, in the case of stopping at a station, COIN and NEAR signals are output
CLOSE. COIN-A is output OPEN.
During JOG operation, the station position output indicates “O” at the same time as
the start of operation and even after stopping, indicates “O.”.
When stopping at a station, the number of the station is output.
When carrying out a JOG operation after setup, there is no need for a zero-point
return operation or setup operation.
Manual/automatic operation is possible without any preparation.
Running speed V6 is set by parameter (EO-50 to -53).
..
-26-
5. PARAMETER SE~lNG / MONITORING
Parameters to be used for station indexing control are shown in the table below.
Perform parameter setting while the motor is stopped.
Cn-NO Function Name Lower Limit Upper Limit Unit Initial Vatue
N(]tes :1. Attach or detach the digital operator (JVOP- I~) whtle the power ii turned OFF.
2. Any pos!tloll]ng operation is possible with the digital o~rator (J VOP- t M)) connected, however, parameters cannot be set during o~ration.
(Parameters can be set only white Juspoint D is not operating.)
3. Parameters out of the upper or the lower limit cannot be set. In this case, tbe upper or the lower limit will be set.
4. When 0 -pint [>ff\et automatic setup is selected and the O-point offset is out of tbe upper timit or the tower tim]t, an error occurs.
–27-
Table 5.2 Parameter Functions
–28-
Table 5.2 Parameter Functions (Cent’d)
-29-
Table 5.2 Parameter Functions (Cent’d)
-30-
Table 5.2 Parameter Functions (Cent’d)
-31-
Table 5.2 Parameter Functions (Cent’d)
-32-
Table 5.2 Parameter Functions (Cent’d)
:’lJ—\>
-33-
Table 5.2 Parameter Functions (Cent’d)
-34-
5.2 OPERATION STATUS MONITOR
Table 5.3 shows the list of operation statuses to be monitored. Monitor the operation status while the
system is at a standstill. Monitoring cannot be carried out during operation.
Uo-oo Input signal block A Sequence input signal status CON 1-A3 to B9
Uo-ol Input signal block B Sequence input signal status CON I -A1O to B 12
A 23 to B23
UO-02 Output signal block A Sequence output signal status CON 1-A 13 to B 19
UO-03 Output signal block B Sequence output signal status CON 1-A20 to B20
UO-04 Station number command value Station number command value STA.NO O to 8 in decimal
notation
UO-05 Current station number value Current station number value POS.NO O to 8 in decimal
notation.
UO-06 Zero-point offset Zero-point offset in decimal notation
UO-07 Zero-point LS position Zero-point LS position in decimal notation
UO-08 Current position (pulse) Current position pulse in decimal notation
UO-09 Deviatoric pulse Deviatoric pulse in decimal notation
-35-
Table 5.4 Monitor Function (Cent’d)
-36-
Table 5.4 Monitor Function (Cent’d)
UO-03 ............
When a signal is CLOSED, the corresponding indicator ( —) is lit.
-37–
5.3 HOW TO USE PARAMETER SETTER (Model JVOP-1 00)
Turning system ON
1
*2 Setting/nlonitor rr]ode *1 Teaching operation mode
I I
I I
>
&
*2 I *2
Y
*2 +*2
v Co-oo dO-02
Y
Eo-00 Uo-oo
I So-oo
P Co-ol dO-03
&
Q
I
Eo-02 UO-02
L SO-02
dO-06
m g
SO-04
* I : Teaching mode is selected by depressing PRGM/DRIVE key. And depress the key again and the teaching mode is ended
*2 : Mode changes one after another when “DSPL’ key is depressed.
1
Press the “ENTER” key to display parameter value.
Parametervaluedisplay
*1
*
Set (display) a parameter value by depressing the
Parameter value setting ~ ~ ~, “~ ,, and “~,, keys
I
I
+
Press the “ENTER” key to input the parameter
Parameter value writing
value.
L
Displays “End” for 0.5 second and completes
“End”display
setting. No display will appear after that. *2
* 1 : Operation will not be possible unless “ENTER” is depressed to finish parameter setting.
No operation commands are accepted.
*2 : To set more than 6-digit parameter , set the lower 4 digits first and then the upper 4 digits.
* 1 : Monitoring data during operation shows the changes made every moment (real time).
*2 : Operation is possible even without depressing “ENTER” to finish monitor setting. However, you
must finish monitor setting before carrying out other settings or monitor operation using the
parameter setter.
*3 : 1()_digit data are to be monitored in two sections, upper and lower 5 digits.The lower 5 digits are
monitored first and the upper 5 digits.
-39–
5.3.4 Parameter initial value setting flow (So-nn)
~
J
‘arameterinitialvalue
Displays “End” for 0.5second and completes
“End” display
setting. No display will appear after that. *2
* 1 : This setting is to be made only upon delivery from the factory. If this setting procedure is carried
out, all parameters will be set back to the initial values used upon delivery.
*2 : Operation is not possible unless “ENTER” is depressed to finish the parameter setting operation.
*3. . when CO-12=1, pwameters cannot be initialized. First set CO-12 to “O” then initialize the parameters.
*4 : Parameters other than S0-00 are for factory inspection use: do not use them.
* 1 : The “DSPL” key is invalid in the teaching mode. Cancel the teaching mode before using the
“DSPL” key.
*2 : The “FOW/REW” key is invalid during operation The JOG direction will not be changed even if
the k. y is depressed during operation.
*3 : The teaching operation is to be performed in the case of [CO-12=0]. Note that the teaching
operation can be performed in the case of [CO-12=1] as well, however, the position data of
teaching will not be written in parameter [dO-**].
*4 : Monitoring data after carrying out the teaching operation allows you to monitor the data that have
been set by the teaching operation. Setting parameters after that will allow you to correct or
change the values that have been set by the teaching operation.
–40–
*5 : Furthermore, it is possible to correct the position error by carrying out teaching after setting the
parameters
*6 : Executing the teaching operation before setup will result in teaching from station number 1.
Teaching for station number 1 ends in the same state as when setup was performed (state
indication 5). After that, teaching to the desired station number will be enabled.
*7 : After the setup operation, teaching to the desired station number is enabled.
*8 : Station numbers must be arranged in order. The direction of the order is set in parameter [CO-03:
Motor rotational direction switching]. When the station numbers are not arranged in order at the
start of setup, manual, or automatic operation, alarm “C” will be occured.
*9 : The distance between adjacent stations (pulses) can be “O”. However, if this value is smaller than
the setting for backlash, alarm “d” will be occured.
*10 : The JOG oPeration speed conforms to the settingof parameter [EO-.5Oto -53] and the input in
MULTO and 1. It also follows the input of the EMG/SVON signal.
*11 Teaching operation can be performed irrespective of the setting of parameter [CO-01: Rotational
axis/linear axis]. The teaching data will be written in parameter [dO-**]. These data will be
written as the absolute coordinate axis data. Therefore, to carry out positioning using the
teaching data, parameter [CO-O1=4: Absolute coordinate axis] must be set.
Carry out the connection of the parameter setter with Juspoint ~ (point module) turned OFF. We do
not guarantee proper operation if the connection is made with Juspoint Ill turned ON.
The following keys do not function (even when depressed) : [RUN] [STOP]
Depress the “ENTER” key to finish parameter setting/monitor operation, and then depress the
“DSPL” key to carry out parameter setting/monitor operation, and the next parameter
number/monitor number will be displayed. (Example : CO-12 s CO-13)
Depress the “ENTER” key to finish parameter setting/monitor operation, and carry out operation,
and then depress the “DSPL” key to carry out parameter setting/monitor operation, and the
following parameter number/monitor number will be displayed.
The parameter setting operator is a not Juspoint ~ accessory. It is identical to the parameter setter
used in the inverter (VS series) made by Yaskawa Electric. (Type : JVOP- 100: made by Yaskawa
Electric)
■ Holding down each key does not cause the key to repeatedly function. Release each key after
depressing it for the next key operation.
-41-
6 1/0 INTERFACE
24V
10k Q
COMPARATOR
12v— +
2.4mA
●24V
2.4mA
/’ \
+ COM COMPARATOR
12V. –
f )
11 10k Q +
10k Q
O.l UF
. .
Ov T Ov
-42–
6.2 OUTPUT INTERFACE
L Ov Ov
24V
COM
COM f \
Max. (service) voltage 35V
Max. (service) current 50mA
SIGNAL n
–43–
6.3 SUPPLEMENT OF SEQUENCE CONTROL OUTPUT SIGNAL
0: OUtpUt\ OPEN at the start <>fthe operatio!l, and <)utput\ CLOSED at the complt’t,(ln [>fthe nperat]on.
x : Output> OPEN at the start of the <?peratlc]n,and outputh OPEN tit the complet]c]n [71[he c)ueratlon.
A : Outputs OPEN at the \t;trt of the (>pcration. and output\ CLOSED at [he c[,n]pletiorl of the opcrattc)tl (after reset in the case of an
e!llergency \tc)p) lf stoppl]>~ at 1 stalion. otherwi\e, outpllts OPEN.
MODE 0-2
F/’R ~___
STA. NO 0-8 —
tl > Omsec t2
d--+ —+
t2 > 10msec
START OPEN
■ At Operation Completion The operation completion signal (COIN) is output at the completion
of operation, and simultaneously, current station number (PDS, NoO-
8) is displayed. Therefore, after detection of out (OPEN +
CLOSED) of operation completion signal (COIN), acquire the current
station number.
COIN . . OPEN
I—Station number can be acquired.—
POS. NO 0-8
–44-
6.5 ABS MODE 1 AND 2
* 1 The time required for storing the memory while the motor is stopped is about 200 msec.
*2 When the ABS mode 1 [CO-09=1] is to be used, use it with the specially designed brake motor. The ABS mode 2 [CO-
09= 1] does not require a special motor.
*3 In the case of ABS mode I [CO-09=1], all the position information is stored in EZROM, thus enabling the control almost
as precise as the absolute value PC, However, if the motor is rotated while the power is turned OFF positioning will have
an error egual to that amount.
In the case of the ABS mode 2 [CO-09=2], only the station number is stored in EROM : use this mode only when you
have the mechanical clamp mechanism (e.g. pin insertion). That way, even when the motor shaft rotates while the power
is turned OFF due to play in the transmission mechanism, the positioning error will not exceed a certain value.
*4 To use the ABS mode for momentary power loss during operation, make sure the following conditions are satisfied.
1. The brake turned ON simultaneously with momentary power loss to stop the motor in a very short period of time.
(Examine the brake operating life.)
2. The ABS.ST input becomes OPEN simultaneously (within about 100msec.) with the momentary power loss.
3. The power (24VDC) is retained until the ABS.READY output becomes CLOSED. (The ABS.READY output
becomes CLOSED in about 200msec. after the motor is stopped.)
*5 When memory storage was not complete before the power was turned OFF, alarm D will be output as soon as the
ABS.ST signal input becomes OPEN.
In this case, reset the fault and carry out the zero-point return and setup operation.
*6 In the case of the AB S mode 1 [CO-09=1], the above operations can be performed when the backlash compensation [CO-
13= 1], is set to other than “O” (zero-point return and setup operation after turning ON the power is not required).
In the case of the ABS mode 2 [CO-09=2], set “O” for the backlash compensation [CO-13].
-.
–45–
■ Sequence diagram 1 (For normal power turning OFF: while the machine is stopped)
200VAC
ABS.ST
‘cLOsED~ OPEN~
Speed O r/rein
;
E2ROM
...............
—24VDC
Brake ON
Brake (motor) <---;
Speed ~0 r/rein ,
v
E2ROM
..
7. STATUS/ALARM INDICATION
Status indication is also possible on the 7-segment indication on the point module board.
Table 7.1 shows the contents of the status indication.
This indication is continuously lit. (A flickering indication is an alarm indication.)
IA!
lb!
c I
I d
I
Memory storage in ABS mode completed. (ABS. READY CLOSED being output)
F Just after turning ON in ABS mode (ABS. READY CLOSED being output)
Whether or not the inverter is in the normal operating state can be monitored with the LED (7 segments)
on the printed circuit board in the inverter main body (the LED is continuously lit in the normal
operating state).
Table 7.2 shows the indication of the normal operating state.
Servo OFF condition, ready for operation. After the power is turned OFF, the inverter
Stopped
carries out self-diagnosis and displays “-” if no error is found.
Running o Servo ON condition and normal operation is continued.
–47-
7.2 TROUBLESHOOTING
() Driver alarm was detected (de\crlption is Check the alarm on the driver. The alarm description is displayed on
displayed on the driver). the amplifier board.
I PC fault (including poor wiring) PG Fdult, PC poor wiring. or motor locked may he the cause, Check them,
Emergency stop operation was c~ccurcd. Emergency st{>pc>peration wa> occured to stop the motc~r.
2 Inputting OPEN fen’the EMG signal executes the emergency s[c)p operation,
After re\etting the alaml, zero-point return or setup operation is not requ]red.
Operation was comm:mded without setup Automatic or manual operation was performed with state “()” (without
3 operation after turning ON tbc power setup),
(except t’or ABS rnocie I and 2) Perfc)ml the setup operotion and then the automatic or manual operation.
Zero-poln[ 1.S was not detected during The zero-point LS was not detected after turning the molc)r for 40000
zero-pc>ln: offset au[umatic setup nperahon. pulsci ( 10 mtations)during the zer(>-pc~intoffset autc>matic setup c>peratinn,
4 Check that the Tcr(~-pc>lntLS is currect]y wired and that the ilgnal ii inpat
[u Jusprrint U 0!-, moun[ [he zerc~-p{>intLS at a pusltion within 40000
pulses ( I() ro[ationi) frmn the zcrc~-point.
Zero-pnint LS was I1OLdetected during The zer(>-pnin[ 1.S was m~[detected after turning [he mc]tor for all se[
5 zer(>-puint return nperatiml. i{aticmi ciuring the zero-pu]nt retul-n opemti cm. Check that the zerc~-pc]inr
LS is correctly wired or that the signal i. input tc>Juspoint D
Undefined station number wiI\ cnnlmande(i. Cml]mand a it:{timl nulllber within the r:mge set by [C()-f)O: number of
6
Statimlil (for setup or autmnatlc operating),
Opemtion mnde was not set currectly. Undefined npetmhnn lmnde was lllpu~. Set the cnrrect opem~iml mc)cic input
7 (MODEO-MODE 2)
Zer(>-pc)int clft’set automatic setup operation was IC()-()4=()] I, .et (/erc)-pc)iIlt {)f’fsetsetup i. set to p,immeter ll]nde).
x cmnln anded whe[l tbc zerc)-pc>l[lt(~ffset setup Tc>perfcmn the zer(~.poin[ c)ll.et tiutmnatlc setup upet-ation. set [C()-()4= 1].
mnde i\ SC(to pammeter rnodc.
Zerc~-pc~intLS positicm el-rrrr (the ~ero-prrint The Zero-puint LS p{)sitiun arid the Z-phase pulse position of PC IS ton
9 LS position is too close to the Z-phase position. CIOSC(+120 pulses). Change the 1.S position or Z-phase position.
with)n +120 pulses)
Zero-point off’set is out of alluwable range The Zerc~-pc~intnt’fset detected durf[lg the lerc)-pc~]nl ofliet automa[ic setup
A (nut c~fthe range set by para,ljeter [C(). 1()].) {)pe]-ati[mis nut of the range of 120-40000. Change [he zert>-pc~intLS
positiun cc~rrectly.
The tc)llc)wing occurred when the backlash A value I:irger than the minimum value of sta~inn interval pulse\ is set fm’
cnmpeniation was nther than “0”. the backlash compensation nr ~ero-prrint re[um WIS tln~ caroled out belore
. Selup operation was commanded without the setup c~peratinn, Check the twn poiiibilitiei and cm-rect the setting ur
b zcrn-Wint return (except fc~rABS nlede 1 and 2), sequence.
. Zero-point offset automatic setup oprtation
was commanded. The backlash compensation
]i larger than the unit station pulses. (Set a
v~lue smaller than the unit station pulses. )
Station numbers are nc)t amanged in <>rderin the Stations are IIULarranged in Ihe order {>fstation numbers in the case of the
case of’the absc>lu~epoiition setting [C()-()1=4). :Ibso lute cc]c>rdinate axi~ [C()-()1=4). Set the pammetcrs nr carry m!t
c Arrange the station numbers in the order of teaching so that the statl[ms WIII be in the (>rder of stnticm numbcri,
station nurnbcrs,
In the ABS m[~de. the memury storage was nc)t In the case c)I the ABS m(>de [C()-()9= I or 2], the inf’otmati[>n required for
completed. Re\et and perform 7ero poirlt the ABS operation was not stored in the nonvc)latile memc>ry before the
return. power w~i, turned OFF. Tu excute ABS operation, first change the ABS. ST
d signal f’rom CLOSED to OPEN and make sure that the ABS. READY signal
. .
becomes CLOSED befure turning OFF the power, This alarm is also issuec
when the motor shaft is fnrced to rotate by exlernal force while the power i:
turned OFF. When the ABS mode I IS to be used, the motor must have a
brake.
MCU error Malfunc[l(>n of the microcomputer (out of control). It is possible that noise
has entered from the ccmtrol signal line or 24 VDC power line. Take
measures to prevent noise lmm entering these lines; shield the cables or
Blank separate the lines from the power lines carrying large cuments. It is also
possible that the control unit is faulty. [t’the error does not disappear by
eliminating the noise, replace the control unit and return it to the factory,
-...—- -
Keset the alarms u$lng the reset signal (RESET). The alarms can also be reset by the power suppty (24 VDC). Keset the power supply
in the case of the MCU error.
–48–
[Cause and remedy of alarms for the inverter (Juspeed-F X3000)]
Error indication (Errors are indicated by blinking indication.)
Errors of the inverter can be monitored on the LED (7 segments) on the printed circuit board in the
inverter main body.
Overcurrent or shofi-circuit It is possible that the torque limit is too high or the output has a shofl-
lvercurrent 1 cumnt wa~ detected and the circuit. If no change can be seen after changing the torque limit to
invertcr output was shut-off. 200% or smaller, check for a short-circuit of the output,
Regeneration overvoltage was The torque limit may be too high or the regeneration resistor may k burned
detected and the the inverter out. If no change can be seen after changing the torque limit to 200% or
overvoltage 2.
output was shut-off. smaller, return the regeneration resistor to the factory for investigation.
DC bus voltage: 450V
The motor speed exceed When the motor $peed gets up to 1980 r/rein, the motor is being forced to
1.1 times max. speed (10 rotate by an external force. Check for the cause and eliminate it.
Overspeed 3 Ycincrea$e) was detected and
, the inverter output was sbut-
I oft.
A voltage drop was detected The power supply voltage has dropped ( 180 VAC or lower) during
Under- and the inierter output was operation or instantaneous power failure was detected, If the cause cannot
v01tage 4 T
, ~hut-uff. DC voltage: be eliminated, add a sequence that will input the reset signal after tbe
\ 213V voltage drop or momentary power loss.
Encoder error was detected PG fault, PC wiring fault, or motor-lock can be considered. Check for the
and the inverter output was cause of these faults.
PG error 5
\hut-off Note that not all the
PG errors can be detected,
The tcmpcmture inside the The temperature inside the motor has become high or the temperature
Exceeding motor bas risen above the detection line (inside the PG cable) is faulty. Check the motor temperature.
6
empcrature regulated value and the inverter If the temperature is normal, check the temperature detection line
output was shut-off, (PG cable).
CPU error was detected during Since the error was detected during self-diagnosis earned out after power
the self-diagnusis carried out was supplied, it is a hardware error. Replace and return it to the factory.
CPUerror I 7 after power was supplied and
the inverter output wa~ shut-
off.
CPU error (WDT) was Malfunction of the microcomputer (out of control). It is possible that noise
detected during operation and has entered from the control signal line or 24 VDC power line. Take
tbe inverter output was shut- measures to prevent noise from entering these lines; shield the cables or
;PU error 11 8 off. This error is detected separate the lines from power lines carrying large currents. [t is also
for extcmal noise. possible that the control unit is faulty. If the error does not disappear after
eliminating the noise, replace the control unit and return it to the factory,
CT (current detector) error was Since the CT error for current detection was detected, it is a hardware error.
CT error 9 detected and tbc inverter Replace and return it to the factory.
output was shut-off.
Ground fault was detected in The ground fault was detected in output lines (U, V, W) upon servo ON.
Ground the output at the start of opera- Check whether tbe output side is being grounded, If this alarm is not reset
b
Fault tion and tbe inverter output after the grounding state was reset, replace and return it to the factory.
was shut-off.
An error (alarm) other than An error other than those listed above was detected. It is possible that it is
those listed above was detected alarm 8 above. Take tbe corrective action listed in the column for alarm 8,
Others 0 and the inverter output was and if no improvement is made, replace and return it to the factory.
shut-off.
Notes: I When more than one alarm is detected, they are indicated cyclically.
Example: When alarms 3,4 and 7 are detected, the LED will display 3 G 4 _ 7* 3~ 40 7 c 3 and so on
2 The alarm state is retained unless the power supply is reset or th reset signal is used.
3 The.indications blink.
–49–
8. PRECAUTIONS ON APPLICATION
(1) Minus Load
Continuous operation in which the motor is rotated by load and regenerative brake is applied
cannot be performed. Juspoint 111regenerative braking capability is short-term rated specification
about motor deceleration time.
(Example) ● Motor drives for delevery
● Motor drives for lifting object (without counter weight)
..
–50–
9. OPTION
For setting the parameters, use the parameter setter manufactured by YASKAWA ELECTRIC.
Specify the following type when ordering. It is common for all capacities.
JVOP–1OO
This is a cable used to connect the parameter setter (JVOP- 100) and Juspoint III. You must specify the
length.
9.3 PG CABLE
This is a cable used to connect the motor PG (pulse encoder) and Juspoint Ill. You must specify the
cable length and the structure of the connector on the motor.
All cables are to be manufactured after receiving the order.
v 4 0 1 7 q – 1.:::;
i..”::“:2
Connector structure ~ L Cable length
7: Straight plug 005: 0.5m
8: Angular plug 010: l.Om
015: 1.5m
020: 2.Om
025: 2.5m
030: 3.Om
040: 4.Om
050: 5.Om
060: 6.Om
070: 7.Om
080: 8.Om
090: 9.Om
100:1 O.Om
abO: (axl O+b)m
-51-
9.4 PARAMETER SETTING SOFTWARE (personal computer software)
Parameters can be set, edited, written, stored onto memory storage media, or verified using your
personaI computer. With the NEC PC98 version, the screen display is in Japanese and with the IBM
version, the screen display is in English. The software will be delivered stored on a 3.5’’2HD floppy
disk. For details, refer to the appropriate document (PC98 version : YDVES-B2 126, IBM version :
YDVES-B2 127).
PC JVOP-JP 3-[:
L Personal computer
1: NEC PC98 computer (Japanese display)
2: IBM computer (English display)
To use the software for parameter setting, you must connect Juspoint III to your personal computer
with a communication (RS232C) cable. The cable specifications are listed in the document sheet.
Specify the following type when ordering it from YASKAWA. This cable is manufactured after
receiving the order. The lead length is 2m.
V 4019::.”;
L Applicable model (personal computer)
4: NEC PC98 (for 25 Pins)
5: IBM (for 9 Pins)
Al:@
B1:Q B4
B4:@
JuspointIII Personalcomputer
(CON3)
(Equivalent product)
T910-B500FL
(SUMITOMO 3M)
Al:@
Bl:@
B4:@
10. CHARACTERISTICS (Speed-Torque Curve)
TORQUE
‘:::R
TOROUE
o’
SPEEO (r/mIn)
1.5kW 4 poles
1800
‘n
TOROUE
01
SPEED (r/m!nl
2.2kW 4 poles
1800
398
TOROUE
0.406
01
H 40%ED
(CONTINUOUSI
SPEED (r/m[n]
3.7kW 4 poles
;
\
1800
n r
h h h
40%E0 : 40%ED : 30%E0 :
795 081 1166 1190 19.62 2.002
(CONTINUOUS) : (CONTINUOUSI ~ (CONTINUOUSI ;
h
01 o’ 0’
1800 1800 1800
SPEED (r/rrlin) SPEED (r/inn) SPEED (r/rriin)
11.1 CONTROLLER
(Heat sink installed in the panel) (Heat sink installed out of the panel)
0.2kW
(114HP)
❑ 130(512}
35) HOLE
RECEPTACLE
FORENCODER
0.4kW MS3102A2O-29P
(314HP)
~ 1;; 4411 [0431HOLE
\
0.75kW
(l HP) DI~S 4$11 (0431HOLE
Encoder Connection
Un ti Sgd
A A@
GND=
: B-
RECEPTACLE FOR ENCOOER D GND
1,5kW MS3102A2O-29P E
x
F z Pks
(2 HP)
‘055’
‘OLE G
H
J
GND
THERM+
K THERM-
e
L
8:
-.
e
,03!1 M
“o” - E N
o
~ 24:,,: P
d
,O?d ;m, R +5V
s GND
T
w
RECEPTACLE FOR ENCOOER R~
2.2kW MS3102A2O29P
Encoder specifications
5VDC. 1000P/R
A, B, Z-phases, O~en corrector tvoe
Connector
MS3 102 A20-29P (Receptacle)
3.7kW
(5 HP) Connection compnent
MS3 108 B20-29S (Angle plug)
MS3057-12A (Cable clamp)
Notes :1. D!mmensions ot’ tbe shaft extension key and key way are based on JISB 130 I-1976
2. Tbe insulation class is B.
3. The drawings show 4-poles motors,
-54–
Motor without brake (Model
0.2kW
(1/4 HP) 0130(512)
~~ 4+9 (O351HOLE
.---
.
:
<,
0.4kW
4411 (043} HOLE
(3/4 HP)
-
0.75kW
(l HP) 4+1 1 (O 43) HOLE
&
-55-
APPENDIX
–56-
A 1 HEAT LOSS DATA (Juspeed-F X3000/Juspoint III)
Total generated heat: Generated heat from power section+control section (Unit:W)
1: Values In ( )indicate the heat dissipated to the outside (rear) from the heat sink
2: Data for servo ON is that under no load.
3: The speed is the base speed, 1800 rlmin.
LOAD CONDITIONS
–57–
A 2 BUILT-IN DISCHARGING RESISTOR CAPACITY
(Juspeed-F X3000/Juspoint III)
The data listed here are for you to refer to and decide whether or not the built-in discharging resistor
can be used.
1 Loads MODEL
If the result of the above calculation shows that the built-in resistor cannot be used, you must use
an external resistor. The following describes how to select the capacity of an external resistor
“WEXT”.
WEXT= Wx 4 (Select a resistor that has a capacity 4 times the generated heat.)
* To use an external resistor, a lead wire is required for connecting to X3000.
The lead wire will be manufactured in our factory after receiving the order. A FASTON(250)
receptacle is attached at the end of the 300 mm lead.
* Use a resistance designated for each capacity. An external resistor is available from YASKAWA
(60 to 1000 W, parallel connection for more).
–58-
A 3 ACCELERATION AND DECELERATION TIME SETTING
The following describes how to set the acceleration and deceleration time.
1 ACCELERATION TIME
following formula.
tACC = Acceleration time parameter setting x VREF = 1800 (msec)
2 DECELERATION TIME
There is no parameter that sets the deceleration time. The deceleration time is determined by the
position control constant (KP).
The deceleration time is not in reverse proportion to KP but is in reverse proportion to KP2.
r~
‘R”
I
-59-
2.2 Using soft stop
The deceleration time (tDEC) can be expressed by position control constant (KP)/soft stop speed
(VSP)/soft stop KP2.
Vsp K P2
--tl [ t2]
t “Ec
Supplementary explanation
1. Note that the acceleration time/deceleration time is made longer by using the soft start/soft stop
function.
2. When the setting is KP<KP2, the control will assume KP=KP2.
3. When the setting is VREF<VSp,the control will use KP2 from the start of deceleration.
4. When the setting is Vsp=O, the soft stop will not be used regardless of the value in KP2.
..
-60-
A 4 SPEED/TORQUE MONITOR
This section describes how to monitor the speed and torque of Juspoint III.
The speed/torque monitor output of X3000 (amplifier) is output from the connector (CON 1) which is
connected to the point module connector (CON4) with a cable.
Therefore, to monitor the speed and torque, use the signal line from the point module board.
nr
1 SPEED MONITOR
1 TORQUE MONITOR
COMMON
@ TERMINAL
(Ov)
1
I
t
1
Short terminals @ - Q and@ - @ and measure the voltage between the common terminal@ (OV).
-61-
A 5 RELATIONSHIP BETWEEN CURRENT AND TORQUE
OutputCurrent(A: rrns)
Capacity
A (O%torque) B (100% torque) C (2~% torque)
0.75kW
I 2.71
I 4.14 I 6.70
5.5kW
7.5kW
Notes: 1. The values in the table are the root-mean-square values (rms ) and will be 1,5 times that at the peak; 1.5 times was obtained
considering the current wave from distortion of the PWM control.
2. The current value at the time of O to 1fM3Y.and 100 to 2007. torque output can be obtained from linear approximation.
B
“7”
A
7
100 200
OUTPUT TORQUE (70)
-..
A 6. OPERATION UPON ALARM OCCURRENCE
Alarm # Description SVON signal OPEN SVON signal CLOSED Reset conditions
I PC error
Base block
2 None
Servo Clamp
to Control error
F
Notes: 1 When the PG error (alarm #1) is detected, the servo clamp may not occur because the correct
feed back of the PG signal cannot be obtained.
2 When the alarm is detected during high-speed operation, deceleration will be started as soon
as the alarm is detected until the zero speed is obtained (zero speed or extreme] y low speed
in the case of the PG error). After the deceleration is completed, zero speed (ZSPD) will be
output closed.
3 When the zero speed output as detected after the alarm output, try to input OPEN for the
SVON signal as promptly as possible.
4 When the amplifier side error (alarm#O) was detected, the alarm cannot be reset unless the
SVON signal is input OPEN.
5 When the alarm was output (alarrn#2) as a result of the EMG (emergency stop) operation,
input CLOSED for the EMG signal before resetting the alarm. Alarm (#2) will be output
again if the alarm is reset while the EMG signal is input OPEN.
6 To reset the alarm, input OPEN, CLOSED, then OPEN again for the reset signal. When the
reset signal changes from CLOSED to OPEN, the alarm will be reset.
7 In the case of the amplifier side alarm (#O), the alarm is indicated on the amplifier (l-digit
display) as well. Refer to Table 9.4 for the correspondence of alarm contents and the
indication.
-63-
A 7. TORQUE LIMIT SETTING
■ Torque larger than the torque limit value will not be output even during acceleration, deceleration,
constant speed, or servo lock.
9 The torque limit value is the same for forward and reverse directions.
■ Normally set the torque limit value to 200% or smaller. Setting the torque limit value higher may
cause overcurrent or overvoltage as well as rapidly increasing the motor loss.
■ Consider protection of the transmission mechanism such as the maximum allowable gear torque
when selecting the torque limit value.
■ On the other hand, setting a smaller value than the load torque will not allow the motor to rotate,
resulting in the PG (encoder) alarm.
-64-
■ By setting an acceleration time longer than that obtained from equation (1) below, the set accelera-
tion time will be used.
On the other hand, when a shorter time is set, the desired result will not be obtained. Acceleration
will be performed in the time (ta) obtained from equation (1).
(The parameter setting for the acceleration time sets the time required to accelerate from O to 1800
rlmin.)
■ By setting a deceleration time longer than that obtained from equation (2) below, the set time will
be used.
Conversely, when a shorter time is set, the desired result will not be obtained.
Deceleration will be performed in the time (td) obtained from equation (2).
(The deceleration time cannot be set directly. Set the position control constant [KP]. Refer to A3.
ACCELERATION AND DECELERATION TIME SETTING for the relationship between the
deceleration time and KP.
GD2M
: Motor inertia (kg.m’)
GD2, : Load inertia (kg-m’)
v : Speed (r/rein)
T,IM : Torque limit value (kgm)
T,. : Load torque (kgm)
-65-
A 8. EVALUATION CONDITIONS FOR TEMPERATURE-RISE TEST
FOR MOTORS
Thermal evaluation of the motor can be made by calculating from operating conditions (e.g. opera-
tion cycle). This section, however, describes how to perform evaluations through actually operating
the motor. When the motor is to be operated with a protective cover, this method is effective since
precise calculation will be difficult.
1 Measure the temperature of the motor at two locations to determine whether or not
the motor can be used from the thermal point of view.
■ Frame surface temperature (At center of frame and avoid the bolt sections.)
■ Internal air temperature inside the encoder enclosure.
2 Criteria
If the temperature-rise values at both points are equal to or smaller than the values listed in the table
below, the motor can be used.
0.2kW 50 48
0.4kW 50 48
0.75kW 57 51
1.5kW 62 51
2.2kW 58 49
3.7kW 59 51
5.5kW
7.5kW
The motor in this example can be used from the thermal point of view.
..
-66-
A9 SELECTION OF MOTOR CAPACITY
This section describes the basic on how to select your motor capacity.
Note that the control unit of the same capacity as the motor must be used. otherwise, the motor
cannot be controlled.
1 Model
v : Speed [r/rein]
TIME ta~tc —+td+ t~~
TV : Motor rated torque [kgm] t
TL : Load torque [kgm] TORQUE T,+ TL+Td+Ts ~
T. : Acceleration torque [kgm]
T, : Deceleration torque [kgm] SPEED ~v+ I
I
T, : Locked rotor torque [kgm]
■ 200% of the motor rated torque is larger than the deceleration torque (T,).
2X TM>T,
■ 100% of the motor rated torque is larger than the load torque (TL).
TM> T.
-67–
Al O GEAR RATlO SETTING
Depending on the gear ratio, the unit station interval pulses can be a fraction (not integer). A
rotational axis can have a further error accumulation.
In such cases, control with no error accumulation is enabled by setting the gear ratio in parameter. The
following describes how to set the gear ratio parameter.
1 Express the ratio of the number of motor shaft rotations to the machine output
shaft rotations in a fraction and set the numerator/denominator in the parameter.
B= Final machine output shaft speed
A Motor shaft speed
2 To control the unit station interval by the gear ratio, set the rotational axis/linear
axis parameter [CO-01 =2].
Example 2
NUMBER OF TEETH: 15 NUMBER OF TEETH: 100
MOTOR
Example 3
SPROCKET
NUMBER OF
TEETH: 15 80-TOOL MAGAZINE
REDUCTION f ●
MOTOR GEAR
–68–
All HOW TO USE EMG SIGNAL
This section describes how to use the EMG (emergency stop) signal.
1 As soon as the EMG signal detects the OPEN input, it starts the emergency stop
operation.
If the motor is running, it will be stopped at once; the deceleration torque for this is
the torque limit value.
After the motor is stopped, the machine will be in the alarm condition [alarm 2].
2 The EMG signal always performs the emergency stop operation as soon as it
detects the OPEN input except in state “F”.
3 Therefore, when turning ON the power or setting the parameters, make sure that
CLOSED is input for the EMG signal. If OPEN is input then, the emergency stop
operation will be performed and alarm 2 will be output, disabling all machine
operations and parameter settings.
5 Position control is continued during the emergency stop operation. Thus, no zero
return nor setup operation is required after the emergency stop. All operations
are enabled.
6 Immediately after alarm 2 is reset, the position at the time of the emergency stop
will be retained. After the next operation command, the motor will start moving.
-69-
A12 HOW TO USE SVON SIGNAL
This section describes how to use the SVON signal.
2 The CLOSED input immediately after the power supply functions as the servo
clamp at the current stopped position.
3 The OPEN input for the SVON signal during operation turns OFF servo and the
motor will stop after coasting. The motor usually does not stop at a station
position in this case. If, however, the motor stops at a station position and within
the COIN/NEAR range, the COIN/NEAR signal will be output.
4 The CLOSED input for the SVON signal after that functions as servo clamp at the
current stopped position. The motor will not rotate to a station position.
5 The motor will start moving according to the following operation command.
Positioning control is continued during the servo OFF state. Thus, no zero-point
return nor setup operation is required after servo ON.
7 Also, if you use a motor with a brake, input OPEN (servo OFF) for the SVON
signal while the brake is on.
8 When an alarm of the amplifier (X3000) is detected, it cannot be reset unless the
SVON signal is input OPEN.
..
-70-
A13 SETUP OPERATION
1 The setup operation sets (commands) a station number to the currently stopped
position in case it is a station position.
W With a mechanical clamp mechanism, the motor shaft will be mechanically clamped at a station
position. After the power supply, command (setup) the number of that station position. Refer to
the memory of the NC unit or the position information of the output shaft encoder.
■ When a mechanical clamp mechanism is not provided, performing the setup operation every time
the power is supplied means that positional errors will be accumulated every time the power is
supplied. Thus, if a mechanical clamp mechanism is not provided, be sure to perfom zero-point
return every time the power is supplied.
■ ABS mode 1
All positional information is stored in the nonvolatile memory before the power is turned OFF;
thus, no zero-point return nor setup operation is required after power is supplied.
■ ABS mode 2
Only the station number is stored in the nonvolatile memory before the power is turned OFF; thus,
no setup operation is required after power is supplied. However, errors will be accumulated every
time the power is supplied when no mechanical clamp mechanism is provided. Thus, when no
mechanical clamp mechanism is provided, perform the zero-point return every time the power is
supplied.
5 The following table shows when and when not the zero-point return and setup
operations are required.
With mechanical clamp Not required/Required Not required~ot required Not required/Not required
* In the case of [CO-15 #0], automatic setup operation is executed, thus setup o~ration is not required.
* In the case of [CO-15=0], setup operation is required after zero-point return.
-71-
A14 TEACHING OPERATION
This section describes the teaching operations and precautions.
1 The teaching operation is performed using the parameter setter (JVOP-1 00). Note
that the following control input signals are valid during the teaching operation.
EMG : OPEN input will start emergency stop and occured alarm 2.
SVON : OPEN input will turn OFF servo and the motor will coast to stop.
MULT O, 1 : Selection of the JOG operation speed.
4 Parameter [dO-**] will be used as the data of the absolute coordinates axis.
. ..0.=4{Fdo-03~ ,
5 Station numbers must be in order from no. 1. Othrwise, alarm C will be output.
The interval between stations must be larger than the backlash compensation.
. .
-72-
Al 5 INTERNAL MEMORY INFORMATION MONITOR
■ Indicated digits
The monitored data are indicated as signed 9-digit data. When the count overflows, ‘O’ is indicated
and count is restarted.
o, 1, 2, 3, 4, .. . .. 999,999,999, 0, 1, 2, 3, ......
0, -1, -2, -3, -4, . . ... -999,999,999, 0, -1, -2, -3, ......
7, 6, 5, 4, 3, 2, 1, 0, -1, -2, -3, -4, -5, -6, -7, ......
-7, -6, -5, -4, -3, -2, -1, 0, 1, 2, 3, 4, 5, 6, 7, ......
3 Others
-73-
A16 PG PULSE SELECTION
2 Differences in control
■ Since the internal control works in multiples of 4 of PG pulses, set the related parameters as 4000
or 4096/rev. according to the setting of CO-16.
, When the detected pulses differ from the PG pulses set in CO-16, it will be processed as the PG
error.
Therefore, when the motor PG pulses and the setting of CO- 16 are different, an alarm will be
output.
3 Others
■ The control unit is determined to be one type at the time of shipment and cannot be changed.
■ The choice of 1024 pulses is available for special overseas motors. Therefore, normally choose the
1000 pulses, the standard specification.
..
-74-
A17 STATION NUMBER OUTPUT DURING OPERATION
3 The numbers of the currently stoppable stations if the stop command is to be input
are output. Note, however, during JOG operation, the machine driven by the motor
will stop before the output station number.
[Example]
SPEED $
Traveling speed A
Traveling speed B
z DISTANCE
Station position @ @ B @
–75–
A18 SPEED COMMAND OFFSET ADJUSTMENT
Speed command (O-10V) is output from the point module (JBFPM 3) to the vector control unit (X3000).
Offset for this speed command has been adjusted before shipment and does not usually require any
further adjustment.
However, if you have changed the offset by mistake or have replaced either (JBFPM 3) or X3000, offset
must be adjusted.
This section describes how to adjust this offset.
2 Adjustment
■ Turn ON the power and set the machine ready for operation.
1 Input CLOSED for the SVON signal.
■ Input OPEN for the EMG signal and turn ON alarm 2. (JBFPM3 side)
I Set the DIP switch “DS 1-2” of X3000 to ON.
■ Adjust VR1 of X3000 to the position where the motor does not turn.
■ Set the DIP switch “DS1-2” of X3000 to OFF.
■ Change the input of the SVON signal from CLOSED to OPEN to CLOSED.
■ After the EMG signal is CLOSED, input OPEN, CLOSED and OPEN again for the RESET signal
to reset alarm 2.
■ During adjustment, the motor will move though at a low speed. Before starting adjustment, make
sure that rotation of the motor will cause no problems.
■ After adjustment, be sure to set the DIP switch “DS 1-2” of X3000 to OFF. Juspoint Ill cannot
operate correctly with the DIP switch set to ON.
■ If the offset is not adjusted correctly, the motor generates abnormal vibration or noise when stopped
(SVON: CLOSED). Also, the motor may rotate at an extremely slow speed when an alarm is
issued.
■ The DIP switch “DS 1-2” of X3000 is read by the microcomputer when the SVON signal changes
from OPEN to CLOSED.
..
-76–
A19 SETTING OF OPERATION CONSTANTS OF AMPLIFIER
The operation constants of X3000 used as the driver (speed control unit) of Juspoint Ill are set by
several switches.
When it has been incorporated as the amplifier for Juspoint Ill, the switches have been adjusted at the
factory before shipment and usually require no further adjustment. However, if a switch setting has
been changed by mistake, it must be adjusted or set again.
1. The switches used to set the constants are located on the board of the driver (X3000).
2. The following table shows the function and set values (A) for Juspoint U.
RDS I o 1 * 2 D E F
RDS 1 P GAIN
P GAIN 1~ ..2000 .......... ...................... 9000
RDS 2 0 1 A B E F
RDS 2 I GAIN
1 GAIN 5W ...... ... .. .. .. .. ..... . 6~ ................................................... 8000
-77-
A20 OPERATION CONSTANTS (PARAMETERS) LIST
Cn-No Name ~ Lower j Upper Initial I Set j
Limit Limit Value ~ Value : Unit
–18-
(Cent’d)
-79-
(Cent’d)
-..
-80-
m
-81-
Juspoint III
VECTOR CONTROL INVERTER POSITIONING SYSTEM
Distribute
( HIP.,
Manufacturer& Distribute
-.
DTSE-S606-9.1
Due t. mgo,ng Lvduct M,f,cat,m !mwoveme”t,
data s“b,ect to
change w,thout not,.. @ Printed m Japan November 199595-110