User Manual
User Manual
3
Installation
Setting up
This part of the manual describes how to set up the This part of the manual describes how to adjust
cabinet. legs / casters on the cabinet.
Due to safety and operating reasons, the cabinet must not be used Cabinets equipped with legs should be levelled as shown in the
outdoors. The cabinet should be installed in a dry and sufficiently illustration below.
ventilated area. To ensure efficient operation, the cabinet should not
be installed in direct sunlight or close to heat sources.
Avoid placement of the cabinet in an chlorine/acidic environment For cabinets equipped with casters, the floor must be level to ensure
due to risk of corrosion. stable positioning and safe use. When the cabinet is positioned, the
2 front casters should be locked.
If the cabinet has been laying down (ex. during transport.).Then the
! cabinet must stand up-right for 24 hours prior to use, This enables
oil in the compressor to run back into place.
4
bioline
Setting up
Cabinets with drawers and / or glass door must be secured to a stable vertical surface, ensuring that the cabinet can not tip over when the
drawers are drawn to the outermost position, or the door is open. Brackets for securing is included.
! The tilt brackets must be fitted when installing the cabinet, ensuring that the users, surroundings and stored items are not damaged by the
cabinet.
5
The cabinet must always be placed max. 75 mm from the wall while
Do not cover the upper part of the cabinet if it has a top
in use. It is optimal to install the cabinet as close to the wall as
possible. ! mounted compressor (applies to BioPlus 500, 600/660 and
1270/1400).
Max. 75mm
Min. 30mm
6
bioline
Voltage-free contact
This part of the manual covers the voltage-free
contact.
The illustration below shows the three connectors for the relay (used ex. in connecting to CTS or other external monitoring systems). The
three connections, are respectively. Common, NO and NC.
The moment when voltage is applied the controller draws the relay, this makes it possible for the controller to respond to both high and low
alarms, door alarms and power failures. Temperature alarms and door alarms must be configured in the external alarm settings (EAL) before
they will activate the voltage-free contact. Find instructions on setting external alarms in the Parameter settings section.
The wires that are connected in the connection block for the voltage-free contact, are secured in place by the press-fit plate that is pressed
onto the block, thereby also preventing access to the electrical circuit.
NO • • • •
NC • • • •
7
Mechanical low temperature protection
This part covers mechanical low temperature The illustrations below depicts the locations of the
protection low temperature protection on the different kinds of
cabinets in the BioMidi/BioPlus range.
Example:
8
bioline
Connection to electricity
Read the following part thoroughly before
connecting the cabinet. Contact an qualified
electrician if in doubt.
Note that there are special regulations for products that are in
accordance with EN 60079-15 zone 2. IMPORTANT
!
The appliance has been manufactured in accordance with EN
60079-15: Electrical apparatus for explosive gas atmospheres - Fuses and similar must never be removed or replaced while the
appliance is connected to a power source.
! Part 15: Type of protection “n”. Zone 2 is the applicable zone. If
the appliance is to be installed in a zone 2 environment, specialist
personnel should perform the installation, or be consulted
The electrical terminal box must never be opened while the
appliance is connected to a power source.
beforehand, in order to ensure that the appliance is installed in
compliance with the guidelines currently contained in the standard. The compressor starting equipment must never be dismantled while
the appliance is connected to a power source.
The cabinet is intended for connection to alternating current. The
connection values for voltage (V) and frequency (Hz) are given on the The halogen lighting must never be dismantled while the appliance
nameplate in the engine room. is connected to a power source.
In both cases:
Power must be connected via a wall socket. The wall socket should
be easily accessible.
9
Start-up
The digital display
The digital display depicted below, shows the
cabinets temperature and indicates if the cabinet is
connected to a power source.
Beyond setting the temperature and on/off, , , and is Press the button to turn the cabinet on. Press the button
used to navigate the menu and set the parameters of the cabinet. for 6 seconds to turn the cabinet off. The software version of the
cabinet will be shown when turning the cabinet on, followed by the
The buttons have following functions in the menu: software variant and a displaytest.
Temperature setting
Temperature adjustments are done by holding the button and
pressing either or . Confirm the settings by letting go of the
buttons.
10
bioline
Walkthrough of menu
The menu below gives a quick overview of the Please note: electric low temperature protection is
parameter settings for the cabinet. not applicable to BioBlood cabinets
User menu
Menu Access +
Local alarm settings LAL LHL [° C] Upper alarm limit. Code for activated alarm [A2]
LLL [° C] Lower alarm limit. Code for activated alarm [A3]
LHd [Min.] Delay of upper alarm limit
LLd [Min.] Delay of lower alarm limit
dA On/off Door alarm. Code for activated alarm [ A1]. [1=on / 0=off]
dAd [Min.] Delay of door alarm.
bU On/off Acoustic signal for alarm codes [ A1], [ A2] and [ A3]. [1=on / 0=off]
External alarm settings EAL EHL [° C] Upper alarm limit. Code for activated alarm [A4]
ELL [° C] Lower alarm limit. Code for activated alarm [A5]
EHd [Min.] Delay of upper alarm limit
ELd [Min.] Delay of lower alarm limit
dA On/off Door alarm. Code for activated alarm [ A1]. [1=on / 0=off]
dAd [Min.] Delay of external door alarm
bU On/off Acoustic signal for external alarm codes [ A1], [ A4], [ A5]. [1=on / 0=off]
Calibration of sensors CAL CA [° K] Calibration of A-sensor. Reference sensor for the refrigeration system
CE [° K] Calibration of E-sensor. Reference sensor for the display and alarms
CF [° K] Calibration of F-sensor. Reference sensor for the low temperature protection
Electric low temperature protection FP ACt On/off Activation/deactivation of low-temperature protection
tES On Test of low-temperature protection
[° C] Setting of the cut-off temperature for the low-temperature protection
SEt
PrE […] Read out of the real-time temperature of the F-sensor
ALL Activation of escorted alarm limits. [FAS]= locked limits / [ESC] = follows setpoint
dEF Number of defrosts per 24 hours (4 is factory setting)
dPS Reference sensor for the display (A, E or F) (E is factory setting)
Other Shortcuts
Buttons: Duration: Function:
+ > 3 seconds Start or stop a defrost.
- Shows the highest registered temperature spike (since the last clear and reset alarm
history).
- Shows the lowest registered temperature spike (since the last clear and reset alarm history).
11
Error codes
A1 Door alarm “dAd” from LAL and/or EAL has been activated.
F1 Error on the main cabinet sensor. The refrigeration system will use an emergency program to make the cabinet
run. Temperature stability will be affected. Service is required.
F7 F7 indicates that the temperature of the condenser is too high. Turn off the cabinet and check that the condenser
is not covered by undesirable items, and insure that the condenser (and possibly filter) is clean. Service is required
if the problem is not alleviated.
Cancelling a temperature alarm: [A2 and/or A3] Flashes in the display. Press to cancel.
The display will continue to flash if the temperature is outside the alarm limits, and will continue until the temperature has recovered.
Press to cancel the [A2]. The display continues to flash, indicating that there is information in the alarm history. Press ,
Htt (High temperature time) is shown, press to see for how long the temperature was above the set alarm limit. Press to return to Htt.
Press to reach Ht (Highest temperature). Press to read the highest recorded temperature during Htt. Press to return to Ht and
press again to leave the alarm history function.
The procedure for reading an [A3] alarm is identical, apart from entering the alarm history with the button. When reading out
temperatures below set limits, the parameters are Ltt and Lt.
A flashing display with no alarm codes indicates that the alarm codes have been cancelled, but the alarm history contains
information.
12
bioline
13
Parameter settings
Dry cool
The following part covers activation / deactivation of
the dry cool feature (only applicable to ER models).
dC - Setting the dry cool feature Please note that the dry cool feature reduces that relative humidity in
Press and hold + for more than 3 seconds the cabinet, but does not control it.
Press to choose “dC”
Furthermore, please note that activation of the dry cool feature can
Press or to choose between cause greater fluctuations in the cabinet temperature during defrost.
[H1= on] [H0=off]
Press to confirm
14
bioline
Press to select “LHL”. The upper alarm limit is now shown in the display
Press or to set the desired value for the upper alarm limit
- The upper alarm limit is now set, proceed to other parameters by pressing , and then navigate by using or .
Leave the user menu by pressing several times until the cabinet temperature is shown in the display
Press to select “LLL”. The lower alarm limit is now shown in the display
Press or to set the desired value for the lower alarm limit
- The lower alarm limit is now set, proceed to other parameters by pressing , and then navigate by using or
.
Leave the user menu by pressing several times until the cabinet temperature is shown in the display
15
Local alarm settings
The following part covers the setting of the delay for
the local upper and lower temperature alarm limits.
LHd - Setting the delay of the local upper alarm limit [min.]
Press to select “LHd”. The delay of the upper alarm limit is now shown in the display
Press or to set the desired value for the delay of the upper alarm limit
- The delay of the upper alarm limit is now set, proceed to other parameters by pressing , and then navigate by using or .
Leave the user menu by pressing several times until the cabinet temperature is shown in the display
LLd - Setting the delay of the local lower alarm limit [min.]
Press to select “LLd”. The delay of the lower alarm limit is now shown in the display
Press or to set the desired value for the delay of the lower alarm limit
- The delay of the lower alarm limit is now set, proceed to other parameters by pressing , and then navigate by using or
.
Leave the user menu by pressing several times until the cabinet temperature is shown in the display
16
bioline
- The local door alarm is now configured, proceed to other parameters by pressing , and then navigate by using or .
Leave the user menu by pressing several times until the cabinet temperature is shown in the display
Press to select “dAd”. The delay of the local door alarm is now shown in the display
Press or to set the desired value for the delay of the local door alarm
- The delay of the local door alarm is now configured, proceed to other parameters by pressing , and then navigate by using or
.
Leave the user menu by pressing several times until the cabinet temperature is shown in the display
17
Local alarm settings
The following part covers the setting of the acoustic
local alarms.
- The local acoustic alarms is configured, proceed to other parameters by pressing , and then navigate by using or .
Leave the user menu by pressing several times until the cabinet temperature is shown in the display
! Important!
In order to assure the safety of the stored items, the local alarms should
be supported by external alarms. This can be done by utilizing the
possibility of external alarms via the voltage-free contact.
18
bioline
Press to select “EHL”. The external upper alarm limit is now shown in the display
Press or to set the desired value for the external upper alarm limit
- The external upper alarm limit is now set, proceed to other parameters by pressing , and then navigate by using or .
Leave the user menu by pressing several times until the cabinet temperature is shown in the display
Press to select “ELL”. The external lower alarm limit is now shown in the display
Press or to set the desired value for the external lower alarm limit
- The external lower alarm limit is now set, proceed to other parameters by pressing , and then navigate by using or
.
Leave the user menu by pressing several times until the cabinet temperature is shown in the display
19
External alarm settings
The following parts covers the setting of the delay
of the external upper and lower alarms.
EHd - Setting the delay of the external upper alarm limit [min.]
Press to select “EHd”. The external delay of the upper alarm limit is now shown in the display
Press or to set the desired value for the external delay of the upper alarm limit
- The delay of the external upper alarm limit is now set, proceed to other parameters by pressing , and then navigate by using or
Leave the user menu by pressing several times until the cabinet temperature is shown in the display
ELd - Setting the delay of the external lower alarm limit [min.]
Press to select “ELd”. The delay of the external lower alarm limit is now shown in the display
Press or to set the desired value for the delay of the lower alarm limit
- The delay of the external lower alarm limit is now set, proceed to other parameters by pressing , and then navigate by using or
Leave the user menu by pressing several times until the cabinet temperature is shown in the display
20
bioline
- The external door alarm is now configured, proceed to other parameters by pressing , and then navigate by using or .
Leave the user menu by pressing several times until the cabinet temperature is shown in the display
Press to select “dAd”. The delay of the external door alarm is now shown in the display
Press or to set the desired value for the delay of the external door alarm
- The delay of the external door alarm is now configured, proceed to other parameters by pressing , and then navigate by using or
.
Leave the user menu by pressing several times until the cabinet temperature is shown in the display
21
External alarm settings
The following part covers the setting of the acoustic
external alarms.
- The external acoustic alarms is configured, proceed to other parameters by pressing , and then navigate by using or .
Leave the user menu by pressing several times until the cabinet temperature is shown in the display
22
bioline
Sensor calibration
The following part covers the calibration of the A-
and E-sensor.
The cabinet is equipped with a sensor (A-sensor) and an extra Press to select “cAL”. “cA” is shown in the display
sensor (E-sensor).
Press to select “cA”
The A-sensor is used to manage the cabinets refrigeration system
and is fixated in a given position in the cabinet, not in storage space.
Press or to calibrate the A-sensor
The location of the A sensor must not be altered.
The E-sensor is placed in the cabinet storage space and can be Press to confirm the set value
moved around in the cabinet to get the desired reference point
for temperature. The E-sensor is the default display sensor and -The A-sensor is now calibrated, proceed to other parameters by
reference for the alarms. The E-sensor has no effect on control of
the refrigeration system. pressing , and then navigate by using or
The A-sensor is calibrated if the actual temperature in the cabinet Leave the user menu by pressing several times until
does not match the setpoint, despite taking the hysteresis into the cabinet temperature is shown in the display
consideration. Calibration of A sensor is named “cA”.
23
Escorted / set alarm limits Defrosts / 24 hours
The following part covers the setting of escorted or The following part covers the setting of the amount
set alarm limits. of defrosts per 24 hours.
Press to confirm the set value Press to confirm the set value
Leave the user menu by pressing several times until Leave the user menu by pressing several times until
the cabinet temperature is shown in the display the cabinet temperature is shown in the display
24
bioline
Display sensor
The following part covers the setting of which
sensor to be shown in the display.
dPS - Selection of reference sensor Please note that dPS only changes the reference sensor for the
for the display display, and not the reference sensor for the alarms.
25
Electric low temperature protection
Electric low temperature protection is not available
for BioBlood.
26
bioline
Press several times until “FP” is shown in the display Press several times until “FP” is shown in the display
Press to select “FP”.“Act” is now shown in the display Press to select “FP”.“Act” is now shown in the display
Press several times until “SEt” is shown in the display Press to select “Pre”
Press to select “SEt” Press to show the low temperature protection sensor
temperature
Press or to select the setpoint temperature for the
low temperature protection Leave the user menu by pressing several times until
the cabinet temperature is shown in the display
Press to confirm the set value
27
Reversing of door
The following part covers the process of reversing a The following part covers the process of reversing
door on a cabinet with a top mounted compressor a door on a cabinet with a bottom mounted
compressor
1. Disconnect the cabinet at the wall socket. Remove the hinge 1. Disconnect the cabinet at the wall socket. Remove the hinge
in position “A”. You are now able to remove the front panel in position “A”. Remove the top front panel (remember to
(remember to disconnect cables to the display and lighting). disconnect cables to the display and lighting). Remove the
bottom front panel by pulling it outwards.
2. Now remove the hinge in position B, lift the door out of the
bottom hinge in position “C”. Remove the foot pedal in position 2. Now remove the hinge in position “B”, lift the door out of the
“D”, and mount the new foot pedal in position “H”. bottom hinge in position “C”. Mount the hinge from position “B”
in position “E”, the nylon washer attached.
3. Move the hinge from position “B” to position “G”, the nylon
washer is attached. 3. Rotate the door 180 ° relative to the original installation. Put the
self closing in the neutral position (see Fig. 1). Check that the
spring is in correct working order before further assembly.
4. Rotate the door 180 ° relative to the original installation. Put the
self closing in the neutral position (see Fig. 1). Check that the
spring is in correct working order before further assembly. 4. Move the hinge from position “C” to position “D”.
5. Move the hinge from position “C” to “F”. Set the door in the 5. Set the door in the hinge at position “E”. Adjust the door and
hinge at position “G”. Adjust the door and finally fasten the hinge finally fasten the hinge in position “D”. Move closing mechanism
in position “F”. for the top front panel from position “I” to position “J”.
6. Drop the front panel into the hinge in position “F”. Attach the 6. Drop the top front panel into the hinge in position “D”. Re-
hinge from position “A” to position “E”. connect the cables in the front panel and the upper hinge of
position “A”. Install the bottom front panel. Reconnect the power
at the wall socket.
7. Re-connect the cables for the front panel and close the panel.
Reconnect the power at the wall socket.
28
bioline
29
Ordinary use
Keep the marked areas in the cabinet (shown on this page) clear
of all items, thereby ensuring adequate air circulation, and therein
cooling.
The illustration on the right shows the maximum load height of the
cabinet.
30
Regular maintenance bioline
Always disconnect the cabinet before cleaning. Door gaskets are an important part of a cabinet, door gaskets
with impaired functionality reduces a cabinets seal with the door.
The cabinet should be cleaned internally with a mild soap solution Impaired seals can lead to increased humidity, iced evaporator
(max. 85 °C) at suitable intervals and checked thoroughly before it is (and thus reduced cooling capacity), and in some cases, decreased
put into operation again. lifetime expectancy of the cabinet.
For the external maintenance – use stainless steel polish. It is therefore very important to be aware of the door gaskets
condition. Regular inspection is recommended.
The compressor compartment and in particular the condenser must
be kept free from dust and dirt. This is best done with a vacuum The door gasket should be cleaned regularly with a mild soap
cleaner and a brush. solution.
The air filters on the condenser and the front panel should be If a gasket is to be replaced, please contact your local Gram BioLine
removed and cleaned with warm water (max. 50°C). distributor.
31
General info
Responsibility Service
Read the following carefully, for information on
technical safety and responsibility on Gram
Commercial products.
Is the cabinet being used for purposes other than its intended The refrigerating system and the hermetically sealed compressor
use, or use of the cabinet is not in accordance with guidelines require no maintenance. However, the condenser and air filter
specified in the user manual, the user bears full responsibility for any requires regular cleaning.
consequences thereof.
If refrigeration fails, first look to see whether the cabinet has been
unintentionally switched off, or whether a fuse has blown.
Defective parts must be replaced with original parts from Gram If the cause of failure cannot be found, contact your supplier
Commercial. Gram Commercial can only guarantee functional and quoting TYPE, PART NO and SE. NO of the cabinet. This information
safety requirements on the cabinets, if above mentioned is adhered can be found on the nameplate.
to.
Gram Commercial A/S
Aage Grams Vej 1, 6500 Vojens
Denmark CVR nr. 12 00 66 32
Type
REF Input: V Hz W A
PO No Defrost: W
S/N Refrigerant: g
Climate class:
Foam propellant Cyclopentane Isolation class:
Type
REF Input: V Hz W A
PO No Defrost: W
S/N Refrigerant: g
Climate class:
Foam propellant Cyclopentane Isolation class:
It is not sufficient to switch the cabinet off on the front panel, due to
the fact that there is still a possibility that there is current in some of
the components of the cabinet.
32
bioline
BioPlus (500, 600/660, 1270/1400): The door is equipped with an automatic closing mechanism. Open
the door up to 90 °, and it will shut by itself. Open the door more
Defrost water is led through a tube in insulation to a re-evaporation than 90 ° and door will remain open.
tray at the back of the cabinet.
BioMidi 425,625:
Below are the re-evaporation trays for a BioMidi 625 and BioPlus
600 shown
33
Access port
All BioLine cabinets are equipped with an access
port on the back of the cabinets, this can be used
to easily fit external sensors and the like.
All access ports are constructed in the same fashion, with a conical polystyrene plug ( fitted from the back of the cabinet ) and a plastic cap
( fitted from the inside of the cabinet ).
Please note, it is very important to re-fit the polystyrene plug and plastic cap after mounting sensor, probe etc. Failing to do so can result in
lowered performance or break-down of the cabinet.
2
1
34
bioline
For more information, as well as a manual for the Gram Data Logger,
go to: www.gram-bioline.com -> Download
35
Important Declaration of conformity
! Important!
1. There may occur sharp edges on the cabinet housing, compressor room, and interior furnishings. Show due diligence when handling
the cabinet, neglect of these precautions can lead to injuries.
2. Danger of wedging of body parts in the frame slot between the door and the cabinet, show due diligence when opening and closing the
cabinet door. Negligence of these precautions can lead to injuries.
3. Danger of wedging of body parts in the drawer column between the drawers and interior of the cabinet , show due diligence when using
the drawers. Negligence of these precautions can lead to injuries.
4. Be particularly vigilant in relation to closing doors with self-close mechanism as these are spring-loaded. Negligence of these
precautions can lead to injuries.
5. Unlocked castors can lead to unexpected movements of the cabinet. Lock the castors after installation. Negligence of these precautions
can lead to injuries.
6. The re-evaporation tray, re-evaporation tray heating element, pressure pipes and compressors develops considerable heat during
operation. Assure yourself that these components are sufficiently tempered before touching. Negligence of these precautions can lead
to injuries.
7. The evaporator develops considerable cold during operation. Reassure yourself that the evaporator is sufficiently tempered before
touching. Negligence of this precaution may lead to injuries.
8. The fan may cause injury during operation, avoiding touching the fans while the cabinet is connected to the mains. Negligence of these
precautions can lead to injuries.
36
bioline
Disposal
Products that are labelled with a “crossed-out wheelie bin ‘is electric
and electronic equipment. The crossed out wheelie bin symbolizes
that waste of this type can not be disposed of with unsorted
municipal waste, but must be collected separately.
! disposed of.
www.Gram-Bioline.com
37
38
bioline