Power Systems (K-Wiki - CH 4 - Stability)
Power Systems (K-Wiki - CH 4 - Stability)
Objectives
Upon completion of this chapter you will be able to:
Understand the dynamics of Synchronous Machines.
Determine the steady state stability of a synchronous machine.
Understand how to improve Steady State Stability.
Determine Transient Stability of the machine.
Understand how to improve the Transient Stability.
Introduction
A system is said to be stable if it can regain its original state even after experiencing a
disturbance. The disturbance in case of Synchronous Machine maybe due to sudden fault at
the terminals of a machine or change in mechanical input pf a machine.
There are three types of Stability in Power Systems:
Voltage Stability: It refers to the voltage regulation at the terminals of machine as it
should be within 5% . If the voltage regulation exceeds that then system is said to be
Voltage unstable.
Frequency Stability: The frequency of a machine must lie within 1% of rated value i.e.
50Hz. The speed of prime mover is controlled by means of speed governor to control the
frequency.
Angular Stability: It refers to the stability of the rotor angle δ. The oscillations in the
rotor angle must be bounded in case of disturbance. It can be broadly divided into three
categories:
o Steady State Stability: It refers to the maximum power transfer capability of a
system. If maximum power transfer limit is exceeded then system loses synchronism.
It is studied by applying small disturbances to the machine.
o Transient Stability: It refers to the ability of a system to remain in synchronism even
after experiencing a large disturbance.
o Dynamic Stability: It refers to the stability of rotor oscillations when small but
continuous disturbance is applied.
The stability study has following objectives:
The system must be secure i.e. it must be prepared to take a disturbance at present
operating point.
The system must be reliable to maintain continuity of supply even after experiencing a
disturbance.
We wish to express the Kinetic Energy in electrical terms. The relation between electrical and
mechanical angle is given by,
P
e m
2
P
s smrad(elec) / s
2
1 2
2 2
1 2 1
KE J s J s s Ms
2 P 2 P 2
2
2
M J s MJ sec/ elect rad
P
M is called as Inertia Constant
The stored kinetic energy can also be expressed as,
Kinetic Energy = GH
1
GH MS
2
Here, G is MVA base of the machine
H is the inertia constant in MJ/MVA
2GH GH
M MJ s / elect rad
s f
GH
M MJ s / elect deg
180f
Inertia Constant in pu is given by,
H H 2
M(pu) s2 / elect rad s / elect deg
f 180f
Swing Equation
The Torque balance equation is given by,
Ts Tem TJ TB
TS Shaft Torque
Tem = electromagnetic torque
TJ = torque required to overcome inertia
TB =torque required to overcome frictional force
If frictional torque is neglected then
d2
J 2m (Ts Te )
dt
m rotor angle rad(mech)/sec
Ts shaft torque
d2 m
Jsm (Ts Te )sm
dt2
d2 m
Jsm (Ps Pe )MW
dt2
2 2 d2
J sm 2e (Ps Pe )MW
P dt
e rotor angle(elec)
Ps Shaft Mechanical Input
Pe Electrical Power Output
d2 e
M (Ps Pe )
dt2
e Position of rotor axis w.r.t fixed reference
(t) Position of rotor w.r.t rotating reference
From the figure,
(t) e s t
d d e
s
dt dt
d
s
dt
d2 e (t) d2
2
dt2 dt
d2 e (t)
Substituting value of
dt2
d2
M (Ps Pe ) MW
dt2
GH d2
(Ps Pe )MW
f dt2
H d2
(Ps Pe )pu
f dt2
If is in degrees
H d2
(Ps Pe )pu
180f dt2
The above equation is valid for a single machine. For multiple machine system it must be
converted to Single Machine System and then stability must be analyzed.
d2
Meq 2 Ps Pe
dt
Where, Meq M1 M2 , is the equivalent inertia of a single machine system
Ps Ps1 Ps2 , is the total shaft input of both the machines
Pe Pe1 Pe2 , is the total electrical output of both the machines
M M2 JJ
Meq orJeq 1 2
M1 M2 J1 J2
Solved Examples
Problem: A large synchronous generator is feeding power into an infinite bus at slightly
lagging power factor. If a total loss of field occurs and the system can supply sufficient
reactance power without a large terminal voltage drop, the unit will
(a) Continue to run as a synchronous generator and no tripping is necessary
(b) Get short circuited and it should be tripped instantaneously
(c) Run as an induction generator and it should be tripped after a time delay
(d) Run as a synchronous motor and it should be tripped after a time delay
Solution: If excitation is lost, Pe decreases
By swing equation
d2
M Pm Pe
dt2
Rotor accelerates & speed increases. So speed becomes more than synchronous speed.
Machine runs as induction generator but it draws magnetizing current from supply so
current increases & stator winding gets overheated. So it must be tripped after a delay.
Problem: In a system, there are two generators operating in parallel. One generator, of
rating 250 MVA, has an inertia constant of 6MJ/MVA while the other generator of 150 MVA
has an inertia constant of 4 MJ/MVA. The inertia constant for the combined system on 100
MVA common base is?
Solution: Equivalent inertia constant
GH G H 250 6 150 4
H 1 1 2 2 15 6 21 MJ / MVA
G G 100 100
Now, a small disturbance is applied to system which changes the operating angle to 0
Thus, electrical output of machine now becomes,
Pe Pmax sin 0 Pmax sin 0 cos cos 0 sin
For small disturbance, 0; sin ; cos 1
Pe Pmax sin 0 Pmax cos 0
Pe Pe0 Pmax cos 0
Pe
Pe Pe0
0
Pe
Pmax cos 0 Psy is called as Synchronizing Power Coefficient
0
Since, Pm Pe0
Swing Equation becomes,
d2 dP
M e
dt 2
d 0
Since, 0
d2 0 d2 dPe
M M
dt 2
dt 2
d 0
Pe
Case-1: 0, the roots are real so the solution of differential equation is of the form
c1ept c2ept
Due to the exponential term the variation in rotor angle continuously increases with time and
thus the system is unstable.
Pe
Case-2: 0, the roots are imaginary and the solution is of the form,
c1 cos t c2 sin t
Pe
0
where, is the frequency of rotor oscillations
M
Thus, rotor angle exhibits un-damped oscillations as shown below,
Practically, system is damped due to resistance and damper winding of the machine so the
rotor oscillations damp out and rotor finally settles to a steady state angle of 0 . Thus, the
system is stable.
Thus, the condition for stability becomes,
Pe
0
Pmax cos 0 0
0 0 900
Pe
If, 0, system is marginally stable.
Thus, Pmax cos 0 0 , 0 900
So, when 0 900 system is on the verge on instability. Thus, it corresponds to stability limit.
Thus, Pe Pmax sin90 Pmax is called as Steady State Stability Limit.
E E0
I
j(2x)
Vth E I( jx)
E E0 E E0 E
Vth E cos jsin 1
2 2 2
E
Vth 2 cos2 2 jsin cos
2 2 2 2
Vth E cos
2 2
X
Z th j
2
SVC will be modeled as a generator which only supplies reactive power and does not
exchange any active power with the Transmission Line.
Emf of the SVC is decided on the basis of assumption that SVC injects no Real Power.
Connecting SVC across the Thevenin Equivalent
The angle of SVC emf is same as Thevenin Voltage so that no Real Power exchange occurs.
The mid-point voltage when SVC is connected is given by,
E cos Es
V E cos 2 2 2 jx
2 2 X 2
j jX s
2
X X X
E cos j jX s j Es j
2 2 2 2 2 2
V
X
j jX s
2
X
E cos X s Es
2 2
V
X 2
Xs
2
2Xs
V Es Ecos Es
X 2Xs 2 2
The power transferred from sending end to midpoint after SVC is connected is given by,
EV
Pe sin
X 2
EV E 2X s
Pmax Es Ecos Es
X X X 2X s 2
E 2X s 2X s
Pmax Es 1 E cos
X X 2X s 2 X 2X s
EEs E2 cos / 2 2X s
Pmax
X 2X s X X 2X s
If internal reactance of SVC X s 0
EEs
Pmax
X
If Es =E (internal emf of SVC)
E2 E2
Pmax ;Pe sin / 2
X X
Before SVC was connected the power-angle equation is,
E2 E2
Pe sin , Pmax
2X 2X
After placing SVC, maximum power transfer capability will be doubled
The power angle curves before and after the connection of SVC have been shown below,
Solved Examples
Problem: A synchronous generator of reactance 1.2pu is connected to infinite bus bar
(|V|=1.0) through transformer and transmission line of reactance 0.6pu & inertia constant H=
4 MW-s/MVA. The resistance & machine damping is negligible, System frequency is 50 Hz.
Calculate frequency of oscillation if system loaded to 50% of maximum limit?
Solution: for 50% loading
Pe 0.5Pmax
0.5Pmax Pmax sin
30o
Pe /
1/2
P /
1/2
P /
1/2
f
pu
e e f
M GH
H
Pe 1.2 1
Pmax cos cos30 0.577pu
1.8
1/2
1 0.577
f f 0.758Hz
2 2 4
Problem: An alternator is connected to an infinite bus as shown in figure. It delivers 1.0 p.u
current at 0.8 pf lagging at V=1.0 p.u. The reactance X d of the alternator is 1.2 p.u.
Determine the active power output and the steady state power limit. Keeping the active
power fixed, if the excitation is reduced, find the critical excitation corresponding to
operation at stability limit.
Solution: Electrical power output= VI cos 1 1 0.8 0.8pu
Armature current= 1 36.860 pu
Excitation emf= Vt jIa X s 10 jX1 36.86 1.2 1.9729.170 pu
Ef Vt 1.97 1
Steady state limit= 1.64pu
Xa 1.2
Now, if machine operates at steady state limit
Pe Pmax 90 0
E 1
0.8
1.2
E 0.96pu
The operating time of the protective circuit breaker is chosen such that after clearing the
fault system should remain in stable mode.
Operating time < Critical Clearing time
Top < tcr
Assumptions
Generator will be modeled as constant voltage source behind transient reactance Xd.
Saturation & saliency in alternator are neglected. Saliency tends to make machine more
stable by increasing maximum power and thus it is neglected.
No damping force as damping force will reduce the oscillations to improve the stability of
the system.
Resistance & shunt elements like Shunt Capacitance are neglected
Speed variations & frequency variations are neglected.
Speed governing action will be de-activated such that mechanical input will be
maintained as constant.
AVR (Automatic Voltage Regulator) will be de-activated such that generated emf E is
maintained as constant.
Power Transfer
In Transient Stability Analysis, we generally consider three cases,
Before the Fault Occurrence
During the Fault
After the Fault Clearance
We assume that the transfer reactance between the source and load changes under different
conditions which changes the power transfer between source and load or Infinite Bus.
d d
2
P d
2 a
dt dt M dt
Integrating both sides
2
d d 2
dt dt dt M Pad
d 2
M a
P d
dt
d
s
dt
rotor speed
s synchronous speed
The system will be stable if the amplitude of oscillations of rotor angle remains constant in
an un-damped system. In a practical system such a system will be stable as due to losses and
damping the oscillations will be damped out and rotor angle will settle to a steady state
value.
d
From above figure if 0 , rotor angle continuously increases and system is unstable.
dt
Thus, for stability
d
0
dt
From above equation, we can observe
d 2
M a
0 P d 0
dt
Pad 0
Area under first swing (accelerating curve) should be zero.
Equal area criterion is called first swing stability study.
Initially, Ps Pe
Speed of rotor, S
At ‘b’ ( 1 )
Accelerating power,
Pa Ps1 Pmax sin 1 0
P
1 sin1 s1
Pmax
d
0 , speed max S
dt
d
0 , increases
dt
From ‘b’ to ‘c’:
Accelerating power, Pa Ps1 Pmax sin 0
d
Rotor decelerates, speed decreases from S but still S , S 0 , increases
dt
At ‘c’:
Accelerating power Pa 0
d
Speed, S , 0
dt
d
Now, since Pa 0 , rotor speed further reduces & becomes less than S , such that 0 &
dt
reduces operating point moves towards ‘B’
Second Swing
From ‘c’ to ‘b’
Pa Ps1 Pmax sin 0
Rotor decelerates, speed S
d
S 0
dt
At ‘b’
1
Pa Ps1 Pmax sin 0
Neither accelerates nor deceleration speed min
d
S 0 , decreases
dt
From ‘b’ to ‘a’
Pa Ps1 Pmax sin 0
Rotor accelerates, speed increases
d
S 0 , decreases
dt
At point ‘a’
Pa Ps1 Pmax sin 0
Rotor accelerates, speed S
d
=0, neither decreases nor increases
dt
As Pa is positive, rotor accelerates and operating point moves towards ‘b’.
Rotor angle is swinging between ‘a’ & ‘c’ with respect to ‘b’ & finally settles down at ’b’.
d 2
M a
P d
dt
2
0
Pad 0
1 2
0
Pad Pad 0
1
1
Accelerating area, A1= 0
Pad
2
Accelerating area, A2= 1
Pad
If speed does not reach S even after reaching max then enters accelerating area & rotor
accelerates so increases further & system is unstable.
max 1
1 max
Pad
0
P d 0
1
a
1 max
P
0
s1
Pmax sin d P
1
s1
Pmax sin d 0
1 max
P
0
s1
Pmax sin d P
1
s1
Pmax sin d
At the instant of fault occurrence, point ‘a’ on swing curve will be shifted to point ‘b’ on
swing curve 2. Suddenly without changing angle & speed.
At point ‘b’ 0 , S
Accelerating power, Pa Ps Pe2 Ps 0 0
Rotor accelerates, starts increasing from S , S
d
0, starts increasing
dt
Assume that at ‘c’ CB clears the fault.
From b to c
Accelerating power, Pa Ps Pe2 0
Rotor accelerates, increases , S
d
0, increases.
dt
As fault is cleared, at point ‘c’ operating point shifts, to ‘d’ without changing angle c
At point d
Speed starts reducing from max , still S
d
0, increases further
dt
d
At point ‘e’ speed S or = 0.
dt
From d to e
Pa Ps Pmax sin ve
Rotor decelerates, reduces but still S
d
0, increases further
dt
2
d
At ‘e’,
dt
0 or P d 0
0
a
C 2
Pad Pad 0
0 c
Second Swing
From e to f
Pa PS Pmax sin 0 , rotor decelerates speed decreases from S
d
s 0 , reduces
dt
At point f = 0
Pa Ps Pmax sin 0
Neither acceleration nor deceleration
d
min s 0 , reduces
dt
From F to G
Pa Ps Pmax sin 0 , rotor accelerates
So, speed increases but still S
d
S 0
dt
decreases & at point G, S
So, rotor angle will rotate between e & g with respect to final steady state ‘f’’.
In first swing, if speed is not becoming S even point max ( 0 ) the angle further
increases & system will be unstable.
Critical Clearing Angle
It is maximum rotor angle at which CB has to clear the fault to maintain stability.
By Equal Area Criterion
max
P d 0
0
a
cr max
P d P d 0
0
a
cr
a
cr max
Ps (cr 0 ) Pmax cos 0 cos cr Ps (max cr ) Pmax cos cr cos max 0
Before Fault
X
Transfer Reactance before fault = X1 X d '' Xm ''
2
Eg Em
Maximum Power capability = Pmax1
X1
Electrical Power Output = Pe Pmax1 sin
P
Initial Operating Angle = 0 sin1 S
P
max1
During Fault
The circuit during the fault looks like as shown below,
Then to find transfer reactance during the fault, we again convert Star to Delta as shown
above,
X2
Xd '' Xa Xm '' Xb Xd '' Xa Xc Xm '' Xb Xc
Xc
Maximum Power during the fault is,
Eg Em
Pmax,2 =Transient Stability Limit
X2
Electrical Power Output = Pe Pmax 2 sin
P d 0
0
a
c 2
Pad Pad 0
0 c
A1 A2 0
For critical clearing angle or marginal stability the
power angle curve is shown,
P
max sin1 S
Pmax3
By Equal Area Criteria,
max cr max
0
Pad 0 Pad
0
P d 0
cr
a
cr max
(P
0
s
Pmax2 sin )d
cr
(Ps Pmax3 sin )d 0
Before Fault
X
Transfer Reactance before fault = X1 X g
2
Eg Em
Maximum Power capability = Pmax1
X1
Electrical Power Output = Pe Pmax1 sin
P
Initial Operating Angle = 0 sin1 S
P
max1
During Fault
Since, the fault is close to bus we will assume that during fault no power is transferred from
generator to infinite bus.
Maximum Power capability = Pmax2 0
The Power Angle curve for this case looks like as shown,
Js 2e Pe PS
P dt
Swing equation
d2
M 2 Pe PS
dt
From the figure,
s t (t) (t)
d(t) d(t)
s
dt dt
d2 (t) d2 (t)
dt2 dt
d2 Pa
Rotor acceleration=
dt2 M
where, Pa Pe PS is the Accelerating Power
At ‘c’
2 , s
Since, Pa 0 rotor accelerates, speed increases and thus s
d
Hence, 0 So, reduces
dt
So now rotor angle falls back & rotor makes oscillations between c & a with respect to ‘b’
If steam input is reduced when the fault occurs then the accelerating power is reduced
which reduces the acceleration of the machine. This can be done by use of Speed Governing
Mechanism.
By using AVR if we increase excitation, then Pe increases and accelerating power reduces
which reduces the acceleration of the machine.
Reducing reactance of system by using larger air gap between stator & rotor increases Pe
and reduces acceleration of the machine.
By using Resistance Grounding,
Net Electrical Output becomes Pe If 2Rn
This is taken for faults where zero sequence currents exist so that current flows through the
neutral resistance. Thus, electrical output increases and acceleration of machine reduces.
If we use 3-pole CB then all lines are isolated in case of an LG fault on a single line so Pe
=0 & Pa is high
But is we use single pole circuit breaker then supply can be maintained through other two
lines and electrical output increases due to which acceleration of machine decreases and
stability is improved.
Solved Examples
Problem: Inertia constant of a 100MVA, 50Hz, 4-pole generator is, 10MJ/MVA. If mechanical
input to the machine is suddenly raised from 50MW to 75 MW, the rotor acceleration will be
equal to?
Solution: Swing equation in electrical degrees
H 2
Pm Pe
180f t2
In steady state Pm Pe 50MW
Now Pm changes to 75MW
25
Pa Pm Pe 25MW 0.25pu
100
10 2
2 0.25
180 50 t
2
225 elect deg/ s2
t 2
Before fault
Pm Pe 1.0pu; 0 300
Pe PmaxI sin 0
1 PmaxI sin30
PmaxI 2pu
During fault Pmax II
0.5pu
After fault Pmax III
1.5pu
P P 1
max sin1 m 180 sin1 m 180 sin1 138.19
0
Pmax III Pmax III 1.5
1138.19 30 0.5cos30 1.5cos138.19
cr cos
1 180
1.5 0.5
cr 70.290
Problem: A generator delivers power of 1.0 p.u to an infinite bus through a purely reactive
network. The maximum power that could be delivered by the generator is 2.0 p.u. A three
phase fault occurs at the terminals of the generator which reduces the generator output to
zero. The fault, is cleared after t c second. The original network is then restored. The
maximum swing of the rotor angle is found to be max 110 electrical degree at t t c is?
Solution: Before fault
Pmax I 2.0pu
Pm Pe 1.0pu
Pe Pmax 0
1 2sin 0 0 300
During fault Pmax II
0pu
After fault Pmax III
Pmax I 2pu
1110 30 0 cos30 2 cos110
cr cos1 180 69.14
0
2 0
This is not the case for critical clearing, still we can use the same expression with suitable
value of max .
Problem: A generator feeds power to an infinite bus through a double circuit transmission
line. A 3 phase fault occurs at the middle point of one of the lines. The infinite bus voltage is
1pu, the transient internal voltage of the generator is 1.1 pu and the equivalent transfer
admittance during fault is 0.8 pu. The 100MVA generator has an inertial constant of
5MJ/MVA and it was delivering 1.0 pu power prior if the fault with rotor power angle of 30 0.
The system frequency is 50Hz. The initial accelerating power (in pu will be)?
Solution: During fault
E 1.1pu V 1pu
Y 0.8pu
Problem: A generator feeds power to an infinite bus through a double circuit transmission
line. A3 phase fault occurs at the middle point of one of the lines. The infinite bus voltage is
1pu, the transient internal voltage of the generator is 1.1 pu and the equivalent transfer
admittance during fault is 0.8 pu. The 100MVA generator has an inertial constant of
5MJ/MVA and it was delivering 1.0 pu power prior if the fault with rotor power angle of 30 0.
The system frequency is 50Hz. If the initial accelerating power is X pu, the initial acceleration
in elect deg/sec, and the inertial constant in MJ-sec/elect deg respectively will be?
Solution: According to swing equation
H 2
Pa
f t 2
5 2
X
180 50 t2
2
1800X elect deg/ sec2
t 2
GH 100 5 1
Inertia constant 0.056
180f 180 50 18
at an instant when t 1300 as shown in the figure. The maximum value of the per unit
line reactance, x such that the system does not lose synchronism subsequent to this tripping
is?
P
180 sin1 m 130
0
Pmax
P
sin1 m 50
0
Pmax
1 1
Pmax
0.1 X
Pm
sin50 0.766
10.1 X
0.1 X 0.766
X 0.66pu