106 - E1.0-Electrical Site Plan

This document contains general notes for an electrical project. It specifies that all exterior devices must be weatherproof and that conduits from the fuel island should route to respective panels or the fuel control panel in the manager's office. The electrical contractor must contact the power and telephone companies to coordinate locations of primary service equipment, trenches, transformers, meters, and more. The contractor is also responsible for secondary conduits, trenching, and concrete for transformers and service equipment per the utility's specifications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
228 views1 page

106 - E1.0-Electrical Site Plan

This document contains general notes for an electrical project. It specifies that all exterior devices must be weatherproof and that conduits from the fuel island should route to respective panels or the fuel control panel in the manager's office. The electrical contractor must contact the power and telephone companies to coordinate locations of primary service equipment, trenches, transformers, meters, and more. The contractor is also responsible for secondary conduits, trenching, and concrete for transformers and service equipment per the utility's specifications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

GENERAL NOTES

XSP-2T3 1. ALL EXTERIOR DEVICES TO BE WEATHERPROOF.


XSP-2T3
2. ALL FUEL ISLAND CONDUITS SHALL BE ROUTED TO THE RESPECTIVE PANELS AND/OR TO
THE FUEL CONTROL PANELS LOCATED IN THE MANAGERS OFFICE/STORAGE ROOM.

3. PROVIDE ALL EMPTY CONDUITS WITH PULL STRING.


20 4. ELECTRICAL CONTRACTOR SHALL CONTACT POWER COMPANY REGARDING EXACT LOCATION
#8,#10G,3/4"C OF ALL PRIMARY SERVICE EQUIPMENT, TRENCH LOCATIONS, TRANSFORMER LOCATION,
A-20 METER LOCATION, ETC.
XSP-2T3
5. ELECTRICAL CONTRACTOR SHALL PROVIDE NECESSARY SECONDARY CONDUITS, POWER
TRENCHING, BACKFILL, CONCRETE PADS FOR TRANSFORMERS AND SERVICE EQUIPMENT
AND CONDUIT STUBS INTO TRENCH AS REQUIRED BY POWER COMPANY AND TO THEIR
SPECIFICATIONS.

6. ELECTRICAL CONTRACTOR SHALL CONTACT TELEPHONE COMPANY REGARDING EXACT ISSUE/REVISION RECORD
LOCATION OF ALL PRIMARY SERVICE EQUIPMENT, SERVICE EQUIPMENT, TRENCH
LOCATIONS, ETC.

21 27 7. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NECESSARY TELEPHONE TRENCHING,


BACKFILL, AND CONDUIT STUBS INTO TRENCH AS REQUIRED BY TELEPHONE COMPANY AND
24
E TO THEIR SPECIFICATIONS.

CAR WASH 25
8. ALL WIRING OUTSIDE SHALL BE A MINIMUM OF #10 COPPER WITH TYPE 'XHHW-2'

E
[

T
8 INSULATION. FOR UNDERGROUND CIRCUITS RUN IN P.V.C., PROVIDE A #10 COPPER BOND IN
27 ADDITION TO CIRCUIT CONDUCTORS.

E
9 9. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATION AND COMPLIANCE

T
WITH THE UTILITY COMPANY'S REQUIREMENTS. WITH-IN TWO WEEKS AFTER AWARD OF
CONTRACT, SUBMIT (2) COMPLETE SETS OF PLANS, INCLUDING PLOT OF SURVEY, TO
18 UTILITY COMPANY FOR COORDINATION. ROUTING OF INCOMING POWER AND TELEPHONE

T
SERVICE SHOWN ARE FOR ESTIMATING PURPOSES ONLY. ACTUAL ROUTING, CONDUIT,
TRENCH, AND PAD REQUIREMENTS SHALL BE AS SPECIFIED BY THE UTILITY COMPANY.

E
10 CONFIRM ALL REQUIREMENTS WITH UTILITIES PRIOR TO INSTALLATION.

T
XSP-T4 10. ALL UNDERGROUND CABLE, PIPE, AND CONDUITS SHALL BE DETECTIBLE (METALLIC) OR
#3/0 AWG BC XSP-2T4

E
HAVE A DETECTABLE UNDERGROUND DEVICE INSTALLED PER AZ STATUTE 40-360.22,M.

T
XSP-2T4
E

T
-
KEY NOTES
14
E

1 1" CONDUIT FOR TANK MONITOR CONTROL.

2 1" CONDUIT FOR VR SENSOR CONTROL.


E

PULL AND TERMINATE VEEDER ROOT WIRING AT PUMPS, AUTO TANK GAUGES, BRINE
XSP-T4 SEAL OFF DETAIL PROFESSIONAL SEAL
SEAL
2 3 4 17
6 NTS
SENSORS, HOOK SWITCHES AND TLS350. PROVIDE BELDEN 8860 OR EQUIV. 18/2 STRANDED,
OAS, JACKETED, PLENUM CABLE. VERIFY/ COORDINATE WITH FUEL PIPING PLANS.
PROFESSIONAL
E

11 TYP. 3 1" CONDUIT TO EQUIPMENT ROOM FOR INTERCOM.


PULL AND TERMINATE INTERCOM WIRING. (2) 18/4 STRANDED, OAS, JACKETED, PLENUM
13
E

12 CABLE PER DISPENSER. VERIFY/ COORDINATE WITH FUEL PIPING PLANS.


T

4 1" EMPTY CONDUIT PER DISPENSER- (EXTRA).


E

5 PROVIDE SEAL-OFF FITTINGS AT EACH END OF CONDUIT IN CONJUNCTION


METAL FRAME WITH/G.V.R. DISPENSER MANUAL.
T
E

E
T T T T T T T T T T T T T XSP-T4 PROVIDE LOCAL DISCONNECT SWITCH FOR MONUMENT SIGN. VERIFY EXACT
16 E T T T T T T T T T T T T T T T
6
E E E E E E E E E E E E E E E E E E E E E E E E E E E E
LOCATION WITH OWNER.
PROVIDE 2-1" CONDUITS 1 FOR POWER - TERMINATED AT ELECTRICAL PANEL AND 1 5/8/17
G-14 G-22 G-30 G-38 G-21 COMPRESSION LUG OR EXOTHERMIC WELD FOR PHONE AND COMMUNICATION - TERMINATED AT TMB. (INSTALLED UNDER
TYP. 5 TYP. 5 TYP. 5 TYP. 5 TYP. 5 GROUNDING CONNECTION. TYPICAL.
SEPARATE PERMIT)
G-37 27
W

G-37 G-37 G-37 G-37 7 1" CONDUIT FOR POWER HOMERUN.


[

2 2 2 2 2 BONDING JUMPER TYPICAL. PROFESSIONAL IN CHARGE


8 SERVICE ENTRANCE SECTION.
ONOFRE MAYUGA
G-39 3 G-39 G-39 G-39 G-39
3 3 3 3
B-26 9 (4) 4" EMPTY CONDUITS FOR SECONDARY FEEDERS.
4 G-41 4 G-41 4 G-41 4 G-41 4 G-41
B-39
10 PROVIDE HOUSEKEEPING PAD FOR POWER CO. PAD MOUNTED TRANSFORMER PER SERVING PROJECT MANAGER
2#4,1#4G,1"C
POWER COMPANY REQUIREMENTS.
11 (2) 4" CONDUITS FOR SERVING POWER CO. PRIMARIES. QUALITY CONTROL
6
G-18 G-26 G-34 G-17 G-25
TYP. 5 TYP. 5 TYP. 5 TYP. 5 TYP. 5 12 TERMINATE IN ACCORDANCE WITH LOCAL UTILITY COMPANY
REQUIREMENTS. DRAWN BY
A-14,16
#10,#10G,3/4"C G-37 G-37 G-37 G-37 G-37 13 (3) 4" EMPTY CONDUITS FOR TELEPHONE SERVICE. VERIFY EXACT QUANTITY AND SIZE WITH
2 2 2 2 2
SERVING TELEPHONE COMPANY.
B-41 3 G-39 3 G-39 3 G-39 3 G-39 3 G-39 "EMERGENCY POWER OFF" SWITCH PER NEC 2014. NEC ART 514.11. PROVIDE SIGNAGE PER PROJECT NAME
14
2#4,1#4G,1"C IFC SECTION 2204, 2205. (VERIFY EXACT LOCATION WITH CIRCLE 'K).
4 G-41 4 G-41
23 27
4 G-41 4 G-41 4 G-41
5 BUILDING STRUCTURE GROUNDING 15 WP J-BOX FOR COMPLETE CONNECTION OF CANOPY SIGN. VERIFY EXACT LOCATION IN
FIELD.
CIRCLE K
NTS
16 PROVIDE LOCAL DISCONNECT FOR COMPLETE CONNECTION OF WATER/AIR FILL STATION.
VERIFY EXACT LOCATION IN FIELD, AND VERIFY REQUIREMENTS PRIOR TO ROUGH-IN.
STORE #
19 METAL FRAME 17 1"C CONDUIT FROM ELECTRICAL ROOM/MECHANICAL ROOM, TO CLOSEST
1 23 27
G-(7,9,11) 19 CANOPY COLUMN. ROUTE UP TO CANOPY DECK FOR SPEAKER CONNECTION.

7 G-(8,10,12)
1
XSP-2T4
18 PROPOSED LOCATION FOR THE NEW CARWASH PANEL. HEMET
1 7
22 27 19 TANK FILL POINT. CALIFORNIA
G-(1,3,5) COMPRESSION LUG OR EXOTHERMIC WELD
7
GROUNDING CONNECTION. TYPICAL.
20 LIGHTING CIRCUITS SHALL BE ROUTED VIA 20A 10 POLE ELECTRICALLY HELD LIGHTING 4852 WEST
20 CONTACTOR CONTROLLED BY THE 'EPO' SWITCH LOCATED ON THE GAS CANOPY. SEE DETAIL 6
#8,#10G,3/4"C SHEET E6.0. FLORIDA AVENUE
2#4,1#4G,1"C 7 G-(2,4,6)
1 A-18 BONDING JUMPER TYPICAL.
21 VENT RISER FROM TANK.
HEMET, CA
B-47,49 2#4,1#4G,1"C
28 B-51,53 CLASS 1 DIVISION 1 HAZARDOUS AREA: UNDERGROUND TANK: INSIDE TANK - ENTIRE INSIDE
6 22
28 VOLUME. FILL OPENING - ENTIRE SPACE WITHIN ANY PIT OR BOX BELOW GRADE LEVEL. PER
NEC TABLE 514.3 (B)(1)
J J
XSP-2T4 23 CLASS 1 DIVISION 2 HAZARDOUS AREA: UNDERGROUND TANK FILL OPENING: UP TO 18"
XSP-2T4 14 ABOVE GRADE LEVEL, EXTENDING 5 FT. HORIZONTALLY IN ALL DIRECTIONS FROM ANY
TIGHT-FILL CONNECTION AND EXTENDING 10 FT. HORIZONTALLY IN ALL DIRECTIONS FROM
CANOPYCOLUMN GROUNDING ANY LOOSE-FILL CONNECTION. PER NEC TABLE 514.3 (B)(1)

A-13,15
4 NTS 24 CLASS 1 DIVISION 1 HAZARDOUS AREA: UNDERGROUND TANK VENT: WITHIN 5 FT. OF OPEN
END OF VENT, EXTENDING IN ALL DIRECTIONS. PER NEC TABLE 514.3(B)(1)
#10,#10G,3/4"C

1 ELECTRICAL SITE PLAN 25 CLASS 1 DIVISION 2 HAZARDOUS AREA: UNDERGROUND TANK VENT: BETWEEN 5FT. AND
10FT. OF OPEN END OF VENT, EXTENDING IN ALL DIRECTIONS. PER NEC TABLE 514.3(B)(1)
1" = 20'-0"
26 CLASS 1 DIVISION 2 HAZARDOUS AREA: OUTDOOR DISPENSING DEVICE: UP TO 18" OF
DISPENSER ENCLOSURE, EXTENDING 20 FT. HORZIONTALLY IN ALL DIRECTIONS FROM
DISPENSER ENCLOSURE. PER NEC TABLE 514.3 (B)(1)
20'-0" SQ. STEEL POLE HANDHOLE W/NON-FERROUS
TAMPER PROOF SCREWS 27 ALL WIRING IN THIS AREA INCLUDING BELOW GRADE SHALL BE INSTALLED IN RIGID METAL
W/ DARK BRONZE FINISH
CONDUIT PER NEC ARTICLE 514.8. PROVIDE ALL EXPLOSION PROOF FITTINGS AND SEALS
NECESSARY TO COMPLETE CONDUIT SYSTEMS. NO SUBSTITUTIONS SHALL BE MADE UNLESS
BASE TAMPER BASE PLATE 8"SQ. APPROVED BY THE AUTHORITY HAVING JURISDICTION. PROVIDE EXPLOSION PROOF J-BOXES
PROOF COVER WITH WITH 8-1/2 BULT CIRCLE (CROUSE HINDS) MODEL GUP215 WITH 0302 'O' RING OR OWNER APPROVED EQUAL.

DARK BRONZE FINISH AND 28 FUTURE ELECTRIC VEHICLE CHARGING STATION - 3703 CHARGEWORKS EV CHARGER POLE
A60 A60 A60 A60 A60 A60 A60 A60 A60 A60 1"X45" CHAMFER
ROUNDED CORNERS MOUNT. PROVIDE GFCI 20MA. 1" C FOR DATA COMMUNICATION

5 8 8 8 8 8 8 8 8 8 8 (4) 3/4"X18"x3" GALV


ANCHOR RODS PER ASTM A-153
TYP.
& 3/4" BOLTS PER ATTACHED
EXPOSED CONC BASE SCHEDULE
20 A-8,10,12
SHALL BE PAINTED
#10,#10,3/4"C 36" FINISH GRADE NOTE:
LIGHTING CONTROL ACCEPTANCE REQUIREMENTS
A60 A60 A60 A60 A60 A60 A60 A60 A60 A60
PER 130.4 A CERTIFICATE OF ACCEPTANCE SHALL
BE SUBMITTED TO THE ENFORCEMENT AGENCY
UNDER SECTION 10-103(a) OF PART 1 FOR:
10 10 10 10 10 10 10 10 10 10 PROJECT NUMBER
A. AUTOMATIC DAYLIGHT CONTROLS
GROUND ROD
B. LIGHTING CONTROLS
5
C. OUTDOOR LIGHTING CONTROLS
TYP. CONDUIT & CONDUCTORS SHEET TITLE
20
A-4,6
#10,#10,3/4"C A60 A60 A60 A60 A60 A60 A60 A60 A60 A60
15 REINF. RODS

15 J ELECTRICAL
4 12 12 12 12 12 12 12 12 12 12 J REFERENCE STRUCTURAL BASE W/C-1 MIX.
SITE PLAN
6
DETAIL 107 ON SHEET S4.1,
RESOLVE ANY CONFLICTS WITH 20'-0" BARE #6 CU. AT
ARCHITECTURAL SHEET SD1.3 BOTTOM OF BASE.
(MAXIMUM OF 30" DIAMETER.) SHEET NUMBER

LIGHT POLE BASE


2 CANOPY LIGHTING PLAN
NTS
3 NTS
E1.0S/CW