Sinteso™

Test units and accessories


FDUL221, FDUD29x, FDUD29x-E, RE6, REF8, REF8-S, REF8-C, RE8, RE8-S, RE8-C,
RE7T, RE8ST, RE8STCO, RE8-CO, RE7T-x, RE10, FDUM29x, FDLU291, LE3, StabexHF

Test units to test detectors and detector lines for FS20 fire detection installa-
tions
● Detector exchanger FDUD291 for the efficient installation and removal of Sinteso
point detectors
● Detector exchanger and tester FDUD292 and intelligent detector tester FDUD293
for commissioning, maintenance, and troubleshooting of point detectors, alarm
sounders, and linear smoke detectors
● Bluetooth extension kit FDUD29x-E for wireless communication between the de-
tector exchanger and tester FDUD292 and a mobile terminal
● Line tester FDUL221 for diagnosing detector lines
● Detector tester RE6 for use with environmentally-friendly test gas REF8, REF8-S,
REF8-C
● Detector tester RE7T with hot air generator, RE8ST with smoke capsule RE8-S,
RE8ST-CO with smoke capsule RE8-S, capsule RE8-CO, and CO capsule
● Detector tester RE10 for undertaking a function check on linear smoke detectors
● Telescope rods FDUM291/292 for extending detector exchanger, detector ex-
changer and tester, and other testers

007228_v_en_-- Smart Infrastructure


2021-09-03
Line tester FDUL221
Properties
● 4-line display with 20 characters per line
● Menu-guided operation
● Supply with battery or via network adapter
● Possible to update the device software (firmware) via the MCL-USB adapter (radio)
FDUZ227 and via a PC
● Environmentally friendly processing
● Reusable materials
● Electronic parts and synthetic materials can be easily separated
Function
Different functions can be called up, e.g.,:
● Number of devices found at A and B connection
● Line errors found, location of the line error
● Short-circuit, open line, ground fault with indication of which conductor/s
● Total resistance is too high and/or charge voltage at the line end is too low
● Data transmission fault due to line capacitance being too high
● Browsing from detector to detector with screen displaying type and serial number
● Display of branches and choice of branch for scrolling
● Activating the internal alarm indicator of the selected detector and recognizing the con-
nected alarm sounder
● Extended operation and functionality on PC with line tester software FXS2017
● The line tester software FXS2017 is included in the scope of delivery of the line tester
FDUL221.

Fig. 1: Line tester software FXS2017

2
Smart Infrastructure 007228_v_en_--
2021-09-03
Fig. 2: Line tester software FXS2017

3
Smart Infrastructure 007228_v_en_--
2021-09-03
Use
The line tester FDUL221 is a universal device for the final testing of fully installed FDnet fire
detector lines if a control panel is not connected. The device is used to for error searches by
the electrician, installer, or service technician.

1 2 3 4

8 7 6 5

1 On/Off switch 5 2x terminal strips for the detector line


2 USB connection 6 Network adapter
3 Connection of a loop or stub line 7 Display
4 Shielding 8 Battery compartment on the underside for
2x 9 V lithium batteries, not included in
scope of delivery

Fig. 3: Scope of delivery FDUL221

4
Smart Infrastructure 007228_v_en_--
2021-09-03
Detector exchanger FDUD291
Properties
● Possible to exchange the detector without a ladder or scaffolding up to a room height of
8 m with the help of the telescope rods
● Joint springs enable the point detectors to be inserted or removed at an angle
● The point detector can be held in four rotational positions This makes it easier to work ef-
ficiently
● Specially developed springs hold the point detector in the detector exchanger
● Compatible with
– Telescope rods FDUM291/292
– Previous straight connectors VR10/11/12/13
– MP/MT handles and straight connectors
● Environmentally friendly processing
● Reusable materials
Function
● Efficient installation and removal of the point detectors FDO, FDOOT, FDT, FDOOTC

121
1

57
2

390

1 Point detectors FDO, FDOOT, FDT, Dimensioned drawing FDUD291


FDOOTC
2 Joint springs of the FDUD291

5
Smart Infrastructure 007228_v_en_--
2021-09-03
Detector exchanger and tester FDUD292 and intelligent detector tester FDUD293
The detector exchanger and tester FDUD292 and the intelligent detector tester FDUD293
are universal tools for inserting and removing point detectors. The FDUD292 is used for
commissioning and maintenance, and the FDUD293 for maintenance of the FDnet devices.
The following devices are exceptions:
● Flame detector FDF2x1-9
● Line separators FDCL221 and FDCL221-M
● Radio gateway FDCW241
● Radio manual call point FDM273
● Neural radio fire detector FDOOT271
Properties
● Efficient and environmentally-friendly checking of the detectors without gas
● Possible to exchange the detector without a ladder or scaffolding up to a room height of
8 m with the help of the telescope rods
● Flexible springs allow the point detectors to be inserted and removed at an angle
● The point detector can be held in four rotational positions This makes it easier to work ef-
ficiently
● Specially developed springs hold the point detector in the detector exchanger and tester
● Efficient operation thanks to alphanumerical display with backlight and keyboard
● Clearly visible LED indicators for 'Test OK', 'Detector exchange recommended', 'Detector
exchange obligatory'
● 9 V battery operation
● Compatible with
– Telescope rods FDUM291/292
– Previous straight connectors VR10/11/12/13
– MP/MT handles and straight connectors
● Possible to update the device software (firmware) via the MCL-USB adapter (radio) and
via a PC
● Environmentally friendly processing
● Reusable materials
● Electronic parts and synthetic materials can be easily separated
Function FDUD292
● Efficient installation and removal of the point detectors FDO, FDOOT, FDT, FDOOTC
● Commissioning, maintenance, status checking, and testing of detectors with further dia-
gnosis information directly on site
● Requesting parameters such as the bus address and changing detector settings
● Efficient error search on the detector and the control panel, particularly during installation
● Access levels with different functional scope
● Efficient testing through communication with the 'Sinteso Test' smartphone app; only with
optional Bluetooth extension kit FDUD29x-E
Function FDUD293
● Efficient installation and removal of the point detectors FDO, FDOOT, FDT, FDOOTC
● Testing and triggering detectors
● Efficient error search on the detector and the control panel, particularly during installation
Use
The test device and line device communicate either wirelessly or via the MC link (Mainten-
ance and Commissioning Link) with an adapter cable.
A wireless connection is possible with the following line devices:
Device Exceptions
All point detectors from the 'Sinteso™' product line: FDOOT271
FDO, FDOOT, FDT, FDOOTC

6
Smart Infrastructure 007228_v_en_--
2021-09-03
Device Exceptions
All manual call points FDM FDM231, FDM233, FDM234, FDM234H,
FDM273
All alarm sounders FDS —
A connection via the adapter cable FDUD292-A is possible with the following line devices:
Device Exceptions
All modules FDCI and FDCIO FDCI221, FDCI223, FDCIO221
Linear smoke detector FDL —

1 LEDs 7 Display
2 Manual call point FDM 8 Joint springs
3 Alarm sounder FDS 9 Keyboard
4 Point detectors FDO, FDOOT, FDOOTC, FDT 10 Modules FDC
5 Battery compartment on the rear 11 Linear smoke detector FDL
6 Adapter cable connection FDUD292-A 12 Adapter cable FDUD292-A

7
Smart Infrastructure 007228_v_en_--
2021-09-03
Bluetooth extension kit FDUD29x-E

● For connecting the detector exchanger and tester FDUD292 to a mobile terminal
● Enables wireless data exchange between a detector exchanger and tester and a mobile
terminal
● Compatible with detector exchanger and tester FDUD292

'Sinteso Test' Android app

'Sinteso Test' simplifies the process of comparing the data stored in the detection tree with
the device information for installed peripheral devices. 'Sinteso Test' is installed on a mobile
terminal – for example, a smartphone – and used alongside a detector exchanger and tester
FDUD292 and a Bluetooth extension kit FDUD29x-E.
The detector exchanger and tester FDUD292 with Bluetooth extension kit FDUD29x-E in-
stalled sends the 'serial no.', or 'ID no.', of an installed peripheral device to 'Sinteso Test'.
'Sinteso Test' displays the data assigned to the 'serial no.', or 'ID no.', in the detection tree.
The detector exchanger and tester allows you to query the device information for the in-
stalled peripheral device and compare this with data from the detection tree.

8
Smart Infrastructure 007228_v_en_--
2021-09-03
Detector tester RE6

● The detector tester RE6 is used together with a test gas can REF8, REF8-S, or REF8-C.
It is designed to test optical smoke detectors, ionization detectors, and CO detectors.
● The detector tester is positioned over the detector for the testing process. Brief pressure
causes the test gas to flow into the measuring chamber of the detector and therefore
simulate the presence of fire aerosols. After a short period of time, the detector responds
and triggers the alarm.
● REF8 and REF8-S are environmentally-friendly test gases and comply with strict envir-
onmental regulations. They do, however, contain flammable substances. REF8 is used
for the temperature range 0…+40 °C and REF8-S for -20…+40 °C in dry and damp con-
ditions. REF8-S is mainly used for temperatures below 0 °C or for point detectors that
only trigger the alarm when there is a high level of smoke density or after longer signal
integration.
● REF8-C is used to test the CO functionality of detectors with a CO sensor. REF8-C can
be used in dry and damp conditions at temperatures between -20 °C and +50 °C.

When transporting, e.g., in a car, we recommend protecting the detector tester and the test
gas cans from heat.
Please observe the notices on the detector tester for operation.

9
Smart Infrastructure 007228_v_en_--
2021-09-03
Detector tester RE7T – Solo461 heat detector tester kit

The heat detector tester kit consists of


● 1x heat detector tester
● 2x rechargeable batteries
● 1x charger with 12 V connection cable
● 2x mains cables AC 110/120-220/240 V.
The heat detector tester contains a hot air generator. The heat detector tester is positioned
over the detector for the function check. The hot air emitted heats the detector which triggers
this alarm.
In high rooms, detectors positioned at an angle can be reached and tested using adapters
and telescope rods.
The adapter RE7T-A and telescope rods FDUM291/292 must be ordered separately.

The heat detector tester must not be used in electrical switching stations or areas where
there is a danger of explosion.

10
Smart Infrastructure 007228_v_en_--
2021-09-03
Detector tester RE8ST – Testifire 1001-101 RT test kit

The test kit RE8ST consists of


● 1x Testifire 1001-101 tester
● 1x RE8-S smoke capsule
● 2x rechargeable batteries
● 1x charger with 12 V connection cable
● 2x mains cables AC 110/120-220/240 V
● 1x USB cable.
The detector tester contains a smoke capsule. The detector tester is positioned over the de-
tector for the function check. The smoke that is emitted triggers an alarm.
In high rooms, detectors positioned at an angle can be reached and tested using adapters
and telescope rods.
The adapter RE7T-A and telescope rods FDUM291/292 must be ordered separately.

The detector tester must not be used in electrical switching stations or areas where there is
a danger of explosion.

11
Smart Infrastructure 007228_v_en_--
2021-09-03
Detector tester RE8STCO – Testifire 1001-101 ST test kit

Fig. 4:
The test kit RE8STCO consists of
● 1x Testifire 2001-101 tester
● 1x RE8-S smoke capsule
● 1x RE8-CO CO capsule
● 2x rechargeable batteries
● 1x charger with 12 V connection cable
● 2x mains cables AC 110/120-220/240 V
● 1x USB cable.
The detector tester contains a smoke capsule or CO capsule. The detector tester is posi-
tioned over the detector for the function check. The smoke or gas that is emitted triggers an
alarm.
In high rooms, detectors positioned at an angle can be reached and tested using adapters
and telescope rods.
The adapter RE7T-A and telescope rods FDUM291/292 must be ordered separately.

The detector tester must not be used in electrical switching stations or areas where there is
a danger of explosion.

12
Smart Infrastructure 007228_v_en_--
2021-09-03
Accessories and spare parts for RE7T/RE8ST/RE8STCO

RE7T-A – Solo719 adapter for FDUM29x

Mounting adapter for the detector testers RE7T, RE8ST, and RE8STCO on the telescope
rods FDUM291 and FDUM292

RE7T-B1 – Solo770 battery

Battery as spare part

RE7T-C1 (Solo727 charger)

Charger as spare part for charging the batteries RE7T-B1

RE8-S smoke capsule for RE8ST and RE8STCO

RE8-CO CO capsule for RE8STCO

13
Smart Infrastructure 007228_v_en_--
2021-09-03
Telescope rods FDUM291 and FDUM292
Properties
● Light and robust yellow plastic pipes, non-conductive material
● Plastic sockets and friction bearings ensure that the pipes run into each other easily.
● Quick spring-type locking mechanisms allow continuous adjustment of the length.
● The pipes can be extended to their maximum length. A stop is used to prevent them from
extending further.
● Existing testers can be used.
● The telescope rods cannot be extended.

WARNING

Falling objects
Danger of injury
● Always wear a hardhat when working with telescope rods.

WARNING

Approaching or touching live lines


Electric shock
● Only use testers with telescope rods in volt-free areas.

CAUTION

Uncontrolled movements of sections of rod


Injuries to hands
● Keep a tight hold of the section of rod during the insertion process.
● Starting at the bottom, insert the sections of rod one after the other, largest diameter
first.
● Maintain the safety distance between the sections of rod.
● Use a spring-type locking mechanism to secure each section of rod.

14
Smart Infrastructure 007228_v_en_--
2021-09-03
FDUM291
● Light telescope rod for all applications in rooms up to 5.5 m high
● Flap closure for continuous adjustment of the length
● Three-part telescope with tri-oval pipes as practical grip
● Twisting the pipe in the opposite direction is not possible
● Weight: 1.2 kg without tester fitted
● Retracted length 1.6 m, extended length 4.2 m
FDUM292
● Long and robust telescope rod for all applications in rooms up to 8 m high
● Flip top closure for continuous adjustment of the length
● Sturdy four-sided telescope with round pipes
● Weight: 3.4 kg, without tester fitted
● Retracted length 2.1 m, extended length 7.3 m

1 Flip top closure


2 Flap closure

15
Smart Infrastructure 007228_v_en_--
2021-09-03
Detector tester RE10, alarm test filter TF04

● For undertaking a function check on the linear smoke detectors. The alarm test filter
TF04 is inserted into the detector tester in accordance with the type of detector to be
tested.
An alarm test filter is also included in the adjustment kit FDLU291.
● For testing, the detector tester is held in front of the detector lens in the IR beam. The
detector responds after a few seconds.

Adjustment kit FDLU291

The adjustment kit is used for commissioning the linear smoke detector FDL241-9. The lens
of the linear smoke detector can be efficiently aligned to the reflector by one man.

Scope of delivery:
● Case with adjustment device
● Alarm test filter
● Visor
● Magnet
● Spiral cable
● MC link cable
● 9 V battery
● Suspension fixture with cable grippers and chain

16
Smart Infrastructure 007228_v_en_--
2021-09-03
LE3 Test lamp

The test lamp LE3 is used to test the function of all flame detectors over distances up to
10 m. It is housed in a transportable case together with the required accessories. In addition,
the case enables the test lamp to be kept in a dust-free condition.
The quartz-halogen lamp used creates an intense ray of light. This helps to align the lamp on
the detector which is to be tested. During the detector test, the ray of light is modulated. The
luminous intensity can be set in accordance with the distance.
The power is supplied by a rechargeable battery. Since the color of the light depends on the
charge state of the battery, it must always be charged in buffer mode. A special charger is
available for this.

WARNING

Use of test lamps in areas at risk of explosion


Risk of explosion
● Do not use the test lamp LE3 in areas at risk of explosion.

Test lamp Stabex HF

The test lamp Stabex HF is used to test the function of intrinsically safe flame detectors in
zone 1 or 2 areas at risk of explosion.
The lamp is used directly in front of the detector for the test. The ray of light must be pulsed
with the sliding switch at half-second intervals.

WARNING

Opening test lamps in areas at risk of explosion


Risk of explosion
● Do not open the test lamp Stabex HF in areas at risk of explosion.

17
Smart Infrastructure 007228_v_en_--
2021-09-03
Technical data

Line tester FDUL221


Supply voltage Min. DC 10 V, max. DC 30 V
Lithium manganese dioxide battery or via ULTRALIFE U9VL or U9VL‑J or EVE CR9V/
P‑S, 2x 9 V
network adapter AC 240 V / DC 24 V, 750 mA
Power consumption during measurement Depends on the number of devices and the
display backlight
Detector line voltage:
FDnet (FS20, AlgoRex) DC 32 V
FDnet (SIGMASYS) DC 28 V
Max. detector key figures (MK) per line
MK with network adapter Min. 550
MK with battery Min. 150
Operating temperature -25…+40 °C
Storage temperature without battery -30…+75 °C
Storage temperature with battery -25…+60 °C
Air humidity (no condensation permitted) ≤95 % rel.

Detector exchanger and tester FDUD292, intelligent detector tester FDUD293


Supply voltage DC 9 V
Alkaline battery Standard 9 V battery
Lithium manganese dioxide battery for temperatures below ULTRALIFE U9VL or U9VL-J or EVE CR9V/P-S
-10 °C Capacity 950–1200 mAh
Operating current:
Ready – light on/off 2 mA / 42 mA
Communication – 3 LEDs + buzzer 95 mA
Operating temperature -20…+40 °C
Storage temperature -30…+75 °C
Storage temperature with battery -25…+60 °C
Air humidity (no condensation permitted) ≤95 % rel.

Detector tester RE6


Operating temperature
REF8 0…+40 °C
REF8-S -20…+40 °C
REF8-C -20…+50 °C
Storage temperature -20…+40 °C
Number of detector tests, depending on detector type Max. 400

Heat detector tester RE7T


Operating temperature 5…+45 °C
Storage temperature -10…+50 °C
Air humidity (no condensation permitted) ≤95 % rel.
Voltage Auto: DC 12 V
Mains: AC 110/120-220/240 V
Charging time Approx. 1 hour per battery

Detector tester RE8ST/RE8STCO


Operating temperature 5…+45 °C

18
Smart Infrastructure 007228_v_en_--
2021-09-03
Detector tester RE8ST/RE8STCO
Storage temperature -10…+50 °C
Air humidity (no condensation permitted) ≤95 % rel.
Voltage Auto: DC 12 V
Mains: AC 110/120-220/240 V
Charging time Approx. 1 hour per battery

Adjustment kit FDLU291
Dimensions of the adjustment device 120 x 65 x 22 mm

Test lamp LE3
Power consumption 50 W
Modulation frequency 4 Hz
Max. distance for alarm activation 10 m
Measuring capacity with charged battery and max. distance
Number of detectors ~ 50
Operating and storage temperature -20...+ 45 °C
Areas of use Areas not at risk of explosion
Incandescent lamp Halogen 12 V / 50 W
Battery 12 V / 7 Ah, lead, gas tight
Charging time Min. 16 h
Power supply connection charger AC 220 / 240 V, 50…60 Hz
Dimensions
● Test lamp 178 x 180 x 369 mm
● Battery 153 x 103 x 67 mm

Test lamp Stabex HF
Max. distance for alarm activation A few cm
Operating and storage temperature -20…+40 °C
Explosion protection II 2 G EEx ib e IIC T4
Ex approvals PTB 98 ATEX 2062
Areas of use Zones 1 and 2
Protection category IP65
Incandescent lamp Halogen 2.8 V / 0.5 A
Battery 2x alkaline batteries 1.5 V
Mono cell UM-1
Disposal

The device is considered an electronic device for disposal in accordance


with European Directive and may not be disposed of as domestic waste.
● Use only designated channels for disposing the devices.
● Comply with all local and currently applicable laws and regulations.
● Dispose of empty batteries at designated collection points.

19
Smart Infrastructure 007228_v_en_--
2021-09-03
Details for ordering

Type Order number Designation Weight


Line tester FDUL221 A5Q00004397 Line tester with line connection kit 1.567 kg
FDUL221‑A, power unit set
FDUL221‑B and carry case
Lithium battery not included in scope
of delivery
Accessories – A5Q00004142 Lithium manganese dioxide battery 0.035 kg
9 V / 1.2 Ah
Spare part FDUL221-A A5Q00008436 Line connection kit 0.088 kg
FDUL221-B A5Q00008437 Power unit kit 0.278 kg
FDUL221-C A5Q00008438 RS232 PC cable as spare part for 0.037 kg
FDUL221 with RS232 interface
FDUL221-3 S54370-S30-A1 Line tester without accessories 0.440 kg

Type Order number Designation Weight


Detector exchanger FDUD291 A5Q00003585 Detector exchanger 0.594 kg
Detector exchanger and FDUD292 A5Q00003357 Detector exchanger and tester incl. 1.079 kg
tester adapter cable FDUD292‑A
Lithium battery not included in scope
of delivery
Intelligent detector FDUD293 A5Q00018261 Intelligent detector tester incl. 1.079 kg
tester adapter cable FDUD292‑A
Lithium battery not included in scope
of delivery
Accessories – A5Q00004142 Lithium manganese dioxide battery 0.035 kg
9 V / 1.2 Ah
Spare part FDUD292-A A5Q00004990 Adapter cable, audio stereo cable 0.040 kg
with 3.5 mm jack plug

Type Order number Designation Weight


Bluetooth extension kit FDUD29x-E S54319-Z30-A1 Bluetooth extension kit 0.028 kg

Type Order number Designation Weight


Detector tester RE6 BPZ:3680300001 Detector tester for smoke detectors 0.950 kg
Accessories REF8 A5Q00011687 Test gas can 0.194 kg
REF8-S A5Q00011688 Test gas can 0.186 kg
REF8-C S54370-N2-A1 Test gas can CO 0.203 kg

Type Order number Designation Weight


Detector tester RE7T S54370-S3-A1 Solo461 heat detector tester kit 2.800 kg
consisting of tester, 2 batteries,
charger, cable
Accessories RE7T-A S54370-N4-A1 Solo719 adapter for FDUM29x 0.260 kg
Spare part RE7T-B1 S54370-N7-A1 Solo770 battery for RE7T 1.090 kg
RE7T-C1 S54370-N8-A1 Solo727 charger for RE7T 1.210 kg

Type Order number Designation Weight


Detector tester RE8ST S54370-S23-A1 Testifire 1001-101 ST test kit 3.470 kg
RE8STCO S54370-S24-A1 Testifire 2001-101 STCO test kit 3.750 kg
Capsule RE8-S S54370-N25-A1 TS3 smoke capsules, 6 items 0.079 kg
RE8-CO S54370-N22-A1 TS3 CO capsules, 6 items 0.077 kg
Accessories RE7T-A S54370-N4-A1 Solo719 adapter for FDUM29x 0.260 kg

20
Smart Infrastructure 007228_v_en_--
2021-09-03
Type Order number Designation Weight
1
Spare part RE7T-B1 S54370-N7-A1 Solo770 battery for RE7T  1.090 kg
1
RE7T-C1 S54370-N8-A1 Solo727 charger for RE7T  1.210 kg
1
  Compatible with RE8ST and RE8STCO
Type Order number Designation Weight
Telescope rod FDUM291 A5Q00004996 Telescope rod – three-part telescope 1.960 kg
with tri-oval pipes, 1.6 m / 4.2 m
Spare part – A5Q00009787 Lever with screw and nut, 0.023 kg
flip top closure
– A5Q00009786 Adapter with lever, screw, and nut 0.088 kg
incl. mounting and sleeve bolt
– A5Q00009788 Small flap with screw and nut, flap 0.015 kg
closure
– A5Q00009789 Large flap with screw and nut, flap 0.016 kg
closure

Type Order number Designation Weight


Telescope rod FDUM292 A5Q00004997 Telescope rod – four-part telescope 4.480 kg
with round pipes, 2.1 m / 7.3 m
Spare part – A5Q00009787 Lever with screw and nut, flip top 0.023 kg
closure
– A5Q00009786 Adapter with lever, screw, and nut 0.088 kg
incl. mounting and sleeve bolt

Type Order number Designation Weight


Detector tester RE10 BPZ:3685190001 Detector tester for linear smoke 0.345 kg
detectors
Alarm test filter for TF04 BPZ:4931090001 Alarm test filter, absorption 77 % 0.005 kg
RE10

Type Order number Designation Weight


Adjustment kit FDLU291 A5Q00004905 Adjustment kit for linear smoke 0.840 kg
detector
incl. case

Type Order number Designation Weight


Test lamp LE3 BPZ:3669510001 Test lamp for flame detector incl. 5.260 kg
case and charger, without battery
Accessories FA2003-A1 A5Q00019353 Battery 12 V / 7 Ah / VdS 2.293 kg
Spare part BPZ:3679630001 Halogen lamp 12 V / 50 W 0.395 kg

Type Order number Designation Weight


Test lamp Stabex HF BPZ:4620910001 Test lamp for areas at risk of 0.175 kg
explosion

21
Smart Infrastructure 007228_v_en_--
2021-09-03
Applicable documents

Document ID Name
008331 List of compatibility (for 'Sinteso™' product line)
008164 Equipment overview Sinteso™ Detector system FD20
007227 Technical manual Detector exchanger and tester FDUD292
009718 Technical Manual Intelligent detector tester FDUD293
A6V10254740 Operating instructions Solo461 heat detector tester kit RE7T
A6V10387053 Installation RE8ST Testifire 1001-101 ST test kit, RE8STCO Testifire
2001-101 STCO test kit
A6V10260320 Operation RE7T-C Solo726 charger for RE7T-B
A6V11432110 Operation RE7T-C1 Solo727 charger for RE7T-B1 Solo770
008250 Technical Manual Line tester FDUL221
A6V10395483 Line tester – operating instructions for electricians
A6V10424692 Installation, Commissioning Sinteso Test
A6V10405496 Installation Bluetooth extension kit FDUD29x-E
007016 Technical manual Linear smoke detector FDL241-9
000257 Operating instructions Test lamp LE3
Safety data sheets
A5Q00011687D Safety data sheet REF8
A5Q00011688D Safety data sheet REF8-S
A5Q00035329C Safety data sheet REF8-C
MCL-USB adapter (radio) FDUZ227, see data sheet A6V10355605.

Issued by © Siemens Switzerland Ltd, 2007


Siemens Switzerland Ltd Technical specifications and availability subject to change without notice.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies

Document ID 007228_v_en_--
Edition 2021-09-03

You might also like