Test Units and Accessories: Sinteso™
Test Units and Accessories: Sinteso™
Test units to test detectors and detector lines for FS20 fire detection installa-
tions
● Detector exchanger FDUD291 for the efficient installation and removal of Sinteso
point detectors
● Detector exchanger and tester FDUD292 and intelligent detector tester FDUD293
for commissioning, maintenance, and troubleshooting of point detectors, alarm
sounders, and linear smoke detectors
● Bluetooth extension kit FDUD29x-E for wireless communication between the de-
tector exchanger and tester FDUD292 and a mobile terminal
● Line tester FDUL221 for diagnosing detector lines
● Detector tester RE6 for use with environmentally-friendly test gas REF8, REF8-S,
REF8-C
● Detector tester RE7T with hot air generator, RE8ST with smoke capsule RE8-S,
RE8ST-CO with smoke capsule RE8-S, capsule RE8-CO, and CO capsule
● Detector tester RE10 for undertaking a function check on linear smoke detectors
● Telescope rods FDUM291/292 for extending detector exchanger, detector ex-
changer and tester, and other testers
2
Smart Infrastructure 007228_v_en_--
2021-09-03
Fig. 2: Line tester software FXS2017
3
Smart Infrastructure 007228_v_en_--
2021-09-03
Use
The line tester FDUL221 is a universal device for the final testing of fully installed FDnet fire
detector lines if a control panel is not connected. The device is used to for error searches by
the electrician, installer, or service technician.
1 2 3 4
8 7 6 5
4
Smart Infrastructure 007228_v_en_--
2021-09-03
Detector exchanger FDUD291
Properties
● Possible to exchange the detector without a ladder or scaffolding up to a room height of
8 m with the help of the telescope rods
● Joint springs enable the point detectors to be inserted or removed at an angle
● The point detector can be held in four rotational positions This makes it easier to work ef-
ficiently
● Specially developed springs hold the point detector in the detector exchanger
● Compatible with
– Telescope rods FDUM291/292
– Previous straight connectors VR10/11/12/13
– MP/MT handles and straight connectors
● Environmentally friendly processing
● Reusable materials
Function
● Efficient installation and removal of the point detectors FDO, FDOOT, FDT, FDOOTC
121
1
57
2
390
5
Smart Infrastructure 007228_v_en_--
2021-09-03
Detector exchanger and tester FDUD292 and intelligent detector tester FDUD293
The detector exchanger and tester FDUD292 and the intelligent detector tester FDUD293
are universal tools for inserting and removing point detectors. The FDUD292 is used for
commissioning and maintenance, and the FDUD293 for maintenance of the FDnet devices.
The following devices are exceptions:
● Flame detector FDF2x1-9
● Line separators FDCL221 and FDCL221-M
● Radio gateway FDCW241
● Radio manual call point FDM273
● Neural radio fire detector FDOOT271
Properties
● Efficient and environmentally-friendly checking of the detectors without gas
● Possible to exchange the detector without a ladder or scaffolding up to a room height of
8 m with the help of the telescope rods
● Flexible springs allow the point detectors to be inserted and removed at an angle
● The point detector can be held in four rotational positions This makes it easier to work ef-
ficiently
● Specially developed springs hold the point detector in the detector exchanger and tester
● Efficient operation thanks to alphanumerical display with backlight and keyboard
● Clearly visible LED indicators for 'Test OK', 'Detector exchange recommended', 'Detector
exchange obligatory'
● 9 V battery operation
● Compatible with
– Telescope rods FDUM291/292
– Previous straight connectors VR10/11/12/13
– MP/MT handles and straight connectors
● Possible to update the device software (firmware) via the MCL-USB adapter (radio) and
via a PC
● Environmentally friendly processing
● Reusable materials
● Electronic parts and synthetic materials can be easily separated
Function FDUD292
● Efficient installation and removal of the point detectors FDO, FDOOT, FDT, FDOOTC
● Commissioning, maintenance, status checking, and testing of detectors with further dia-
gnosis information directly on site
● Requesting parameters such as the bus address and changing detector settings
● Efficient error search on the detector and the control panel, particularly during installation
● Access levels with different functional scope
● Efficient testing through communication with the 'Sinteso Test' smartphone app; only with
optional Bluetooth extension kit FDUD29x-E
Function FDUD293
● Efficient installation and removal of the point detectors FDO, FDOOT, FDT, FDOOTC
● Testing and triggering detectors
● Efficient error search on the detector and the control panel, particularly during installation
Use
The test device and line device communicate either wirelessly or via the MC link (Mainten-
ance and Commissioning Link) with an adapter cable.
A wireless connection is possible with the following line devices:
Device Exceptions
All point detectors from the 'Sinteso™' product line: FDOOT271
FDO, FDOOT, FDT, FDOOTC
6
Smart Infrastructure 007228_v_en_--
2021-09-03
Device Exceptions
All manual call points FDM FDM231, FDM233, FDM234, FDM234H,
FDM273
All alarm sounders FDS —
A connection via the adapter cable FDUD292-A is possible with the following line devices:
Device Exceptions
All modules FDCI and FDCIO FDCI221, FDCI223, FDCIO221
Linear smoke detector FDL —
1 LEDs 7 Display
2 Manual call point FDM 8 Joint springs
3 Alarm sounder FDS 9 Keyboard
4 Point detectors FDO, FDOOT, FDOOTC, FDT 10 Modules FDC
5 Battery compartment on the rear 11 Linear smoke detector FDL
6 Adapter cable connection FDUD292-A 12 Adapter cable FDUD292-A
7
Smart Infrastructure 007228_v_en_--
2021-09-03
Bluetooth extension kit FDUD29x-E
● For connecting the detector exchanger and tester FDUD292 to a mobile terminal
● Enables wireless data exchange between a detector exchanger and tester and a mobile
terminal
● Compatible with detector exchanger and tester FDUD292
'Sinteso Test' simplifies the process of comparing the data stored in the detection tree with
the device information for installed peripheral devices. 'Sinteso Test' is installed on a mobile
terminal – for example, a smartphone – and used alongside a detector exchanger and tester
FDUD292 and a Bluetooth extension kit FDUD29x-E.
The detector exchanger and tester FDUD292 with Bluetooth extension kit FDUD29x-E in-
stalled sends the 'serial no.', or 'ID no.', of an installed peripheral device to 'Sinteso Test'.
'Sinteso Test' displays the data assigned to the 'serial no.', or 'ID no.', in the detection tree.
The detector exchanger and tester allows you to query the device information for the in-
stalled peripheral device and compare this with data from the detection tree.
8
Smart Infrastructure 007228_v_en_--
2021-09-03
Detector tester RE6
● The detector tester RE6 is used together with a test gas can REF8, REF8-S, or REF8-C.
It is designed to test optical smoke detectors, ionization detectors, and CO detectors.
● The detector tester is positioned over the detector for the testing process. Brief pressure
causes the test gas to flow into the measuring chamber of the detector and therefore
simulate the presence of fire aerosols. After a short period of time, the detector responds
and triggers the alarm.
● REF8 and REF8-S are environmentally-friendly test gases and comply with strict envir-
onmental regulations. They do, however, contain flammable substances. REF8 is used
for the temperature range 0…+40 °C and REF8-S for -20…+40 °C in dry and damp con-
ditions. REF8-S is mainly used for temperatures below 0 °C or for point detectors that
only trigger the alarm when there is a high level of smoke density or after longer signal
integration.
● REF8-C is used to test the CO functionality of detectors with a CO sensor. REF8-C can
be used in dry and damp conditions at temperatures between -20 °C and +50 °C.
When transporting, e.g., in a car, we recommend protecting the detector tester and the test
gas cans from heat.
Please observe the notices on the detector tester for operation.
9
Smart Infrastructure 007228_v_en_--
2021-09-03
Detector tester RE7T – Solo461 heat detector tester kit
The heat detector tester must not be used in electrical switching stations or areas where
there is a danger of explosion.
10
Smart Infrastructure 007228_v_en_--
2021-09-03
Detector tester RE8ST – Testifire 1001-101 RT test kit
The detector tester must not be used in electrical switching stations or areas where there is
a danger of explosion.
11
Smart Infrastructure 007228_v_en_--
2021-09-03
Detector tester RE8STCO – Testifire 1001-101 ST test kit
Fig. 4:
The test kit RE8STCO consists of
● 1x Testifire 2001-101 tester
● 1x RE8-S smoke capsule
● 1x RE8-CO CO capsule
● 2x rechargeable batteries
● 1x charger with 12 V connection cable
● 2x mains cables AC 110/120-220/240 V
● 1x USB cable.
The detector tester contains a smoke capsule or CO capsule. The detector tester is posi-
tioned over the detector for the function check. The smoke or gas that is emitted triggers an
alarm.
In high rooms, detectors positioned at an angle can be reached and tested using adapters
and telescope rods.
The adapter RE7T-A and telescope rods FDUM291/292 must be ordered separately.
The detector tester must not be used in electrical switching stations or areas where there is
a danger of explosion.
12
Smart Infrastructure 007228_v_en_--
2021-09-03
Accessories and spare parts for RE7T/RE8ST/RE8STCO
Mounting adapter for the detector testers RE7T, RE8ST, and RE8STCO on the telescope
rods FDUM291 and FDUM292
13
Smart Infrastructure 007228_v_en_--
2021-09-03
Telescope rods FDUM291 and FDUM292
Properties
● Light and robust yellow plastic pipes, non-conductive material
● Plastic sockets and friction bearings ensure that the pipes run into each other easily.
● Quick spring-type locking mechanisms allow continuous adjustment of the length.
● The pipes can be extended to their maximum length. A stop is used to prevent them from
extending further.
● Existing testers can be used.
● The telescope rods cannot be extended.
WARNING
Falling objects
Danger of injury
● Always wear a hardhat when working with telescope rods.
WARNING
CAUTION
14
Smart Infrastructure 007228_v_en_--
2021-09-03
FDUM291
● Light telescope rod for all applications in rooms up to 5.5 m high
● Flap closure for continuous adjustment of the length
● Three-part telescope with tri-oval pipes as practical grip
● Twisting the pipe in the opposite direction is not possible
● Weight: 1.2 kg without tester fitted
● Retracted length 1.6 m, extended length 4.2 m
FDUM292
● Long and robust telescope rod for all applications in rooms up to 8 m high
● Flip top closure for continuous adjustment of the length
● Sturdy four-sided telescope with round pipes
● Weight: 3.4 kg, without tester fitted
● Retracted length 2.1 m, extended length 7.3 m
15
Smart Infrastructure 007228_v_en_--
2021-09-03
Detector tester RE10, alarm test filter TF04
● For undertaking a function check on the linear smoke detectors. The alarm test filter
TF04 is inserted into the detector tester in accordance with the type of detector to be
tested.
An alarm test filter is also included in the adjustment kit FDLU291.
● For testing, the detector tester is held in front of the detector lens in the IR beam. The
detector responds after a few seconds.
The adjustment kit is used for commissioning the linear smoke detector FDL241-9. The lens
of the linear smoke detector can be efficiently aligned to the reflector by one man.
Scope of delivery:
● Case with adjustment device
● Alarm test filter
● Visor
● Magnet
● Spiral cable
● MC link cable
● 9 V battery
● Suspension fixture with cable grippers and chain
16
Smart Infrastructure 007228_v_en_--
2021-09-03
LE3 Test lamp
The test lamp LE3 is used to test the function of all flame detectors over distances up to
10 m. It is housed in a transportable case together with the required accessories. In addition,
the case enables the test lamp to be kept in a dust-free condition.
The quartz-halogen lamp used creates an intense ray of light. This helps to align the lamp on
the detector which is to be tested. During the detector test, the ray of light is modulated. The
luminous intensity can be set in accordance with the distance.
The power is supplied by a rechargeable battery. Since the color of the light depends on the
charge state of the battery, it must always be charged in buffer mode. A special charger is
available for this.
WARNING
The test lamp Stabex HF is used to test the function of intrinsically safe flame detectors in
zone 1 or 2 areas at risk of explosion.
The lamp is used directly in front of the detector for the test. The ray of light must be pulsed
with the sliding switch at half-second intervals.
WARNING
17
Smart Infrastructure 007228_v_en_--
2021-09-03
Technical data
18
Smart Infrastructure 007228_v_en_--
2021-09-03
Detector tester RE8ST/RE8STCO
Storage temperature -10…+50 °C
Air humidity (no condensation permitted) ≤95 % rel.
Voltage Auto: DC 12 V
Mains: AC 110/120-220/240 V
Charging time Approx. 1 hour per battery
Adjustment kit FDLU291
Dimensions of the adjustment device 120 x 65 x 22 mm
Test lamp LE3
Power consumption 50 W
Modulation frequency 4 Hz
Max. distance for alarm activation 10 m
Measuring capacity with charged battery and max. distance
Number of detectors ~ 50
Operating and storage temperature -20...+ 45 °C
Areas of use Areas not at risk of explosion
Incandescent lamp Halogen 12 V / 50 W
Battery 12 V / 7 Ah, lead, gas tight
Charging time Min. 16 h
Power supply connection charger AC 220 / 240 V, 50…60 Hz
Dimensions
● Test lamp 178 x 180 x 369 mm
● Battery 153 x 103 x 67 mm
Test lamp Stabex HF
Max. distance for alarm activation A few cm
Operating and storage temperature -20…+40 °C
Explosion protection II 2 G EEx ib e IIC T4
Ex approvals PTB 98 ATEX 2062
Areas of use Zones 1 and 2
Protection category IP65
Incandescent lamp Halogen 2.8 V / 0.5 A
Battery 2x alkaline batteries 1.5 V
Mono cell UM-1
Disposal
19
Smart Infrastructure 007228_v_en_--
2021-09-03
Details for ordering
20
Smart Infrastructure 007228_v_en_--
2021-09-03
Type Order number Designation Weight
1
Spare part RE7T-B1 S54370-N7-A1 Solo770 battery for RE7T 1.090 kg
1
RE7T-C1 S54370-N8-A1 Solo727 charger for RE7T 1.210 kg
1
Compatible with RE8ST and RE8STCO
Type Order number Designation Weight
Telescope rod FDUM291 A5Q00004996 Telescope rod – three-part telescope 1.960 kg
with tri-oval pipes, 1.6 m / 4.2 m
Spare part – A5Q00009787 Lever with screw and nut, 0.023 kg
flip top closure
– A5Q00009786 Adapter with lever, screw, and nut 0.088 kg
incl. mounting and sleeve bolt
– A5Q00009788 Small flap with screw and nut, flap 0.015 kg
closure
– A5Q00009789 Large flap with screw and nut, flap 0.016 kg
closure
21
Smart Infrastructure 007228_v_en_--
2021-09-03
Applicable documents
Document ID Name
008331 List of compatibility (for 'Sinteso™' product line)
008164 Equipment overview Sinteso™ Detector system FD20
007227 Technical manual Detector exchanger and tester FDUD292
009718 Technical Manual Intelligent detector tester FDUD293
A6V10254740 Operating instructions Solo461 heat detector tester kit RE7T
A6V10387053 Installation RE8ST Testifire 1001-101 ST test kit, RE8STCO Testifire
2001-101 STCO test kit
A6V10260320 Operation RE7T-C Solo726 charger for RE7T-B
A6V11432110 Operation RE7T-C1 Solo727 charger for RE7T-B1 Solo770
008250 Technical Manual Line tester FDUL221
A6V10395483 Line tester – operating instructions for electricians
A6V10424692 Installation, Commissioning Sinteso Test
A6V10405496 Installation Bluetooth extension kit FDUD29x-E
007016 Technical manual Linear smoke detector FDL241-9
000257 Operating instructions Test lamp LE3
Safety data sheets
A5Q00011687D Safety data sheet REF8
A5Q00011688D Safety data sheet REF8-S
A5Q00035329C Safety data sheet REF8-C
MCL-USB adapter (radio) FDUZ227, see data sheet A6V10355605.
Document ID 007228_v_en_--
Edition 2021-09-03