0% found this document useful (0 votes)
116 views4 pages

Megger DLRO10HD - A700000006855725

The document describes the DLRO10HD 10 Amp Digital Low Resistance Ohmmeter. It has the following key features: 1. It can deliver 10 A for 60 seconds or 1 A for measurements up to 2.5 Ohms, allowing for testing of low resistance values. 2. It has five test modes that are selected via a simple rotary switch including automatic, continuous, and inductive modes. 3. It is powered by a rechargeable battery or line power, has an IP65 rated rugged case, and large clear backlit display.

Uploaded by

rey chico
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
116 views4 pages

Megger DLRO10HD - A700000006855725

The document describes the DLRO10HD 10 Amp Digital Low Resistance Ohmmeter. It has the following key features: 1. It can deliver 10 A for 60 seconds or 1 A for measurements up to 2.5 Ohms, allowing for testing of low resistance values. 2. It has five test modes that are selected via a simple rotary switch including automatic, continuous, and inductive modes. 3. It is powered by a rechargeable battery or line power, has an IP65 rated rugged case, and large clear backlit display.

Uploaded by

rey chico
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

DLRO10HD

10 A Digital Low Resistance Ohmmeter

DLRO10HD
10 Amp Digital Low Resistance
nn NEW interchangeable test lead terminations
nn High or low output power selection for
condition diagnosis
nn Rechargeable battery or line power supply,
continuous operation, even with dead
battery
nn 10 A for 60 seconds, less time waiting to
cool
nn Protected to 600 V without blowing a fuse,
test lead live voltage warning light
nn Heavy duty case: IP 65 lid closed, IP54
battery operation
nn Simple rotary switch selection of five test
modes, including auto start on connection

DESCRIPTION
Augmenting Megger’s DLRO10 and 10X range the DLRO10HD
combines ultimate simplicity of operation with a rugged IP65
History of ‘Ducter’ testing
case designed for stable ground and bench operation.
For over 100 years the ‘Ducter test’ has been used to describe
The unit is powered from either its rechargeable battery or line
a simple test for measuring very low contact resistances
power making it suitable for continuous testing in production
and “Ducter”, which is still used as a trade mark, was the
line/repetitive use environments.
name originally given to the low resistance ohmmeter
Rotary switch controls are simple and easy to operate in all manufactured by Megger. The name Ducter was registered
weather conditions and with gloved hands. A large, clear, by Megger in June 1908 and ‘Ducter’ has since become the
backlit LCD display is easy to read from a distance. The industry standard.
DLRO10HD provides significantly enhanced compliance and
is capable of delivering 10 A into measurements up to 250
mΩ and 1 A into measurements up to 2.5 Ω. The duration of
each test may be up to 60 seconds.
The DLRO10HD is rated CATIII 300 V provided the optional
terminal cover is fitted to the instrument. Details of which can
be found in the ordering information panel of this data sheet.
The DLRO10HD provides five test modes each of which is
selected through a simple rotary control.
DLRO10HD
10 A Digital Low Resistance Ohmmeter
TEST modes
ADDITONAL FEATURES AND BENEFITS Automatic unidirectional mode applies current in one
nn Rugged case well suited to transportation with shoulder direction only to speed up the measurement process.
strap and lead set pouch
However thermal EMF resulting from dissimilar metal bonds
nn Removable lid facilitates easy test lead connection can cause lower accuracy. Test starts automatically when
probes are connected.
nn Operational ingress protection is IP 54 (battery power
only) ensuring protection from the elements Continuous mode allows repeated measurements to be made
on the same sample. Simply connect the test leads and press
nn 7Ah lead acid battery provides extended operation and the test button. The measurement is updated every three
can be charged whilst operating from line power seconds until the circuit is broken.
nn Rotary mode switch with bidirectional (current reversal Inductive mode is selected when measuring resistance on, for
with averaging cancels thermal EMFs), unidirectional, example, motors and generators. When measuring inductive
automatic, continuous and inductive modes loads it is necessary to wait for the voltage to stabilise as the
nn Large, clear LCD display with backlight and contrast inductive element is charged. Test leads are firmly connected
adjustment to the device under test and the ‘Test’ button pressed. The
instrument will pass the selected current through the sample
nn Auto power off function conserves battery continuously in one direction only and take repetitive readings
that will gradually decrease to the true value as the voltage
stabilises. The operator decides when the result is stable and
APPLICATIONS presses the ‘Test’ button to terminate the test

The DLRO10HD measures low resistance values in applications


ranging from railways and aircraft to resistance of components ELECTRICAL SPECIFICATIONS
in industry.
Resistance/Current Ranges
Any metallic joint can be measured but users must be aware
of measurement limitations depending on application. For The green resistance ranges on the keypad indicate low
example, if a cable manufacturer plans to make resistive output power (<0.25 W) outputs. Red ranges indicate higher
measurements on a thin wire, a low test current should be 2.5 W (1 A) and 25 W (10 A) power outputs.
selected to prevent heating the wire thereby changing its
resistance
Resolution and Accuracy
Measurements on electric motors and generators will be
inductive and require the user to understand the inductive Test current accuracy ±10%
mode and charging process before a correct result is achieved.
Voltmeter input impedance >200 kΩ
The DLRO10HD is well suited to measuring thick conductors,
Maximum lead resistance at 10 A <100 mΩ
bonds and quality of welding because of its 10 A range for
resistance values up to 250 mΩ.
(as displayed)

Electromagnetic noise induced into the leads can interfere


Resolution
Resistance

accuracy*

with a reading. A noise symbol alerts the user and prevents


voltage
current

a measurement when the instrument detects noise above its


output
power
range

Basic

Max.
scale

threshold.
Test

Full

When dissimilar metals are joined a thermocouple effect is


±0.2%
created. Users should select a bidirectional mode to ensure 100 µA 0 - 2.5 kΩ 0.1 Ω 25 mV 25 μW
±200 mΩ
cancellation of this effect. The instrument measures with
±0.2%
current flowing in both directions and averages the result. 100 µA 0 - 250 Ω 0.01 Ω 25 mV 2.5 μW
±20 mΩ
Normal mode is initiated by pressing the ‘Test’ button after ±0.2%
connecting the test leads to the unit under test. Continuity 1 mA 0 - 25 Ω 1 mΩ 25 mV 25 μW
±2 mΩ
of all four connections is checked. Current is applied in both ±0.2%
forward and reverse direction following which measurement 10 mA 0 - 2.5 Ω 0.1 mΩ 25mV 250 μW
±200 µΩ
is displayed. ±0.2%
100 mA 0 - 250 mΩ 0.01 mΩ 25 mV 2.5 mW
Automatic mode is started as soon as the probes make contact. ±20 µΩ
Forward and reverse current measurements are made and the ±0.2%
1A 0 - 25 mΩ 1 μΩ 25 mV 25 mW
average value is displayed. This mode is ideal when working ±2 µΩ
with handspikes. Each time the probes are removed and ±0.2%
10 A 0 - 2.5 mΩ 0.1 μΩ 25 mV 0.25 W
reconnected to the load a new test will be performed without ±0.2 µΩ
the need to press the test button. ±0.2%
1 A** 0 - 2.5 Ω 0.1 mΩ 2.5 V 2.5 W
±200 µΩ
±0.2%
10 A ** 0 - 250 mΩ 0.01 mΩ 2.5 V 25 W
±50 µΩ

2
DLRO10HD
10 A Digital Low Resistance Ohmmeter
OPTIONAL TERMINAL COVER
* Basic accuracy stated assumes forward and reverse
measurements.
The CATIII 300 V rating on the
** Higher 2.5 W (1 A) and 25 W (10 A) power outputs (G DLRO10HD is only valid when
shows). the instrument is fitted with
the optional terminal cover to
Inductive mode or undirectional mode will introduce an
provide the required creepage
undefined error if an external EMF is present.
and clearances at the
Basic accuracy at reference conditions. instrument terminals.
Although the terminal cover
may be used with any test
GENERAL SPECIFICATIONS leads, only the Megger DH4,
Temperature coefficient < 0.01% per ºC, from 5 ºC to DH5 and DP1-C duplex handspikes, and KC2-C insulated
40 ºC kelvin clips have suitable probe insulation to comply with the
requirements of IEC61010-1 and the CATIII 300 V rating.
Maximum altitude 2000 m (6562 ft) to full safety
specifications
Display size/type Main 5 digit + 2 x 5 digit
secondary displays
Battery type 6 V, 7Ah sealed lead acid
Voltage input range 100 - 240 V 50 / 60 Hz 90 VA
Charge time 8 hours
Backlight LED backlight
Battery life >1000 Auto (3 sec) tests
Auto power down 300s
Mode selection Rotary switch SUPPLIED LEADSET OPTIONS
Range selection Rotary switch
Weight 6.7 kg
Case dimensions L315 mm x W285 mm x
H181 mm
Pouch for test leads Yes (lid mounted)
Test leads DH4C lead set
DLRO10HD
IP rating IP65 case closed,
IP54 battery
operation
Safety rating
In accordance with IEC61010-1, CATIII 300V when used
with optional terminal cover (details in ordering information)
Operating temperature and humidity
-10 °C to +50 °C + DH4-C probe 1.5 m leads 

(14 °F to 122 °F) <90% RH


Reference conditions 20 °C ±3 °C
Storage temperature and humidity
-25 °C to +60 °C, <90% RH
EMC
In accordance with IEC61326-1 (Heavy industrial)
+ KC1 Kelvin clip 3 m leads
Noise rejection
Less than 1% ±20 digits additional error with 100 mV peak
50/60 Hz. on the potential leads. Warning will show if hum
or noise exceeds this level.
+ No test leads supplied 
Maximum lead resistance
100 mΩ total for 10 A operation irrespective of battery
condition.

3
DLRO10HD
10 A Digital Low Resistance Ohmmeter

ORDERING INFORMATION
Item (Qty) Order No. Item (Qty) Order No.
DLRO10HD + DH4-C probe 1,5m leads 1006-603 Straight Duplex Handspikes (2) Heavy Duty with fixed contacts
DLRO10HD + KC1 kelvin clip 3m leads 1006-604 9m/30ft 242002-30
DLRO10HD without test leads supplied 1006-657
Duplex Heavy Duty 5cm (2”) C-Clamps. (2)
2m/7ft 242004-7
Standard included accessories Duplex Heavy Duty 5cm (2”) C-Clamps. (2)
DLRO10HD user guide CD 1000-869 5.5m/18ft 242004-18
Warranty book. 6170618 Duplex Heavy Duty 5cm (2”) C-Clamps. (2)
9m/30ft 242004-30
Test leads supplied with instruments
1006-603 DLRO10HD = DH4-C probe 1,5m leads 1006-444
Duplex handspikes with replaceable
1006-604 DLRO10HD = KC1 kelvin clip 3m leads 1006-462 Needle Points 2m/7ft 242003-7
1006-657 DLRO10HD = No test leads supplied 1006-657
Optional Accessories at extra cost Duplex 1.27 cm (1/2 “) Kelvin Clips. (2)
Calibration Shunt,10 Ω, current rating 1 mA. 249000 gold plated 2m/7ft 241005-7

Calibration Shunt, 1 Ω, current rating 10 mA. 249001 Duplex 1.27 cm (1/2 “) Kelvin Clips. (2)
silver plated 2m/7ft 242005-7
Calibration Shunt, 100 mΩ current rating 1A. 249002
Calibration Shunt, 10 mΩ current rating 10 A. 249003
Duplex 3.8 cm (11/2”) Kelvin Clips. (2)
Certificate of Calibration for Shunts, NIST CERT-NIST 2m/7ft 242006-7
Replacement tips for DH4 and DH5 handspikes. Duplex 3.8 cm (11/2”) Kelvin Clips. (2)
Needle point 1008-024 5.5m/18ft 242006-18
Replacement tips for DH4 and DH5 handspikes. Duplex 3.8 cm (11/2”) Kelvin Clips. (2)
Serrated end 1010-924 9m/30ft 242006-30

Optional Test Leads at extra cost


Single handspike (1) for potential measurement.
Normal test leads not fitted with in-line connector:
2m/7ft 242021-7
Industrial application kit 1011-376
Single handspike (1) for potential measurement.
Terminal cover (use in conjunction with DH4 test leads supplied as 5.5m/18ft 242021-18
standard, or optional DH5 test leads for CATIII 300 V Single handspike (1) for potential measurement.
compliance) 1002-390 9m/30ft 242021-30
Duplex Handspikes (2) with spring loaded helical contacts. Current clip (1) for current connections.
2m/7ft 242011-7 2m/7ft 242041-7
DH1 5.5m/18ft 242011-18 Current clip (1) for current connections
DH2 9m/30ft (only 1 lead supplied) 242011-30 5.5m/18ft 242041-18
Straight Duplex Handspikes (2) Heavy Duty with fixed contacts. Current clip (1) for current connections
2m/7ft 242002-7 9m/30ft 242041-30
Straight Duplex Handspikes (2) Heavy Duty with fixed contacts
5.5m/18ft 242002-18 Note: For more details of optional leadsets see separate test lead
datasheet DLROTest Leads_DS_V##.pdf

For detailed information on connecting lead accessories refer


to the supplied “accessory important information sheet”
(DLROTestLeads--2007-431_UG_EN-DE-FR-ES-IT_V##)

SALES OFFICE DLRO10HD_DS_en_V12


Megger Limited www.megger.com
Archcliffe Road Dover ISO 9001
CT17 9EN England The word ‘Megger’ is a registered trademark
T +44 (0) 1304 502101
E [email protected]

You might also like