Arrange Circuits, Control and Protection For General Electrical Installations Week 2: Fault Loop Impedance
Arrange Circuits, Control and Protection For General Electrical Installations Week 2: Fault Loop Impedance
and
protection
for
general electrical installations
Week 2: Fault Loop Impedance
All writing in BLUE is examinable
Slide 2 of 33
The cable selection process
Glossary:
MD = Maximum Demand
CB = Circuit Breaker
CCC = Current Carrying
Capacity
VD = Voltage Drop
FLI = Fault Loop Impedance
PFC = Prospective Fault Current
SCTR = Short Circuit
Temperature Rise
Slide 3 of 33
1) Calculate MD Consumer mains (Table C1, C2, C3)
(AS/NZS 3000) Sub mains (Table C1, C2, C3)
Final sub circuits (Table C4, C8)
This course covers FLI, SCTR and PFC, however these are
only topics inside the much greater cable selection
process.
Slide 5 of 33
Fault-Loop Impedance
What you need to know about Fault-Loop Impedance
Slide 6 of 33
Circuit breakers
If not enough current We calculate this
flows this Solenoid using another
wont trip during a application of Ohms
short. law.
Slide 7 of 33
Thermal trip Magnetic trip
(Conventional (Instantaneous
trip Trip)
Time)
(Fault-Loop
(IB ≤ IN ≤ IZ) Impedance)
Slide 8 of 33
Not all circuit breakers trip the same
Slide 10 of 33
Type C: 7.5 x
Slide 11 of 33
Type D: 12.5 x
Slide 12 of 33
Glossary:
FLI = Fault-Loop Impedance
TX = Transformer
CM = Consumer Main
MSB = Main Switch Board
SM = Sub-Main
DB = Distribution Board
FSC = Final Sub-Circuit
Load = Load
P/E = Protective Earth
M/E = Main Earth
MEN = Main Earth Neutral
PEN = Protective Earth Neutral
Slide 13 of 33
The Fault Loop
TX MSB DB LOAD
CM SM FSC
PEN
MEN
P/E P/E
M/E
Slide 14 of 33
Need 150A (20A x 7.5)
z
z z z
z
z z
PEN z z
TX E
M/E
Slide 16 of 33
Need 150A (20A x 7.5)
z
z z z
z
z z
Zmax C20A CB
V 230
Zmax= = =1.533 Ω
I a (7.5×20)
Slide 17 of 33
Need 150A (20A x 7.5)
z
z z z
z
z z
What if there was 5Ω
in the fault loop?
C20A CB
Transposed = V 230 V
Ia = = =46 A
Z 5Ω
46 A
=2.3×Overload
20 A
How long will it take to trip the CB
Slide 18 of 33
Not fast enough (60
seconds) we need 7.5 x
overload to turn the
power off in 0.4
seconds max.
5.7.2 AS/NZS 3000
2.3 x Overload
Slide 19 of 33
Need 150A (20A x 7.5)
z
z z z
z
z z
What if there was 50Ω
in the fault loop?
C20A CB
V 230 V
Ia = = =4.6 A
Z 50 Ω
4.6 A=0×Overload
Slide 20 of 33
A circuit breaker may
never trip with a 50Ω
Fault-Loop
0 x Overload
Slide 21 of 33
Need 150A (20A x 7.5)
z
z z z
z
z z
What if there was 0.5Ω
in the fault loop?
C20A CB
V 230 V
Ia = = =460 A
Z 0.5 Ω
460 A
=23×Overload
20 A
How long will it take to trip the CB
Slide 22 of 33
Easily faster than the
minimum disconnection
time or 0.4 seconds
23 x Overload
Slide 23 of 33
7.5 x overload is the
minimum current
required to cause
automatic
disconnection of
supply, (in 0.4 s)
therefore 1.53Ω is the
maximum fault-loop
impedance for a C20A
CB
V 230
Zmax= = =1.533 Ω
I a (7.5×20)
Slide 24 of 33
Need 30mA!
z
z z z
z
z z
230 V
RCD= =7667 Ω
30 m A
You can have almost 8kΩ in the fault loop and it will still
trip (if the RCD is faulty, we are back to needing 150A)
Slide 25 of 33
Live testing
(Table 8.1)
“Live”
test
FLI Tester
1.02Ω
Plug in the FLI tester A N E
(safely).
Bridge Active/s Ω
to Earth
Connect a sensitive
Ohm meter
A method accepted by
The value must be less AS/NZS 3000 that does
than those in table 8.2 not require an
(Zmax for dead test) expensive meter
Slide 27 of 33
20% (bigger cables) 80%
LOAD
Dead test.
Ohm meter.
Slide 28 of 33
20% (bigger cables) 80%
LOAD
Dead test.
Ohm meter.
Int/Ext Temp
Therefore we use
the following V 0.8×0.8
Zmax= ×0.8×0.8
modified formula: Ia =0.64
Slide 29 of 33
V 230
Zmax= I ×0.64= =0.98 Ω
a (20×7.5)
Slide 30 of 33
Max Circuit length
(So as not to have FLI issues)
Lmax – Maximum length
B5.2.2 AS/NZS 3000 Use Table B1 for most
0.8×Uo ×S ph ×S pe cases
Lmax=
I a ×ρ×(Sph +S pe )
Slide 32 of 33
Why are slabs bonded under wet areas?
No Earth? Ω?
Bonded Slab
Slide 33 of 33