PITO-E
PLUG-IN
TERMINATION
Application Technical characteristics Up to 24 kV - 250 A
• Separable termination Each plug-in termination is tested
designed to connect overhead for AC withstand prior to leaving
lines or bus bars to equipment. the factory.
• Is suitable for indoor and
outdoor use for medium
polluted atmosphere. 6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
Design Dia. 80
The plug-in termination is a Dia. 20 A
moulded epoxy insulated part. M12
It meets the type A - 250 A
interface as described in 30
CENELEC EN 50180 and
50181.
Specifications and
standards
The separable termination
267
PITO-E meets the requirements
of IEC 137. 235
Dia. 8.2
Ordering instructions
To order the plug-in termination
10
for 12 or 24 kV, specify PITO-E.
The kit includes the bail 35
restraint and 2 brass nuts.
Dia. 70
90 B
Dia. 110
In mm.
Plug-in Voltage Current Creepage distance
termination Ur Ir A-B
type (kV) (A) (mm)
PITO-E 12 250 510
PITO-E 24 250 510
13
180AR-1 /-2 /-3
INTERFACE A
EQUIPMENT BUSHING
Application Specifications and Up to 24 kV - 250 A
For use in equipment insulated standards
with oil fluid, typically for The plug-in type equipment
transformers, switch gear, bushings 180AR-X meet the
capacitors... requirements of CENELEC EN
50180 and IEC 137.
Technical characteristics 6/10 (12) kV
Each bushing is tested for
6.35/11 (12) kV
AC withstand and partial
8.7/15 (17.5) kV
discharge prior to leaving the
12/20 (24) kV
factory.
12.7/22 (24) kV
Design
• The equipment bushing is a
moulded epoxy insulated part
in accordance with CENELEC
EN 50180.
The 180AR-2 bushing has a
length B outside this standard.
• The standard bushings,
28
(K)180AR-1 /-2 /-3, are
equipped with 6 tabs for the
8
bail restraint.
• The (K)180AR-1-G and A
(K)180AR-3-G are equipped
with 4 tabs and 2 threaded
inserts M6x1 (-G version).
B
Minimum oil level:
Ordering instructions - 12 kV: 40 mm
- 24 kV: 50 mm
To order the equipment
bushing, specify the type.
The bushings are supplied
19
with an earth lead (/J) or an
earth plate (/GS). This earth
M10
connection must be specified
Dia. 75
when ordering.
Dia. 80
In mm.
Equipment Voltage Current Dimensions (mm)
bushing Ur Ir
type (kV) (A) A B
180AR-1 12 250 222 106
K180AR-1 24 250 222 106
180AR-2 12 250 284 168
K180AR-2 24 250 284 168
180AR-3 12 250 171 55
K180AR-3 24 250 171 55
14