Backup/Restore Options For Simatic Hmi Operator Panels: Wincc Unified V17, Wincc Advanced V17
Backup/Restore Options For Simatic Hmi Operator Panels: Wincc Unified V17, Wincc Advanced V17
options for
SIMATIC HMI
Operator Panels
Siemens
WinCC Unified V17, WinCC Advanced V17 Industry
Online
https://support.industry.siemens.com/cs/ww/en/view/68373729 Support
Legal information
Legal information
Use of application examples
Application examples illustrate the solution of automation tasks through an interaction of several
components in the form of text, graphics and/or software modules. The application examples are
a free service by Siemens AG and/or a subsidiary of Siemens AG ("Siemens"). They are
non-binding and make no claim to completeness or functionality regarding configuration and
equipment. The application examples merely offer help with typical tasks; they do not constitute
customer-specific solutions. You yourself are responsible for the proper and safe operation of the
products in accordance with applicable regulations and must also check the function of the
respective application example and customize it for your system.
Siemens grants you the non-exclusive, non-sublicensable and non-transferable right to have the
application examples used by technically trained personnel. Any change to the application
examples is your responsibility. Sharing the application examples with third parties or copying the
application examples or excerpts thereof is permitted only in combination with your own products.
The application examples are not required to undergo the customary tests and quality inspections
of a chargeable product; they may have functional and performance defects as well as errors. It is
your responsibility to use them in such a manner that any malfunctions that may occur do not
result in property damage or injury to persons.
Disclaimer of liability
Siemens shall not assume any liability, for any legal reason whatsoever, including, without
limitation, liability for the usability, availability, completeness and freedom from defects of the
application examples as well as for related information, configuration and performance data and
any damage caused thereby. This shall not apply in cases of mandatory liability, for example
under the German Product Liability Act, or in cases of intent, gross negligence, or culpable loss of
life, bodily injury or damage to health, non-compliance with a guarantee, fraudulent
non-disclosure of a defect, or culpable breach of material contractual obligations. Claims for
damages arising from a breach of material contractual obligations shall however be limited to the
© Siemens 2021 All rights reserved
foreseeable damage typical of the type of agreement, unless liability arises from intent or gross
negligence or is based on loss of life, bodily injury or damage to health. The foregoing provisions
do not imply any change in the burden of proof to your detriment. You shall indemnify Siemens
against existing or future claims of third parties in this connection except where Siemens is
mandatorily liable.
By using the application examples you acknowledge that Siemens cannot be held liable for any
damage beyond the liability provisions described.
Other information
Siemens reserves the right to make changes to the application examples at any time without
notice. In case of discrepancies between the suggestions in the application examples and other
Siemens publications such as catalogs, the content of the other documentation shall have
precedence.
The Siemens terms of use (https://support.industry.siemens.com) shall also apply.
Security information
Siemens provides products and solutions with Industrial Security functions that support the secure
operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary
to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept.
Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems, machines
and networks. Such systems, machines and components should only be connected to an
enterprise network or the Internet if and to the extent such a connection is necessary and only
when appropriate security measures (e.g. firewalls and/or network segmentation) are in place.
For additional information on industrial security measures that may be implemented, please visit
https://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are no longer
supported, and failure to apply the latest updates may increase customer’s exposure to cyber
threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed
at: https://www.siemens.com/industrialsecurity.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 2
Table of contents
Table of contents
Legal information ......................................................................................................... 2
1 Introduction ........................................................................................................ 4
1.1 Overview .............................................................................................. 4
1.2 Backup Methods................................................................................... 4
1.3 Brief Description of the Backup Types ................................................. 4
1.4 Components Used................................................................................ 6
2 WinCC Advanced ............................................................................................... 7
2.1 Service Concept/Automatic Backup ..................................................... 7
2.1.1 Enable/Disable the Service Concept.................................................... 7
2.1.2 Enabling the Service Concept on the Operator Panel ......................... 7
2.1.3 Replacing the Operator Panel .............................................................. 7
2.2 Backup/Restore via the Operator Panel............................................... 8
2.2.1 Creating a Backup ................................................................................ 8
2.2.2 Restoring Data ..................................................................................... 9
2.3 Backup/Restore via WinCC (TIA Portal) ............................................ 10
2.3.1 Creating a Backup .............................................................................. 10
2.3.2 Restoring Data ................................................................................... 12
2.4 Backup/Restore with ProSave ........................................................... 14
2.4.1 Creating a Backup .............................................................................. 14
2.4.2 Restoring Data ................................................................................... 16
2.5 Backup/Restore with the SIMATIC Automation Tool ......................... 18
© Siemens AG 2021 All rights reserved
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 3
1 Introduction
1 Introduction
1.1 Overview
Time and again, improper handling or other factors, such as harsh environmental
conditions, can damage HMI Operator Panels, making it impossible to operate
machines or system sections.
To keep the associated downtimes as low as possible, you should consider in
advance which data backup options are offered by the SIMATIC Comfort Panel, for
example, and which method makes the most sense.
Note It is not possible to open and edit the backup file with WinCC (TIA Portal). The
© Siemens AG 2021 All rights reserved
file can only be loaded to the original Panel or a Panel of the same type using a
restore command.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 4
1 Introduction
Refer to the Comfort Panel manual for information on the automatic backup
parameters for the SIMATIC HMI memory card:
"Comfort Panels > Commissioning the Device > Using the Service Concept >
Enabling the Service Concept".
• The key advantage of automatic backup is that the data on the system memory
card is continuously and automatically updated.
• Only a SIMATIC HMI memory card (SD card) with at least 2 GB
(6AV2181-8XP00-0AX0) (an SMC for short) is permitted as the system
memory card. All other memory cards will not be recognized by the Operator
Panel as system memory cards. The system memory card is part of the
Operator Panels Service Concept. If you enable the Service Concept, all data
from the internal memory of the Operator Panel is transferred to the system
memory card. The system memory card is not visible in the user interface of
the Operator Panel and cannot be used as a data memory.
Notes
• The "SIMATIC IPC USB flash drive" is a storage device for IPCs,
Comfort Panel, and Basic Panels 2nd Generation. Use the
"SIMATIC HMI USB memory stick" for touch, operator, or Multipanels.
• SIMATIC storage devices are preformatted at the factory. They should not be
formatted, because in this case, they become unusable for certain functions.
By overwriting the internal structure, they are no longer recognized in SIMATIC
devices and can, therefore, no longer be used in these devices.
For more information on formatting and restoring SIMATIC storage devices,
refer to the entry IDs: 95853895 and 69063974.
• Do not confuse Multi Media Cards with Micro Memory Cards. For both
products, the abbreviation "MMC" or "MM" may appear.
"SIMATIC HMI Multi Media Cards" are used in Panels.
"SIMATIC S7 Micro Memory Cards" may only be used in SIMATIC S7 CPUs,
ET200 series modules with CPU functionality, SIMATIC Field PGs, SIMATIC
Power PGs, and USBs.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 5
1 Introduction
You then define the setting for the Operator Panel and the interface in ProSave
and in the PG/PC interface.
Detailed information about ProSave can be found via \4\.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 6
2 WinCC Advanced
2 WinCC Advanced
2.1 Service Concept/Automatic Backup
2.1.1 Enable/Disable the Service Concept
To enable the Service Concept on an Operator Panel during initial startup, proceed
as follows:
1. Switch on the power supply of the Operator Panel.
2. Slide the sliding cover to position 2.
3. Insert the system memory card into the slot provided.
© Siemens AG 2021 All rights reserved
CAUTION The SIMATIC HMI Memory Card must not be formatted. See the following
entry \3\.
Requirements
• The Service Concept was enabled on the defective Operator Panel.
• An identical replacement unit is available.
• The slot for the system memory card is enabled on the replacement device
(delivery state).
• If required, check the setting in the Control Panel under "OP Properties" in the
"System Card" tab.
Procedure
1. Switch off the defective Operator Panel.
2. Remove the defective Operator Panel.
3. Install the replacement Operator Panel.
4. Switch on the power supply of the replacement device.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 7
2 WinCC Advanced
5. Insert the system memory card of the defective Operator Panel into the
corresponding slot of the replacement Operator Panel.
6. Confirm the "Use system card?" message prompting you to enable the Service
Concept.
The contents of the system memory card are copied to the internal memory of the
Operator Panel. The Operator Panel is then restarted.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 8
2 WinCC Advanced
The content of the backup file is checked. After a successful test, the alarm is
displayed stating that the data of the internal memory has been deleted.
6. Acknowledge this message.
The internal memory is deleted. The content of the backup file is then copied to
the internal memory. A progress bar shows the status of the restore process.
After successful restoration, you are prompted to remove the external storage
device and restart the Operator Panel.
7. Remove the external memory and confirm the message.
8. The Operator Panel starts.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 9
2 WinCC Advanced
1. In the project navigation, select the Operator Panel from which you want to
restore the data.
2. Select "Online > HMI Operator Panel Maintenance > Save" in the menu bar.
The connection settings window opens.
3. After you have configured the connection settings and established a
connection to the Operator Panel, press the "Create" button.
Figure 2-1
© Siemens AG 2021 All rights reserved
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 10
2 WinCC Advanced
3
© Siemens AG 2021 All rights reserved
5. (1) Select one of the following backup options from the "Data type" drop-down
list.
a. Complete backup with licenses
b. Recipes
c. User administration
(2) Use the "…" button to select the storage location. Subsequently, you can
specify a name for the backup file.
(3) Start the backup process via the "Start backup" button.
6. Close the windows after the successful backup.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 11
2 WinCC Advanced
1. In the project navigation, select the Operator Panel from which you want to
restore the data.
2. Select "Online > HMI Operator Panel Maintenance > Restore" in the menu bar.
The connection settings window opens.
Figure 2-3
© Siemens AG 2021 All rights reserved
After you have configured the connection settings and established a connection to the
Operator Panel, press the "Load" button.
The following ProSave menu opens.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 12
2 WinCC Advanced
Figure 2-4
3
© Siemens AG 2021 All rights reserved
3. (1) Use the button to select the storage location in which you have saved the
"backup file".
(2) After selecting the backup file, information about this backup file is
displayed here.
4. Before the restore process starts, the following message appears. (data and
licenses are deleted).
To continue the restore process, press the "Yes" button.
Figure 2-5
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 13
2 WinCC Advanced
(3) Enter the address of the Operator Panel here. In this example, it is the IP
address.
Figure 2-6
© Siemens AG 2021 All rights reserved
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 14
2 WinCC Advanced
3
© Siemens AG 2021 All rights reserved
5. (1) Select one of the following backup options from the "Data type" drop-down
list.
– Complete backup with licenses
– Recipes
– User administration
(2) Use the "…" button to select the storage location. Subsequently, you can
specify a name for the backup file.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 15
2 WinCC Advanced
(3) Enter the address of the Operator Panel here. In this example, it is the IP
address.
Figure 2-8
© Siemens AG 2021 All rights reserved
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 16
2 WinCC Advanced
3
© Siemens AG 2021 All rights reserved
5. (1) Use the button to select the storage location in which you have saved the
"backup file".
(2) After selecting the backup file, information about this backup file is
displayed here.
6. Before the restore process starts, the following message appears (data and
licenses will be deleted).
To continue the restore process, press the "Yes" button.
Figure 2-10
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 17
2 WinCC Advanced
4. "Communication" settings
Select the communication type here. Ensure that the same settings are
available on the Operator Panel and in the SAT.
Figure 2-12
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 18
2 WinCC Advanced
5. "Backup/Restore" settings
Enter the storage location for the backup file here.
Figure 2-13
7. Scan network
(1) Click the icon to scan the network.
(2) All devices that can be reached with the SAT are displayed.
Figure 2-15
1
2
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 19
2 WinCC Advanced
8. Select "Operations > Backup Device > Full Backup" from the menu bar.
Alternatively, open the menu via the icon.
Figure 2-16
9. The following security query appears. To continue with the process, press the
"Continue" button.
Figure 2-17
© Siemens AG 2021 All rights reserved
By confirming with the "Continue" button, the SAT establishes a connection to the
Operator Panel and the backup is performed. During the backup, the progress is
displayed.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 20
2 WinCC Advanced
Figure 2-18
10. After the backup has been completed, the Operator Panel Runtime is
automatically restarted.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 21
2 WinCC Advanced
3. Select "Operations > Restore Device" from the menu bar. Alternatively, open
the menu via the icon.
Figure 2-21
4. The following security query appears. To continue with the process, press the
"Continue" button.
Figure 2-22
© Siemens AG 2021 All rights reserved
After completion of the restore process, the Operator Panel boots automatically.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 22
3 WinCC Unified
3 WinCC Unified
3.1 General remarks
View of the main window from a Unified Comfort Panel. Select the entry "Service
and Commissioning" via the navigation pane or the tile in the window area.
Figure 3-1
© Siemens AG 2021 All rights reserved
The following data backup functions can be performed via the "Service and
Commissioning" function.
• Automatic backup
• Backup
• Restore
The slots for the data memory card and system memory card are located on the
back of the Operator Panel. The memory cards are secured via a sliding cover.
The following figure shows the slots with sliding covers.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 23
3 WinCC Unified
Figure 3-2
(1) Slot "X51" for the data memory card in "SD(IO/HC)" format. Card
recommendations: SIMATIC SD card with at least 32 GB.
(2) Slot "X50" for the system memory card.
Permitted card: SIMATIC HMI memory card 32 GB.
(3) Sliding cover, two-stage.
Note Only the SIMATIC SD memory card with at least 32 GB is permitted as a system
memory card. All other memory cards will not be recognized by the Operator
© Siemens AG 2021 All rights reserved
Further information
Detailed information about backup/restore (discussion of multiple configurations)
and the use of memory cards can be found via the following link \5\.
Note To be able to execute the function, a system memory card must be inserted in
the "X50" slot. See Section 3.1.2.
1. With a newly inserted system memory card and after starting the Operator
Panel, the following message is displayed.
Figure 3-3
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 24
3 WinCC Unified
2. Click the "OK" button. In the Control Panel "Service and Commissioning"
window, "Automatic Backup" opens.
"Ready for automatic backup" is displayed in the "Status" field.
Figure 3-4
6. Click the "OK" button. The status message "Starting automatic backup" is
displayed. The system memory card is prepared.
Figure 3-6
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 25
3 WinCC Unified
Under "Backup", you can back up the operating system, applications, and data
located in the flash memory of the Operator Panel to an external storage device.
Use a SIMATIC SD memory card with at least 32 GB or an industrial USB stick as
storage device
– "Complete backup":
Back up all Operator Panel data including operating system, project, and
User Administration data.
© Siemens AG 2021 All rights reserved
– "Runtime project":
Save the project of the Operator Panel.
– "Only user management data":
Save the Operator Panel User Administration.
3. "Backup File" section
a. File name: Specify a file name for the backup file.
b. Storage media: Specify a storage location via the drop-down list
(e.g., X51 or X61).
c. Start the backup by clicking the "Create Backup" button.
After pressing the "Create backup" button, the Operator Panel restarts and the data
backup is started.
A dialog box with a progress bar is displayed for each backup file.
After the backup process has been completed, the Operator Panel is restarted.
After the restart, the main window of the Control Panel is displayed.
The Operator Panel data is saved on the storage device.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 26
3 WinCC Unified
A restore operation deletes the old data from flash memory of the Operator Panel
upon confirmation. The data backed up on the storage device is then transferred.
3. Backup files
The list shows all backups that can be loaded onto the Operator Panel.
Select the desired backup from the list.
Figure 3-11
After pressing the "Restore" button, the Operator Panel restarts. The restore
process then begins.
During the restore process, a dialog box with a progress bar is displayed for each
backup file loaded.
After the restore process has been completed, the Operator Panel is restarted
again.
After the restart, the main window of the Control Panel is displayed.
The data from the storage medium is now restored on the Operator Panel.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 27
3 WinCC Unified
1. Connect the Unified Comfort Panel to the PC via the Ethernet interface.
2. In the project navigation, select the Unified Comfort Panel from which you want
to create a backup.
3. Select "Online > HMI Operator Panel Maintenance > Save" in the menu bar.
The connection settings window opens.
4. After you have configured the connection settings and established a
connection via Ethernet to the Operator Panel, press the "Load" button.
Figure 3-12
© Siemens AG 2021 All rights reserved
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 28
3 WinCC Unified
After pressing the "Create" button, the following menu screen opens.
Figure 3-13
To continue with the function, press the "Backup" button. The ProSave menu screen
opens.
© Siemens AG 2021 All rights reserved
Figure 3-14
(1) Use the "Data type" drop-down list to select the "Complete backup with licenses"
option.
(2) Use the "…" button to select the storage location. Subsequently, you can
specify a name for the backup file.
(3) Start the backup process via the "Start backup" button.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 29
3 WinCC Unified
After pressing the "Start backup" button, the Operator Panel restarts and the data
backup is started.
During the backup, a dialog box with a progress bar is displayed.
After the backup process has been completed, the Operator Panel is restarted.
After restarting, the main window of the Control Panel is displayed.
Operator Panel data is saved on the PC.
1. Connect the Unified Comfort Panel to the PC via the Ethernet interface.
2. In the project navigation, select the Operator Panel from which you want to
create a backup.
3. Select "Online > HMI Operator Panel Maintenance > Restore" in the menu bar.
The connection settings window opens.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 30
3 WinCC Unified
5. After you press the "Load" button, the following menu screen is displayed.
Figure 3-16
6. To continue the function, press the "Restore" button. The ProSave menu
opens.
© Siemens AG 2021 All rights reserved
Figure 3-17
7. (1) Use the button to select the storage location in which you have saved the
"backup file".
(2) After selecting the backup file, information about this backup file is
displayed here.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 31
3 WinCC Unified
8. Before the restore process starts, the following message appears. (data and
licenses are deleted).
To continue the restore process, press the "Yes" button.
Figure 3-18
After pressing the "Yes" button, the Operator Panel restarts and the data is
transferred to the Operator Panel.
During the restore process, a dialog box with a progress bar is displayed.
After the restore process has been completed, the Operator Panel is restarted
again.
© Siemens AG 2021 All rights reserved
After the restart, the main window of the Control Panel is displayed.
The data of the Operator Panel is restored on the panel.
(3) Enter the address of the Operator Panel here. In this example, it is the IP
address.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 32
3 WinCC Unified
Figure 3-19
3
© Siemens AG 2021 All rights reserved
(2) Use the "…" button to select the storage location. Subsequently, you can
specify a name for the backup file.
(3) Start the backup process via the "Start backup" button.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 33
3 WinCC Unified
Figure 3-20
3
© Siemens AG 2021 All rights reserved
After pressing the "Start backup" button, the Operator Panel restarts and the data
backup is started.
A dialog box with a progress bar is displayed for each backup file.
After the backup process has been completed, the Operator Panel is restarted.
After the restart, the main window of the Control Panel is displayed.
Operator Panel data is saved on the PC.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 34
3 WinCC Unified
(2) Use the "Connection" drop-down list to select the communication connection
via which you have connected the Operator Panel to ProSave. In this example,
"Ethernet".
– MPI/PROFIBUS DP
– Ethernet
– PN/IO
– S7Usb
(3) Enter the address of the Operator Panel here. In this example, it is the IP
address.
Figure 3-21
© Siemens AG 2021 All rights reserved
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 35
3 WinCC Unified
5. (1) Use the button to select the storage location in which you have saved the
"backup file".
(2) After selecting the backup file, information about this backup file is
displayed here.
2
© Siemens AG 2021 All rights reserved
After pressing the "Yes" button, the Operator Panel restarts. The restore process
then begins.
A dialog box with a progress bar is displayed during the restore process.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 36
3 WinCC Unified
After the restore process has been completed, the Operator Panel is restarted
again.
After restarting, the main window of the Control Panel is displayed.
The data from the storage medium is now restored on the Operator Panel.
• the Operator Panel communicates with the SAT via the Ethernet interface.
• the "Ethernet" option is selected in the SAT under "Options > Settings >
Communication > Transfer channel".
1. Select "Operations > Backup Device > Full Backup" from the menu bar.
© Siemens AG 2021 All rights reserved
2. The following security query appears. To continue with the process, press the
"Continue" button.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 37
3 WinCC Unified
Figure 3-25
By confirming with the "Continue" button, the SAT establishes a connection to the
Operator Panel and the backup is performed. During the backup, the progress is
displayed.
Figure 3-26
© Siemens AG 2021 All rights reserved
3. After the backup has been completed, the Operator Panel Runtime is
automatically restarted.
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 38
3 WinCC Unified
Figure 3-28
3. Select "Operations > Restore Device" from the menu bar. Alternatively, open
the menu via the icon.
Figure 3-29
© Siemens AG 2021 All rights reserved
4. The following security query appears. To continue with the process, press the
"Continue" button.
Figure 3-30
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 39
3 WinCC Unified
Figure 3-31
After completion of the restore process, the Operator Panel boots automatically.
© Siemens AG 2021 All rights reserved
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 40
4 Appendix
4 Appendix
4.1 Service and support
Industry Online Support
Do you have any questions or need assistance?
Siemens Industry Online Support offers round the clock access to our entire
service and support know-how and portfolio.
The Industry Online Support is the central address for information about our
products, solutions and services.
Product information, manuals, downloads, FAQs, application examples and videos
– all information is accessible with just a few mouse clicks:
support.industry.siemens.com
Technical Support
The Technical Support of Siemens Industry provides you fast and competent
support regarding all technical queries with numerous tailor-made offers
– ranging from basic support to individual support contracts.
Please send queries to Technical Support via Web form:
support.industry.siemens.com/cs/my/src
© Siemens AG 2021 All rights reserved
Service offer
Our range of services includes the following:
• Plant data services
• Spare parts services
• Repair services
• On-site and maintenance services
• Retrofitting and modernization services
• Service programs and contracts
You can find detailed information on our range of services in the service catalog
web page:
support.industry.siemens.com/cs/sc
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 41
4 Appendix
The Siemens Industry Mall is the platform on which the entire siemens Industry
product portfolio is accessible. From the selection of products to the order and the
delivery tracking, the Industry Mall enables the complete purchasing processing –
directly and independently of time and location:
mall.industry.siemens.com
https://support.industry.siemens.com
\2\ Link to the entry page of the application example
https://support.industry.siemens.com/cs/ww/en/view/68373729
\3\ Why must a SIMATIC HMI Memory Card not be formatted and what must be
observed when using commercially available memory cards?
https://support.industry.siemens.com/cs/ww/en/view/95853895
\4\ SIMATIC ProSave service tool
https://support.industry.siemens.com/cs/ww/en/view/10347815
\5\ Unified Comfort Panel instruction manual
https://support.industry.siemens.com/cs/ww/en/view/109773257
\6\ Guide for switching from Comfort Panels to Unified Comfort Panels
https://support.industry.siemens.com/cs/ww/en/view/109768002
\7\ Which external storage devices can you use with the current SIMATIC Panels, or
which memory card interfaces do they have?
https://support.industry.siemens.com/cs/ww/en/view/21847868
Backup/Restore
Entry ID: 68373729, V2.0, 09/2021 42