Sigma XT+: Multi-Area Extinguishant Control Panels
Sigma XT+: Multi-Area Extinguishant Control Panels
2013
Technical
Construction - 1.2mm mild sheet steel
IP Rating - IP30
Finish - Epoxy powder coated
Colour - lid & box - BS 00 A 05 grey - fine texture
Colour - controls plate & labels - RAL 7047 light grey - satin
Weight - 8kg (standard panel)
Mains supply - 230V AC, 50Hz +10% - 15% (100 Watts maximum)
Mains supply fuse - 1.6 Amp ( F1.6A L250V)
Power supply rating (1 & 2 area units) - 3 Amps total including battery charge 28V +/- 2V
Power supply rating (3 & 4 area units) - 5.25 Amps including battery charge 28V +/- 2V
Maximum ripple current - 200 millivolts
Battery charge voltage - 27.6VDC nominal (temperature compensated)
Battery charge current - 0.7A maximum
Battery fuse - 20mm, 3.15A glass
Current draw in mains fail condition - 54 milliamps per module
Max. current draw from batteries - 3A (K21021, K21041, K21042, K21081, K21082)
4A (K21083, K21084)
Sigma XT+ module Aux 24V output - Fused at 500mA with electronic fuse - 1 per extinguishant area
Sigma CP Aux 24V output - Fused at 2.5A - not available to user
1st and 2nd stage Sounder outputs - 21 to 28V DC Fused at 1A with electronic fuse
Fault relay contact rating - 5 to 30VDC 1A Amp maximum for each
Fire relay contact rating - 5 to 30VDC 1A Amp maximum for each
Local fire relay contact rating - 5 to 30VDC 1A Amp maximum for each
First stage contact rating - 5 to 30VDC 1A Amp maximum for each
Second stage contact rating - 5 to 30VDC 1A Amp maximum for each
Extract contact rating - 5 to 30VDC 1A Amp maximum for each
Zone quiescent current - 0mA minimum, 2mA maximum
Terminal capacity - 0.5mm2 to 2.5mm2 solid or stranded wire
Number of detectors per zone - Dependent on type - typically 20
Number of sounders per circuit - Dependent on type and current consumption - typically 20+
Detection circuit end of line - 6K8 +/- 5% ½ Watt resistor
Monitored input end of line - 6K8 +/- 5% ½ Watt resistor
Sounder circuit end of line - 10K +/- 5% ¼ Watt resistor
Extinguishant output end of line - 1N4004 Diode
No. of detection circuits - Two to eight. 21 to 28V DC
No. of sounder circuits - Dependent on model 21 to 28V DC
Extinguishant release output - 21 to 28V DC. Fused at 1 Amp
Extinguishant release delay - Adjustable 0 to 60 seconds (+/- 10%)
Extinguishant release duration - Adjustable 60 to 300 seconds
SIL, AL, FLT, RST inputs - Switched -ve, min resistance 0 ohms, max resistance 100 Ohms
Zone normal threshold (Allowable EOL) - 10K ohm to 2K ohm
Detector alarm threshold - 1K ohms to 390 ohms
Call point alarm threshold - 370 ohms to 150 ohms
Short circuit threshold - 130 ohms to 0 ohms
Head removal condition - 15.5 to 17.5 volts
Cabling - FP200 or equivalent (max capacitance 1uF max inductance 1 mH
Monitored inputs normal threshold - 10K ohm to 2K ohm
(Allowable EOL)
Monitored inputs alarm threshold - 2K ohms to 150 ohms +/- 5%
Monitored inputs Short circuit threshold - 140 ohms to 0 ohms +/- 5%
Status unit/Ancillary board connection - Two wire RS485 connection (EIA-485 specification)
Status unit power output - 21 to 28V DC. Fused at 500mA with electronic fuse
The manufacturer reserves the right to amend specifications without prior notice